Professional Documents
Culture Documents
Research On The Protection of Hybrid HVDC System
Research On The Protection of Hybrid HVDC System
of the 4rth International Conference on Power Generation Systems and Renewable Energy Technologies (PGSRET)
10-12 September 2018, Islamabad, Pakistan
Abstract— The traditional and conventional HVDC system has tens of megawatts to hundreds of megawatts and it mainly has
the advantages of lower installing cost and it is a mature state of the following advantages [21]–[23];
the art, but it also has some drawbacks like huge reactive power
absorption and commutation fault in the system. Similarly, HVDC It can operate in passive inversion mode and transmit
based on VSC (Voltage Source Converter) is easily operational electricity for long distance isolated loads[24].
and flexible in control but it needs high cost for the installation
that’s a drawback. A theoretical type of hybrid HVDC It can simultaneously and independently control active and
transmission scheme is presented in this manuscript after the reactive power and is more flexible and convenient to
combination of above-mentioned advantages of two HVDC control. At the same time, it can also be used as a static var
systems. In this proposed scheme two control techniques are compensator (Static Compensator, STATCOM);
merged like PCC (Phase Control Converter) at sending terminal
and VSC at receiving terminal of HVDC transmission system. Because VSC is controlled by the AC side current, so it
Furthermore, the stability and steadily operation of the proposed will not increase the short circuit capacity of the system
system are verified by generating single phase to ground fault or
[25];
short circuit fault in all phases. After getting the simulation
results, it is observed that proposed hybrid HVDC system is VSC usually uses sinusoidal pulse width modulation
capable of restoring the system rapidly by minimizing the effect of technique (Sinusoidal Pulse width Modulation, SPWM)
these faults.
the switching frequency of the technology is relatively high
Keywords: HVDC, VSC-HVDC, Simulink HVDC Model, and the capacity of the required filter device is relatively
Hybrid Transmission, Power System Protection small;
Because the VSC-HVDC technology are short of research
I. INTRODUCTION
and application time, the technical maturity is far less than that
Since the first HVDC contact line in the world was put into of traditional H V D C. VSC-HVDC requires the use of
commercial operation in 1954. HVDC is an increasingly mature insulated gate bipolar transistors (Insulated Gate Bipolar
technology and it has been widely used in long distance high- Transistor, IGBT) and SPWM in both the transmission and the
power transmission, submarine cable transmission and receiving terminals of the transmission system. So, the cost for
asynchronous communication between the two communication the manufacturing is still relatively high.
systems. However, HVDC also has the danger of the need for On the basis of comparing the advantages and disadvantages
rotating motor in the receiving grid and the danger of of traditional HVDC and VSC-HVDC, a new hybrid DC
commutation failure. So, the converter needs more reactive transmission mode is proposed in this paper. The structure,
power and other limitations in the operation of the converter technical characteristics and operation characteristics of the
[1]–[3]. Therefore, the high performance self-commutating Hybrid DC transmission are comprehensively discussed.
converter is studied in literature [4]–[6]. Finally, the feasibility and effectiveness of the Hybrid DC
With the development of fully controlled power electronic transmission are confirmed by the preliminary simulation
devices, power electronics and the power system itself, the new research materials.
type of high-voltage direct current transmission (HVDC) based
on Voltage Source Converter (VSC) [7] and Pulse Width II. STRUCTURE AND BASIC PRINCIPLE OF NEW
Modulation (PWM) technology have been studied and applied. HYBRID HVDC TRANSMISSION MODE
The systematic model of VSC-HVDC [8]–[12] control policy
A. Structure and Working Principle
[13]–[16] and running characteristics [17]–[20] are analyzed
and studied in this manuscript. The basic structure of the Hybrid DC transmission is shown
in figure 1. From the sending end there is a traditional HVDC
The economic power of VSC-HVDC can be ranged from
controller (Phase Control Converter, PCC) which is used along
*Corresponding Author: Muhammad Tanveer Riaz, Chongqing University. with a commutation bridge arm consisting of 6 sets of thyristors
Mob: +8613206025065, Email: Tanveer.riaz@ieee.org
AC Filter
A B C
AC Filter
Z
Z
and diodes in reverse parallel configuration. A converter From equation (1) to (5) the basic formulas to describe the
transformer and AC filter is also used at sending end. The operational characteristics of HVDC is presented. In the
receiving end converter uses VSC, which consists of a formula (4), (5) it can be seen that the active power depends
converter bridge, a commutation bridge, a DC capacitor and an mainly on the phase angle δ, the reactive power is mainly
AC filter. In the diagram, Us1 and Us2 are the effective values of determined by the Uc2 and the Uc2 is controlled by the
the voltage base components for sending and the receiving ends modulation (Pulse Width Modulation, PWM) of the VSC.
respectively. Similarly, the Uc1 and Uc2: are the effective values Therefore, the active power of the system can be controlled by
of the fundamental components of the AC voltage for PCC and controlling the angle δ and the reactive power emitted or
VSC respectively. absorbed by the VSC can be controlled by the controlling the
Uc2.
This new hybrid DC transmission system combines the
advantages of traditional HVDC and VSC-HVDC system, For Hybrid DC transmission systems, the operation and
which can control the power and phase angle of the system and control of PCC and VSC are very different from the operation
does not increase its installing cost. For the sending end, if the and control of the dual end PCC of the traditional HVDC. In
trigger lag angle is α and the angle of commutation is γ then the order to make the system operate smoothly and have good anti-
DC voltage of the sending terminal is Ud1. interference ability, the HVDC transmission system can use the
angle α at rectifier side to adjust the DC current and DC voltage
3 2 of VSC at the inverter side through the adjustment port. When
U d1 = U s1[cos α + cos(α + γ )] (1) the current fluctuates, the system has the characteristics of
2π
automatically keeping the fluctuation decreasing.
For the receiving end, assuming that the voltage modulation
ratio is m and the DC line resistance is Rd, the DC voltage at the However, due to the traditional HVDC and VSC-HVDC are
receiving end is Ud2 and the DC current is Id. dependent on the polarity of current and voltage to change the
power flow. Therefore, the power flow reversal cannot be
U d 2 = 2U s 2 / m (2) realized by Hybrid DC transmission.
2
side, but also can dynamically compensate the reactive operating without any fault. Later some faults are generated in
power of the AC bus and stabilize the AC bus voltage. it for the observation of grounding current and restoring time
which are the main concern of this research.
Because the current side of V S C can be controlled, it will
not increase. With increase of short circuit capacity of Table 1: Parameters description for the proposed system
system, the protection setting of the AC system does not
need to be changed after the new HVDC transmission lines Sr. Parameters Sending Receiving
are added. Multiple VSC can be connected to a fixed No End End
polarity DC bus, which is easy to form a multi terminal DC 1 Power 5000 MVA 10000 MVA
system with the same topology as the AC system and the Capacity
operation control mode is flexible and changeable.
2 Line 500kV 345kV
The Hybrid DC transmission technology combines the
Voltage
advantages of traditional H V D C technology, low cost and
good adjustment performance of VSC-HVDC technology 3 Frequency 60 Hz 50 Hz
which can be easily extended to a Hybrid DC transmission
system on the traditional HVDC system. But its
transmission power is not as big as that of traditional H V
D C and its adjustment flexibility is not as good as that of
VSC-HVDC.
3
Figure 4: DC fault curve in the system
Figure 6: Grounding current flowing towards the ground electrode
Since, there are protection control schemes like PCC and
VSC which are used in this hybrid HVDC model therefore, in
figure 5 system goes to stable and normal working condition at
t=0.77s. It is also clear that system have the ability to restore a
sudden fault in transmission lines, but the problem faced here
is the long restoring time. Fault is occurred at t=0.77s but the
system gets completely restored after the t=1.05s. The gap
between system shutdown and restored normal condition is a
large for the users so in future suggestions it is needed to
improve the protection scheme which minimize the restoring
time. These signals are captured at rectifier of sending end side
while the signals at inverter side are same with it.
4
that de-energization of whole system mostly happens and at the The grounding current with the impact of AC fault in system
result there is huge infeed loss. These phenomena are not is shown in figure 10 which also goes to 4000A as its maximum
suitable for the grids associated with DC transmission. value. The DC line voltage is also shown in the figure 11 which
According to reliable protection, it is required to isolate the goes to negative after the AC fault. It is also observed that
faulted line from HVDC grids so that remaining lines can system voltage is going to stable after t=1.45s because of fault
operate normally. Also, the braking time should be minimized controlling schemes in it.
for the improvement of DC CBs[26].
V. CONCLUSION
The hybrid HVDC transmission system proposed in this
paper adopts the traditional HVDC and PCC technology at
sending converter, while the receiving converter uses VSC
technology. The Hybrid DC transmission technology combines
the advantages of traditional HVDC with mature technology,
lower cost and good adjustment performance of VSC-HVDC
technology. It can be conveniently extended to hybrid HVDC on
the traditional H V D C system.
The hybrid (HVDC) transmission system can carry out the
power transmission steadily, and the stable operation of the
system can be quickly recovered when the single-phase
grounding fault and three-phase short circuit fault occur in the
DC and AC systems, respectively.
The Hybrid DC transmission is a new type of transmission
Figure 9: Rectifier side V-I response mode. For more detailed operation characteristics of the system,
the fault analysis and related protection strategy still need to be
further studied. The interaction between the control mode and
the communication system should be deeply studied for the
operation characteristics of the multi terminal DC system
composed of this transmission mode.
ACKNOWLEDGMENT
This work was supported by the Fundamental Research
Funds for Central Universities (No. CDJZR14155501), the
National Natural Science Foundation of China (No. 51477013)
and the science project of state grid headquarters (No.
GYW17201600045). The authors would like to thank the
anonymous reviewers for their instructive comments.
REFERENCES
[1] G. Tang, Z. He, and H. Pang, “Research, Application and Development
Figure 10: Current flowing towards the ground of VSC-HVDC Engineering Technology [J],” Autom. Electr. Power Syst.,
vol. 15, p. 3, 2013.
[2] L. Gengyin, L. Pengfei, L. Guangkai, and Z. Ming, “Development and
prospects for HVDC Light [J],” Autom. Electr. Power Syst., vol. 4, pp.
77–81, 2003.
[3] M. Daryabak et al., “Modeling of LCC-HVDC systems using dynamic
phasors,” IEEE Trans. Power Deliv., vol. 29, no. 4, pp. 1989–1998, 2014.
[4] M. M. C. Merlin, T. C. Green, P. D. Mitcheson, D. R. Trainer, D. R.
Critchley, and R. W. Crookes, “A new hybrid multi-level voltage-source
converter with DC fault blocking capability,” 2010.
[5] S. Cole, J. Beerten, and R. Belmans, “Generalized dynamic VSC MTDC
model for power system stability studies,” IEEE Trans. Power Syst., vol.
25, no. 3, pp. 1655–1662, 2010.
[6] M. Guan and Z. Xu, “Modeling and control of a modular multilevel
converter-based HVDC system under unbalanced grid conditions,” IEEE
Trans. power Electron., vol. 27, no. 12, pp. 4858–4867, 2012.
[7] G. P. Adam, K. H. Ahmed, S. J. Finney, K. Bell, and B. W. Williams,
“New breed of network fault-tolerant voltage-source-converter HVDC
Figure 11: DC voltage after AC fault in system transmission system,” IEEE Trans. Power Syst., vol. 28, no. 1, pp. 335–
346, 2013.
5
[8] A. Farag, M. Durrant, H. Werner, and K. Abbott, “Robust control of a
VSC HVDC terminal attached to a weak AC system,” in Control Muhammad Tanveer Riaz (1993), Master’s
Applications, 2003. CCA 2003. Proceedings of 2003 IEEE Conference
on, 2003, vol. 1, pp. 173–177. Degree Student at Chongqing University,
[9] Z. Guibin, X. Zheng, and W. Guangzhu, “Steady-state model and its China. He has done Bachelor’s degree from
nonlinear control of VSC-HVDC system,” PROCEEDINGS-CHINESE University of Engineering & Technology
Soc. Electr. Eng., vol. 22, no. 1, pp. 17–22, 2002. Lahore Pakistan in 2015. The research
[10] M. Yin, G. Li, T. Niu, G. Li, H. Liang, and M. Zhou, “Continuous-time directions are the HVDC transmission application technology,
state-space model of VSC-HVDC and its control strategy,”
PROCEEDINGS-CHINESE Soc. Electr. Eng., vol. 25, no. 18, p. 34, 2005.
Smart grid and micro grid security issues and new electrical
[11] W. Guan, C. A. I. Ye, Z. Guibin, and X. U. Zheng, “Equivalent model of
technologies. Email: tanveer.riaz@ieee.org
HVDC-VSC and its hybrid simulation technique,” POWER Syst.
Technol., vol. 27, no. 2, pp. 4–8, 2003.
[12] W. Wei, X. Wang, and Y. Chen, “New generation digital HVDC
simulation module of SCDTS,” in Power System Technology, 2002.
Proceedings. PowerCon 2002. International Conference on, 2002, vol. 1,
pp. 552–555.
[13] Z. Guibin, X. Zheng, and S. Wei, “Research on the control and simulation
of HVDC-VSC,” in Proc. 2001 International Conference on Power
System, Wuhan China, 2001, pp. 371–375.
[14] A. Egea-Alvarez, F. Bianchi, A. Junyent-Ferré, G. Gross, and O. Gomis-
Bellmunt, “Voltage control of multiterminal VSC-HVDC transmission
systems for offshore wind power plants: Design and implementation in a
scaled platform,” IEEE Trans. Ind. Electron., vol. 60, no. 6, pp. 2381–
2391, 2013.
[15] H. Liu, Z. Xu, and Z. Gao, “A control strategy for three-level VSC-HVDC
system,” in Power Engineering Society Summer Meeting, 2002 IEEE,
2002, vol. 1, pp. 480–485.
[16] Z. Hu, C. Mao, and J. Lu, “Application of an optimal control strategy to
a new type of HVDC system based on voltage source converters,” Power
Syst. Technol., vol. 10, no. 28, pp. 38–41, 2004.
[17] H. Liang, G. LI, G. Li, K. Zhang, and M. Zhou, “Simulation study of
VSC-HVDC system connected to passive network [J],” Power Syst.
Technol., vol. 8, pp. 45–50, 2005.
[18] C. Zheng, X. ZHOU, R. LI, and C. SHENG, “Study on the steady
characteristic and algorithm of power flow for VSC-HVDC,” Proc.
CSEE, vol. 6, p. 0, 2005.
[19] L. Xu, B. R. Andersen, and P. Cartwright, “VSC transmission operating
under unbalanced AC conditions-analysis and control design,” IEEE
Trans. Power Deliv., vol. 20, no. 1, pp. 427–434, 2005.
[20] Z. Huang, B. T. Ooi, L.-A. Dessaint, and F. D. Galiana, “Exploiting
voltage support of voltage-source HVDC,” IEE Proceedings-Generation,
Transm. Distrib., vol. 150, no. 2, pp. 252–256, 2003.
[21] J. Li, G. Li, C. Zhao, and G. Li, “Control strategy for VSC-HVDC system
under unsymmetry of three phase voltage,” Power Syst. Technol., vol. 29,
no. 16, pp. 16–20, 2005.
[22] W. Jun, Z. Yigong, and H. Minxiao, “HVDC based on voltage source
converter-a new generation of HVDC technique,” POWER Syst. Technol.,
vol. 27, no. 1, pp. 47–51, 2003.
[23] G. Tang, X. Luo, and X. Wei, “Multi-terminal HVDC and DC-grid
technology,” in Zhongguo Dianji Gongcheng Xuebao(Proceedings of the
Chinese Society of Electrical Engineering), 2013, vol. 33, no. 10, pp. 8–
17.
[24] J. Zhu, C. D. Booth, G. P. Adam, A. J. Roscoe, and C. G. Bright, “Inertia
emulation control strategy for VSC-HVDC transmission systems,” IEEE
Trans. Power Syst, vol. 28, no. 2, pp. 1277–1287, 2013.
[25] B. Gemmell, J. Dorn, D. Retzmann, and D. Soerangr, “Prospects of
multilevel VSC technologies for power transmission,” in Transmission
and Distribution Conference and Exposition, 2008. T&D. IEEE/PES,
2008, pp. 1–16.
[26] D. Larruskain, O. Abarrategui, I. Zamora, G. Buigues, V. Valverde, and
A. Iturregi, “Requirements for Fault Protection in HVDC Grids,” in
International Conference on Renewable Energies and Power Quality,
2015.