Professional Documents
Culture Documents
208.8. Lateral Force: V 0.7C IW
208.8. Lateral Force: V 0.7C IW
Lateral Force
Lateral-force procedures for non-building structures with structural systems similar to buildings
(those with structural systems which are listed in Table 208-11) shall be selected in accordance
with the provisions of Section 208.4
Exception:
Intermediate moment-resisting frames (IMRF) may be used in Seismic Zone for non-building
structures in Occupancy Categories III and IV if (I) the structures is less than 15m in height and
(2) the value R used in reducing calculated member forces and moments does not exceed 2.8.
The concentrated force F t at the top, which is in addition to F n, shall be determined from the
equation:
F t=0.07 (208-16)
The value of T used for the purpose of calculating F t shall be the period that corresponds with
the design base shear as computed using Equation 208-4. F t need not exceed 0.25V and may be
considered as zero where T is 0.7 s or less. The remaining portion of the base shear shall be
distributed over the height of the structure, including Level n, according to the following
equation:
(V −Ft )w x hx
F x= n
(208-17)
∑ wi hi
i=1
At each level designated as x, the force F x shall be applied over the area of the building in
accordance with the mass distribution at that level. Structural displacements and design seismic
forces shall be calculated as the effects of forces F x and F t applied at the appropriate levels
above the base.
Exception:
For irregular structures assigned to Occupancy Categories I and II that cannot be
modeled as a single mass, the procedures of Section 208.5.3 shall be used.
3. Where an approved national standard provides a basis for the earthquake-resistant design
of a particular type of non-building structure covered by this section, such a standard may
be used, subject to the limitations in this section:
The seismic zones and occupancy categories shall be in conformance with the provisions of
Sections 208.4.4 and 208.4.2, respectively.
The values for total lateral force and total base overturning moment used in design shall not
be less than 80 percent of the values that would be obtained using these provisions.
Table 208-12 R and Ωo Factors for Non-building Structures
STRUCTURE TYPE R Ωo
1. Vessels, including tanks and pressurized spheres,
2.2 2.0
on braced or unbraced legs.
2. Cast-in-place concrete silos and chimneys
3.6 2.0
having walls continuous to the foundations.
3. Distributed mass cantilever structure such as
stacks, chimneys, silos and skirt-supported vertical 2.9 2.0
vessels.
4. Trussed towers (freestanding or guyed), guyed
2.9 2.0
stacks and chimneys.
5. Cantilevered column-type structures. 2.2 2.0
6. Cooling Towers. 3.6 2.0
7. Bins and hoppers on braced or unbraced legs. 2.9 2.0
8. Storage racks. 3.6 2.0
9. Signs and Billboards. 3.6 2.0
10. Amusement structures and monuments 2.2 2.0
11. All other self-supporting structures not
2.9 2.0
otherwise covered.