ES30-5 D
Series IDU/IDF
Meets specified
Montreal Protocol
Regulations
Series IDU Small series: R134a
Series IDF
Medium series: R22
Large series: R407C
IDU3D to 15C, IDF3D to 15C
Available in single phase
200VAC without transformer
Features 1
Series Variations
Note)
Air flow capacity (l/min(ANR) Screw type air
compressor power Rated inlet
Series 50 Hz 60Hz (kW) Refrigerant air temp. Air connection Page
Small
IDU4D 430 500 3.7 60°C
R134a 1 to 4
High inlet air temperature type IDU6D 640 750 5.5 R 1/2
Rated temperature Air cooled IDU8D 850 1000 7.5 55°C R 3/4
of 50 to 60°C
IDU11D 1300 –– R134a
11 R 3/4
IDU11C 1300 1500
IDU15C 2050 2400 15 55°C
Medium
R1
IDU22C/22C1 3150 3700 22
R22 5 to 8
IDU37C/37C1 5200 6100 37 R 1 1/2
IDU55C 7650 9000 55
50°C R2
IDU75C 10500 12400 75
R1
IDF22C/22C1 3150 3700 22 40°C
R22 13 to 15
IDF37C/37C1 5200 6100 37 R 1 1/2
IDF55C 7650 9000 55
R2
IDF75C 10500 12400 75
For medium air pressure With terminal block For cool compressed With motor operated
Max. operating pressure 1.5MPa for signal air output. auto drain.
Options With terminal block for With anti-corrosive With circuit breaker. 19 to 20
run & alarm signals and treatment of copper tube. With power cord
remote operations With evaporation connection.
thermometer Water cooled condenser.
Technical Data Pressure dew point–Condensed water calculation chart, Pressure dew point temperature–Atmospheric pressure dew point temperature conversion cart 25
Note) l/min (ANR) is for reference conditions of 20°C, 1 ATM and 65% relative humidity.
Features 2
Model Selection
1 Obtain the correction factor for the temperature from data
A or B and the correction factor for the air pressure from data C.
Temperature Data A or B =
Series IDU: Data A
IDF1D to 240D: Data B-1
IDF 370B: Data B-2
Note) l/min (ANR) is for reference conditions of 20°C, 1 ATM and 65% relative humidity.
Features 3
Model Selection
IDU22C1, 37C1 45 50 55 65 70
IDU55C, 75C 40 45 50 55 60
Ambient
temperature Outlet air pressure
(°C) dew point (°C) 5 10 15 5 10 15 5 10 15 5 10 15 5 10 15
25 0.60 1.35 1.35 0.60 1.35 1.35 0.60 1.35 1.35 0.60 1.35 1.35 0.60 1.35 1.35
30 0.60 1.25 1.35 0.55 1.20 1.35 0.50 1.10 1.35 0.50 1.05 1.35 0.50 1.05 1.35
32 0.60 1.25 1.35 0.55 1.15 1.35 0.50 1.00 1.30 0.45 0.95 1.25 0.45 0.95 1.25
35 0.50 0.95 1.25 0.45 0.85 1.15 0.35 0.75 1.05 0.30 0.70 1.00 0.30 0.70 1.00
40 0.25 0.70 1.00 0.20 0.65 0.90 0.15 0.55 0.80 0.10 0.50 0.80 0.10 0.50 0.80
Features 4
Refrigerant R134a
Series IDU Small
3D, 4D, 6D, 8D
How to Order
IDU 3D 1 C
4D 2 E
6D 4 H
8D 6 L
M
R
Voltage S
100VAC (50Hz) T
100 to 110VAC (60Hz) 1
200VAC (50Hz)
Single 200 to 220VAC (60Hz)
2
phase 240VAC (50Hz)
220 to 240VAC (50Hz) 4
220VAC (50Hz) 6
Air
Model compressor Refrigerant
3D 2.2kW
4D 3.7kW
R134a
6D 5.5kW
Model and voltage combinations
8D 7.5kW
Voltage 1 2 4 6
100VAC (50Hz) 200VAC (50Hz) 220 to 240VAC
240VAC (50Hz) 220VAC (50Hz)
Model 100 to 110VAC (60Hz) 200 to 220VAC (60Hz) (50Hz)
3D
4D
6D
8D
1
Refrigerated Air Dryer Series IDU Small
Standard Specifications/Models
Specification Model IDU3D IDU4D IDU6D IDU8D
Air flow rate Note 2) 50Hz 300 430 640 850
Pressure switch
Capillary tube Fan motor
Condenser
Compressor
Compressed Compressed
IDU4D Compressed
Reheater IDU6D, 8D air inlet air outlet
air outlet
Drain separator
Compressed
air inlet Aftercooler
Fan motor
Drain outlet
Evaporation
Cooler thermometer
Aftercooler
Fan motor Capacity
Cooler reheater
control valve
Auto drain
Capacity Drain outlet
Pressure switch Condenser control valve
Valve
Capillary tube Fan motor
Condenser Pressure switch Capillary tube
Compressor
Fan motor
Compressor
2
Series IDU Small
IDU3D, 4D
Illuminated switch
E D B A
Ventilation
air inlet
C
Ventilation direction
F
[100VAC specification]
Power cord
(900)
[200 to 240VAC
specification]
J
Terminal block
L Drain tube
H 63 20 K
4-ø13
[200 to 240VAC specification]
Power cord outlet
3
Refrigerated Air Dryer Series IDU Small
IDU6D, 8D
Compressed Compressed
air inlet air outlet
(315)
600 220 (60)
(141)
(85) (445)
Illuminated switch
Evaporation thermometer
(B)
A
[200 to 240VAC
specification]
Terminal block
D
(159)
250
C 4-ø13
278 Drain port
Rc 1/4 450 65
[100VAC specification]
Power cord
∗ Auto drain is packed together with air dryer. (Some assembly is required.)
Model Port size A B C D
IDU6D R 1/2 710 760
560 551 240 75
IDU8D R 3/4 810 860
: Power source 220 to 240VAC
4
Refrigerant R22, R134a
Series IDU Medium
11D, 11C, 15C, 15C1, 22C, 22C1, 37C, 37C1, 55C, 75C
How to Order
IDU 11D 1 C
11C 2 E
15C 3 H
22C 4 L
22C1 6 M
37C R
37C1 Voltage S
55C Single phase 100VAC (50Hz) T
75C 100 to 110VAC (60Hz) 1
Single phase 200VAC (50Hz)
200 to 220VAC (60Hz) 2
Three phase 200VAC (50Hz)
200 to 220VAC (60Hz) 3
Note 1) Options for "-4" and "-6" are not currently available. Please contact our
Single phase 240VAC (50Hz)
220 to 240VAC (50Hz) 4 subsidiaries if necessary.
Note 2) A combination of two options is standard. A combination of three or
more optional items is handled as a special order product.
Note 3) 200 to 240VAC is "S" specification standard.
Single phase 220VAC (50Hz) 6 Note 4) Combinations of M and H, H and M, R and S, S and T, L and M are
not available.
Note 5) Option "T" is not available for IDU55C and 75C-4/6.
Air Option
Model Refrigerant C E H L M R S T
compressor
Optional
With With terminal
11D R134a specification With For With With motor With With block for run
11kW anti-
11C corrosive evaporation high air heavy duty operated circuit power cord & alarm
Model treatment thermometer pressure auto drain auto drain breaker connection signal
15C 15kW
22C/22C1 22kW 11C/11D
R22 15C
37C/37C1 37kW
Standard
75C Note 5)
5
Refrigerated Air Dryer Series IDU Medium
Standard Specifications/Models
Specification Model IDU11D IDU11C IDU15C IDU22C IDU22C1 IDU37C IDU37C1 IDU55C IDU75C
Air flow rate Note 2) 50Hz 1300 1300 2050 3150 5200 7650 10500
Operation Principles
Compressed Compressed
IDU11D, 11C, 15C air inlet air outlet
Humid hot air entering the air dryer is cooled in the after-cooler.
It then enters the reheater to creat an initial condensation with
Aftercooler
cooled and dehumidified air. The hot air is cooled further and
Fan motor dehumidified inside the cooler as heat is transferred to the
refrigerant. The water vapor condensed by the cooling process is
cooled and discharged automatically through the auto drain.
Evaporation Cool air is then heated again inside the reheater (heat is
thermometer Outlet air
pressure gauge transferred from incoming hot air), before leaving the air dryer.
Cooler reheater
Auto drain
Compressed Compressed
Capacity Drain outlet
control
IDU22C to 75C air inlet air outlet
Valve
valve
Accumulator Condenser Pressure switch Capillary tube
Fan motor Aftercooler
Compressor Outlet air pressure
gauge
Fan motor
Evaporation
thermometer
Cooler reheater
Auto drain
Capacity Capillary tube Drain outlet
control valve
Valve
Accumulator Condenser Pressure switch
Compressor Fan motor
6
Series IDU Medium
Compressed Compressed
air inlet air outlet
(F)
620 A (68)
Run light
(91) (445) (D)
Stop switch
Operation switch
Ventilation Ventilation
direction direction
(Aftercooler) Outlet air
pressure gauge
[200 to 240VAC specification]
Terminal block Evaporation Ventilation
thermometer
air outlet
Ventilation Valve
(C)
air inlet (77)
B
[200 to 240VAC specification]
Power cord outlet
Ventilation Ventilation
direction direction
(Condenser)
(E)
G
J Drain port
K
H 470 65
Rc 1/4
∗ Auto drain is packed together with air dryer. (Some assembly is required.)
Model Port size A B C D E F G H J K
IDU11C/11D R 3/4 260 910 959 152 157 363 289 317
571 580 30 70
IDU15C R1 280 960 1009 175 207 383 309 337
: Power source 220 to 240VAC
7
Refrigerated Air Dryer Series IDU Medium
Compressed Compressed
air inlet air outlet
(K)
B
A (H)
(F) (G) (E)
Run light
Operation switch
(Aftercooler) Stop switch (Aftercooler)
Outlet air pressure gauge
Evaporation thermometer Ventilation air outlet
(D)
C
(I)
Ventilation air inlet Ventilation direction Ventilation direction
L
G
P Drain port
M N 65
Rc 1/4 4-ø13
∗ Auto drain is packed together with air dryer. (Some assembly is required.)
Model Port size A B C D E F G H I J K L M N P Q
IDU22C1/22C R1 300 750 1155 1235 71 70 445 63 642 219 398 328 356 600 700 700 50 90
IDU37C1/37C R 1 1/2 360 830 1260 1350 112 136 550 68 722 269 463 388 416 680 780 776 50 90
IDU55C R2 405 850 1340 1440 87 155 530 68 722 267 508 433 461 700 800 800 50 95
IDU75C R2 425 850 1475 1575 87 220 530 68 722 317 528 453 481 700 800 800 50 95
: Power source 220 to 240VAC
8
Refrigerant R134a
Series IDF Small
1D, 2D, 3D, 4D, 6D, 8D
How to Order
IDF 1D 1 A
2D 2 C
3D 4 E
4D 6 H
6D L
8D M
Voltage R
100VAC (50Hz) S
100 to 110VAC (60Hz) 1 T
200VAC (50Hz)
Single 200 to 220VAC (60Hz)
2
phase 240VAC (50Hz)
220 to 240VAC (50Hz) 4
Note 1) A combination of three or more optional items is handled as a special
220VAC (50Hz) 6 order product.
Note 2) Single phase 220 to 240VAC is "S" specification standard.
Note 3) Combinations of H and M, R and S, S and T, A and H, L and M are
not available.
Air Note 4) Option "T" is not available for IDF6D, 8D-4 and -6.
Model Refrigerant
compressor
Option
1D 0.75kW A C E H L M R S T
2D 1.5kW Optional
With With For With With With With With terminal
3D 2.2kW specification With cool block for run &
R134a compressed
anti- evaporation medium air heavy duty motor circuit power cord alarm signal and
4D 3.7kW corrosive operated
Model air output treatment thermometer pressure auto drain auto drain breaker connection remote operation
6D 5.5kW
1D
8D 7.5kW
2D
3D
4D
Note 4)
6D
Standard Note 4)
8D
∗ Refer to pages 19 and 20 for further information on options.
9
Refrigerated Air Dryer Series IDF Small
Standard Specifications/Models
Specification Model IDF1D IDF2D IDD3D IDF4D IDF6D IDF8D
Air flow rate Note 2) 50Hz 100 200 300 430 640 850
Operation Principles
IDF1D IDF2D, 3D IDF4D
Drain separator Compressed Drain separator Compressed Compressed Reheater
Compressed air inlet
air inlet air outlet Drain
air inlet Compressed
Cooler Compressed Cooler separator
Reheater air outlet
air outlet
Reheater Drain outlet Drain Cooler
outlet
Drain outlet
Capacity control
Capacity control valve
valve
Capacity control
Pressure Condenser valve
Pressure switch
Fan motor
switch Capillary tube
Capillary Condenser Compressor Pressure
switch
tube Fan motor Compressor Capillary tube Condenser
Fan motor Compressor
IDF6D, 8D
Hot humid air entering the air dryer is cooled by the cooler. At that time, Compressed
condensed moisture is separated from the air by the drain separator and air inlet Compressed
automatically discharged. The dried clean air is heated by the reheater to Evaporation air outlet
about the ambient temperature, and is then discharged from the air dryer thermometer
outlet.
Cooler reheater
Auto drain
Drain outlet
Capacity control valve
Pressure
Compressor Condenser switch Capillary tube
Fan motor
10
Series IDF Small
IDF1D, 2D, 3D
Illuminated switch
E D B A
Ventilation
direction
C
F
[100VAC specification]
Power cord (900)
J
H Drain tube
M N K L
[200 to 240VAC specification]
Power cord outlet
[200 to 240VAC specification]
Terminal block
IDF4D
Illuminated switch
Inspection grill
Ventilation direction
606
469
[100VAC specification]
Power cord (900)
67
179
63 20 202
[200 to 240VAC 336
specification]
Power cord outlet [200 to 240VAC specification] 4-ø13 Drain tube
Terminal block
11
Refrigerated Air Dryer Series IDF Small
IDF6D, 8D
Compressed Compressed
air inlet air outlet
(315)
(60)
220
600
120 (72) 410 (456) (141)
Evaporation thermometer
Ventilation Ventilation air outlet
air inlet
[200 to 240VAC specification]
Terminal block
Ventilation
(570)
520
Ventilation direction direction
240 75
(159)
Power cord outlet
250
560 551 450 65
278 4-ø13
[200 to 240VAC specification]
Power cord outlet
Drain port
Rc 1/4
: In case of 200VAC. Dimension shown on the right is for 220 to 240VAC.
( ): Dimension within bracket is for air dryer with option A, with cool compressed air output.
Air inlet and outlet are reversed for air dryer with option A, with cool compressed air output.
∗ Auto drain is packed together with the air dryer. (Some assembly is required.)
Model Port size
IDF6D R 1/2
IDF8D R 3/4
12
Refrigerant R22
Series IDF Medium
11D, 11C, 15C, 15C1, 22C, 22C1, 37C, 37C1, 55C, 75C
How to Order
IDF 11D 1 A
11C 2 C
15C 3 E
15C1 4 H
22C 6 L
22C1 M
37C R
Voltage
37C1 S
Single phase 100VAC (50Hz)
55C 100 to 110VAC (60Hz) 1 T
75C Single phase 200VAC (50Hz) W
200 to 220VAC (60Hz) 2
Air
Model compressor Refrigerant Three phase 200VAC (50Hz)
11D
11kW
R134a 200 to 220VAC (60Hz) 3
11C
Single phase 240VAC (50Hz)
15C/15C1
22C/22C1
15kW
22kW R22
220 to 240VAC (50Hz) 4 Note 1) A combination of two is standard. A combination of three or more
optional items is handled as a special order product.
37C/37C1 37kW Note 2) 200 to 240VAC is "S" specification standard.
55C
75C
55kW
75kW
Single phase 220VAC (50Hz) 6 Note 3) Combinations of A and H, H and M, R and S, S and T are not
available.
Note 4) Options "T" and "W" are not available for IDF37C, 55C and 75C-4/6.
Option
A C E H L M R S T W
Optional
With With
specification With cool anti- For medium With With motor With With With terminal Water
compressed evaporation air pressure heavy duty operated circuit power cord block for run cooled
corrosive thermometer auto drain auto drain
Model air output treatment breaker connection & alarm signal condenser
11C/11D
15C/15C1
Standard
22C/22C1
Standard
Note 4) Note 4)
37C/37C1
Note 4) Note 4)
55C
Note 4) Note 4)
75C
∗ Refer to pages 19 and 20 for further information on options.
13
Refrigerated Air Dryer Series IDF Medium
Standard Specifications/Models
Specification Model IDF11D IDF11C IDF15C IDF15C1 IDF22C IDF22C1 IDF37C IDR37C1 IDF55C IDF75C
Air flow rate Note 2) 50Hz 1300 2050 3150 5200 7650 10500
Operation Principles
IDF11D, 11C, 15C, 15C1
Compressed
Compressed
air inlet air outlet Hot humid air entering the reheater is precooled by
Evaporation dehumidified cool air. (The hot air is cooled further
thermometer Outlet air
pressure gauge and dehumidified inside the cooler as heat is
transferred to the refrigerant. The water condensed
Cooler reheater
by the cooling process is collected and discharged
automatically by the auto drain.) Finally, the cool
Auto drain dehumidified air is heated in the reheater by hot inlet
air and discharged in a dry state.
Capacity Drain outlet
control valve
Accumulator Pressure
Condenser switch Capillary tube
Compressor Fan motor
Cooler reheater
Auto drain
Capacity Capillary tube
control valve Drain outlet
Pressure
Accumulator switch
Condenser Fan motor
Compressor
14
Series IDF Medium
Compressed Compressed
air inlet air outlet
(J)
B A (68) IDF11D, 11C, 15C, 15C1
Run light
(F) (G) (E)
Stop switch
(H)
Operation switch
Outlet air pressure gauge
Evaporation thermometer Ventilation
air outlet
Ventilation [200 to 240VAC specification]
air inlet Terminal block
Ventilation
(D)
C
Ventilation direction
direction
[100VAC specification]
(Condenser) Power cord
IDF11C, 15C
(I)
K
P
N M 65
L 4-ø13
Ventilation
air outlet
M 65
4-ø13
∗ Auto drain is packed together with the air dryer. (Some assembly is required.)
Model Port size A B C D E F G H I J K L M N P
IDF11C/11D R 3/4 260 620 570 630 152 131 (85) 405 (450) 77 157 363 289 317 470 580 580 70 65
IDF15C/15C R1 280 620 620 680 175 131 (85) 405 (450) 77 207 383 309 337 470 580 580 70 65
IDF22C/22C1 R1 295 750 680 760 183 98 405 (530) 642 199 398 323 351 600 700 700 70 30
IDF37C/37C1 R 1 1/2 320 830 730 810 208 98 405 (610) 722 249 423 348 376 680 776 780 70 30
IDF55C R2 405 850 850 930 85 98 405 (610) 722 247 508 433 461 700 800 800 75 30
IDF75C R2 425 850 900 980 85 98 405 (610) 722 297 528 453 481 700 802 800 75 30
: Power source 200VAC. Dimension shown on the right is for 220 to 240VAC.
( ): Dimension within bracket is for air dryer with option A, with cool compressed air output.
Air inlet and outlet are reversed for air dryer with option A, with cool compressed air output.
15
Refrigerant R407C, R22
Series IDF Large
120D, 150D, 190D, 240D, 370B
How to Order
Refrigerant R407C
120D, 150D Options
Model Voltage (No options for standard specification models)
IDF 120D 3 C
150D 7 M
190D 8 R
240D 9 W
220V
Symbol
3
Voltage
200/200 to 220VAC (50/60Hz)
240V Note 2) Possible to combine 2 options.
When requiring 3 options or more,
7 Three
phase
380VAC (50Hz) 400V it is made to order.
8 415VAC (50Hz)
Air
Model compressor Refrigerant
9 Built-in transformer 440V Option
C M R W
Refrigerant R22
Port
370B Size size Voltage Options (No options for standard specification models)
Symbol
X202 X204 X205
16
Series IDF Large
Refrigerated
50Hz 2.5 4.0 4.9 6.3 8.1 air dryer
200AVC
Power consumption 60Hz 3.1 5.0 5.9 7.6 9.5
Auto drain
(kw)
380AVC 2.1 3.3 – – –
50Hz
415AVC 2.2 3.4 – – –
200AVC 30 50 50 60 80
Circuit breaker (A) 380AVC
15 20 – – –
451AVC
Condenser Air cooled Water
cooled
Refrigerant R407C R22
Air connection 2 1/2B flange 3B flange 4B flange 6B flange
Drain connection (Rc) Rc 1/2 Rc 3/8
Auto drain ADH4000-04 ADM200-042-8
Weight (kg) 330 350 450 660 1100
Front panel: Munsell
Body panel: Munsell 10Y8/0.5 (White) 2.5PB5/8.5 (Blue)
Coating color Other panels (Except
Base: Black base): Munsell N-8
(White)
Applicable compressor (kw) 120 150 190 240 370
Note 1) The data for l/min (ANR) refers to the conditions of 20°C, 1atm. pressure and relative humidity of 65%.
Note 2) This is made to order.
Operation Principles
IDF120D to 240D IDF370B
Compressed air inlet
Air reheater Air cooler Compressed air outlet
Compressed (humid and high
air inlet temperature air) (dry and warm air) Volume
Pressure gauge control valve
Condenser Accumulator Temperature
expansion valve
Compressed
air outlet Auto drain
Evaporation Drain
thermometer
Low pressure switch Capillary tube
High temperature humid air is cooled in the reheater . Then it is further cooled
to a specified temperature using the evaporation heat in the air cooler . The oil
mist and moisture occurring due to condensation is exhausted through the auto
drain . Cooled and dehumidified air is returned to the air reheater and heat
is transferred from the incoming high temperature air. It is then exhausted out of
the air dryer as dry air.
17
Refrigerated Air Dryer Series IDF Large
K Port size
A (80) B 100 (JIS 10K) D
F
C
Compressed
Power supply air outlet
cable entry
Rc 1/2
E
J
200
G 650
Anchor bolt hole H I
4-ø20
IDF370B
Compressed Compressed
air inlet air outlet
Port size
(400)
(280) (310) (JIS 10K 6B)
Power supply
cable entry
1670
Cooling water
100
outlet
(190)
(Rc 1 1/4)
(250)
Cooling water
inlet
(Rc 1 1/4)
(90)
(210)
75 650 (390) 1050
(800) Rc 3/8
1810
18
Series IDU/IDF
Option Specification Refer to pages 1, 5, 9, 13 and 16
for "How to order" of options.
(A)
discharge port
IDU75C 463 IDF75C 447
This minimizes the corrosion of the copper and copper alloy parts when the Rc 3/8
air dryer is used in an atmosphere containing hydrogen sulfide or sulfurous IDF120D 464
acid gas. This option extends the service life. IDF150D 464
Special epoxy coating of copper tube and copper alloy parts. IDF190D 526
The coating is not applied on the heat exchanger or around electrical parts, ∗ Motor operated auto drain is packed together with main unit. IDF240D 690
where operation may be affected by coating. Assembly is required.
E
Option symbol
R With circuit breaker X202 (IDF220B, 370B)
With evaporation thermometer
A circuit breaker with bowl is attached to the side of the air dryer. This saves
A thermometer (pressure gauge) indicating the evaporating temperature of the additional electrical wiring at the time of installation. (IDF120D to 370B do not
refrigerant is attached to the operation panel, facilitating maintenance and daily have an electric leakage detection function.)
checks. IDU6D to 75C, IDF6D to 370B standard. IDU6D to 75C IDF370B
Option symbol IDF6D to 75C
H For medium air pressure IDF120D to 240D
No fuse breaker
(B)
This option provides a heat exchanger, auto drain, air pressure gauge and
ball valve, etc., with a medium pressure capability. This is different from the
Power
standard specifications. Maximum operating pressure is 1.5MPa. cord
outlet
Option symbol
L With heavy duty auto drain
ø35
Ground fault
circuit breaker
A dryer with heavy duty auto drain (ADH4000-04) is installed instead of the with bowl
float type auto drain (INA20-41-04), which is used for standard models to
discharge drainage. IDF120D, 150D,190D, 240D standard.
Note ) For IDF370B, option L is assigned as X205.
Model B Breaker capacity Sensitivity current
Model A Model A IDU6D, IDF6D
IDU6D 210 IDF6D 210 IDU8D, IDF8D 10A (100VAC)
IDU8D 210 IDF8D 210 IDU11C, IDF11C 5A (200VAC)
IDU11C 208 IDF11C 208 IDU15C, IDF15C
95
IDU15C 258 IDF15C 258 IDU22C1, IDF22C1
10A
IDU22C1 270 IDF22C1 250 IDU37C1, IDF37C1
IDU37C1 320 IDF37C1 300 IDU55C, IDF55C 15 to 30mA
15A
IDU55C 318 IDF55C 298 IDU75C, IDF75C
IDU75C 368 IDF75C 348 IDF120D 69 30A
IDF120D 365 IDF150D 94 45A
IDF150D 365 IDF190D 50A
95
IDF190D 427 IDF240D 60A
IDF240D 592 IDF370B 156 80A
19
Option Specification
Model A B Model A B C D E
Back side
Power cord outlet (ø17) IDU6D 240 40 IDF37C1 425 375 75 153 225
Grommet with waist IDU8D 240 40 IDF55C 190 140 75 153 225
Cooling
IDU11C 30 49 water outlet IDF75C 208 158 66 144 181
IDU15C 30 49
Cooling
IDF6D 240 40 water inlet
A
IDF8D 240 40
E
IDF11C 65 40 Compressed
air pressure
D
B IDF15C 65 40 gauge
C
Drain B
Rc 3/8 A
With plug
Option symbol
T With terminal block for run & alarm signal and remote operation IDF120D to 240D
180 Cooling water outlet
With the optional terminal, in addition to connection of the power supply, the
air dryer can be started and stopped by remote control and an operation Compressed air
pressure gauge
failure signal can be obtained. (If no voltage contact is made, an operation
Cooling water inlet
225
C C
A
Model A B C Model A B C
IDU6D 240 38 70 IDF6D 240 38 70 Transformer box
(1795)
IDU75C 50 45 50 IDF75C 30 45 50
(440) 1700 ±3
4-ø20
(2240)
(Anchor bolt hole)
IDF370B
20
Accessories (Options)
Description Features Specifications Applicable dryer Dimensions
Base integrated
with transformer This is the base for integrating the __ IDU3D to15C
Page 23
transformer and air dryer. IDF4D to 75C
How to Order
Transformer separately installed Base integrated with transformer
IDF TR 1500 5 IDF TB 2
Volume Supply voltage Size order
Symbol Volume Applicable dryer Symbol Primary voltage Secondary voltage Model Symbol Applicable dryer
IDU3D-1 to11C-1, 110VAC (50Hz), 1 IDU3D, IDF4D
500 500VA 1
IDF1D-1 to11C-1 110 to 120VAC (60Hz) Single 2 IDU4D to 15C, IDF6D to 15C
1000 1kVA IDU15C-1, IDF15C-1 200, 220, 230, 240VAC (50Hz), turn 3 IDF22C1
2 100VAC (50Hz)
IDU22C1-3, 37C1-3, 200 to 260VAC (60Hz) Single 4 IDF37C1 to 75C
1500 1.5kVA 100 to 110VAC
IDF22C1-3, 37C1-3 380, 400, 415VAC (50Hz), phase Not available for IDF1D to 3D,
3 (60Hz)
IDU55C-3, 75C-3, 380 to 420VAC (60Hz) IDU22C to 75C.
4000 4kVA Compound
IDF55C-3, 75C-3 420, 440, 480VAC (50Hz),
4
7000 7kVA IDF120D 420 to 520VAC (60Hz)
9000 9kVA IDF150D 220VAC (50Hz),
5
11000 11kVA IDF190D 220 to 240VAC (60Hz)
200VAC (50Hz)
13000 13kVA IDF240D 380, 400, 415VAC (50Hz), Three Single
6 200 to 220VAC phase
18000 18kVA IDF370B 380 to 440VAC (60HZ) turn
(60Hz)
440, 460VAC (50Hz),
7
440 to 500VAC (60Hz)
220, 240, 380, 400, 415, 200VAC Three
8
440VAC (50/60Hz) (50/60Hz) phase Compound
IDU FL 22 C IDU BP 22 C
Applicable dryer Applicable dryer
Symbol Dryer Symbol Dryer Symbol Dryer Symbol Dryer Symbol Dryer Symbol Dryer
3 IDU3D 6 IDU6D 22 IDU22C1 3 IDU3D 6 IDU6D 22 IDU22C1
4 IDU4D 8 IDU8D 37 IDU37C1 4 IDU4D 8 IDU8D 37 IDU37C1
11 IDU11C 55 IDU55C 11 IDU11C 55 IDU55C
15 IDU15C 75 IDU75C 15 IDU15C 75 IDU75C
IDF FL 22 C IDF BP 22 C
Applicable dryer Applicable dryer
Symbol Dryer Symbol Dryer Symbol Dryer Symbol Dryer Symbol Dryer Symbol Dryer
1 IDF1D 6 IDF6D 22 IDF22C1 1 IDF1D 6 IDF6D 22 IDF22C1
2 IDF2D 8 IDF8D 37 IDF37C1 2 IDF2D 8 IDF8D 37 IDF37C1
3 IDF3D 11 IDF11C 55 IDF55C 3 IDF3D 11 IDF11C 55 IDF55C
4 IDF4D 15 IDF15C 75 IDF75C 4 IDF4D 15 IDF15C 75 IDF75C
Cannot be mounted on models with option "A" (IDF6D to 75C).
21
Accessories (Options)
Transformers
IDF-TR -1
A C
OUT PUT
Primary Secondary Weight
B
OUT PUT
220V
IDF-TR -3, 4 C
VOLUTAGE
SELECTOR
Weight
FUSE
Part No. Dryer Capacity Model Primary voltage Secondary voltage A B C D E F (kg)
B
Weight
ø25 Part No. Dryer Capacity Model Primary voltage Secondary voltage (kg)
IDF22C1-3 Three
IDF37C1-3 220V (50Hz) 200V (50Hz)
4-ø11 IDF-TR1500-5 1.5kVA phase 9
210 160 IDU22C1-3 Single 220 to 240V (60Hz) 200 to 220V (60Hz)
IDU37C1-3 turn
IDF-TR -5, 6, 7
Terminal
Weight
Part No. Dryer Capacity Model Primary voltage Secondary voltage A B C (kg)
block
45
C
380, 400, 415V (50Hz) 200V (50Hz)
IDF22C1-3, 37C1-3
IDF-TR1500-6 1.5kVA 380 to 400, 400 to 415, 275 259 240 18
IDU22C1-3, 37C1-3 415 to 440V (60Hz) 200 to 220V (60Hz)
440, 460V (50Hz)
IDF22C1-3, 37C1-3 200V (50Hz)
IDF-TR1500-7 1.5kVA 440 to 460, 275 259 240 18
Three phase
IDF-TR9000-8 IDF150D 9kVA 220, 240, 400 650 450 300 350 13 40 109
380, 400, 200V
IDF-TR11000-8 IDF190D 11kVA 415, 550 450 600 350 400 13 60 131
(50/60Hz)
4-øF A D IDF-TR13000-8 IDF240D 13kVA 440V 400 600 450 300 350 13 60 138
(50/60Hz)
IDF-TR18000-8 IDF370B 18kVA 400 650 450 300 350 13 40 179
22
Accessories (Options)
IDF-TR500-1 171 – 33
IDF4D-1 IDF-TR500-2 681 217 356 328 – 37
IDF-TR500-3.4 284 – 46
IDF-TB1 53
IDF-TR500-1 171 – 30
IDU3D-1 IDF-TR500-2 584 217 376 348 – 34
Transformer IDF-TR500-3.4 284 – 43
separately
IDF-TR500-1 171 39
installed
A
75
B
(C)
(C)
Port size
Part No. Applicable dryer A B C
Rc
Port size IDF-BP1C IDF1D 34 112 563
Part No. Applicable dryer A B C
Rc IDF-BP2C IDF2D 62 112 571
3/8
IDU-BP3C IDU3D 77 112 706 IDF-BP3C IDF3D 57 112 632
3/8
IDU-BP4C IDU4D 66 112 791 IDF-BP4C IDF4D 66 112 792
IDU6D, 8D, 11C, 15C, 22C1, 37C1, 55C, 75C IDF6D, 8D, 11C, 15C, 22C1, 37C1, 55C, 75C
Compressed Compressed
air outlet air inlet
Compressed Compressed
(E) Port size air outlet air inlet
(A) (D)
(B)
(C)
(C)
24
Technical Data
Pressure dew point — Condensed water calculation
ssure
45
pre
pheric
100%
40
Atmos
Amount of water in air g /m³
ity
Pa
umid 35
0.1M
80 %
60%
0.2
40%
ive h
0.3
0.4
0.5
0.6
30
0.7
0.8
Relat
25
Amount of condensed water
20%
1.0
20 18.2 – 3.0 = 15.2g/m³
1.5
15
10
3.0
0
–20 –10 0 10 20 30 40 50 60 0 10 20 30 40 50 60 70 80
Intake air temperature °C (atmospheric pressure) Air temperature (Pressure dew point) °C
[Example] If air at 30°C and 60% humidity is pressurized to 0.7MPa, the dew point of the air will be 62°C. ( ) If this is cooled to 25°C, the amount of
condensed water generated will be 15.2g/m³. ( ) Therefore, with an air flow rate of 3m³/min (22kW equivalent compressor), the amount of condensed
water per unit of time is 15.2 x 3 x 60 = 2736g/h.
20
10
1.5MPa
0 1.3MPa
1.1MPa
–10 0.9MPa
–20 0.7MPa
0.5MPa
–30 0.3MPa
0.1MPa
–40
Atmospheric
–50 pressure
–60
–60 –50 –40 –30 –20 –10 0 10 20 30
25
Series IDU/IDF
Safety Instructions
These safety instructions are intended to prevent a hazardous situation and/or
equipment damage. These instructions indicate the level of potential hazard by a
label of "Caution", "Warning" or "Danger". To ensure safety, be sure to observe
ISO 4414 Note 1), JIS B 8370 Note 2) and other safety practices.
Danger : In extreme conditions, there is a possible result of serious injury or loss of life.
Note 1) ISO 4414: Pneumatic fluid power -- Recommendations for the application of equipment to transmission and control
systems
Note 2) JIS B 8370: General Rules for Pneumatic Equipment
Warning
1. The compatibility of pneumatic equipment is the responsibility of the person
who designs the pneumatic system or decides its specifications.
Since the products specified here are used in various operating conditions, their compatibility for the
specific pneumatic system must be based on specifications or after analysis and/or tests to meet your
specific requirements.
2. Only trained personnel should operate pneumatically operated machinery and
equipment.
Compressed air can be dangerous if handled incorrectly. Assembly, handling or repair of pneumatic
systems should be performed by trained and experienced operators.
3. Do not service machinery/equipment or attempt to remove components until
safety is confirmed.
1. Inspection and maintenance of machinery/equipment should only be performed after confirmation of safe
locked-out control positions.
2. When equipment is to be removed, first confirm the safety process as mentioned above.
3. Before machinery/equipment is restarted, first confirm that safety measures are implemented, and
proceed with caution.
4. Contact SMC if the product is to be used in any of the following conditions:
1. Conditions and environments beyond the given specifications, or if product is used outdoors.
2. Installation on equipment in conjunction with atomic energy, railway, air navigation, vehicles, medical
equipment, food and beverages, recreation equipment, emergency stop circuits, press applications, or
safety equipment.
3. An application which has the possibility of having negative effects on people, property, or animals,
requiring special safety analysis.
26
IDU/IDF
Series
Air Preparation Equipment Precautions 1
Be sure to read before handling.
Warning Piping
1. When selecting equipment, first adequately
confirm the purpose for which it will be used, Caution
the required specifications and the operating
1. Preparation before piping
conditions (pressure, flow rate, temperature,
Before piping is connected, it should be thoroughly blown out
environment), etc. Then select equipment with air (flushing) or washed to remove chips, cutting oil and
from the latest catalogs without exceeding other debris from inside the pipe.
the specification ranges. Contact SMC in ad- 2. Wrapping of pipe tape
vance regarding any questions. When screwing together pipes and fittings, etc., be certain that
2. Do not use for caisson shields, breathing, chips from the pipe threads and sealing material do not get in-
medical treatment or for blowing of medicine side the piping.
or food products which will enter the human Furthermore, when pipe tape is used, leave 1.5 to 2 thread
body. ridges exposed at the end of the threads.
This cleaning equipment is exclusively for use with industrial 3. Implement measures to prevent drainage
compressed air, and should not be used for other applications. from collecting inside piping.
If other application is unavoidable, give attention to safety
measures and contact SMC in advance. Drains should be installed in the lower sections of piping that
rises, or piping should be designed with a slight taper provided
3. This product cannot be used on board vehi- along the direction of flow so that drainage will not accumulate.
cles or vessels. 4. Confirm IN and Out ports.
This product cannot be used on board vehicles, vessels or oth-
When piping is being installed, take care to prevent incorrect
er transportation devices, because vibration will cause damage.
connection of the water and air sides, or the IN and OUT ports.
If this type of use is unavoidable, contact SMC in advance.
27
IDU/IDF
Series
Air Preparation Equipment Precautions 2
Be sure to read before handling.
Warning Warning
1. Do not use with fluids other than compressed 1. If an abnormality occurs, stop the com-
air. pressed air.
Cleaning equipment is designed exclusively for use with com- If abnormalities such as smoke, unusual odor or unusual noise
pressed air. Contact SMC in advance if a fluid other than com- occur, stop the inflow of compressed air, as this may indicate a
pressed air is to be used. fire.
2. Do not use compressed air which contains 2. When performing inspections, set the com-
chemicals, organic solvents or corrosive gas- pressed air pressure at zero.
es. When the compressed air side is to be disassembled for auto
Do not use compressed air containing chemicals, organic sol- drain inspection, separator element replacement or film module
vents, salt or corrosive gases, as this can cause damage replacement, etc., confirm that the pressure is at zero before
and/or malfunction, etc. proceeding.
28
Series IDU/IDF Specific Product Precautions 1
Air Preparation Equipment Precautions
Refer to pages 26 through 28 for safety instructions and cleaning equipment precautions.
Caution Caution
• Avoid locations where the air dryer will be in direct contact with <100VAC>
wind and rain. (Places where relative humidity is more than • Insert the power supply plug into an exclusive 100VAC power
85%) outlet.
• Avoid exposure to direct sunlight. • Install a circuit breaker (10A)∗ at the power supply.
• Avoid dusty or corrosive environments. • Be sure to ground the power supply prior to use.
Wind • Multiple-branch wiring is dangerous as it causes over-heating.
If it is used in
Rain • Do not extend the power supply cord length using an extension
the above
environments, cord.
select option C A voltage drop may cause the air dryer to stop operating.
(with anti- ∗ Use a circuit breaker having a sensitivity current of 30mA or
corrosive less and a rated current of 10A.
treatment). Dust Corrosive gas Exclusive Install circuit
100V power breaker (10A)
outlet
• Avoid places with poor ventilation and high temperature.
Valve closed
• Avoid installation on moving objects like trucks, ships, and so forth. Valve open
Drain Tube
Caution IDF6D to 75C
IDU6D to 75C
• A polyurethane tube of 10mm outer diameter is attached as the
drain tube for IDF1D to 4D and IDU3D, 4D. Use this tube to
discharge drainage.
• Do not use the drain tube in an upward direction. • When tightening piping at the air
Do not bend or crush the drain tube. inlet/outlet tube, the nozzle should
(Operation of auto drain be held firmly with a pipe wrench.
will stop and water will (IDF6D to 75C, IDU6D to 75C)
flow out through the air • Variation of operating conditions may cause condensate to form
outlet.) on the surface of the outlet piping. In the case of models larger
than IDF6D and IDU6D, roll thermal insulation around piping to
prevent condensate from forming.
• Vibration caused by the compressor should not be transmitted
through air piping to the air dryer.
• Do not allow the weight of piping to be applied directly to the air
dryer.
29
Series IDU/IDF Specific Product Precautions 2
Air Preparation Equipment Precautions
Refer to pages 26 through 28 for safety instructions and cleaning equipment precautions.
Caution Caution
When the air dryer is operated under the following conditions, the Allow at least three minutes
protection circuit is activated, the light goes off and operation before restarting the dryer. If
Please wait
stops. the air dryer is restarted within three minutes!
three minutes after being
• When compressed air stopped, the protection circuit
temperature is too high will be activated, the operating
• When compressed air flow light goes off and the dryer will
rate is too high not be activated.
• When ambient temperature
is too high (40°C or higher)
• When power supply is
beyond rated voltage by
±10%
• When ventilation port is obstructed by a wall or clogged with dust
Caution Caution
Use an air compressor of 100 l/min or greater air delivery with A crank case heater is installed on IDF370B. Energize the crank
IDF2D to 4D/IDU3D, 4D, and 300 l/min or greater air delivery case heater 12 hours prior to operation of the dryer to prevent
with IDF6D to 75C/IDU6D to 75C. trouble occurring in the refrigerant compressor.
Auto Drain
Caution
The auto drain may not function properly, depending on the quality
of compressed air. Check its operation once a day.
Caution
Remove dust from the ventilation area once a month using a
vacuum cleaner or an air blow nozzle.
30