CUSTOMER : PT DELTA SARANA ENGINEERING

P.O. NO. : 01/BT/DSE/X/2018 Dated : 22.10.2018

PROJECT : IDN - 150KV BATI-BATI - ITR

QTY. : 6 Nos.

LIST OF DRAWINGS BEING SUBMITTED FOR 150 kV C.T (TYPE OSKF-170)

SL DRAWING NUMBER DESCRIPTION OF DRAWING

01 OUTLINE DIAGRAM OF 150KV CT TYPE OSKF -170

02 RATING & CONNECTION PLATE OF 150 KV CT TYPE OSKF-170

03 SECTIONAL VIEW OF 150 KV CT TYPE OSKF-170

04 DETAIL OF SEC TERMINAL BOX 150 KV CT TYPE OSKF-170

PRPD: CHKD: APPRD:

ISO :
ALL EXPOSED FERROUS PARTS WILL BE HOT DIP GALVANIZED.

1. NOMINAL CREEPAGE DISTANCE: 5270 mm.


2. TOTAL WEIGHT OF C.T : 550 Kgs (APPROX.)
3. TOTAL SHIPPING WEIGHT: 700 Kgs (APPROX.)
4. GENERAL TOLERANCE WILL BE APPLICABLE
WHERE TOLERANCE IS NOT INDICATED

5. APPROX. PACKING DIMENSIONS = LENGTH 122'' x WIDTH 45" X HEIGHT 46"

EARTHING PAD DETAILS

CT RATIO: 600-1200/1-1A, 2000-4000/1-1A, 600-1200-1600/1A


NAME DATE
28JAN2019_5889

DRN. Arun.J 26.10.2018 OUTLINE DIAGRAM 110004774/10


FOR 150 kV C.T (TYPE OSKF-170)
CHD. Mayank 26.10.2018
FOR LINE BAY DENTE TELADAS
DCR No.:

APPD. S Mohan 26.10.2018 (120% EXTENDED PRIMARY CURRENT)

GE T&D India Limited 411-B-8441


01.

Rev:01
GE T&D INDIA LIMITED CURRENT TRANSFORMER
Instrument Transformers Division-India.
Signature_________
Date____________

TYPE OSKF-170
SL.No./YR. -
FREQ.50 Hz REF.STD. IEC:61869-1&2
kA
HSV/NSV 170/150 kV BIL 325/750 kV(r.m.s)/kVp Ith 40/1 Sec.
OIL Wt. 135 kg. TOTAL Wt. 550 kg. Idyn 100 kAp

RATIO 600-1200/1-1 2000-4000/1-1 600-1200-1600/1 "A"-COMPENSATING CORE


CONNECTION FOR CORE.No. 5
CORE NUMBER 1 2 3 4 5 PURPOSE:-TO MEET ISF AT RATIOS
our written permission.

RATED PRIMARY CURRENT (A) 1600


This must be returned

RATED SEC.CURRENT (A) 1 1 1 1 1 FOR 600/1 RATIO TAKE OUTPUT FROM 5S1-5S2 WITH 5S2-S' SHORTED.
Tender No.-------

FOR 1200/1 RATIO TAKE OUTPUT FROM 5S1-5S3 WITH 5S3-S' SHORTED.
OUTPUT (VA) - 20 - - 15 FOR 1600/1 RATIO TAKE OUTPUT FROM 5S1-5S4 WITH 5S4-S' SHORTED.
ACCURACY CLASS PX 5P PX PX 0.2S
A.L.F/I.S.F 20 _
<10
3-6 - 10 - 20 10 - 20 -
KPV (V) 647-1294 - 474-948 474-948 -
RATED EXTENDED PRIMARY CURRENT = 120% CONTINUOUS
150-75 - 100 - 50 100-50 - INSULATION LEVEL = CLASS "A"

P1 P2
"A"
1S1 1S2 1S3 2S1 2S2 2S3 3S1 3S2 3S3 4S1 4S2 4S3 5S1 5S2 5S3 S' 5S4

ATTENTION PRIMARY/SECONDARY CURRENT (A) 600/1 1200/1 1600/1 2000/1 4000/1


01. L.V.BUSHING SHOULD ALWAYS BE EARTHED
may it be copied or lent without

PRIMARY CONNECTION P1 - P2 P1 - P2 P1 - P2 P1 - P2 P1 - P2
& DISCONNECTED ONLY FOR TAN DELTA
Connection with our enquiry/

MEASUREMENT SECONDARY CONNECTION CORE-1 1S1 - 1S2 1S1 - 1S3


02. EARTHING LINK TO BE RECONNECTED FIRMLY CORE-2 2S1 - 2S2 2S1 - 2S3
GE T&D India Limited,

BEFORE C.T'S ENERGISED CORE-3 3S1 - 3S2 3S1 - 3S3


CORE-4 4S1 - 4S2 4S1 - 4S3
CORE-5 5S1 - 5S2 S' 5S1 - 5S3 S' 5S1 - 5S4 S'

431-B-5737 Rev:02

NOTES:-
01. OUTDOOR PROOF (MATERIAL : STAINLESS STEEL 0.5 mm THICK )
It is not to be used for any other purpose nor
on request. It is submitted as confidential in

CT RATIO: 600-1200/1-1A, 2000-4000/1-1A, 600-1200-1600/1A


This drawing is the property of

NAME DATE SCALE : NTS

DRN. Arun.J 26.10.2018 RATING & CONNECTION PLATE 110004774/10


22NOV2018_5769

23NOV2018_5774

FOR 150 kV C.T (TYPE OSKF-170)


DESCRIPTION

CHD. Mayank 26.10.2018 FOR LINE BAY DENTE TELADAS


(120% EXTENDED PRIMARY CURRENT)
REVISION

APPD. S Mohan
DCR No.:

DCR No.:

26.10.2018

DRG.No.

GE T&D India Limited 431-B-5737


01.

02.

Rev:02
It.
2

14
4

10

17

15
6
16

7 13

11

12

CT RATIO: 600-1200/1-1A, 2000-4000/1-1A, 600-1200-1600/1A


NAME DATE

DRN. Arun.J 26.10.2018 SECTIONAL VIEW 110004774/10


CHD. Mayank 26.10.2018 FOR 150 kV C.T (TYPE OSKF-170)
FOR LINE BAY DENTE TELADAS
APPD. S Mohan 26.10.2018 (120% EXTENDED PRIMARY CURRENT)

GE T&D India Limited 411-B-8442


Rev:00
X

4S2
4S3
5S1
5S2
5S3

5S4
1S1
1S2
1S3
2S1
2S2
2S3
3S1
3S2
3S3
4S1

S'

01

VIEW-X X

CT RATIO: 600-1200/1-1A, 2000-4000/1-1A, 600-1200-1600/1A


NAME DATE
DRN. Arun.J 26.10.2018 TYPICAL VIEW OF SECONDARY TERMINAL 110004774/10
CHD. Mayank 26.10.2018
BOX FOR 150 kV C.T (TYPE OSKF-170)
FOR LINE BAY DENTE TELADAS
APPD. S Mohan 26.10.2018 (120% EXTENDED PRIMARY CURRENT)

GE T&D India Limited 422-B-3995


Rev:00