Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

CIRED 22nd International Conference on Electricity Distribution Stockholm, 10-13 June 2013

Paper 0357

CONDITION ASSESSMENT AND FAULT DIAGNOSIS OF TWO LOAD TAP CHANGERS


USING DISSOLVED GAS ANALYSIS

Hoda MOLAVI Alireza ZAHIRI Katayoun ANVARIZADEH


Niroo Research Institute – Iran Niroo Research Institute – Iran Australia
hmolavi@nri.ac.ir azahiri@nri.ac.ir k_anvarizadeh@yahoo.com
hoda.molavi@hotmail.com
measurement, infrared thermography, chemical implants
ABSTRACT which are used as condition monitoring and diagnostic
methods to detect the incipient signs of deterioration in
Considering the objectives of "condition based LTCs.
preventative maintenance strategy", condition assessment Among the mentioned techniques, dissolved gas analysis
was performed over two load tap changers of 125 MVA is accepted as a sensitive, informative and reliable
power transformers in 230/63 substations using dissolved technique [6] and is widely used in incipient faults
gas analysis (DGA). detection in transformers [7-9]. In the last few years the
The selected load tap changers were: (1) an MR M-type method has been recommended by IEEE Power & Energy
load tap changer and (2) an Elin load tap changer. society for fault detection in LTCs [10].
Choosing load tap changers of 230/63 kV power This technique is based on the determination of types and
transformers are quite reasonable since the mentioned amounts of dissolved gases in oil, as well as interpretation
power transformers are the most frequently being used of the obtained results. Since LTCs contain switching
power transformers in Iran. contacts immersed in the insulating oil, as byproducts of
The oil samplings were performed according to normal operation, combustible gases (especially
ASTM D 3613 standard, in two stages and in a three- hydrogen, methane, ethane, ethylene and acetylene) are
month interval. Furthermore, samples were analyzed for usually formed [10, 11]. Despite the variability of gas
dissolved gases considering ASTM D 3612 standard. accumulation even under normal conditions in non-faulty
equipment, it is possible to discern certain patterns which
INTRODUCTION can be used to distinguish between normal and faulty
Load tap changers (LTCs) for power transformers are the behavior of the equipment in many cases [10]. Unusual
only movable part of power transformers and they suffer gas concentrations and also gas concentrations ratios have
from various aging mechanisms [1]. LTCs are essential been found to be useful indicators of the faults presence
components of the electrical networks and it has been [10, 12].
estimated that more than 30% of all transformer failures
are due to faulty LTCs [2], [3]. Mechanical malfunction, PERFORMANCE PROCEDURE
increased contact resistance, localized thermal stress,
material failure, breakdown of the insulating oil (coking), The Pilot LTCs
contact wear, improper design or high loads cause
Two load tap changers of 125 MVA power transformers
common failures in LTCs [2].
in 230/63 substations were selected as pilot LTCs due to
Among the classical maintenance strategies; corrective
the fact that 230/63 kV transformers are considered as the
maintenance, period based preventative maintenance and
most frequently being used power transformers in Iran.
condition based preventative maintenance [4]; the latter is The selected load tap changers were: (1) an MR M-type
the most accepted strategy for LTCs. This is due to and (2) an Elin load tap changers; which are called as
several advantages such as reduction in the required LTC1 and LTC2, respectively. The characteristic
number of maintenance visits, maintenance costs, information of the LTCs such as LTC's type and
possible interruptions to supply, number of catastrophic operating time has been presented in Table 1.
failures and also increment in the reliability of power
delivery and distribution [5] which are in accordance with Table 1. The characteristics of the pilot LTCs
utilities aim to extend the service intervals and monitor Characteristic LTC1 LTC2
equipment condition [2]. Manufacturer MR, Germany Elin, Austria
There are several methods such as dissolved gas analysis LTC's type MIIIY500 MLG3.720
in oil (DGA), dissolved metals in oil analysis, suspended Operating time 19 years 26 years
particles in oil analysis, acoustic and vibration Last Overhaul date August 2007 2003
fingerprints, motor power fingerprints, position
measurement of the driving axis, static and dynamic
The pilot LTCs had sampling valves in the bottom of the
resistance measurements, temperature difference

CIRED2013 Session 3 Paper No 0357


CIRED 22nd International Conference on Electricity Distribution Stockholm, 10-13 June 2013

Paper 0357

equipment which facilitated sampling procedure. equipment. In this condition using the Duval triangle 2,
Furthermore it was possible to have overhaul over the the fault type would be identified [17].
equipment in the near future which enables the authors to In addition of mentioned interpretation, a comparison
have eye inspection over the selected LTCs to compare between DGA results interpretation from two sampling
their predictions with the results from inspection. stages was performed.
It should be noted that according to manufacturer advice,
overhaul operation for LTC1 should be performed every RESULTS AND DISCUSSION
7 years or the number of operation of 80,000, depending
on which is reached first. For LTC2 the overhaul Figures 1 and 2 demonstrate dissolved gases in oil
operation criteria are every 5-7 years or the number of concentrations (including key, other and total dissolved
operation of 70,000, depending on which is reached first. combustible gases concentration (TDCG)) for each
sampling stage for both pilot LTCs, respectively.

Oil Sampling 12000


10595
1st stage
Oil samplings were performed in accordance with 10000
8717.566 2nd stage
ASTM D 3613 standard. The samples were tagged, 7908.236

Concentration (ppm)
8000
6847.511
packed and forwarded to the laboratory considering the 6151.339
6000 5473.3
mentioned standard [13].
There is some information for each sampling stage 4000

presented in Table 2. 2000

0
Table 2. The Information for Each Sampling Stage H2 C2H2 C2H4
50000
Pilot LTC LTC1 LTC2 45000
1st stage
st nd st nd 2nd stage
Sampling stage 1 2 1 2 40000
Concentration (ppm)

35000
Feb. May March June
Sampling date 30000
2012 2012 2012 2012 25000

No. of operation 2568 3162 203030 203528 20000

Tap position 16 14 20 22 15000


10000
Oil Temp. 27ºC 37ºC 28ºC 29ºC 5000
Environ. Temp. 21ºC 30ºC 18ºC 21ºC 0
CO CH4 CO2 C2H6 O2 N2 TDCG
Samples' Analyzing Procedure Figure 1. Dissolved gases concentrations for LTC1
The oil samples were analyzed using ASTM D 3612
18000
standard for determining dissolved gas type and amount 15546.4
15062.6
16421.7
16000 14218.4 1st stage
in a reliable laboratory [14]. 14000 2nd stage
Concentration (ppm)

12000

INTERPRETATION OF DGA RESULTS 10000


6307.767
8000
5852.439
Interpretation of DGA data for both LTCs was performed 6000
as following: 4000

First step: Comparison of each sampling stage data to the 2000


0
LTC monthly watch criteria (presented by Youngblood et H2 C2H2 C2H4
al. [15]) was carried out. If none of the concentrations 45000
exceeds the threshold values, the LTC performance is 40000 1st stage
2nd stage
concluded to be normal operation. 35000
30000
Second step: In case of exceeding one of the gas
Concentration (ppm)

25000
concentration from its threshold value, the possibility of 20000
fault presence was investigated by gas concentration ratio 15000
method presented in reference [16]. If the ratios were in 10000
the "Needs attention" range, the equipment is in normal 5000
0
operating condition. However, sampling in three-month
CO CH4 CO2 C2H6 O2 N2 TDCG
intervals is recommended. Figure 2. Dissolved gases concentrations for LTC2
Third stage: In the case of laying data in the "Possible
damage" or "Detected damage" range, fault exists in the

CIRED2013 Session 3 Paper No 0357


CIRED 22nd International Conference on Electricity Distribution Stockholm, 10-13 June 2013

Paper 0357

Using the LTC monthly watch criteria (1st step), it was The Triangle coordinates corresponding to DGA results
revealed that the concentrations of hydrogen, ethylene can be calculated using following equations:
and acetylene (key gases) for both sampling stages in CH 4
both pilot LTCs are beyond the criteria. Therefore, the %CH 4   100 (5)
CH 4  C 2 H 4  C 2 H 2
gas ratio method (2nd step) using following ratios should
C2 H 4
be applied. %C 2 H 4   100 (6)
C2 H 2  H 2 CH 4  C 2 H 4  C 2 H 2
FR  (1)
CH 4  C 2 H 6  C 2 H 4  C 2 H 2  CO  H 2 %C 2 H 2 
C2 H 2
 100 (7)
CH 4  C 2 H 6  C 2 H 4 CH 4  C 2 H 4  C 2 H 2
R1  (2) For LTC1 (Figure 3) the crossing point for both sampling
CH 4  C 2 H 6  C 2 H 4  C 2 H 2
stages were located in X3 section which corresponded to
CH 4  C 2 H 6  C 2 H 4
R2  (3) in progress thermal fault with light coking or increased
C2 H 2 resistance of the contacts or severe arcing. Therefore, it is
C2 H 4 recommended to test or inspect the LTC for signs of
R3  (4) faults. However, this is in spite of the fact that the number
C2 H 2
of tap changes is very low (much lower than 80,000) and
Calculated ratios for both sampling data of LTC1 showed
the number of years since last overhaul is less than 7
that, except R1 ratio which was laid in "Possible damage"
years (the recommended overhaul criteria by
range, all other ratios corresponded to "Needs attention"
manufacturer).
range. However, all ratios for LTC2 were laid in "Needs
attention" range.
To identify fault type in LTC1 and also to ensure the fault
absence in LTC2, the Duval triangle 2 was applied (3rd
step), as shown in Figures 3 and 4, respectively.

Figure 4. Condition assessment of LTC2 using the Duval


triangle 2 for the 1st and 2nd stage samplings

DGA data interpretation for LTC2 (Figure 4) shows that


Figure 3. Condition assessment of LTC1 using the Duval for the 1st sampling stage, the crossing point is located in
triangle 2 for the 1st and 2nd stage samplings N section which indicates the normal operation and fault
absence. While for the 2nd sampling stage, the crossing
point is placed in X3 section which related to in progress

CIRED2013 Session 3 Paper No 0357


CIRED 22nd International Conference on Electricity Distribution Stockholm, 10-13 June 2013

Paper 0357

thermal fault with light coking or increased resistance of Contact Coking", Proceedings of the Forty-
the contacts or severe arcing. In this case equipment Eighth IEEE Holm Conference on Electrical
inspection is recommended. contacts, 259-272.
Despite the recommended overhaul criteria by [3] EPRI Report #1001946, 2001, "Development of
manufacturer that the overhaul operation should have Load Tap Changer Monitoring Technique:
performed at least 2-5 years ago, LTC2 is in good Mechanism of Coking", Technical Progress.
condition in the 1st sampling stage. However, there are [4] P. Lyonnet, 1991, "Maintenance planning-
signs of fault presence in the 2nd sampling stage. methods and mathematics", Chapman and Hall.
Therefore performing overhaul for LTC2 is suggested, [5] M. A. Redfern and W. R. C. Handley, 2001,
"Duty based maintenance for on-load
but it is not an obligation.
transformer tap changers", Power Engineering
Society Summer Meeting, IEEE, vol.3, 1824-29.
CONCLUSIONS [6] N.A. Muhamad, B.T. Phung, T.R. Blackburn
Condition assessment was performed over two load tap and K.X Lai, 2007, "Comparative Study and
changers of 125 MVA power transformers in 230/63 Analysis of DGA Methods for Transformer
substations using dissolved gas analysis (DGA). Mineral Oil", IEEE Power tech, 45-50.
Interpretation of DGA data was carried out using [7] M. Duval, 2006, "Dissolved gas analysis and the
Threshold value method, Gas concentration ratio method Duval triangle", 5th AVO New Zealand
as well as the Duval triangle 2 method. The obtained International Technical Conference.
results from data interpretation were used in making [8] R. Cox, "The benefits of on-line DGA tap
decision for overhaul operation over the selected changer monitoring", Available at:
equipment. www.weidmann-diagnostics.com.
DGA data interpretation reveals that there were in [9] M. Duval, 2008, "Calculation of DGA Limit
progress thermal fault with light coking or increased Values and Sampling Intervals in Transformers
resistance of the contacts or severe arcing in the LTCs. in Service", IEEE Electrical Insulation
Performing overhaul for LTC1 is strongly recommended, Magazine, Vol. 24, 5, 7-13.
while it is not an obligation for LTC2 overhaul (regarding [10] IEEE Guide for Dissolved Gas Analysis in
its determined good condition in the 1st sampling stage). Transformer Load Tap Changers, IEEE Std
However, this is despite the suggested overhaul criteria C57.139, 2010.
by the manufacturers that recommend no overhaul for [11] EPRI Report #1006654, 2001, "Transformer
LTC1 and necessary overhaul for LTC2. Load Tap Changer Management, Diagnostics,
In case of impossibility for performing overhaul operation Contact Coking, and On-line Filtration".
over the LTCs in the near future, it is advised to perform [12] EPRI Report #1012350, 2006, "New Equipment
dissolved gas analysis in three-month intervals. This and Performance Design Review – LTC
would help to be aware of the equipment condition which Management Course Materials".
would avert catastrophic failures. [13] ASTM series, Vol. 10.03, "Electrical Insulation
Liquids and Gasaes, Electrical Protective
Acknowledgments Equipment, D3613-98 Standard Practices for
The authors would like to acknowledge NRI and also Mr. Sampling Electrical Insulating Liquids".
Marjanmehr, Mr. Jalali and Mr. Fathi for supporting this [14] ASTM series, Vol. 10.03, "Electrical Insulating
research. We also gratefully acknowledge the colleagues Liquids and Gases; Electrical Protective
in NRI: Mr. Zhaam, Mr. Ahmadi, Mr. Ghadimi and also Equipment, D 3612-02 Standard Test Method
Dr. Porkar from IGMC. Furthermore, special thanks go to for Analysis of Gases Dissolved in Electrical
Mr. Mosalrezaei, Mr. Ma'refat, and Mr. Asgari from Insulating Oil by Gas Chromatography".
EREC and also Mr. Sohrabi from BREC for their [15] R. Youngblood, C. Baker, F. Jakob, N. Perjanik,
"Application of Dissolved Gas Analysis to Load
cooperation and providing the pilot LTCs.
Tap Changers", Available at:
www.weidmannacti.com
REFERENCES
[16] H.U. Schellhase, I. Wilye, M. Lau and B. Ward,
[1] J. J. Erbrink, E. Gulski, J. Smit and R. Leich,
1999, "Load tap-changer diagnostics: a critical
2009, "Experimental model for diagnosing on-
review of the past ten years", EPRI.
load tap changer contact aging with dynamic
[17] M. Duval, 2008, "The Duval Triangle for Load
resistance measurements", 20th International
Tap Changers, Non-Mineral Oils and Low
Conference on Electricity Distribution, 1-4.
Temperature Faults in Transformers", IEEE
[2] H. Schellhase, R. G. Pollock, A. S. Rao and E.
Electrical Insulation Magazine, Vol. 24, 6, 22-
C. Korolenko, 2002, "Load Tap Changers:
29.
Investigations of Contacts, Contact Wear and

CIRED2013 Session 3 Paper No 0357

You might also like