Location GC 4 Wko-Viec Container: Punch Category A, B and C
Location GC 4 Wko-Viec Container: Punch Category A, B and C
AGI KOC
In outdoor unit addistional JB (IP66) box installed, no access to open oil inspection. Should change JB
1 A
location
2 AC NO 2 condnesing unit not explosion proof - replace with expolsion proof unit. A
4 Main untility panel reset push button operation tag should be provided in panel. A
5 Approved drawing (unit selection and approved units capacity)should be provided at site. B
7 Need apply, change over program while one unit trip by any fault - must be change over stand by unit. A
8 Louver with filter as per approved schedule need fix in let pressurization fan. A
12 Operation training with all change over, trip, fault details with vendor to maintenance team at site. C
Warranty period certificate spare parts such as PC board,contactor, condenser fan motor,blower motor blade
13
and blower must be supplied to KOC store.