Tool
458-8181 Calibration Tool
Calibration tool
458-8181
Note: Tool is enough to test 20 units Picture shows a unit
with a UMR option.
XQ1475 Methane Detector Replacement
(Schematic)
TB2-8
ELECTRONIC
SENSOR
WHITE TB1-WHT
RED TB1-RED
Testing
After calibration place the unit in Local Mode.
1.) Place the calibration tool on the sensor.
2.) Watch the % methane gas increase in value.
At 10% , DEIF Controller will display Gas Detected – Shutdown
3.) Remove calibration tool.
4.) Reset shutdown signal
5.) XQ1475 is now ready for service
Supplemental Information
Actual Methane Detector as installed
Note: Sensor can also be mounted using existing bracket and hardware.