Professional Documents
Culture Documents
Anly Temperature Controller
Anly Temperature Controller
AT-902 ( 9 6 x 9 6 ) AT-402 ( 4 8 x 9 6 )
CHARACTERISTICS :
Easy-to-use
PID function selectable
Relay or SSR ouput, selectable via DIP switch
Accepts thermocouple and platinum RTD inputs
Heating or cooling control selectable
Panel lock protection function
Sensor malfunction detection function
Available in 5 sizes : 48 x 48mm(1/16DIN), 48 x 96mm(1/16DIN), 72 x 72,
96 x 48mm, 96 x 96mm(1/4DIN)
TYPE SELECTION :
Dimension Series
(mm)
A T - 4 0 2
4=48x96
5=48x48
6=96x48
7=72x72
9=96x96
Pr oduc t is s u b j e c t t o c h a n g e w i t h o u t n o t i c e . H03
SPECIFICATIONS :
Rated frequency 50 / 60 Hz
Thermocouple K, J, R
Sensor input
(DIP SW. Setting) RTD Pt100
Relay 240VAC 3A
Control output
(DIP SW. Setting) SSR DC 24V
Weight AT-402 / 602 Approx. 187g, AT-502 Approx. 145g, AT-702 Approx.200g , AT-902 Approx. 241g
FEATURES :
SV-AL1L SV+AL1U
6 Band alarm OFF ON
SV
OFF
PV
CONNECTION :
AT-402 / 602 / 902 AT-502 AT-702
100~240VAC
100~240V
50/60 Hz
50/60 Hz
1 11 12 11 1 8
AC/DC
AC/DC
A
50/60 Hz
24~48V
1 6
AC/DC
2 12 2 9 B
ALM
NO 2 7 NO
3 13 3 10 B
COM COM
SSR
NO
3 8 A
OUT
OUT
4 14 COM 4 11
NC NC
OUT
4 9 B
5 15 NC 5 12
5 10 B
6 16 6 13
ALM
ALM
SSR
14 13
7 17 7 14
A 8 18 SSR
B 9 19
B 10 20 12 11
100~240V
50/60 Hz
1 6
AC/DC
ALM
2 7
NO
3 8 A
COM
OUT
4 9 B
NC
5 10 B
14 13
SSR
DIMENSIONS : (mm)
A A
A A
B B
B B
C
A D
A B C D E
AT - 402 48 96 8.0 83 90
AT - 502 48 48 8.0 83 44.5
B E AT - 602 96 48 8.0 83 44.5
AT - 702 72 72 8.0 83 66.5
AT - 902 96 96 8.0 83 90
AT-702
a b c d
+0.5 +0.5
AT - 402 45.5 -0 91-0 120 70
AT - 502 45.5 +0.5
-0 45.5 +0.5
-0 70 70
+0.5 +0.5
AT - 602 91 -0 45.5 -0 70 120
AT - 702 67.5 +0.5
-0
+0.5
67.5 -0 100 100
AT - 902 91 +0.5
-0 91 +0.5
-0 120 120