Duct Smoke Detector

Photoelectric Type 6266 Series


SPECIFICATION DATA

FEATURES
• INFRARED PHOTO-OPTIC SMOKE SENSING
CHAMBER
• SUITABLE FOR HIGH AIR VELOCITIES
- UL Model: 300 to 4000 ft/min (1.5 to 20.0 m/sec)
- ULC Model: 300 to 4500 ft/min (1.5 to 22.8 m/sec)
• USES STANDARD OR RELAY DETECTOR BASE
- Plugs in to base then easily installs into housing
- Allows interchange with Ionization Detector
• ALL FIELD WIRING TO BASE TERMINALS
- Wiring to base is same as that for Honeywell area
smoke detection products
6266C-001 • LOW STANDBY (SUPERVISORY) AND ALARM
CURRENT
• 2 OR 4-WIRE CIRCUIT CONNECTION
DESCRIPTION
The Honeywell 6266 Series Photoelectric Duct Smoke Testing — The detector sensitivity is preset at the factory
Detectors use the light scattering principle to ensure for added installation convenience. A special calibrated
reliable smoke detection. Advanced photo-optic technology Test Probe is available to test the detector's sensitivity
ensures fast response to products of combustion from both without the need for smoke generation or aerosol sprays.
fast burning "clean" fires and slow smoldering fires. The 6262A-001 Alarm Indicator/Test Switch can also be
Dependable solid state circuitry minimizes current drain connected for convenient testing.
during supervision and permits up to 30 smoke detectors to
be installed on a single circuit.
APPLICATION DATA
Duct smoke detectors continually sample airflow in a HVAC
duct and initiate an alarm condition at the associated The UL Listed 6266B-001 detector is usable in HVAC ducts
Honeywell Fire Alarm Control Panel whenever the quantity with air velocities ranging from 300 to 4000 ft/min (1.5 to 20
(percent obscuration) of combustion products in that air m/sec). The ULC Listed 6266C-001 detector is usable in
sample exceeds the detector's sensitivity setting. Upon HVAC ducts with air velocities ranging from 300 to 4500 ft/
activation, the detector may also energize an optional min (1.5 to 22.8 m/sec). Bothe detectors are intended for
5956A Fire Alarm LED Indicator and/or an associated installation into the Honeywell 6260A-100 Duct Smoke
6254A-003 Fire Alarm Relay. For more deteails, refer to the Detector/Sensor Housing (ordered separatley).
catalog sheet for the 6260A-100 Duct Smoke Detector/
Sensor Housing. Applications with Detector Relays —
Up to 30 duct detectors may be installed on any single 2-
Installation — The 6266 Series detectors plug in to a wire non-addressable circuit. However, whenever the
separately ordered detector mounting base (6251 Series). 6260A-100 duct detector assembly includes an optional
All field wiring connections are made to terminals on the 6254A-003 Fire Alarm Relay to be operated by the detector,
base. The detector assembly is then easily installed into the only one detector is permitted per circuit. Also, when relay
6260A-100 housing. The plug-in base is simple to wire and bases are used to control more than one function (eg.
also allows for convenient interchange with Honeywell elevator capture, fan shutdown, etc.) only one detector is
6264B-001 and 6264C-001 Ionization detectors. permitted per circuit , all other initiating devices, such as
Stability — An infrared LED combined with a high speed heat detectors, manual stations, waterflow switches, etc.,
light sensing photo diode within the sensing chamber gives must be connected to other initiating circuits.
the detector a natural stability, essentially eliminating false
alarms caused by transient electrical disturbances. Self-
compensating circuitry provides maximum stability against
the effects of aging and dust film accumulation.

® U.S. Registered Trademark


Copyright © 1995 Honeywell Inc. • All Rights Reserved
74- 1947
DUCT SMOKE DETECTOR

INSTALLATION AND MOUNTING TYPICAL WIRING


Honeywell recommends that duct detectors always be Maximum wire size #14 AWG (150 mm2).
installed in accordance with the latest recognized editions of
local and national fire alarm codes. Exhaust tube 6"
(150 mm) (supplied)
WARNING
Adhesive backed Slant on exhaust tube must be Duct detectors have specific
drill template directed away from the airflow. limitations. Duct detectors
are not a replacement for a
Sampling Tube building's regular fire detec-
Clearance Hole tion system. They are not a
substitute for an open area
Exhaust tube connector on the
housing is painted red smoke detector or for early
warning detection. Smoke
detectors are not designed
Smoke chamber to detect toxic gases which
can build up to hazardous
Duct Detector mounting
levels in some fires.
clamp (one of two)
These devices will not oper-
ate without electrical power.
6266 Series
As fires frequently cause
Duct Detector/Base power interruptions, you
CAUTION: Combination should discuss further safe-
Rubber stopper must
be installed into end of guards with your local fire
sampling tube. protection specialist.

Sampling tube
(ordered separately)
Air holes must be oriented
to face airflow Detector/Sensor locating pin
CAUTION: Do not bend.

Air sampling Neoprene gasket -


tube connector attached to housing

SPECIFICATIONS ORDERING INFORMATION


Catalog Number 6266B-001 6266C-001 Catalog Description Ship Wt.
Approvals UL ULC Number lb. (kg)
Sensitivity - Maximum: 0.65% Maximum: 0.5% 6266B-001 Photoelectric Duct Smoke Detector - UL 1.3 (0.6)
Obscuration per Minimum: 3.9% Minimum: 4.0% 6266C-001 Photoelectric Duct Smoke Detector - ULC 1.3 (0.6)
foot (305 mm) Factory Setting: Factory Setting: 6278-001A Calibrated Test Probe 0.25 (0.1)
1.8% nominal 1.42% nominal DETECTOR MOUNTING BASES
Air Velocity Range 300 to 4000 ft/min 300 to 4500 ft/min 6251B-001A Detector Mounting Base - UL 0.25 (0.1)
(1.5 to 20 m/sec) (1.5 to 22.8 m/sec)
6251C-001A Detector Mounting Base - ULC 0.25 (0.1)
Compatible
6251B-003 Detector Mounting Base with Relay - UL 0.3 (0.14)
Duct Detector 6260A-100
Housing (Contact rating: 5.0 A @ 28 V dc,
3.0 A @ 120 V ac Resistive)
Operating Voltage Minimum: 16 V dc
Range Maximum: 26 V dc 6251C-003 Detector Mounting Base with Relay - ULC 0.3 (0.14)
Nominal: 22 V dc (Contact rating: 5.0 A @ 28 V dc,
3.0 A @ 120 V ac Resistive)
Current Consumption Standby: 50 µA
(at nominal voltage) Alarm: 55 mA DUCT SMOKE HOUSING
Supervisory: determined by control panel 6260A-100 Duct Smoke Detector/Sensor Housing 6.5 (3.0)
Operating Altitude no limit - UL/ULC
Operating Tested from 32 to 120 deg F 6261-001 Air Sampling Inlet Tube - 8" (200 mm) 0.25 (0.1)
Temperature Range (0 to 49 deg C) 6261-002 Air Sampling Inlet Tube - 24" (600 mm) 0.5 (0.2)
Humidity Range 0% to 85% 6261-003 Air Sampling Inlet Tube - 42" (1.06 m) 1.6 (0.75)
Detection Source Light Scattering Method - Infrared LED 6261-006 Air Sampling Inlet Tube - 78" (1.98 m) 2.2 (1.0)
with light sensing photo diode 6261-010 Air Sampling Inlet Tube - 120" (3.05 m) 4.4 (2.0)

Home and Building Control Honeywell Home and Building Control Honeywell Asia Pacific Inc. Honeywell Europe S.A.
Honeywell Inc. Latin American Division Honeywell Limited - Room 3213-3225 3 Avenue du bourget
Honeywell Plaza 480 Sawgrass Corporate Parkway Honeywell Limitée Sun Hung Kai Centre 1140 Brussels
P.O. Box 524 Suite 200 155 Gordon Baker Road No. 30 Harbour Road Belgium
Minneapolis MN 55408-0524 Sunrise FL 33325 North York, Ontario Wanchai Hong Kong
M2H 3N7

74-1947 Rev. 3-95 www.honeywell.com