Multiple Causes - This 11 year old sample of 2-1/2 in. Total Failure - This extraordinary photo shows a
condenser water pipe failed at the threads due to a completely failed threaded nipple at a 24 in. main
combination of galvanic activity at the steel to brass condenser water return riser.
valve connection and a basic design flaw.
Accumulation of interior deposits at the valve first
The use of threaded schedule 40 steel pipe for condenser clogged the 1 in. nipple completely. Then, a
water use was an even greater factor - with over 50% of combination of general and galvanic corrosion caused
wall lost due to threading, and only 35 mils or 0.035 in. its failure and total separation - leaving those rust
remaining in that area. deposits to alone hold back 15 upper floors of water.
Amazing that it held!
 

Dry Sprinkler - Top and bottom view of dry Thread Failure - This is an extremely
fire sprinkler pipe showing virtually new common problem due to the use of thin wall
pipe on the top at left, and severely schedule 40 pipe in open water condenser or
corroded bottom pipe on the right. process cooling piping applications.

Water remaining at the bottom after While larger diameter main riser and
pressure testing typically creates distribution lines can be constructed of
accelerated wall loss along the bottom area schedule 40 pipe in most applications,
and lower sides. Pinholes are typically the schedule 40 for small diameter run-out lines
first indication of a problem, followed by a will not provide sufficient remaining wall
general and complete failure of the entire thickness and acceptable service life.
system.
 
Mold - A combination of poorly insulated chill Pinhole Leak - This 4 in. schedule 40 condenser
water pipe and an excessive humidity condition water system produced fine pinhole leaks after
combined to create a serious mold problem less than 4 years of service.
throughout this entire area.
Ultrasonic testing showed a generally high
While UT testing showed the corrosive corrosion rate of over 15 MPY, with random and
moisture effect against the steel pipe as isolated areas showing excessive corrosion rates
surprisingly minimal, mold had thoroughly exceeding 50 MPY. Areas of pipe showed 0.075 in.
contaminated the entire area, creating a health remaining, and further pinholes imminent. The
threat. All ceilings had to be opened, the loss of 0.237 in. of pipe wall for this size pipe itself
insulation removed, the pipe scraped and defines a corrosion rate exceeding 60 MPY - for
coated to prevent further rusting, and heavier which no piping system can survive.
insulation properly applied.

 
Extremely High Corrosion - A high corrosion Internal Deposits - Corrosion of steel pipe
rate of near 15 MPY destroyed this new results in iron oxide deposits of
piping installation in under 2 years. This approximately 19 times the volume of the
client was in the process of replacing 15 floors steel lost. The presence of internal deposits
of threaded 2 in. distribution piping therefore defines a corrosion problem, and
beginning at the bottom floors and working vice versa.
upward.
For the above domestic cold water pipe, loss
Performed halfway through the project, of water flow due to internal constriction was
ultrasonic testing showed that the new pipe actually the lesser threat. Wall loss at the
would fail before pipe replacement would be threads had reached the point of failure.
completed.
   
Cut Grooving - Thread Failure -
Victaulic and Six years of service
other brand under a 6 MPY
groove clamped corrosion rate left
piping systems this schedule 40
offer substantial condenser water
advantages in piping system with
piping only 33 mils or
construction. 0.033 in. of pipe
Rolling or wall remaining at
swagging the the threads -
groove into the therefore the leaks
pipe simply seen.
displaces the
metal inside, and Under normal
therefore no wall corrosion
loss results. conditions of 1-2
MPY, and using
Cutting the heavier schedule
groove, however, 80 pipe, this pipe
a sometimes would last for
used option, decades. However,
significantly its failure, prior to
lessens available any shut off valve,
wall thickness, required draining
and if combined of the entire
with a higher system for
corrosion rate - replacement.
will lead to
advanced joint
failure.
 
Maintenance Neglect - This roof level pipe Weld Failure - A relatively uncommon
near the cooling tower suffered both from the problem due to either inappropriate welding
outdoor elements and a constant over spray rod use or poor workmanship.
from the cooling tower itself.
This mechanical defect is often made worse
The pipe showed sufficient exterior pitting to by a high corrosion rate and can only be
reduce its remaining overall wall thickness to repaired by grinding away the weld and
approximately 0.130 in., requiring placement. rewelding it properly, or by total
replacement.

 
Weld Failure - Generally, a single leak of Pipe Repair? - Most often, pipe problems
failure problem may be attributed to a remain hidden until the first leak brings it to
random and isolated event. Further examples attention and further diagnosis and repairs
usually suggest a more system wide defect are quickly made.
with much greater threat potential.
Then again, some repairs are postponed, and
For welding failures such as above, and other postponed until no alternative remains -
mechanical questions, metallurgical testing actions which always increase the potential
and ultrasonic flaw detection are the two for significant damage, the need for
main diagnostic tools available. shutdown, and usually overall cost
 
Line Failure - This is a fairly typical form of Cast Pipe - Another example showing the typical
e at cast iron waste lines. Cast iron lines corrode at corrosion characteristics of cast iron pipe.
varying rates at top and bottom of the pipe, and at
ntal vs. vertical lines. Moisture alone is especially This 75 year old cast iron pipe had multiple leak clamps
ctive to cast iron. applied to its top surface but showed acceptable wall
thickness elsewhere. Wall thickness at the bottom was not
sting at cast pipe is difficult due to the inherent far below specification - yet the top was obviously beyond
ty of the material, and due to its varying corrosion service
cteristics.

 
Tank Corrosion - Steel domestic Hidden Corrosion -
water tanks often suffer from a Discoloration of piping
combination of internal and insulation is always a stro
external corrosion, as shown sign that a leak is underw
here. Interior protective coatings In many cases, this may b
can fail in areas, which allows attributed to condensatio
deep pitting activity. though unlikely.

In addition, the cold inlet water Fiberglass insulation can


often produces condensation at absorb a substantial amo
the tank exterior, and corrosion water, more if jacketed a
where the coating has weakened. painted, and can allow a
A lack of maintenance is the pinhole problem the time
obvious cause, more so than a necessary to develop into
corrosion problem. more serious threat.
 
Under Deposit Corrosion - This extreme case Contractor Error? - These two adjacent
of under deposit corrosion resulted in the total samples of 12 in. pipe were taken from the
penetration of some areas of 12 in. schedule 40 same condenser water system. Comparison of
pipe in under 10 years. Shown here is the very wall thickness in areas of little deposit and
beginning of a pipe failure. corrosion showed it as schedule 40 on the left,
and schedule 20 on the right.
Ultrasonic testing showed thickness values of
under 0.100 in. in some areas, with other areas Examples of schedule 20 substitution were
at near factory new thickness specification of found throughout. Compounding the problem
0.406 in. The removal of the pipe showed that is the under deposit corrosion present - which
high volumes of iron oxide deposits along the is more threatening to the schedule 20 pipe.
bottom of the pipe were the cause.

 
Replacement Due - Secondary equipment can Weld Failure - Multiple causes always exist
often show corrosion problems far sooner for explaining problems at a pipe weld, and
than the actual piping itself. This centrifugal usually require a close metallurgical
separator had three leaks beginning, while examination to provide a reliable answer.
none were found at the main piping.
Improper cleaning or joint preparation, lack
With an original wall thickness of only 0.100 of weld penetration, incorrect rod selection,
in. the pitting in this system reached through or just poor workmanship can all produce the
this metal wall sooner than the 0.280 in. of the same result. Multiple examples of the same
6 in. condenser water pipe. deposits are sure sign that faulty welds exist.
 
Pinhole Leaks - An aggressive pitting condition usually Missing Insulation - A lack of insulation can often produce
spells disaster for any piping system. Here, a reliance on even worse piping damage at cold water piping than an
temporary pipe clamps produced a virtual lawn excessive internal corrosion condition.
sprinkler system at this section of condenser water
piping. Such corrosion activity is often random and very difficult
to predict. It is largely dependent upon area humidity,
Where one pinhole leak might be assumed to be an surface temperature, as well as the natural corrosion
isolated case possibly related to a material defect or very susceptibility of the pipe itself. Exterior corrosion is often
localized condition, multiple leaks demand prompt too severe to permit any nondestructive testing.
attention and usually replacement.

 
Insulation Failure - Here, breaks in the Pinhole Leaks - This relatively new piping
hard outer insulation covering allowed system showed multiple pinhole leaks due to
water and moisture to enter. Saturating the a severe pitting condition at its interior. In
insulation with water substantially many cases, a growth or encrustation of
deteriorated the pipe's outer surface. rust deposits will seem to appear to grow at
the pipe's outer surface. This is actually due
Ultrasonic testing showed that the pipe wall to a microfine pinhole leak.
had been reduced to below acceptable
minimum levels and that replacement of In such examples, the rate of evaporation
those exterior pitted sections of pipe was exceeds the rate of the leak - which them
required. The degree of exterior corrosion produces the deposit made up of formerly
and hidden water damage also destroyed dissolved iron and minerals which have
the electrical heat tracing cable - a fact precipitated out at the pipe's outer surface.
previously unknown.
 
Galvanizing Failure - A severe internal Localized Pitting - Deep internal pitting
pitting condition at this domestic water line exposed at galvanized domestic water pipe.
produce near total failure after Cross section of soon to fail area revealed by
approximately 12 years of service. ultrasonic testing illustrates the depth of wall
loss at this 6 in. pipe.
Wet insulation suggested a corrosion under
insulation condition, but the pipe had become Less the thread cut, failure was certain
nearly porous in some areas due to severe
pitting.

 
Deep Pitting - Various examples of exterior Insulation Failure - Failure of pipe insulation,
rust product at this fire sprinkler line especially at underground installations such
suggested a failure at the threads. However, as here, can easily produce dramatic
testing showed a system wide deep pitting corrosion rates of 50 MPY or more.
condition primarily at the bottom of the pipe
to be the cause of the leaks. Testing of pipe where the insulation held
showed wall thickness readings at
Leaks at the threads had not occurred first specification for this hot water piping after 25
simply due to the randomness of the pitting years of service. In this example, outer
condition not existing in that area. corrosion penetrated 0.375 in. of thickness in
the same time