From 1.17 To 7.2 MVA: Medium Voltage Inverter Station, Customized Up To 7.2 Mva
From 1.17 To 7.2 MVA: Medium Voltage Inverter Station, Customized Up To 7.2 Mva
1,500 Vdc
www.ingeteam.com
solar.energy@ingeteam.com
SUN InverterStation 1,500 Vdc
Steel base frame. Up to four inverters with an Low voltage distribution panel. Meteo station.
output power of 7.2 MVA.
Suitable for slab or piers Power plant commissioning. Energy meter for auxiliary
mounting. Liquid-filled hermetically sealed High-speed Ethernet / fibre optic services and/or energy
transformer up to 34.5 kV. communication infrastructure production.
Compact design,
minimizing freight costs. Oil-retention tank. for Plug & Play connection to Insulation monitoring relay for
the Power Plant Controller and/ continuous monitoring of IS
Frame for installation of LV or SCADA systems. systems insulation.
equipment.
INGECON® SUN StringBox with
Reactive power regulation when
Minimum installation at 16 / 24 / 32 input channels.
there is no PV power available.
project site. Intelligent or passive string
combiner box. Ground connection of the PV array.
Sand trap kit.
Single Inverter +
Dual Inverter Station
From 3,510 up to 5,400 kVA.
Rated power @50 ºC / 122 ºF 1,613 kVA 3,227 kVA 4,840 kVA 6,456 kVA
Max. power @30 ºC / 86 ºF 1,793 kVA 3,586 kVA 5,379 kVA 7,172 kVA
Skid Size 5,200 x 2,100 mm / 17 x 7 ft 5,200 x 2,100 mm / 17 x 7 ft 5,200 x 2,100 mm / 17 x 7 ft 5,200 x 2,100 mm / 17 x 7 ft
Max. estimated skid weight (without inverters) 10 tons 16 tons 21 tons 26 tons
Voltage class 24 - 36 kV 24 - 36 kV 24 - 36 kV 24 - 36 kV
Installation altitude(1) Up to 4,500 m (14,765 ft) Up to 4,500 m (14,765 ft) Up to 4,500 m (14,765 ft) Up to 4,500 m (14,765 ft)
Operating temperature range -20 ºC to +57 ºC / -4 ºF to +135 ºF -20 ºC to +57 ºC / -4 ºF to +135 ºF -20 ºC to +57 ºC / -4 ºF to +135 ºF -20 ºC to +57 ºC / -4 ºF to +135 ºF
Notes: (1) For installations beyond 1,000 m (3,280 ft), please contact Ingeteam’s solar sales department.
Dual inverter
M M
LINE IN
LV / MV Transformer 20T
Y01
YU
Y0
M
M M
50, 51
51N
LINE IN
Single inverter
LINE OUT
M M
Auxiliary
Services
Optional