Calibration of Boom Sensors
Calibration of Boom Sensors
FIRST PAGE
Press MENU
MENU PAGE
ADJUST MENU
Now you have to enter in a PIN CODE for access to the calibration menu.
The code is written by the “scroller button.
Turn the “scroller button” until the right No. is shown in the marked square, press then
the “scroller button” to move to the next No.
When all 4 No. are written and OK is marked, press the scroller button to open the
calibration menu.
”Scroller button”
Min: Press A button to select calibration of MIN value for the angle sensor.
IMPORTANT ! Lower the boom to its mechanical end position.
(The boom has a soft brake function when it close to its end position)
Turn the “scroller button” to adjust Actual value to 0, and press the ”scroller
button” to save the value.
Max: Press B button to select calibration of MAX value for the angle sensor.
IMPORTANT ! Lift up the boom to its mechanical end position.
(The boom has a soft brake function when it close to its end position)
Turn the “scroller button” to adjust Actual value, and press the ”scroller
button” to save the value.
Actual value: This is the value the angle sensor is sending to IQAN-MDL display.
With the Boom lowered to its end position, should the value be as close to 0 as possible.
With the Boom lifted up to its end position, there is used several different MAX values
depending on which machine model it is.
IMPORTANT !
At calibration you have to make sure that the
sensor is in its mechanical min /max positions !!
Ex. Lower the boom to its mechanical end position.
If not, the sensor will transmit an inaccurate value !!
Min: Press A button to select calibration of MIN value for the length sensor.
IMPORTANT ! Retract the boom to its mechanical end position.
(The boom has a soft brake function when it close to its end position)
Turn the “scroller button” to adjust Actual value to 0, and press the ”scroller
button” to save the value.
Max: Press B button to select calibration of MAX value for the length sensor.
IMPORTANT ! Extend the boom to its mechanical end position.
(The boom has a soft brake function when it close to its end position)
Turn the “scroller button” to adjust Actual value, and press the ”scroller
button” to save the value.
Actual value: This is the value the angle sensor is sending to IQAN-MDL display.
With the Boom retracted to its end position, should the value be as close to 0 as possible.
With the Boom extended to its end position, there is used several different MAX values
depending on which machine model it is.
IMPORTANT !
At calibration you have to make sure that the
sensor is in its mechanical min /max positions !!
Ex. Retract the boom to its mechanical end position.
If not, the sensor will transmit an inaccurate value !!
Min: Press A button to select calibration of MIN value for the pressure sensor.
Push the joystick forward or press the emergency lowering button to be sure that
there is no pressure in the sensors when doing calibration.
Turn the “scroller button” to adjust Actual value to 0, and press the ”scroller
button” to save the value.
Max: Press B button to select calibration of MAX value for the pressure sensor.
IMPORTANT !
This value is a fixed value from the factory and does not need to be calibrated.
The value shall always be 4545.
Actual value: This is the value the angle sensor is sending to IQAN-MDL display.
With the boom lowered to its end position, should the value be as close to 0 as possible.
IMPORTANT !
At calibration of the MIN value you have to make sure
That there is no pressure in the cylinders !!
Ex. Press the emergency lowering button under calibration.
If not, the sensor will transmit an inaccurate value !!