Project Spreadsheets to BS 8110 & EC2 REINFORCED CONCRETE COUNCIL

Client Advisory Group Made by Date Page


Location 8rd Floor slab rmw 01-Aug-2022 116
1-WAY SOLID CONCRETE SLAB DESIGN to BS 8110:1997 Table 3.12 Checked Revision Job No
Originated from RCC91.xls on CD © 1999 BCA for RCC chg - R68

LOCATION Supports from grid A to grid F STATUS


End support condition is C (C)ontinuous or (S)imple VALID DESIGN

DIMENSIONS MATERIALS
Nº of spans Nº 3 fy N/mm² 460 gs = 1.05
Max Span m 7.200 fcu N/mm² 35 gc = 1.50
Thickness, h mm 200 Density kN/m³ 23.6
80
cover mm 20 (Normal weight concrete) 60
40
20
LOADING
0
Self Weight kN/m² 4.72 -20
Additional Dead kN/m² 1.00 -40
Total Dead, gk kN/m² 5.72 -60

Imposed Load, qk kN/m² 2.50 A F A F


Design load, n = kN/m² 12.01 Geometry and Loading Indicative Bending Moment Diagram

MAIN STEEL END END FIRST INT INTERIOR INTERNAL BS 8110


SUPPORTS (A & F) SPANS SUPPORTS SPANS SUPPORTS Reference

Factor 0.040 0.075 0.086 0.063 0.000 Table 3.12


M kNm/m 24.9 46.7 53.5 39.2 0.0
d mm 175 172 174 172 
K 0.023 0.045 0.051 0.038  M/bd²fcu
z 166.3 162.9 163.6 163.4  Clause 3.4.4.4
As mm²/m 342 654 747 548 
Rebar T T T T 
Ø mm 10 16 12 16 12
@ mm c/c 225 150 150 225 
As prov mm²/m 349 1340 754 894 
= % 0.199 0.779 0.433 0.520 
Max S 535 532 534 532  Clause
subclause (a) (a) (a) (a)  3.12.11.2.7

DEFLECTION
fs N/mm² 300 150 304 188  Eqn 8
Top steel provided % bd 0 0
Comp Mod factor 1.000 1.000 Table 3.11
Tens Mod factor 1.651 1.632 Eqn 7
Perm L/d 43 As auto-increased 42.5 As auto-increased Table 3.9
Actual L/d 41.8 by 86 % 41.8 by 56 %

DISTRIBUTION STEEL As = 0.13% = 260 mm²/m Table 3.25


Provide T 10 at 300 = 262 mm²/m

SHEAR END SUPPORT FIRST INT SUPT INTERNAL SUPTS


V kN/m 39.8 51.9  Table 3.12
As prov % 0.390 0.433 
v N/mm² 0.231 0.298  equation 3
vc N/mm² 0.638 0.659  Table 3.8

OUTPUT/SUMMARY
END END FIRST INT INTERIOR INTERNAL
SUPPORTS SPANS SUPPORTS SPANS SUPPORTS DISTRIBUTION
PROVIDE T10 @ 225 T1 T16 @ 150 B1 T12 @ 150 T1 T16 @ 225 B1 T10 @ 300

CHECKS BAR Ø SINGLY BAR NO SHEAR GLOBAL


< COVER REINFORCED SPACING DEFLECTION LINKS STATUS
OK OK OK OK OK VALID DESIGN
Project Spreadsheets to BS 8110 & EC2
Location 8rd Floor slab
1-WAY SOLID CONCRETE SLAB DESIGN to BS 8110:1997 Table 3.12 Made by rmw Job No R68
Originated from RCC91.xls on CD © 1999 BCA for RCC Date 1-Aug-22

APPROXIMATE WEIGHT of REINFORCEMENT Bay width 10000 mm


Support width 350 mm

TOP STEEL Type Dia Spacing No No off Total Length Unit wt Weight
End supts T 10 @ 225 45 2 90 2050 0.617 113.8
0 0 0 0 0 0 0 0 0 0.000 0.0
Pen supts 0 12 @ 150 67 2 134 3600 0.888 428.3
0 0 0 0 0 0 0 0 0 0.000 0.0
0 0 0 0 0 0 0 0 0 0.000 0.0
BOTTOM STEEL
End spans T 16 @ 150 67 2 134 6325 1.578 1337.7
Int spans T 16 @ 225 45 1 45 5925 1.578 420.8
DISTRIBUTION STEEL
Bottom End spans T 10 @ 300 23 2 46 10400 0.617 295.0
Int spans T 10 @ 300 23 1 23 10400 0.617 147.5
Top End spans T 10 @ 300 11 2 22 10400 0.617 141.1
Int spans T 10 @ 300 12 1 12 10400 0.617 76.9
SUMMARY
Reinforcement density (kg/m³) 67.4 Total reinforcement in bay (kg) 2961
Project Spreadsheets to BS 8110 & EC2
Location 8rd Floor slab GRAPH I
1-WAY SOLID CONCRETE SLAB DESIGN to BS 8110:1997 Table 3.12 Made by rmw Job No R68
Originated from RCC91.xls on CD © 1999 BCA for RCC Date 1-Aug-22

LOADING DIAGRAM
Support 1 2 3 4 5 6 7 8 9 gk = 5.72 gk = 5.72 kN/m²
Distance 0 0 7.2 14.4 21.6 21.6 21.6 21.6 21.6 21.6 21.6 qk = 2.50 qk = 2.50 kN/m²
Dead 0 5.72 5.72 5.72 5.72 0 0 0 0 0 0
Imposed 5.72 8.22 8.22 8.22 8.22 5.72 5.72 5.72 5.72 5.72 5.72
Base 0 0 0 0 0 0 0 0 0 0 0
1 2 3 4 5 6 7 8 9
Grids 0 0 7.2 7.2 14.4 14.4 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
-1.644 0 -1.644 0.00 -1.644 0 -1.644 0 -1.644 0 -1.644 0 -1.644 0 -1.644 0 -1.644 0

BM DIAGRAM F/2 = 43.229


Support 1 End 2 Mid 3 End
Local X 0 0 0.72 1.44 2.16 2.88 3.6 4.32 5.04 5.76 6.48 0 0.72 1.44 2.16 2.88 3.6 4.32 5.04 5.76 6.48 0 0.72 1.44 2.16 2.88 3.6
Global X 0 0 0.72 1.44 2.16 2.88 3.6 4.32 5.04 5.76 6.48 7.2 7.92 8.64 9.36 10.08 10.8 11.52 12.24 12.96 13.68 14.4 15.12 15.84 16.56 17.28 18
Base 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Moment 0 12.45 -11.45 -29.13 -40.59 -45.82 -44.82 -37.6 -24.15 -4.482 21.414 53.535 25.522 3.735 -11.83 -21.16 -24.28 -21.16 -11.83 3.735 25.522 53.535 21.414 -4.482 -24.15 -37.6 -44.82
28.012 49.8 65.362 74.699 77.812 74.699 65.362 49.8 28.012
Grids 0 0 7.2 7.2 14.4 14.4 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
-45.82 58.888 -45.82 58.888 -45.82 58.888 -45.82 58.888 -45.82 58.888 -45.82 58.888 -45.82 58.888 -45.82 58.888 -45.82 58.888
Spreadsheets to BS 8110 & EC2
8rd Floor slab GRAPH II
1-WAY SOLID CONCRETE SLAB DESIGN to BS 8110:1997 Table 3.12 Made by rmw Job No R68
Originated from RCC91.xls on CD © 1999 BCA for RCC Date 1-Aug-22

4 0 5 0 6
4.32 5.04 5.76 6.48 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
18.72 19.44 20.16 20.88 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
-45.82 -40.59 -29.13 -11.45 12.45 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Spreadsheets to BS 8110 & EC2
8rd Floor slab GRAPH III
1-WAY SOLID CONCRETE SLAB DESIGN to BS 8110:1997 Table 3.12 Made by rmw Job No R68
Originated from RCC91.xls on CD © 1999 BCA for RCC Date 1-Aug-22

0 7 0 8 0 9
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6 21.6
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Disclaimer
All advice or information from the British Cement Association and/or Reinforced Concrete Council is intended for
those who will evaluate the significance and limitations of its contents and take responsibility for its use and
application. No liability (including that for negligence) for any loss resulting from such advice or information is
accepted by the BCA, RCC or their subcontractors, suppliers or advisors. Users should note that all BCA software
and publications are subject to revision from time to time and should therefore ensure that they are in possession of
the latest version.

This spreadsheet should be used in compliance with the accompanying publication 'Spreadsheets for concrete
design to BS 8110 and EC2' available from British Cement Association, Telford Avenue, Crowthorne, Berkshire
RG45 6YS.

Status of spreadsheet
Public release version.

Revision history RCC91 One-way Solid Slabs (Tables)

Date Version Action