Vigilohm in Healthcare Presentation

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

Vigilohm in Healthcare Applications

EB- Technical overview


Power Solutions Global Training

Confidential Property of Schneider Electric


Insulation monitoring
Dedicated to highly critical applications, to ensure
Continuity of Service and Safety in case of ground fault

User segments are


Hospital, Industry, O&G, Marine, Utilities, Solar, MMM, WWW, MV, Seaport, Airport…...

high customer value on Operations and costs


Confidential Property of Schneider Electric | Page 2
1 What is an IT / ungrounded system

2 Healthcare Standards

3 Vigilohm offer dedicated to healthcare

4 Architectures

Confidential Property of Schneider Electric | Page 3


Monitoring of ungrounded systems
EcoStruxure Power Monitoring Expert
Specific Hospital
Supervision et SCADA
Modbus TCP/IP

Link 150
Communication
gateway, Web Server

Modbus RS485
Magelis
O.T. Room display HRP

Insulation Monitor IM20-H IM10-H

IFL12H
Insulation fault Locator

Confidential Property of Schneider Electric


Toroids Power Solutions
What is an IT / ungrounded system ?

According to IEC Standard,

TT system means
T T I
Transformer Neutral is grounded (T)
Loads shielding are grounded (T)

TN system means
Transformer Neutral is grounded (T)
Loads shielding are to Neutral, (N)
3Ph 3Ph+N
IT system means
Transformer Neutral is Isolated from ground (I)
Loads shielding are grounded (T)
Load Load Load

T N T
Vigirex Vigilohm
Why an ungrounded network ? TT, TN, grounding arrangement
At 1st ground fault,
the current loop from the transformer, to the load,
then to the ground, back to the transformer
. The RCCB opens : Continuity of service
. Electrical shock is possible : Safety √

IT, isolated arrangement


At 1st ground fault,
there is NO current to loop as the transformer is
not grounded
Confidential Property of Schneider Electric | Page 6 . The RCCB closed : Continuity of service √
. No dangerous voltage : Safety √
Key benefits of ungrounded systems
Ungrounded system, provides Continuity of service and Safety even in case of ground fault

Focused on critical applications such as continuous processes, ATEX, harsh environment,


“critical for safety” sites

Benefits lands on OPEX, measured in


cost per minute of disrupted process
cost of the wasted production
cost on O&M to stop current work and rush at locating and fixing the problem
cost of immobilized production staff due to the disruption
cost of damaged equipment, overheat, fire, explosion…
And
human impact due to interruption of supply and in case a person would be injured

But if Continuity of Service & Safety remains even in case of fault, How do I know the issue ?

Confidential Property of Schneider Electric | Page 7


Values provided by the IMD
Monitors Insulation resistance of the system

. Injects a specific signal in the system and measure this signal


coming back from ground
. Displays the measured Insulation Resistance and Capacitance
. Compares measurement with alarms thresholds
. In case the preventive alarm threshold is breached,
Generate a prev-alarm (if set) thru output relays and com port
. In case the alarm threshold is breached,
Generate an alarm thru the output relays and com port
. Detects a lost connection (R >10MΩ), allow Injection inhibition (DI)
Detection
Compliant to
. Low Voltage systems
. THR versions dedicated to Medium Voltage systems
. L versions dedicated to 24-48VDC power supplies
. H versions dedicated to Healthcare applications Localization
. T versions dedicated to harsh environment, conformal coated
Confidential Property of Schneider Electric | Page 8
Low Frequency AC injection
Values provided by the IFL
Monitors Insulation resistance per feeder / branch

. Associated to 1 toroid per feeder, monitors up to 12 of them


. Measures accurately the specific signal injected by the IMD
. No wiring / physical connection between IMD and IFL
. Display the measured Insulation resistance and capacitance (MC versions)
. Compares measurement with alarm thresholds
. In case an alarm threshold is breached,
Display the (customized) name of the faulty feeder
Generate an alarm thru output alarm relay & Serial port RS485 (C version)

Compliant to Detection
. Low Voltage systems
. L versions dedicated to 24-48VDC power supplies
. H versions dedicated to Healthcare applications
. T versions dedicated to harsh environment, conformal coated
Localization

Confidential Property of Schneider Electric | Page 9


Low Frequency AC injection
1 What is an IT / ungrounded system

2 Healthcare Standards

3 Vigilohm offer dedicated to healthcare

4 Architectures

Confidential Property of Schneider Electric | Page 10


Healthcare Installation Standards
IEC 60364-7-710 Electrical Installation in buildings,
Requirements for special installations or locations: Medical locations

Medical locations have been classified in 3 groups Group 2

Anaesthetic room
Group 2: Medical location where medical electrical
equipment have to be used into the body. Isolated ground Operating theatre
system is mandatory
Operating preparation room

Group 1: Medical location where medical electrical have to Operating plaster room
be used as follows: externally or invasively to any part of the
body. A limited residual 30mA current device is mandatory Operating recovery room

Heart catheterization room


Group 0: Medical location where no medical electrical
Intensive care room
equipment is in contact with the body
Angiographic examination room

Confidential Property of Schneider Electric 11


Healthcare Installation Standards
> Hospital architecture is dedicated to continuity of
service

Confidential Property of Schneider Electric 12


Healthcare Installation Standards Maintenance team
Till 2018 standard version Supervision system (PME, BMS…)

Electric room
IT transformer +Vigilohm

Chief nurse room


Local display

Operating Theaters
HRP or Magelis OTD in each operating theater
Confidential Property of Schneider Electric 13
Healthcare Installation Standards
According to 2018 standard evolutions Maintenance team
Supervision system: PME, BMS

Electric room
is moving closer to
the O.T. room.
Max cable length
Operating Theaters <25m
IT Insulation Smart Panel
moves close/inside the O.T. room
Includes
. Ins transformer
. IM15H or IM20H
. HRP or Magelis
. IFL12H
. other

Confidential Property of Schneider Electric 14


Healthcare Installation Standards
Maintenance action plan is clearly recommended and usually mandatory through local Healthcare
authority

Monthly verification Safety services with battery: 15mn


with 50% to 100% of the rated power Safety services with combustion engines: 60mn

Each year Functional testing of changeover devices


Functional testing of insulation monitoring devices
Checking setting protection device included
tripping of RCD (30mA)

Measurement of leakage currents of IT


Each 36 months transformer
Measurement of additional equipotential bonding

Traceability The date and results of each verification shall be


recorded

Schneider Electric - Energy Management Solutions 15


Healthcare products Standards. Key aspects
IEC 61557-8 Insulation Monitoring devices, Annex A

IM10-H, IM15H, IM20-H are designed for permanent


monitoring

Confidential Property of Schneider Electric 16


Healthcare products Standards. Key aspects
IEC 61557-8 Insulation Monitoring devices, Annex A

IM10-H, IM15H, IM20-H alarm threshold do not allow


alarm threshold lower than 50 kΩ, but allow above 50 kΩ

OTD or HRP are equipped with a test button generating


an insulation resistance of 39 kΩ, thus generating an
alarm

OTD or HRP are equipped with acoustic (buzzer) and


visual (LED / display) alarm systems
The acoustic system can be acknowledged while the
visual alarm remains until the fault is no longer active

Confidential Property of Schneider Electric 17


Healthcare products Standards. Key aspects
IEC 61557-8 Insulation Monitoring devices, Annex A

IM10-H, IM15H, IM20-H monitor both symmetrical and


asymmetrical faults

IM10-H, IM15H, IM20-H are equipped with a relay /


communication to report to OTD; HRP; supervision
system, other

IM10-H, IM15H, IM20-H alarm in case they considered


disconnected from the system, due to very high ins R.
OTD and HRP reduce system ins resistance to prevent
the system from false alarm

Confidential Property of Schneider Electric 18


Healthcare products Standards. Key aspects
IEC 61557-8 Insulation Monitoring devices, Annex A

IM10-H, IM15H, IM20-H response is < 5seconds

IM10-H, IM15H, IM20-H injects a 2,5Hz sinus


measuring voltage at < 25V peak.

The max measuring current is 25 / 144 kΩ = 0,17mA

144 kΩ

IM10-H, IM15H, IM20-H passed. Test report available


Confidential Property of Schneider Electric 19
Healthcare products Standards. Key aspects
IEC 61557-8 Insulation Monitoring devices, Annex B

IM15H, IM20-H monitor transformer overheat and


overload
These functions are incorporated into these IMDs

IM15H, IM20-H incorporate a special alarm relay for the


Transformer, and specific Modbus registers for these
faults

Confidential Property of Schneider Electric 20


Healthcare products Standards. Key aspects
IEC 61557-8 Insulation Monitoring devices, Annex B

IM15H, IM20-H provides settings for transformer


overload, with different CT ratings

IM15H, IM20-H provides settings for transformer


overheat, to adapt to the thermal sensor

Confidential Property of Schneider Electric 21


Healthcare products Standards. Key aspects
IEC 61557-9 Insulation Fault locators Annex A

IFL12H is designed to meet IEC61557-9, and more

IFL12H is consistent with IM20-H and with standard, with


sensitivity from 200 Ω to 250 kΩ per channel, with 0,5µF
system capacitance

Confidential Property of Schneider Electric 22


Healthcare products Standards. Key aspects
IEC 61557-9 Insulation Fault locators Annex A

IFL12H is < 5 second on any channel, as for IMDs

IFL12H tells which feeder(s) is(are) faulty, and display


their customized name(s), if set

IFL12H sensitivity is from 200 Ω to 250 kΩ per channel

IFL12H passed. Test report is available


Confidential Property of Schneider Electric 23
1 What is an IT / ungrounded system

2 Healthcare Standards

3 Vigilohm offer dedicated to healthcare

4 Architectures

24
Confidential Property of Schneider Electric | Page 24
Vigilohm, a complete solution for medical IT premises
EcoStruxure Power Monitoring Expert
EcoStruxure Building Operations
Monitoring and control
Monitoring & SCADA system

Ethernet
Communication Link 150

Modbus protocol
Gateway

OTD HRP
Operating Theater Display

Modbus
IT system local status & testing

IM20-H
Insulation Monitoring Devices
Monitoring of the global network insulation IM10-H & IM15H

Insulation Fault Locators IFL12H

Identify the faulty feeder

Toroids Transformers
Confidential Property of Schneider Electric Used along with the Fault Single phase 25
Locators Three phase
Medical transformer
Single phase Three phase

Secondary voltage = 250 Vac max, acc to IEC Secondary voltage = 250 Vac max, acc to IEC
380 Vac on secondary of transformer is NOT allowed Output voltage is 230 Vac between phases. Neutral is not
distributed

4 versions 3 versions available from BCV only


3,3 kVA; 6,3 kVA; 8 kVA; 10 kVA 6.3 kVA; 8 kVA; 10 kVA

Key advantages / drawbacks during operations Key advantages / drawbacks during operations
. Adv: Full power of the transformer available on the . Drw: Full power of the transformer is distributed over the 3
same 2 lines lines. 3,3 kVA per line on a 10kVA transformer
. Adv: The medical staff can plug equipment anywhere . Drw: The medical staff might plug too many equipment on the
same 2 lines, which lead to
. unbalanced power distribution
. potential TR overload on these 2 lines
. Potential undervoltage on these 2 lines
Confidential Property of Schneider Electric . Equipment mal-function due to non-availability of the 26
necessary power during the operation
Medical transformer Europ North Africa

Confidential Property of Schneider Electric 27


Medical transformer APAC Africa ME LatAM

Confidential Property of Schneider Electric 28


Insulation Monitor IM10-H
Monitors the electrical network Injection

Monitors and trigger alarm from


Insulation resistance
Product failure
Wiring failure (Injection loss)
Settings on
Insulation resistance >50kΩ
Other
HMI with 8 languages
30 Event log
110-230 VAC & 125-250 VDC
IEC60364-7-710 compliant
IACS & CE

Confidential Property of Schneider Electric 29


Insulation Monitor IM15H Overheat

Overload

Monitors the electrical network Injection

Monitors the Transformer overheat & overload


Monitors and trigger alarm from
Insulation resistance
Transformer overheat
Transformer overload
Product failure
Wiring failure (Injection loss)
Settings on
Insulation resistance >50kΩ
Transformer overload, based on TR power and CT
Other
HMI with 8 languages
30 Event log
110-230 VAC & 125-250 VDC
IEC60364-7-710 compliant
IACS & CE

Confidential Property of Schneider Electric 30


Insulation Monitor IM20-H Overheat

Overload
Monitors the electrical network Injection

Monitors the Transformer overheat & overload Com

Embed RS485 Modbus communication port


Monitors and trigger alarm from
Insulation resistance
Transformer overheat
Transformer overload
Product failure
Wiring failure (Injection loss)
Settings on
Insulation resistance >50kΩ
Transformer overload, based on TR power and CT
Other
RS485 Serial port
Integrated into PME4HC
HMI with 8 languages
30 Event log
110-230 VAC & 125-250 VDC
IEC60364-7-710 compliant
IACS & CE

Confidential Property of Schneider Electric 31


Insulation Fault Locator IFL12H Overheat

Overload
Monitors up to 12 feeders, individually Injection

Embed RS485 Modbus communication port, and more


Monitors and trigger alarm on
Insulation resistance, per individual feeder
Product failure
Toroid loss during operations, per individual feeder
Settings of
Insulation resistance >50kΩ, per individual feeder
Customized feeder name, individually
Other
Do not need any wiring with its IMD ( no limitation in distance)
Associated to Vigilohm CTs, TA30
Automatic detection of toroid during Commissioning, per feeder
Fast response time <5sec whatever is the faulty feeder
RS485 Serial port
Integrated into PME4HC
Transient Detection (Fault occurring then disappearing by itself)
HMI with 8 languages
120 Event log
110-230 VAC & 125-250 VDC
IEC61557-9 and IEC60364-7-710 compliant
IACS & CE
Only compatible with IM20-H; IM15H; IM10-H
Confidential Property of Schneider Electric 32
Toroids

Monitors the transformer overload, connected to IM15h or IM20-H


TC 50/5, serie CC here
Associated to IM15H or IM20-H
Diameter 21 mm, or above
Dedicated to monitoring the current consumed by all the loads of the system.
1 per IMD
Overconsumption will trigger a transformer Overload alarm

Monitors the Insulation resistance per feeder, for IFL12H


TA30 model here
Associated to IFL12H
Diameter 30mm here, or above till 300 mm
Dedicated to monitoring the differential (leakage) current to ground of each feeder
Up to 12 per IFL
Overconsumption will trigger an insulation alarm from the mentioned feeder

Confidential Property of Schneider Electric 33


O.T. Panel HRP

Insulation fault indicator Remote Display of IMD


Displays from IM10-H; IM15H; IM20-H
Insulation alarm and/or Product failure
Electrical fault indicator Transformer Overheat and/or Overload
. Transformer overload or Other
. Transformer overheat or Insulation Fault Test
Alarm buzzer Acknowledgement
. Circuit Breaker trip (IMD)

Buzzer Acknowledgment

Insulation Fault Test

Confidential Property of Schneider Electric 34


Displays information from 1 or 2 cabinets, incl IMD, IFL, Smart Link, transformer,
Medical gas, UPS
O.T. Display IMDLRDH From IMD, IMD-IM20-H only ( 1 per cabinet )
Insulation alarm; Product failure
Transformer Overheat Transformer Overload
From IFL12H (up to 4 per cabinet)
Insulation alarm, Toroid loss during operations,
incl the name of the faulty feeder
From Smart Link (up to 2 per cabinet)
Circuit Breaker trip, incl the name of the tripped breaker
From Medical gaz (1 per O.T. room)
Medical gaz default
From UPS (1 per O.T. room)
UPS is ON, 15’ remaining
Displays
Communication with devices OK or failed
No Alarm (green screen), or the alarm(s) name(s) (orange or red screen)
Specific message for the medical staff, depending on the type of alarm
Guiding message fpor the medical staff
Settings
Password
Language En, Fr, It, Ge, Sp, Po, Zh, Ru,
Communication RS485 or TCP/IP
Number of cabinets 1 or 2
IMD type IM20-H
Number of IFL 0 to 4 per cabinet
Number of Smart Link 0 to 2 per cabinet
Medical gaz monitoring Yes or No
UPS last minute monitoring Yes or No
Other
include the 2 Mohm resistance to ground (prevent false alarm due to high R)
Allow Insulation Monitoring Test, same as in HRP
Alarm Buzzer Acknowledgement 35
Confidential Property of Schneider Electric
O.T. Detergent proof
Vigilohm products Installation
Existing and 2018 new offer

36
36
Insulation Monitors
IM10-H IM15-H IM20-H

Insulation Fault detection & alarming Yes Yes Yes

Injection loss detection Yes Yes Yes

Display R Yes Yes Yes

Date stamped Event log No Yes Yes

Output relay for insulation alarm Yes Yes Yes

Output relay for transformer alarm No Yes Yes

Transformer monitoring:

Overcurrent No Yes Yes

Overheat No Yes Yes

Modbus RS485 No No Yes

Confidential Property of Schneider Electric 37


IMDs interface & dimensions

Confidential Property of Schneider Electric 38


IM10-H Menu

1> Screen identification área


menu selectionned
2> Information área
menu data or info
3> Navigation buttons

Confidential Property of Schneider Electric 39


IM15H; IM20-H Menu

Confidential Property of Schneider Electric 40


IM15H; IM20-H Configuration

Confidential Property of Schneider Electric 41


Refer to IM20H User Manual and Installation Sheet
IM15H; IM20-H Logs and events

IM15H and IM20-H record the details of the 30 most


recent insulation fault events.
The fault events are triggered by one of following
statuses:
• insulation fault
• transformer overload
• transformer overheating
Event 1 is the event that was recorded most recently
and event 30 is the oldest recorded event.
The oldest event is deleted when a new event
occurs (the table is not reset).

Confidential Property of Schneider Electric 42


IMDs: Alarming principles

Confidential Property of Schneider Electric 43


IMD15H; IM20-H Transformer monitoring
According to standards, monitoring the insulation transformer overheat and overload is mandatory

Over temperature monitoring done by IMD Overload monitoring by IMD


Temperature sensor from the transformer is to be accessible Current transformer is needed (Exp: METSECT5CC0xx)

IMD setting is needed accordingly IMD setting is needed accordingly


. Type of sensor if NO, then “NO”, . CT primary current if CT 100/5, then 100
if NC, then “NC” . CT secondary current if CT 100/5, then 5
The contacts of the sensor gets close (or open) when the . TR Nominal current if TR=8 kVA / L-N, then 40A
temperature breaches the temperature alarm threshold . TR overload threshold if 80% (of nominal current), then 32A
PTxxx sensors are non compliant with IM20-H

CT

Confidential Property of Schneider Electric 44


IMD15H; IM20-H Transformer monitoring
Transformer monitoring is done through the IMD.
Insulation fault and electrical fault can be displayed by :
IMD
HRP (Hospital Remote Panel)
Magelis display (only IM20-H solution from Operating
Theater offer)
Supervisor (only IM20-H)

IM15-H / IM20-H

Confidential Property of Schneider Electric 45


IM10-H Wiring
● Outputs
● Normally Open- Normally Closed mechanical relays
●240VAC, 6A
●12-24VDC, 6A
● 6 : N.O. contact
● 7 : Common point
● 8 : N.C. contact

1. Injection ● Compliance with standard:


2. Insulation alarm ● Another device must be monitoring the IT transformer over
contacts temperature and overload
3. Local interface

Confidential Property of Schneider Electric 47


IM15H; IM20-H Wiring 1. Insulation transformer overheating monitoring
2. Insulation transformer overload
Monitoring with current transformer, model
40 Amps : METSECT5CC004
50 Amps: METSECT5CC005
3. Hospital Remote Panel
4. Modbus communication (ONLY IM20H)
> Outputs
> Solid state (static) relays
- 24VDC
- 30mA max
6 7 8
> 6 : Insulation alarm output, set in Failsafe mode
> 7 : Common point
> 8 : Transformer alarm output (on overcurrent or
over temperature), set in Failsafe mode

Only IM20H

Confidential Property of Schneider Electric 48


Insulation test
O.T. Panel HRP & OTD
By pressing the test button, a 39kΩ insulation fault is created between network
and earth
IMD must trigger an alarm, the HRP buzzer buzz…

Comments
The standard do not request any test on the transformer
Prevention of false alarm

IMxx-H measures extremely low currents @2,5Hz.


IMxx-H is very specific and very precise to detect a few µA leakage currents, which lead to
high Insulation resistance, >8 or 10 MΩ, when off-load

When installing HRP, the insulation resistance will drop to 2 MΩ


This is to prevent IMxx-H to potentially display “ injection disconnected”, due to R > 10 MΩ
HRP creates a controlled leakage current with a 2MΩ resistance from system to earth.
This insulation resistance does not mitigate system safety, the system minimum insulation
alarm is 50 kΩ
Competition pull down is 1MΩ max
Confidential Property of Schneider Electric 49
IM10-H to HRP wiring !
Do not reverse the polarities

Wiring to PE and Neutral is required to


perform insulation test

Confidential Property of Schneider Electric 50


Do not reverse the polarities
IM15H or IM20-H to HRP wiring !
Wiring to PE and Neutral is required to
perform insulation test

Confidential Property of Schneider Electric 51


IFL12H front

Confidential Property of Schneider Electric 52


IFL12H Installation

Confidential Property of Schneider Electric 53


IFL12H System Comissioning
F LED

F LED
IFL is power on & Detected toroids: Press to exit Device displays
detecting toroids 4-10-11-12 commisioning mode Summary screen

Confidential Property of Schneider Electric 54


IFL12H Operation
Insulation
Threshold
Hysteresis

Display
MC/MCT

F LED
H LED

Failsafe Relay

Standard Relay
Network insulation is Active alarm on Active alarm on Fault eliminated
normal.No alarm on channel 4. Push ACK Channel 4 is No alarm state
any channel button acknowledged
Confidential Property of Schneider Electric 55
IFL12H Other Operation LED Status

Confidential Property of Schneider Electric 56


IFL12-H Insulation fault log display screen

> The device records the details of the 240


most recent fault events.
> Access to 240 logs through HMI and
communication. The fault events are
triggered by insulation fault status.
> Event 1 is the event that was recorded
most recently and event 240 is the oldest
recorded event.
> The oldest event is deleted when a new
event occurs (the table is not reset).

Confidential Property of Schneider Electric 57


HC Democase V1

Confidential Property of Schneider Electric 58


1 What is an IT / ungrounded system

2 Healthcare Standards

3 Vigilohm offer dedicated to healthcare

4 Architectures

59
Confidential Property of Schneider Electric | Page 59
Entry Local Monitoring
Value Propositions

1/ « OT Electrical System test » with the test button on


the HRP.

2/ « Event Notification » alarm in case of


“insulation fault”
“transformer fault” (15H and 20-H only) on the HRP
+ “fault location” on IFL12H

IM10H; 15H or 20-H

60
Entry Local Monitoring
Value Propositions

1/ « Local Monitoring of real-time value and


healthy/faulty conditions » on product display

2/ « Event Notification » alarm in case of


“insulation fault”
“transformer fault” (15H and 20-H only) on the HRP
+ “fault location” on IFL12H

3/ « Data and Event storage »


- « Event Log » : Storage and display for
preventive maintenance on IM15H, 20-H & IFL12H
IM10H; 15H or 20-H

4/ « Local Configuration » : IM15H; 20-H & IFL12H

5/ No communication required between IMD’s and


IFL’s

61
Advanced Local Monitoring
Value Propositions

1/ « OT Electrical System test » with the test button


on the Operating Theater Display (OTD)

2/ « Event Notification » on the OT panel in case of


alarm
Alarm name
Location of the fault (with IFL12H)
Guidance for the medical staff facing an
insulation or an electrical fault

Modbus RS485

62
Advanced Local Monitoring
Value Propositions

1/ « Local Monitoring of real-time value and


healthy/faulty conditions » on product display

2/ « Event Notification » alarm in case of


“insulation fault” or “transformer fault” on the on
IM20-H display with “fault location” on IFL12H
display

3/ « Data and Event storage »


- « Event Logging » : Storage and display for
preventive maintenance on IM20-H & IFL12MC

Modbus RS485
4/ « Local Configuration » : IMD & IFL HMI

63
Remote Monitoring
Value Propositions Electrical Maintenance
Use-Case
1/ « Centralized real time Monitoring and Event Notification »
of all connected rooms

2/ « Data and Event storage »


- Data (R&C) History Trending for preventive maintenance
- Event Logging with time-stamp : correlation with other events for
troubleshooting

3/ « Remote configuration »
- Configuration of IFL/IMD device parameter

Modbus RS485
4/ Report Generation
- Generating reports on Data History, Event history,

Modbus RS485
Last User triggered self-test

5/ Maintain device time

6/ Integration in Customer Network Performance System


(PME4HC)
- Unlimited data storage
- Fine timestamping
- One system for Network Management
64
- Allow analysis on historical data for preventive maintenance