ABB Utility Automation RTU560

Remote Terminal Unit


Data Sheet
Mains Adapter 23VG23

Application
The mains adapter 23VG23 is an AC/DC converter in The mains adapter 23VG23 offers high operational
combination with an external back up battery for the reliability and resistance to disturbances.
use as an uninterruptible power system (UPS). It
contains a switch-mode power supply of 92 V AC to
265 V AC without switch over the input voltage. The Battery with
temperature sensor
mains adapter supplies an output voltage of 24 V DC
Ut1
with an output current of min. 0.2 A and max. 2 A.
Ut2
It can supply the boards of an RTU560 subrack with L1
a power output of 48 W. F1 +Ub
115 / 230 V AC
--- Ub
N back up
Characteristics K1 battery
Power fail
K2
In the mains adapter there is integrated: LB1
Low battery
--- a battery charging device LB2
PE
--- a switch---over device and
--- Ua
--- a exhaustive discharge protection.
F2 +Ua Output
The mains adapter contains contacts for monitoring --- Ua 24 V DC

of mains failure and of low battery. Double output ter- +Ua


minals are available for simplified wiring.
Abb. 1: Block diagram of mains adapter 23VG23
The mains connection is on the front of the adapter.

165 mm 86 mm
105 mm

Fig. 2: Dimension of 23VG23

Doc.--- No.: 1KGT 150 423 V000 1 81


ABB Utility Automation

Data Sheet Mains Adapter 23VG23 RTU560

Technical Data
In addition to the RTU560 general technical data, the following applies:
Input Temperature sensor:only necessary with battery
operation
Nominal voltage: 115 / 230 V AC connetion to Ut1 and Ut2
without switch over type: K164 / 10 k / 5 % bead-type
(B57164-K103-J) (Siemens)
Operating range: 1.2 A typical at 115 V AC or type: M703 / 10 k/G
0.7 A typical at 230 V AC with fixing eye
(B57703-M103-G) (Siemens)
Tolerance: 92 V AC to 265 V AC or type: K45 / 10 k / 10 %
with screw-type
(B57045-K103-K) (Siemens)
Frequency: 47 to 63 Hz Connection length: max. 10 m, twisted
Rsupply lead < 10 Ohm
Input fuse : F1 = 4 A (slow)
(inaccessible fuse )
Output
Nominal voltage: 24 V DC
Back up battery (external) Output current: max. 2 A
min. 0.2 A
There are special data of manufactuer for back up (with battery operation)
battery
Ripple: max. 80 mVss
Battery voltage: 24 V DC nominal Current limiting: 2.5 A typical
Series dryfit A500, 12 V
2 batteries connected in series Efficiency: 82 % typical
Supplier: Sonnenschein GmbH Tolerance: max.  3 %
Charge voltage: 26.4 V to 29.4 V Back up Battery: min. ---20 %
depending on sensor Rated power: 48 W
temperature
Fuse: F2 = 2.5 A (F)
Charge current: Ib max = 0.35 A
Current limiting: 0.4 A (typ.) Output voltage
continued short circuit-proof

Time of battery 24 V DC
Battery with
Function
3.5 Ah 6.5 Ah
Operation at full load and appr. appr.
20 C 50 min. 135
min.
Loadtime until 90 % loading appr. appr.
9.5 h 13 h
100%
Signalling before switching- appr. appr. Output current
off the undervoltage of the 15 min. 25 min.
battery at contact LB1, LB2 Abb. 3: Current limiting characteristic

82 Doc.--- No.: 1KGT 150 423 000 1


ABB Utility Automation
RTU560 Data Sheet

Signal Outputs Environmental Conditions


Power failure signal: Contact K1 - K2 (60 V / 2 A) Temperature: 0 ... 55 _C

Undervoltage Contact LB1 - LB2 (60 V / 2 A) Relative humidity: 5 ... 95 %


Battery: (non condensing)
Storage temperature: ---25 _C ... +85 _C
Protection equipment Mechanical Oscillation low frequency
influence: IEC870-2; Cl. VL3/VS1/VT1
Overvoltage Ua with Oscillation higher frequency
protection: Suppressor diode 27 V IEC870-2; Cl. VH3/VS1/VT1
Shock resistance
Current limiting: IEC870-2; Cl. SH4/SF3/SR1
without battery: Continued
short-circuit-proof Mechanical Layout
with battery: Fuse F2 trips with Construction: Closed housing
short-circuit of Ua
Stable at no load: Yes, both outputs Dimensions: 105x86x165 mm (HxBxT)
Mains buffering time: > 50 ms of 230 V AC Fixing: Mounting rails acc to
DIN EN 50022-35
Reverse voltage up to 30 V battery voltage
protection Ub: Weight: Approx. 0.8 kg
Cooling: Natural convection
Electromagnetic Compatibility Type of protection: IP 20
(CE ---conformity)
Protection class: I
Electrostatic 8 kV contact discharge
Connections: Plug-in terminal strips
discharge ESD: 5 kV air discharge
IEC 801-2; Primary plug: e.g. Phönix - Combicon
Art. ---No. 1767012
Elektromagnetic 10 V / m
fields: IEC 801-3 Secondary plug: e.g. Phönix - Combicon
Series MSTB
Fast transiente Input 4 kV
disturbances: Output 2 kV
Secondary terminal assignment
IEC 801-4
K1
Surge immunity: 4 kV asymmetrical Power failure
K2
2 kV symmetrical
IEC 801-5 LB1
Low battery
LB2
Impulse voltage 5 kV pulses 1.2/50 ←s
withstand test: asymmetrical Ut2
Temperature sensor
IEC 255-4; Cl. 3 Ut1
2.5 kV pulses 1.2/50 ←s ---Ub
symmetrical Battery
IEC 255-4; Cl. 3 +Ub
---Ua
Output terminals 1
+Ua
Test Voltage ---Ua
Output terminals 2
+Ua
Primary --- Secondary: 1.5 kV DC

Primary --- Protective conductor 1.5 kV DC


Ordering Information
Secondary--- Protective conductor 0.5 kV DC 23VG23R0001 1KGT 005500 R0001

Doc.--- No.: 1KGT 150 423 V000 1 83


ABB Utility Automation

Data Sheet Mains Adapter 23VG23 RTU560

ABB Utility Automation


P.O. Box 1140, 68520 Ladenburg (Germany)
Telephone +49 (0) 6203 71---2932
Telefax +49 (0) 6203 71---2812 03/2000 Subject to alteration

84 Doc.--- No.: 1KGT 150 423 000 1