5.13. Series capacitors are installed atthe midpoint of she line of Problem 5.8, pro-
viding 40 percent compensation. In addition, shunt capacitors are installed ai the
receiving end. The line delivers 2000 MVA, 0.8 lagging power factor. Determine
the total Mvar and the capacitance per phase of the series and shunt capacitors to
keep the receiving end voltage at 735 KV when the sending end voltage is 765 KV.
Find the sending end quantities and voltage regulation for the compensated line.
‘The receiving end power is
‘Spysg) = 20002cos~"(0.8) = 1600 + j1200 MVA.
With the series reactance X' = 77 2, and cos ¢ = A = 0.92476, the power angle
6 is obtained from (5.93)
1600 (costes) sind
which results in 6 = 12.657°. Using the approximate relation given by (5.94), the
net reactive power atthe receiving end is
(765)(735)
7
(735)? 6
Qrise) ‘c0s(12.657°) — Gz 0.92476 = 636.75 Mvar
‘Thus, the required shunt capacitor Mvar is S¢ = 636.75 — 1200 =
‘The shunt capacitive reactance is given by
7563.25.
959.12 2
or
10°
2(60)(959.12)
The net receiving end complex power is
c = 2.765 uF
‘Siqag) = 1600 + 7636.75 = 1722.05221.7° MVA
The receiving end current is
(1600 ~ j636.75)10°
3(424.35220°)
‘We can check the sending end voltage
Vs = AVp + Bln = (0.92476) (424.35220°) + (57)
(1352.69 x 10-8¢ ~ 21.7°) = 441.67212.657° kV_
In= = 1952.69/-21.7° A
Wsci-1)| = V3 [Vs| = 765 kV
The sending end current is
Is = CVp + DIp = (J0.0018805)(4243520°) + (0.92476)
(1352.69¢ ~ 21.7°) = 1209.7216.1° A
‘The sending end power is
‘Ss(a9) = 3V5 Ig = 3 x 441.672 12.687 x 1209.74 — 16.1° x 10->
= 1600 MW — 396.3 Mvar
= 1602.9 - 3.44° MVA
‘Voltage regulation is
35
Percent VR = BHbit= 735 , 199 — 12.55%
735