Test Report No. 7191049787-EEC13-KYM: Dated 04 Jul 2013

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 31

Test Report No.

7191049787-EEC13-KYM
dated 04 Jul 2013

Note: This report is issued subject to TÜV SÜD PSB's "Terms and Conditions Governing Technical Services".
The terms and conditions governing the issue of this report are set out as attached within this report.

Subject

TYPE TESTING OF LED EMERGENCY EXIT SIGN

Client

PNE Translite Pte Ltd


996 Bendemeer Road
#07-07 Kallang Basin Ind Estate
Singapore 339944

Attention: Mr. Adrian Chau

Sample Submission Date

24 Dec 2012

Description of Sample

LED Emergency Exit Sign


Trade Name : PNE
Model : TEX 300; TEX 300 RM;
TEX 300 LA; TEX 300 RM LA;
TEX 300 RA; TEX 300 RM RA;
TEX 300 DWA; TEX 300 RM UA;
TEX 300 RM DA; TEX 300 RM DWA
Rating : 240V 50Hz
Load : 18 × SMD LED
Battery : 2.4V 1.6AH NI-CAD
Quantity : One (1) sample for each model
Manufacturer : PNE Translite Pte Ltd
Country of origin : Malaysia

LED lamp manufacturer : CREE


LED lamp model : CLA1A-WKW
LED Colour : Cool White

LA-2007-0380-A The results reported herein have been performed in


LA-2007-0381-F accordance with the laboratory’s terms of accreditation
LA-2007-0382-B under the Singapore Accreditation Council - Singapore
LA-2007-0383-G Laboratory Accreditation Scheme. Tests/Calibrations marked
LA-2007-0384-G "Not SAC-SINGLAS Accredited" in this Report are not
LA-2007-0385-E included in the SAC-SINGLAS Accreditation Schedule for
LA-2007-0386-C our laboratory.
LA-2010-0464-D

Laboratory: Phone : +65-6885 1333 Regional Head Office:


TÜV SÜD PSB Pte. Ltd. Fax : +65-6776 8670 TÜV SÜD Asia Pacific Pte. Ltd.
Testing Services E-mail: testing@tuv-sud-psb.sg 3 Science Park Drive, #04-01/05
No.1 Science Park Drive www.tuv-sud-psb.sg The Franklin, Singapore 118223
Singapore 118221 Co. Reg : 199002667R Page 1 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Method of Test

The assessment detailed in this document was carried out in accordance with Singapore Standard 563 : Part
1 : 2010 “Emergency lighting”, Singapore Standard 563 : Part 2 : 2010 “Installation requirements and
maintenance procedures”, and Singapore Standard 263 : Part 2 : 1998 (IEC 60598-2-22 : 1997) “Particular
Requirements for Luminaires for Emergency Lighting”, used in conjunction with Singapore Standard 263 :
Part 1 : 2010.

Results

Test to SS 563 : Part 1 : 2010

Clause No. Title/Description Results Permissible Limits

10 Internally illuminated graphical symbol


signs

10.1 Standards Complied -

10.2 Colour Complied -

10.3 Luminance

10.3.1 Requirements for emergency mode Complied -

10.3.2 Requirements for non-emergency mode Complied -

10.4 Uniformity

10.4.1 Uniformity of colours Complied Greater than 1:5


Greater than 1:10
(for luminance greater
than 100cd/m2)

10.4.2 Uniformity between colours Complied Not less than 5:1 and
not greater than 15:1

10.5 Height of the sign equating to viewing


distance
- Height of the sign 150mm -
- Viewing distance 30m -

11 Influence of smoke

Luminance of any area of the safely colour 2 2


11.1 cd/m Minimum: 10cd/m
of exit signs and direction arrows not less Suitable for use
2
than 10cd/m when smoke is of
prime consideration

Page 2 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Results (cont’d

Test to SS 563 : Part 2 : 2010

Clause No. Title/Description Results Permissible Limits

5.2 Illumination

5.2.2 Electrically operated internally illuminated Complied -


graphical symbol signs

5.2.3 Electrically operated internally illuminated


'EXIT' signs
a) The luminance of the background in the Complied Minimum : 8 cd/m²
area within 25mm of the legend

b) The ratio of the luminance of legend to Complied Not less than 4:1
that of the adjacent background

c) The variation in luminance within the Complied Not more than 5:1
legend and within the background

5.4 Dimensions and viewing distances

5.4.1 Graphical symbol signs Complied -

5.4.2 'EXIT' signs


- Letter style Complied -
- Letter height Complied Minimum : 100mm
- Border surrounding the legend Complied Minimum : 25mm

5.5 Colours Complied -

6 Operation of emergency lighting

6.1 Maximum delay (sec) Less than 1 Maximum : 1

6.2 Battery voltage at rated duration (Vdc) 2.36 Minimum : 2.04

Duration of operation (hrs) 5hr 34min Minimum : 2


(declared duration)
Minimum : 3
(upon commissioning)
6.3 Arrangement and Control

6.3.1 a) Provision of a time delay or other suitable Not Applicable -


means to allow the normal lighting lamp to
restrike

Page 3 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Results (cont’d)

Test to SS 563 : Part 2 : 2010

Clause No. Title/Description Results Permissible Limits

6.3.3 Self-contained emergency escape Complied -


luminaires
Self-contained emergency escape
luminaires and exit sign arranged so that
each is automatically connected to its
emergency power source upon failure of
electrical supply to normal lighting in
designated area.

6.4 Labelling of devices controlling the Not Applicable -


operation of emergency lighting
Device which if turned off or removed,
causes emergency escape lighting or exit
signs to operate shall provide warning
notice clearly and durably affixed.

7 Emergency power supply (centrally


supplied system)

7.2 Battery and battery installation Not Applicable -

7.3 Battery chargers Not Applicable


-
7.4 Inverters Not Applicable

7.5 Stanby generator Not Applicable -


-
8 Emergency power supply (self-
contained)

8.1 Application Complied -

8.2 Arrangement and Control

8.2.1 Requirements for self-contained emergency Complied -


luminaire / exit sign

8.2.2 Test switch Complied -

8.3 Batteries

8.3.1 Required type Complied -

8.3.2 Battery capacity Complied -

8.3.3 Provision for battery replacement Complied -

8.4 Battery chargers Complied -

Page 4 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Results (cont’d)

Test to SS 563 : Part 2 : 2010

Clause No. Title/Description Results Permissible Limits

8.5 Control equipment Not Applicable -

8.6 Self-contained emergency luminaires Complied -

8.6.1 Electrical and mechanical requirements Complied -

8.6.2 Marking Complied -

9 Provision of discharge test facilities

9.2 Required facilities Complied -

9.3 Manual testing facilities Complied -

10.6 Emergency escape luminaires and exit -


signs
-
10.6.1 Electrical safety Complied

10.6.2 Marking Complied -

10.7 Identification of emergency escape Complied -

Page 5 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Results (cont’d)

Test to SS 263 Part 2 : 1998

Clause No. Title/Description Results Permissible Limits

22.4 Classification of luminaires

a) Classification according to type of Class I -


protection against electric shock

b) Classification according to degree of IP20 -


protection against ingress of dust and
moisture

c) Classification according to material of Non-Flammable -


supporting

22.5 Marking Complied -

22.6 Construction Complied -

a) Discharge current when battery voltage Complied Max : 0.0015 × C5A


fell below Vmin (A) = 0.0024

b) Measured Vmin (V) 2.04 Minimum: 1.6

22.7 Creepage distances and clearances Complied -

22.8 Provision for earthing Complied -

22.9 Terminals Complied -

22.10 External and internal wiring


a) External wiring Complied -
b) Internal wiring
- Minimum cross-sectional area Complied -
- Minimum insulation thickness Complied -

22.11 Protection against electric shock Complied -

22.12 Endurance test and thermal tests

a) Endurance test

Test temperature = 25°C Complied -


Test voltage = 240VAC

i) Test duration = 390 hours


Ten cycles of 36 hrs, each cycle
consists of 30 hrs operated normally
and 6 hrs operated under emergency
mode. The last 30 hrs operated
normally.

Page 6 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Results (cont’d)

Test to SS 263 Part 2 : 1998

Clause No. Title/Description Results Permissible Limits

Contd. ii) 50 supply voltage switching operations Complied -


22.12 Test voltage = 240VAC
60s on and 20s off

b) Thermal test (Normal operation)


Test temperature = 25°C
Test voltage = 254.4VAC

* Maximum temperature Complied -

c) Thermal test (Emergency operation)


Test temperature = 25°C
Test voltage = DC mode

* Maximum temperature Complied -

d) Thermal test (Abnormal operation)


Test temperature = 25°C
Test voltage = 264VAC

* Maximum temperature Complied -

22.13 Resistance to dust and moisture


Ingress of dust and moisture Not Applicable -
Humidity test Complied -

22.14 Insulation resistance and electric strength


7
Insulation resistance (Megohm) 2.8 10 Minimum : 2
Electric strength Complied -
Leakage current (mA) Complied Maximum : 1

22.15 Resistance to heat, fire and tracking


a) Resistance to heat Complied -
b) Resistance to fire Complied -
c) Resistance to tracking Not Applicable -

22.16 Functional safety


22.16.1 Rated lumen output (Im) Not Applicable -
22.16.2 Photometric data Not Applicable -
22.16.3 Photometric measurements Not Applicable -
22.16.4 Colour-rendering index Complied Minimum : 40
22.16.5 Illuminance and luminance requirements Complied -

22.17 Changeover operation Complied -

* All surface temperature measurements were made using thermocouple method, except for magnetic ballast
temperature measurement using resistive method.

Page 7 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Results (cont’d)

Test to SS 263 Part 2 : 1998

Clause No. Title/Description Results Permissible Limits

22.18 High temperature operation Complied -


Self-contained emergency luminaires shall be
capable of operating satisfactorily in the
emergency mode at an ambient temperature of
70°C for at least half of rated duration

22.19 Battery chargers for self-contained Complied -


emergency luminaires
The battery charger shall provide the rated
charge performance specified by the battery
manufacturer

22.20 Test devices for emergency operation Complied -

A Appendix A
Type of batteries Nickel-Cadmium -
Battery

a) Maximum continuous ambient air 26.6 Maximum: 50


temperature, measured by a
thermocouple within 5 mm of but not
touching the cells (°C)

b) Maximum continuous overcharge rate 0.09 Maximum: 0.08 x C5


(1.06 times rated voltage) (A) = 0.128

c) Minimum continuous ambient temperature 22.2 Minimum: 5


of cells ( C)

d) Maximum discharge rate (A) 0.42 Maximum: 0.425 x C5


= 0.68

Page 8 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Remarks:

1) The “PNE” LED Emergency Exit Signs was submitted for type testing.

2) The test results were based on testing of one (1) sample each of the following models supplied by
the client:

TEX 300; TEX 300 RM;


TEX 300 LA; TEX 300 RM LA;
TEX 300 RA; TEX 300 RM RA;
TEX 300 DWA; TEX 300 RM UA;
TEX 300 RM DA; TEX 300 RM DWA

3) The “PNE” LED Emergency Exit Signs submitted was evaluated to Singapore Standard 563 : Part : 1
and 2, and deemed to comply with the selected clauses of Singapore Standard 563 : Part 2 : 2010
“Installation requirements and maintenance procedures”, SS263 : Part 2 : 1998 (IEC 60598-2-22 :
1997) “Particular requirements for luminaires for emergency lighting” with Amendment No. 1: 2003
and Amendment No. 2: 2008, used in conjunction with Singapore Standard 263 : Part 1 : 2010.

____________________________
KWOK YEE MENG TAN HENG KHOON
TESTING OFFICER PRODUCT MANAGER
LIGHTING
TESTING SERVICES

Page 9 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix I

Component list

object/part manufacturer/ type/model technical data standard mark(s) of


No. trademark conformity
Input Heavy Power PA 12 450V 2.5mm 2 EN 60998-2- VDE Approval
terminals Co. Ltd T40 100A 1:2004 No.
EN 60998- 40016433
1:2004
Battery Sylva Industries GP 160SCKT 2.4V, 1.6Ah IEC 61951- PSB
Ltd 1:2003 Certificate No.
01561
Transformer PNE Electric C9A1055L028 i/p:240V, o/p: IEC 61558-2- PSB ref:
Sdn Bhd 000 8V 6:1997 7191052848-
IEC 61558- EEC13-CMF
1:1998
LED control PNE Electric PNE 300 230-240V 50- IEC 61347-2- PSB
gear Sdn Bhd 60Hz 7; IEC 61347- Ref:
2-13:2006 7191052848-
(selected EEC13-CMF
clauses); IEC
61347-1:2007
(selected
clauses); IEC
62384
(selected
clauses)
LED CREE CLA1A-WKW Forward IEC Tested as
current : 35mA 62031:2008 intergrated
Forward (selected component
voltage : 3.6V clauses); IEC
62471: 2006
(selected
clauses)
Secondary Furukuawa TEX-E Class B - UL
winding Electric Co Ltd
(Reinforced
insulation)
Power pack

Page 10 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II

View of Emergency Exit Signs

7191049787-EEC13-KYM

Page 11 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

7191049787-EEC13-KYM

Page 12 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

7191049787-EEC13-KYM

Page 13 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

Front View
Exit Right (model: TEX 300 DWA)

7191049787-EEC13-KYM

Page 14 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

Back View
Exit Left (model: TEX 300 DWA)

7191049787-EEC13-KYM

Page 15 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

7191049787-EEC13-KYM

Page 16 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

Exit Left

7191049787-EEC13-KYM

Page 17 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

Exit Right

7191049787-EEC13-KYM

Page 18 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

Exit Up

7191049787-EEC13-KYM

Page 19 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

Exit down

7191049787-EEC13-KYM

Page 20 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

Front view
Exit right (model: TEX 300 RM DWA)

7191049787-EEC13-KYM

Page 21 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix II(Cont'd)

View of Emergency Exit Signs

Back view
Exit left (model: TEX 300 RM DWA)

7191049787-EEC13-KYM

Page 22 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix III

General view of LED Emergency Exit Signs

7191049787-EEC13-KYM

7191049787-EEC13-KYM

Page 23 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix IV

Internal view of LED Emergency Exit Signs

7191049787-EEC13-KYM

7191049787-EEC13-KYM

Page 24 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix V

View of components

LED control gear

7191049787-EEC13-KYM

Front view

7191049787-EEC13-KYM

Page 25 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix V (Cont’d)

View of components

Back view

7191049787-EEC13-KYM

Page 26 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix V (Cont’d)

View of components

Transformer

7191049787-EEC13-KYM

7191049787-EEC13-KYM

Page 27 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix V (Cont’d)

View of components

Test Switch, LED and Charge Indicator (Green)

7191049787-EEC13-KYM

Batteries

7191049787-EEC13-KYM

Page 28 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix V (Cont’d)

View of components

LED

7191049787-EEC13-KYM

7191049787-EEC13-KYM

Page 29 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Appendix V (Cont’d)

View of components

Supply Terminal

7191049787-EEC13-KYM

Page 30 of 31
Test Report No. 7191049787-EEC13-KYM
dated 04 Jul 2013

Please note that this Report is issued under the following terms :

1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.

2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no
responsibility for the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information
supplied.

3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.

4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or results
furnished by TÜV SÜD PSB in any advertisements or sales promotion.

5. Unless otherwise stated, the tests were carried out in TÜV SÜD PSB Pte Ltd, No.1 Science Park Drive Singapore 118221.

July 2011

Page 31 of 31