Medidor de Velocidade CTV 200
Medidor de Velocidade CTV 200
Transmitter features
Air velocity
Working principle : air velocity measurement is made using a hotwire in constant
thermal equilibrium. The temperature is measured with a Pt 100 element.
Example : CTV200-MN150 = air velocity and airflow transmitter type CTV 200, Airflow 0 to 100 000 m3/h 1 m3/h - 0,1 m3/s
with 115 Vac power supply, without display, with hotwire probe length 150mm. (depends on air velocity and duct dimensions) 0,1 l/s - 1 cfm
Housing dimensions Hotwire probe features
(including wall-mounting plate)
Probe material .................................316 L stainless steel
Dimensions......................................Ø 8 mm, lg. 150mm or 300 mm
Working temperature......................from 0 to +50°C
70 mm
Cable ................................................PVC Ø 4,8 mm, lg. 2 m
150 mm
Housing features
115 mm
160 mm
150 or 300 mm
Tube
Ø 8 mm
Housing ..................................ABS
Fire-proof classification ........V.0 as per UL 94
Dimensions ............................see drawing alongside
45 mm
Protection ...............................IP 65
23 mm
locking ring
and st.steel o’ring
Display .....................................alphanumeric, 2 lines of 16 digits,
98mm x 22mm, backlit
protection screen made of PMMA
Connection fittings ................polyamide for cables Ø 7 mm max.
Weight.....................................800 g (with display)
Technical Specifications
Power supply .............................24 Vac / Vdc ±10%
.....................................................115 Vac or 230 Vac ±10%, 50-60 Hz
Relays and Alarms Output .........................................2 x 4-20 mA or 2 x 0-10 V (4 wires)
.....................................................maximum load : 500 Ohms (4-20 mA)
.....................................................minimum load : 1 K Ohms (0-10 V)
Class 200 transmitters have 4 stand-alone and configurable alarms : 2
Galvanic isolation ......................inputs and outputs (115 Vac/230 Vac models)
visual alarms (dual color LED) and 2 relays (contacts).
.....................................................outputs (24 Vac/Vdc models)
You can set : Consumption..............................5 VA
Relays .........................................2 RCR relays 6A / 230 Vac
- the parameter (air velocity, airflow, temperature) Visual alarms..............................2 dual color LED
- 1 or 2 set points (high and low) for each alarm Audible alarm .............................buzzer
- the time-delay / 60 sec. max. Electro-magnetical compatibility ...EN 61 326
- the alarm action : rising or falling Electrical connection ..................screw terminal block for cable Ø 1.5 mm² max
- the relay operation mode : positive or negative security RS 232 communication .............digital : ASCII, proprietary protocol
- the audible alarm (buzzer) activation. Working temperature.................0 to +50°C
Storage temperature..................-10 to +70°C
Environment...............................air and neutral gases
RS 232 communication
Configuration
You can configure all the parameters of the transmitter : units, measuring
• Via the RS 232 connection, the CTV 200 can transmit its ranges, alarms, outputs, channels, calculation formula... via the
different methods shown below :
measurements to a KIMO Class 300 transmitter.
Example : a CP 300 can display (in addition to the pressure) other Via keypad : only on models with display.
parameters such as air velocity and airflow from a CTV 200. A code-locking system combined with keypad guarantees the
security of the installation. See configuration manual.
0V 10V
4 mA 20 mA
Connection
d b
Output selection Analogue outputs Relay terminal blocks
4-20 mA
or 0-10 V h
Power supply
a terminal block
24 Vdc / ac
i
[ 230 Vac
115 Vac
The ticked box shows
the power supply type
of the transmitter
(230 Vac shown above).
RS 232 Hotwire probe
connector e connector e
d g Connection fittings
b
{
{
Analogue output 1 Analogue output 2 Relay 1 Relay 2 a or a or a
Power supply Up
terminal block
0-10 V 4-20 mA Pin # Description
- 1 NC *
Alimentation 2 NC *
24 Vdc
3 NC *
+
4 B-
• For 24 Vac power supply models :
Vac Vac
Output connection : 5 A+
Power supply ~ ~ N L • 4-20 mA current output : 6 NC *
terminal block 0-10 V GND 4-20 mA
OR 7 NC *
-
8 NC *
+
Output
terminal block
Pe
9 RX (RS 232)
N ~ Pe 10 NC *
230 Vac 24 Vac N N Regulator display -
L
~ 230 Vac 24 Vac or PLC/BMS
11 TX (RS 232)
power supply L Ph passive type + 12 NC *
Class II power supply
13 NC *
• For 115 or 230 Vac power supply models : • 0-10 V voltage output : 14 NC *
ground phase 0-10 V GND 4-20 mA
neutral 15 GND (RS 232)
Output -
+
terminal block
Power supply ! CAUTION :
terminal block
NC * --> DO NOT CONNECT
Regulator display +
or PLC/BMS
115 / 230 Vac passive type -
power supply
Calibration Mounting
To install the transmitter on a wall : fix the
stainless steel plate to the wall (this plate
is supplied with the transmitter).
Output diagnostics : Drill 8mm holes and mount the plate with
With this function, you can check with a the screws and wall-plugs supplied with
multimeter (or a regulator display, or a the transmitter. Insert the transmitter on
PLC/BMS) if the transmitter outputs work the plate (see A on the drawing shown
properly. The transmitter generates a below), by aligning it at 30°. Rotate its
voltage of 0 V, 5 V and 10 V or a current of housing in clockwise direction until you
4 mA, 12 mA and 20 mA . hear a “click” which confirms that the
transmitter is correctly installed. Then,
Certificate :
open the housing, lock the clamping system of the housing on the plate, with
• Class 200 transmitters are supplied with adjusting certificates.
the screws as shown (to remove the transmitter from the plate, remember to
Calibration certificates are offered as an option.
remove the screws first).
120 mm
316 L
Maintenance stainless steel A
65 mm
98 mm
plate
Avoid aggressive solvents.
Protect the transmitter and probes from any cleaning product A
containing formol, which may be used for cleaning rooms or
Ref. FT ang - CTV 200 - 02/06 B- We reserve the right to modify the characteristics of our products without notice.
ducts.
65 mm Ø 5,4 mm
Options
Configuration software type LCC 300 supplied with
RS 232 connection cable
Calibration certificate. ! Positioning the measuring element in the air flow
direction
of the air flow
protection tube
red dot