1. Tripping Conditions of NGR Fail-Safe Relay with Neutral Grounding Resistor Monitoring Relay and
Ground Fault(Earth Fault) Monitoring Relay of 0 to 750 mAmp, Aux. Supply of the Relay: 80V to 230V
AC. Green LED for Relay Healthy and Red LED for Trip.
i) Neutral Connection Open
ii) Ground Connection Open
iii) Neutral Grounding Resistor Connection Open
iv) Phase to Earth Fault
v) Faulty current is display
vi) In All Fault of the Transformer Neutral terminal and Ground Terminal Primary or Secondary
breaker will trip.
vii) In All Fault of the Transformer Neutral terminal and Ground Terminal Buzzer will Operated.
viii) Test and Reset Push Button Mounted on Cover For NGR System Check, No external power supply or
test equipment is required.
ix) Neutral Earth Fault relay.
x) NGR Monitoring fail safe relay.
xi) Neutral to Earth through Resistance to be connected by cable or Insulated strip.
xii) Sensor open circuit.
2) Neutral Grounding Resistor: Resistance (NICROME NICKEL CRONIUM WIRE WOUND INDUSTRIAL TYPE) of
Suitable Rating.
3) Sensor– Sensing of signals for Fail Safe Relay and Protections Of High Voltage, High Insulation
Level, Ensure Healthy Condition of NGR, Epoxy Molded.
4) Enclosure of NGR- IP-55, Powder Coated, dust proof, Heat Proof Covered Outdoor Type
5) NCT Current Transformer Type: Ring / IND Resin Cast, System Voltage: 433VAC, Ratio: 100/1 A, 10
VA, 5P10