Project Summary
Location and Weather
Project Project Name
Address
Calculation Time Friday, February 11, 2022 7:56 PM
Report Type Standard
Latitude 31.41°
Longitude 73.11°
Summer Dry Bulb 102 °F
Summer Wet Bulb 83 °F
Winter Dry Bulb 36 °F
Mean Daily Range 17 °F

Building Summary
Inputs
Building Type Manufacturing
Area (SF) 30,139
Volume (CF) 301,387.71
Calculated Results
Peak Cooling Total Load (Btu/h) 566,760.3
Peak Cooling Month and Hour July 3:00 PM
Peak Cooling Sensible Load (Btu/h) 412,374.9
Peak Cooling Latent Load (Btu/h) 154,385.5
Maximum Cooling Capacity (Btu/h) 541,291.6
Peak Cooling Airflow (CFM) 17,890
Peak Heating Load (Btu/h) -185,305.2
Peak Heating Airflow (CFM) 2,656
Checksums
Cooling Load Density (Btu/(h·ft²)) 18.81
Cooling Flow Density (CFM/SF) 0.59
Cooling Flow / Load (CFM/ton) 378.77
Cooling Area / Load (SF/ton) 638.13
Heating Load Density (Btu/(h·ft²)) -6.15
Heating Flow Density (CFM/SF) 0.09

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 2 of 10

Zone Summary - Default


Inputs
Area (SF) 28,043
Volume (CF) 280,432.85
Cooling Setpoint 74 °F
Heating Setpoint 70 °F
Supply Air Temperature 54 °F
Number of People 66
Infiltration (CFM) 270
Air Volume Calculation Type VAV - Single Duct
Relative Humidity 46.00% (Calculated)
Psychrometrics
Psychrometric Message None
Cooling Coil Entering Dry-Bulb Temperature 78 °F
Cooling Coil Entering Wet-Bulb Temperature 63 °F
Cooling Coil Leaving Dry-Bulb Temperature 49 °F
Cooling Coil Leaving Wet-Bulb Temperature 50 °F
Mixed Air Dry-Bulb Temperature 78 °F
Calculated Results
Peak Cooling Load (Btu/h) 493,619.4
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 395,649.9
Peak Cooling Latent Load (Btu/h) 97,969.5
Peak Cooling Airflow (CFM) 16,363
Peak Heating Load (Btu/h) -179,664.2
Peak Heating Airflow (CFM) 2,174
Peak Ventilation Airflow (CFM) 2,010
Checksums
Cooling Load Density (Btu/(h·ft²)) 17.60
Cooling Flow Density (CFM/SF) 0.58
Cooling Flow / Load (CFM/ton) 397.78
Cooling Area / Load (SF/ton) 681.74
Heating Load Density (Btu/(h·ft²)) -6.41
Heating Flow Density (CFM/SF) 0.08
Ventilation Density (CFM/SF) 0.07
Ventilation / Person (CFM) 30

Cooling Heating
Components Percentage of Percentage of
Loads (Btu/h) Loads (Btu/h)
Total Total
Wall 29,691.1 6.01% 32,390.0 7.61%
Window 2,345.4 0.48% 1,060.1 0.25%
Door 8,394.8 1.70% 8,763.4 2.06%
Roof 0.0 0.00% 0.0 0.00%
Skylight 0.0 0.00% 0.0 0.00%
Partition 0.0 0.00% 0.0 0.00%
Infiltration 16,568.1 3.36% 9,583.0 2.25%
Ventilation 124,297.3 25.18% 71,250.6 16.73%
Lighting 93,194.5 18.88% -93,194.5 -21.89%
Power 157,713.8 31.95% -157,713.8 -37.04%
People 51,803.1 10.49% -51,803.1 -12.17%
Plenum 0.0 0.00%
Fan Heat 9,611.3 1.95%
Reheat 0.0 0.00%
Total 493,619.4 100% -179,664.2 100%

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 3 of 10

Default Spaces
Peak Cooling Cooling Airflow Peak Heating Heating Airflow
Space Name Area (SF) Volume (CF)
Load (Btu/h) (CFM) Load (Btu/h) (CFM)
7 Space 28,043 280,432.85 359,710.8 16,363 -250,914.7 2,174

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 4 of 10

Zone Summary - 2
Inputs
Area (SF) 2,095
Volume (CF) 20,954.86
Cooling Setpoint 74 °F
Heating Setpoint 70 °F
Supply Air Temperature 54 °F
Number of People 5
Infiltration (CFM) 65
Air Volume Calculation Type VAV - Single Duct
Relative Humidity 46.00% (Calculated)
Psychrometrics
Psychrometric Message None
Cooling Coil Entering Dry-Bulb Temperature 77 °F
Cooling Coil Entering Wet-Bulb Temperature 63 °F
Cooling Coil Leaving Dry-Bulb Temperature 47 °F
Cooling Coil Leaving Wet-Bulb Temperature 48 °F
Mixed Air Dry-Bulb Temperature 77 °F
Calculated Results
Peak Cooling Load (Btu/h) 47,672.3
Peak Cooling Month and Hour July 3:00 PM
Peak Cooling Sensible Load (Btu/h) 35,057.7
Peak Cooling Latent Load (Btu/h) 12,614.6
Peak Cooling Airflow (CFM) 1,527
Peak Heating Load (Btu/h) -5,641.0
Peak Heating Airflow (CFM) 482
Peak Ventilation Airflow (CFM) 150
Checksums
Cooling Load Density (Btu/(h·ft²)) 22.75
Cooling Flow Density (CFM/SF) 0.73
Cooling Flow / Load (CFM/ton) 384.35
Cooling Area / Load (SF/ton) 527.47
Heating Load Density (Btu/(h·ft²)) -2.69
Heating Flow Density (CFM/SF) 0.23
Ventilation Density (CFM/SF) 0.07
Ventilation / Person (CFM) 30

Cooling Heating
Components Percentage of Percentage of
Loads (Btu/h) Loads (Btu/h)
Total Total
Wall 7,046.4 14.78% 7,995.2 20.37%
Window 577.7 1.21% 265.0 0.68%
Door 759.8 1.59% 931.0 2.37%
Roof 0.0 0.00% 0.0 0.00%
Skylight 0.0 0.00% 0.0 0.00%
Partition 0.0 0.00% 0.0 0.00%
Infiltration 4,729.0 9.92% 2,290.8 5.84%
Ventilation 11,209.3 23.51% 5,318.9 13.55%
Lighting 6,901.8 14.48% -6,901.8 -17.59%
Power 11,680.0 24.50% -11,680.0 -29.76%
People 3,860.0 8.10% -3,860.0 -9.84%
Plenum 0.0 0.00%
Fan Heat 908.1 1.90%
Reheat 0.0 0.00%
Total 47,672.3 100% -5,641.0 100%

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 5 of 10

2 Spaces
Peak Cooling Cooling Airflow Peak Heating Heating Airflow
Space Name Area (SF) Volume (CF)
Load (Btu/h) (CFM) Load (Btu/h) (CFM)
2 Space 350 3,497.64 7,824.8 328 -340.2 144
3 Space 301 3,014.24 4,419.5 190 -2,075.7 48
4 Space 439 4,385.49 7,841.0 337 -1,924.3 116
5 Space 1,006 10,057.50 15,671.4 673 -6,619.6 174

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 6 of 10

Space Summary - 7 Space


Inputs
Area (SF) 28,043
Volume (CF) 280,432.85
Wall Area (SF) 7,115
Roof Area (SF) 0
Door Area (SF) 450
Partition Area (SF) 0
Window Area (SF) 48
Skylight Area (SF) 0
Lighting Load (VA) 36,456
Power Load (VA) 61,695
Number of People 66
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 270
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Load (Btu/h) 359,710.8
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 317,728.5
Peak Cooling Latent Load (Btu/h) 41,982.3
Peak Cooling Airflow (CFM) 16,363
Peak Heating Load (Btu/h) -250,914.7
Peak Heating Airflow (CFM) 2,174

Cooling Heating
Components Percentage of Percentage of
Loads (Btu/h) Loads (Btu/h)
Total Total
Wall 29,691.1 8.25% 32,390.0 9.14%
Window 2,345.4 0.65% 1,060.1 0.30%
Door 8,394.8 2.33% 8,763.4 2.47%
Roof 0.0 0.00% 0.0 0.00%
Skylight 0.0 0.00% 0.0 0.00%
Partition 0.0 0.00% 0.0 0.00%
Infiltration 16,568.1 4.61% 9,583.0 2.70%
Lighting 93,194.5 25.91% -93,194.5 -26.29%
Power 157,713.8 43.84% -157,713.8 -44.49%
People 51,803.1 14.40% -51,803.1 -14.61%
Plenum 0.0 0.00%
Total 359,710.8 100% -250,914.7 100%

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 7 of 10

Space Summary - 2 Space


Inputs
Area (SF) 350
Volume (CF) 3,497.64
Wall Area (SF) 403
Roof Area (SF) 0
Door Area (SF) 75
Partition Area (SF) 0
Window Area (SF) 12
Skylight Area (SF) 0
Lighting Load (VA) 455
Power Load (VA) 769
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 15
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Load (Btu/h) 7,824.8
Peak Cooling Month and Hour September 1:00 PM
Peak Cooling Sensible Load (Btu/h) 6,619.7
Peak Cooling Latent Load (Btu/h) 1,205.1
Peak Cooling Airflow (CFM) 328
Peak Heating Load (Btu/h) -340.2
Peak Heating Airflow (CFM) 144

Cooling Heating
Components Percentage of Percentage of
Loads (Btu/h) Loads (Btu/h)
Total Total
Wall 1,028.2 13.14% 1,696.0 23.52%
Window 1,452.9 18.57% 265.0 3.68%
Door 564.3 7.21% 931.0 12.91%
Roof 0.0 0.00% 0.0 0.00%
Skylight 0.0 0.00% 0.0 0.00%
Partition 0.0 0.00% 0.0 0.00%
Infiltration 1,093.9 13.98% 543.2 7.53%
Lighting 1,131.3 14.46% -1,162.3 -16.12%
Power 1,914.5 24.47% -1,967.1 -27.28%
People 639.7 8.18% -646.1 -8.96%
Plenum 0.0 0.00%
Total 7,824.8 100% -340.2 100%

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 8 of 10

Space Summary - 3 Space


Inputs
Area (SF) 301
Volume (CF) 3,014.24
Wall Area (SF) 185
Roof Area (SF) 0
Door Area (SF) 21
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 392
Power Load (VA) 663
Number of People 1
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 7
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Load (Btu/h) 4,419.5
Peak Cooling Month and Hour July 3:00 PM
Peak Cooling Sensible Load (Btu/h) 3,726.7
Peak Cooling Latent Load (Btu/h) 692.8
Peak Cooling Airflow (CFM) 190
Peak Heating Load (Btu/h) -2,075.7
Peak Heating Airflow (CFM) 48

Cooling Heating
Components Percentage of Percentage of
Loads (Btu/h) Loads (Btu/h)
Total Total
Wall 682.1 15.43% 898.1 20.55%
Window 0.0 0.00% 0.0 0.00%
Door 0.0 0.00% 0.0 0.00%
Roof 0.0 0.00% 0.0 0.00%
Skylight 0.0 0.00% 0.0 0.00%
Partition 0.0 0.00% 0.0 0.00%
Infiltration 514.4 11.64% 249.2 5.70%
Lighting 991.0 22.42% -991.0 -22.68%
Power 1,677.1 37.95% -1,677.1 -38.37%
People 554.9 12.56% -554.9 -12.70%
Plenum 0.0 0.00%
Total 4,419.5 100% -2,075.7 100%

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 9 of 10

Space Summary - 4 Space


Inputs
Area (SF) 439
Volume (CF) 4,385.49
Wall Area (SF) 446
Roof Area (SF) 0
Door Area (SF) 0
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 570
Power Load (VA) 965
Number of People 2
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 17
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Load (Btu/h) 7,841.0
Peak Cooling Month and Hour July 3:00 PM
Peak Cooling Sensible Load (Btu/h) 6,526.6
Peak Cooling Latent Load (Btu/h) 1,314.4
Peak Cooling Airflow (CFM) 337
Peak Heating Load (Btu/h) -1,924.3
Peak Heating Airflow (CFM) 116

Cooling Heating
Components Percentage of Percentage of
Loads (Btu/h) Loads (Btu/h)
Total Total
Wall 1,912.2 24.39% 2,164.5 29.04%
Window 0.0 0.00% 0.0 0.00%
Door 0.0 0.00% 0.0 0.00%
Roof 0.0 0.00% 0.0 0.00%
Skylight 0.0 0.00% 0.0 0.00%
Partition 0.0 0.00% 0.0 0.00%
Infiltration 1,239.6 15.81% 600.5 8.06%
Lighting 1,441.8 18.39% -1,441.8 -19.34%
Power 2,440.0 31.12% -2,440.0 -32.73%
People 807.4 10.30% -807.4 -10.83%
Plenum 0.0 0.00%
Total 7,841.0 100% -1,924.3 100%

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022
Page 10 of 10

Space Summary - 5 Space


Inputs
Area (SF) 1,006
Volume (CF) 10,057.50
Wall Area (SF) 667
Roof Area (SF) 0
Door Area (SF) 0
Partition Area (SF) 0
Window Area (SF) 0
Skylight Area (SF) 0
Lighting Load (VA) 1,307
Power Load (VA) 2,213
Number of People 3
Sensible Heat Gain / Person (Btu/h) 375.0
Latent Heat Gain / Person (Btu/h) 625.0
Infiltration Airflow (CFM) 25
Space Type Manufacturing (inherited from building type)
Calculated Results
Peak Cooling Load (Btu/h) 15,671.4
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (Btu/h) 13,738.9
Peak Cooling Latent Load (Btu/h) 1,932.5
Peak Cooling Airflow (CFM) 673
Peak Heating Load (Btu/h) -6,619.6
Peak Heating Airflow (CFM) 174

Cooling Heating
Components Percentage of Percentage of
Loads (Btu/h) Loads (Btu/h)
Total Total
Wall 3,364.9 21.47% 3,236.6 21.74%
Window 0.0 0.00% 0.0 0.00%
Door 0.0 0.00% 0.0 0.00%
Roof 0.0 0.00% 0.0 0.00%
Skylight 0.0 0.00% 0.0 0.00%
Partition 0.0 0.00% 0.0 0.00%
Infiltration 1,552.4 9.91% 897.9 6.03%
Lighting 3,306.6 21.10% -3,306.6 -22.21%
Power 5,595.9 35.71% -5,595.9 -37.58%
People 1,851.6 11.82% -1,851.6 -12.44%
Plenum 0.0 0.00%
Total 15,671.4 100% -6,619.6 100%

file:///C:/Users/DELL%20Pre%205510/AppData/Local/Temp/d8dad5e3-89cb-4b3c-b389-... 2/11/2022