Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

COMPARISON OF CROSSFLOW VS COUNTERFLOW COOLING TOWER

COUNTER FLOW COOLING TOWER CROSS FLOW COOLING TOWER


1 1
Counter flow Cooling Towers are designed so In crossflow towers the water flows
that air flows vertically upward, counter to vertically through the fill while the air
the flow of falling water in the fill. Because of flows horizontally, across the flow of the
this vertical airflow, it is not possible to use falling water. It employs open gravity flow
the open, gravity-flow basins typical in basin for water distribution.
crossflow designs. But uses a pressurized
water piping distribution system.
2 2
In a counter flow cooling tower the fill area is The fill area is visible from the outside
not visible from the outside. and can be approached both from outside
and from plenum area for checking the
For maintenance purposes as well as for
condition of the fill whilst the tower is
inspection it is essential that the tower is to
running.
be shut down and dismantled before any
inspection/maintenance can be carried out. The hot water distribution deck is also
approachable whilst the tower is running
and choking of fills, nozzles can be
checked easily. Minor repairs including
cleaning of nozzles can be done without
taking a shutdown.
3 A running C-flow cooling tower may appear 3 As stated above fill area can be checked
apparently running fine, however, there may even during the running condition of the
hidden deterioration / scaling / fouling of the cooling tower. Normally cleaning can be
fill and distribution system as the CT internals done by water jet from outside or from
are enclosed inside the casing wall. plenum area.
Once the fill needs to be cleaned it has to be
done from dried up CW basin by water spray.
For replacement entire fill assembly to be
dismantled and reinstalled.
Maintenance down time is longer and costly.

4 Uses Hot pressed polystyrene for fill and 4 Employs vacuum formed PVC sheet with
Eliminator material and louvers are made of integral louvres & drift eliminators. The
Aluminum or FRP sheets. Polystyrene is highly sheet profile ensures proper heat transfer
inflammable. is achieved throughout the travel length.
PVC has good flame retardant properties.
5 Fan Power consumption is high due to higher 5 Fan power consumption is low due to
pressure drop in eliminator, pipe distribution lesser pressure drop across the integral
system , pressurized nozzles, fill and louvers. fill /louver and eliminator and absence of
pipe distribution system and pressurized
nozzles.
6 The water is distributed in the cooling tower 6 The water is distributed by gravity and
by a sprinkler system where certain minimum therefore the pumping head required for
amount of pressure is required for the the cooling tower is only the height of the
sprinkler to distribute water. cooling tower from the basin level.
Further, if the sprinkler gets choked due to Nozzles are non-clogging type and can be
quality of water, uneven distribution takes cleaned even whilst the tower is running.
place inside the cooling tower leading to loss
of cooling efficiency.
7 Foot print area requirement is comparatively 7 Because of trapezoidal cross-section of
higher at a certain duty condition and design Cross-flow cooling tower foot print area
parameter. requirement is lesser. As a result overall
area requirement for cross flow cooling
tower is lesser with comparison to
counter flow cooling tower.
8 Can use only Film type fills if water quality is 8 In cross flow cooling tower both film fill
good. and splash type fills can be used.
9 9

You might also like