DIVISION NO.

4
BOQ FOR MEDICAL GASES WORKS FOR IBN KHALDOUN HOSPITAL, LAHJ GOVERNORATE.
UNIT PRICE TOTAL COST
Item NO DESCRIPTION UNIT QTY
(USD) (USD)

PREAMBLE
- This section shall be read in conjunction with parts of (the MG Technical Specifications
General and Particular) and the mech-MG DWG except where otherwise indicated.
- All medical gas products MUST be European made by well-known companies that conform
with HTM-02-01standards.
- The unit price for all items in this section shall inclusive of supply, installation, selection,
operation (commissioning) works and all other luxurious, accessories, appended and
required. Therefore, the item will be fully inclusive, ready for use, with all its requirements,
materials, civil works, forming or cutting holes, chases, channels... etc in concrete structures
and block/stone walls, making good, and execution methods which the supervising engineer
will demand, so as the item will become finally completed.
- The work in this section shall include the rate of carefully dismantle all existing medical
Note.
gases fixtures serving existing spaces, work includes but is not limited to: dismantling bed
head units, gases outlets, control panels, gases networks including pipes and fittings, all
existing cables and connections to electrical power supply, and all existing system
accessories with closing any cores/openings in the existing walls with proper finishing
materials to match the existing in accordance the unops engineer's instructions and all
dismantled items shall be handled to the health facility management team/storage and
subject to the approval of the health facility operator.
- In the event any item is not mentioned in this section and it is necessary or complementary
of the work of another item already mentioned in the table of quantities, it is the contractor’s
responsibility to provide all items without any additional cost.

4.1 Primary and Secondary Automatic Oxygen Manifold :


Supply, lift into position, install, test, set to work, and commission fully automatic oxygen
manifold. Outlet nominal pressure 5 bar , 2x16 consists of two banks right and left each one
4.1.1 for 16 cylinders and automatic change over between the two banks. Set 2 $0.0
Price include cylinders Equipment and installation shall be in full compliance with the HTM
02-01.
4.2 Steel Oxygen Cylinders
Supply, lift into position, steel oxygen cylinders . 6800L - 137 bar -(pin- index) - side spindle- j
size -wheel type -outside dimater 232mm - thickness 5.2mm-filling pressure 150bar- test
4.2.1 pressure 200 bar-water capacity 47.2L- height 1,520mm including valve-j size- weight No 81 $0.0
68.9kg. Equipment and installation shall be in full compliance with the HTM 02-01.

4.3 Triplex Medical Vacuum System:


Supply, install and test commission Triplex floor mounted vacuum plant, Rotary pumps ,to
meet the latest and rigid HTM-02-01 requirements . Triplex pumps, receiver tank, secretion
4.3.1 device, control panel alternate, with duplex bacterial filter and bypass and all required fitting, Set 1 $0.0
connections all as specified and as shown on drawings. Equipment and installation shall be
in full compliance with the HTM 02-01.
4.4 Combined Medical/Surgical Air Compressed Air System:
Supply, install, test and commission Triplex rotary screw floor mounted air compressor unit,
electrical motor, compressor working pressure 13 Bar, safety valve, 2 x 1000 liter receiver
4.4.1 tanks,Maximum receiver pressure 14 bar, secretion device, control panel, air dryer, medical Set 1 $0.0
air regulator( 4 bar , 7 bar), alternate pressure switch and all required fitting, connections all
as specified and shown on drawings.
4.5 Emergency Automatic Medical Air Manifold :
Supply, lift into position, install, test, set to work, and commission fully automatic medical air
manifold. Outlet nominal pressure ≤ 5 bar , consists of two banks right and left each one for 6
4.5.1 cylinders ( 2x6 ) and automatic change over between the two banks. Set 1 $0.0
Price include cylinders and all required fitting, connections and as specified and shown on
drawings.
4.6 Emergency Automatic Surgical Air Manifold :
Supply, lift into position, install, test, set to work, and commission fully automatic medical air
manifold. Outlet nominal pressure ≤ 8 bar , consists of two banks right and left each one for 6
4.6.1 cylinders ( 2x6 ) and automatic change over between the two banks. Set 1 $0.0
Price include cylinders and all required fitting, connections and as specified and shown on
drawings.
4.7 Steel Medical /Surgical Cylinders
Supply, lift into position, steel oxygen cylinders. 6800L - 137 bar -(pin- index) - side spindle-J
size -wheel type -outside diameter 232mm - thickness 5.2mm-filling pressure 150bar- test
4.7.1 pressure 200bar-water capacity 47.2L- height 1,520mm including valve-j size- weight 68.9kg No 54 $0.0

4.8 Copper Piping:


Supply and install , test and commission, Copper pipes type BS EN 1412:1996 grade
CW024A & BS EN 13348:2001 – R250 for medical gases pipes, the pipes shall be cleaned,
flushed and two ends capped. Including but not limited to the risers and risers' duct covering
with all connections, fittings, hangers and supports, and identification colors all as specified
Note
and as shown on drawings. Equipment and installation shall be in full compliance with the
HTM 02-01.
4.8.1 Ø 76 mm copper pipe L.M 131 $0.0
4.8.2 Ø 42 mm copper pipe L.M 24 $0.0
4.8.3 Ø 35 mm copper pipe L.M 118 $0.0
4.8.4 Ø 28 mm copper pipe L.M 638 $0.0
4.8.5 Ø 22 mm copper pipe L.M 335 $0.0
4.8.6 Ø 15 mm copper pipe L.M 596 $0.0
4.8.7 Ø 12 mm copper pipe L.M 183 $0.0
4.9 Isolation Valves:
Supply and install , test and commission, Ø76 mm valves for medical gases pipes, the valves
4.9.1 shall be cleaned, flushed and two ends capped. with nipples and all connection and fittingsall NO 1 $0.0
as specified and as shown on drawings.
4.9.2 Ditto but Ø28 mm valves. NO 3 $0.0
4.10 OUTLET POINTS.
Supply, lift into position, install, test, set to work, and commission according to the drawing
and specifications Wall Outlets Quick Disconnect /parking stage. Gas outlets wall mounted
type complete in box gas specific, self-sealing valve, indexed to eliminate Note
interchangeability /erroneous tapping of gas, filter & cover plate as per standard design.
Unit installation shall be in full compliance with the HTM 02-01.
4.10.1 Oxygen (O2) NO 48 $0.0
4.10.2 Medical Vacuum (VAC) NO 51 $0.0
4.10.3 Medical Air (MA4) NO 47 $0.0
4.10.4 Surgical Air (SA7) NO 16 $0.0
4.11 AREA CONTROL PANEL
Supply, install, and test First Class ionized aluminum Area control panel, with alarm system,
repeater, and indicator lamps for four gases (MA , O2 , VA ), including all valves connections,
4.11.1 fittings. Including, the risers and risers' duct covering, connections and all requirements, NO 4 $0.0
according to Specifications, drawings, and engineers approval. Unit installation shall be in full
compliance with the HTM 02-01.
4.11.2 Ditto 4.11.1, but Three gases NO 10 $0.0
4.11.3 Ditto 4.11.1, but Two gases NO 1 $0.0
4.11.4 Ditto 4.11.1, but central alarm panel as per HTM 02-01 NO 1 $0.0
4.11.5 Ditto 4.11.1, but repeater alarm panel as per HTM 02-01 NO 3 $0.0
SUB TOTAL DIV-04 $0.0