Professional Documents
Culture Documents
User Manual Sperre Controller
User Manual Sperre Controller
User Manual
Sperre controller
GB www.sperre.com
User manual Z-controller
'RFXPHQW,':UHYE
Contents
1 Introduction ............................................................................................ 4
1.1 Purpose ............................................................................................................................. 4
1.2 Annotations ....................................................................................................................... 4
1.3 Abbreviations ..................................................................................................................... 4
1.4 Warranty ............................................................................................................................ 5
5 Menu ...................................................................................................... 10
5.1 Menu structure ................................................................................................................ 10
5.2 Setup menu ..................................................................................................................... 14
8 Appendix ............................................................................................... 27
8.1 Abbreviations ................................................................................................................... 27
8.2 Alarm list (30 Bar)............................................................................................................ 28
ϴ͘ϯ dƌŽƵďůĞƐŚŽŽƚŝŶŐ͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘͘Ϯϵ
1.2 Annotations
All safety directions must be respected in order to avoid damage to personnel, the environment and equipment. In this manual the
annotations are used, as illustrated below:
Indicates possibilities for hazards or unsafe practices, which COULD result in fatal or
Warning severe personnel injuries or substantial product or property damage, if the required
precautions are not taken.
1.3 Abbreviations
Abbreviation Description
Barg Unit of pressure (Barg = Bar gauge)
CW Cooling Water
DOL Direct On Load
HP High Pressure
LP Low Pressure
C Classic range compressor
XA X-range compressor Air-cooled
XW X-range compressor Water-cooled
Please note that the warranty will be void if the equipment is misused or not
handled in accordance with prescribed operating and service standards.
Sperre type approval and classification certificates are only valid when
genuine Sperre parts are used for maintenance.
Genuine Sperre parts are certified with certificate of conformity and authenticity as shown below.
The Z-control provides a complete package of easy-to-use control and monitoring functions in one standard, configurable module.
The controller is installed with a full graphic display with multiple languages. The display shows:
Start counter and running hours,
Instant readout of status information,
Logging of alarms and service history.
And more ...
The control system simplifies preventive maintenance with an easy to read service countdown so there is no need to remove the cover
of the compressor to find out if maintenance necessary. If any blackout on board occurs, the compressor restart is automatically
delayed to avoid power failure.
Items that an operator may need to view during routine operation, for example; pressure or temperature can easily be read from the
display. If a fault condition is active, the display will show a fault code and identification.
Note
If the compressor control system is not
centralized with the ships central alarm
system, the controller needs daily
inspection to observe fault, warning or
alarm conditions.
Start [a] and Stop [b] have one defined function and are not used for any other purpose.
Reset [c] will acknowledge and reset any active alarm or shutdown statuses.
Reset [d] will enter the menu screen.
Reset [e-f] will activate / deactivate the function indicated.
4.2 Information
The normal operational display is described and illustrated below.
a. Delivery pressure.
b. Delivery air temperature.
c. Additional information depending on compressor type.
d. Running hours.
e. Time to next service.
f. Compressor status and state-diagram reference.
g. Alarm tag of the last alarm or shutdown.
h. Current load and unload pressure settings.
i. Time since last service.
Menu
|
Setpoints --> Load and Unload pressures
Load Lead: Start pressure when the compressor is set as lead compressor.
Load Follow: Start pressure when the compressor is set as lead compressor.
Unload Lead: Stop pressure when the compressor is set as lead compressor.
Unload Follow: Stop pressure when the compressor is set as follow compressor.
Sea / harbour mode allow for a lower load/unload setting to be used during periodes when less air is required (eg.
transit).
Note
In a two compressor set-up using lead/follow functions, both compressor pressure settings should be set identical.
The Active alarm tab show all alarm, shutdown and inhibit conditions that has not been cleared.
Refer to Chapter 8.2 for a complete list of alarm and shutdown conditions.
Refer to chapter ‘Service and ordering’ for information regarding service procedures.
User Setting
Setup menu
Note
(Service Level)
Access codes are needed to enter the
| different levels of menu level
Service Settings --> Drain Start Time Service level: Use access code 0100
Drain Stop Time
Note
Drain Interval Time The setup-menu button is deactivated when
Drain Time Open the compressor is running
Auto Restart Time
Lead / Follow Switchover Time
All alarm limits are pre-set from our factory, contact Sperre before making changes.
Diagnostic
The diagnostic screen gives information about the status and values of the digital and analogue IO.
Operation mode is selected by sliding the selector switch In case of malfunction the
located at the main screen to the preferred mode. ‘Emergency stop’ button must be
used to stop the compressor.
Manual mode
Start:
1. Press the start button to start the compressor
The compressor will achieve the set unload pressure and then stop.
When the operator presses the start button again, the compressor will start if the
reciever pressure is below the unload/stop pressure.
When the unload pressure level is achieved the compressor will stop. The compressor
will only start again if the operator presses the start button again.
Stop:
2. Press the stop button. The operator can stop the compressor at any time.
Auto mode
Start:
1. Press the start button to start the compressor
If the pressure is below the load level the compressor is started and the pressure will
begin to rise. When the unload pressure level is achieved, the compressor will stop and
the compressor will remain active in a standby condition.
The compressor will automatically start again when the delivery pressure falls below the
load pressure level. This cycle will continue until the compressor is stopped by pressing
the stop button.
When the delivery pressure is below the unload level, but above the load level, the
compressor can be started again immediately by pressing the start button. This will
cause the compressor to start and increase pressure to the unload level, without the
need to wait for pressure to decrease to the load level.
Stop:
2. Press the stop button to exit auto operation, and stop the compressor.
Lead / Follow and Load Sharing functionality levels out the running hours on the
compressors and can be configured as explained below. Note
Compressor 1 decides which is lead and follow. Optional functionality only available if
specified by the customer when
Lead and follow pressure settings should be equal for both compressors, as seen in ordering.
figure below. Pressure settings are found under menu->set-points.
If this function is desired later on,
please contact Sperre Aftersales
Department for purchasing upgrade kit.
In this example the lead compressor
will start at 26 Bar and stop at 30
Bar. Follow compressor will start at
25 Bar and stop at 30 Bar.
Normally the unload pressure is set
to the same pressure.
Compressor 1 Compressor 2
Compressor 1 decides if compressor 2 should use its lead or follow pressures, by giving
a signal from one of the relay outputs to one of the digital inputs on compressor 2.
The connection between compressor 1 and compressor 2 is fail-safe. If connection
between compressors is lost, compressor 2 becomes ‘lead’ as default.
Load Sharing
When the lead/follow function is activated a timer switches between lead and follow
pressures for the compressors. Note
The timer can be adjusted in the controller configuration (menu->setup menu). Access code 0100 is required to enter
the setup menu.
The timer counts time and is by default set to 12 hours (720 min).
Sea / harbour mode allow for a lower load/unload setting to be used during periodes when less air is required (eg. transit).
If Sea / harbor mode Is enabled, a additional set of load / unload pressures appear in the Setpoint screen.
A example of how a 30Bar system could be set up is shown below.
Note
Optional functionality only available if
specified by the customer when
ordering.
If this function is desired later on,
please contact Sperre Aftersales
Department for purchasing upgrade kit.
The compressors can be operated from a remote location by connecting a switch (not
push buttons) or a relay output from IAS to one of the digital inputs DI3 - DI8. Note
‘Local / Remote’ selection does only
affect the ‘Start / Stop’ function.
Remote Start / Stop:
If any of the other functions are set to
As long as the input is closed the compressor will enter standby or running mode remote operation, they remain remote
depending on the current reciver pressure, and then be controlled depending on the controlled even when the controller is
mode selected (Automatic or Manual). set to local.
When the input is opened the compressor will be set to stopped mode.
The following selections are normally done locally on the display, but can also be
connected to a digital input. *
Load / Unload
*Note
Lead / Follow
Optional functionality. All inputs for
Sea / Harbour Mode remote operation are only available if
specified by the customer when
Automatic / Manual
ordering.
Local / Remote If this function is desired later on,
please contact Sperre Aftersales
Department for purchasing upgrade kit.
When any of these functions are coupled to a digital input, the selector-switch on the
main screen will be dimmed and become inoperatable. It will still indicate the current
state of the input.
Note
Sperre takes no responsibility for
damage caused by use of non-original
parts.
Service procedure A is change of filters and running in oil, and should always be
performed 250 running hours after first time start up. Note
Service procedures should be performed according to the intervals mentioned in the *Use access code 0100 to enter the
compressor manual depending og the compressor type.. Service procedures A2 (X- menus.
range only), B, C, D and E are to be performed in the order illustrated above.
When a service is complete the service technician must confirm service done for that
service type. The controller will automatically increment to the next service type using
the recommended service interval for the compressor type.
Note
Service Warning Please make sure that a complete
gasket kit always is available.
A service warning will occur 200 running hours or 30 days prior to a service, providing a
pre-warning enabling service arrangements, and/or service kit parts, to be organised
prior to the service becoming due. To see the service warning, press “Menu” -> “Alarms”.
Service Alarm
A ‘Service Alarm’ indication will occur when the ‘service interval’ run hours counter
reaches 0(zero) hours, or the service interval ‘time’ expires (whichever occurs sooner).
The Service Alarm will be displayed on the start screen and in the active alarms list
(Menu->Alarms).
The ‘Service Due’ indication on the start screen will be calculated from ‘next service
hours value’ minus ‘current running hours’.
When a service warning occurs the controller will display the “Service Due in 200
Running Hours or 30 days” in the active alarm list (Menu->Alarms). The service counter
on the start screen always shows when the next service is due and which service kit is
needed for the service.
1. Reset the service warning by pressing the “Reset” button in the “Active” alarms
list. The service warnings will not occur again. This facility is intended to provide Note
pre-warning enabling service arrangements.
2. Order the Sperre service kit. Please refer to “Service procedures overview” in the The text line on the start screen will
compressor service manual for the service kit ordering number. indicate the type of service.
Service A will only appear once,
A Sperre service kit contains all necessary spare parts. throughout the life time of the
When a ‘service warning’ is generated no further service warnings for the service type compressor, and will only be indicated
will be generated. A service warning will only be generated once prior to a service with a service alarm.
becoming due and a service alarm being generated.
Service ‘A’:
Service type ‘A’ does not have a ‘Warning’ indication. The controller will show an ‘Alarm’ when the running hours counter reaches 250
hours.
Service type ‘A’ is a unique service type. When a service type ‘A’ has been carried out once no future service type ‘A’ alarms will be
generated. A Service type ‘A’ normally occurs only once in the operational life of the compressor.
When a service alarm occurs the controller will display the “Service Due: [servicename]
0 h” message on the start screen. In the active alarms list there will be displayed a
“Service Due Now” message.
Note
Please make sure that a complete
gasket kit always is available.
1. The service type displayed must be performed with the relevant Sperre service
kit. Please refer to “Service procedures overview” in the compressor service
manual for service kit information.
2. The Service alarm indication can be reset before the service is completed. In this
case the service alarm indication will re-occur again after 24 hours. This goes
on until the “Confirm Service Done” reset procedure has been carried out.
If the “Confirm Service Done” button is colored light gray there is no service alarm
reset procedure necessary or even available.
Using the menu navigation press “Menu”-> “Service Log” on the startscreen to enter the
service log. In the service log all completed and non-completed services will be stored
with a date, run hours and number of motor starts.
In the service log is also an overview over total running hours, running hours to next
service, time since last service, time to next service and total motor starts.
Alarm:
Delivery Pressure low level AA7 4-20mA 0 45 Disabled [Bar]
HP Pressure Alarm AA1 4-20mA 0 45 31 31 31 [Bar]
LP Pressure Alarm AA2 4-20mA 0 8 6.5 6.5 6.5 [Bar]
Delivery Pressure Alarm AA3 4-20mA 0 45 33 33 33 33 [Bar]
Oil Pressure AA5 4-20mA 0 10 0.3 2 [Bar]
High Temperature AA6 4-20mA -20 120 85 85 85 85 [Celsius]
Long Run Alarm AL1 0 1440 Disabled [min]
Shutdown:
HP Pressure Shutdown SA1 4-20mA 0 45 32 32 32 [Bar]
LP Pressure Shutdown SA2 4-20mA 0 8 7.5 7.5 7.5 [Bar]
Delivery Pressure Shutdown SA3 4-20mA 0 45 34 34 34 34 [Bar]
Oil Pressure SA5 4-20mA 0 10 0.2 1.5 [Bar]
Air Temperature SA6 4-20mA -20 120 90 90 90 90 [Celsius]
Oil Level Switch SD2 Digital NC n/a
Emergency stop SD1 Digital NC n/a
Motor Overload SD3 Digital NO n/a
Low Feed Pressure SD5 Digital NO Used only for Booster compressors
Service pre-warning:
Service Warning AS1-x Controller Refer to controller manual chapter 7
Service Alarms AS2-x Controller Refer to controller manual chapter 7
8.3 Troubleshooting
Alarms
Check compressors.
Page 1/4
Parameter setting in controller Check alarm parameter settings in alarm menu.
Compressor HP pressure
AA1 HP Pressure high alarm
high (PT12) Air blockage Check piping and outlet valve
Non return valve failure Check non return valve and replace if defective.
Compressor LP pressure
AA2 LP Pressure high alarm Non return drain valve failure Check non return drain valve and replace if defective.
high (PT13)
Shutdowns
Emergency stop engaged locally or Check that no personnel nor machinery can be harmed
remotly and disengage.
Local or remote Emergency
SD1 Emergency stop shutdown
stop
Loose wires Check and tighten all loose connections.
Non return valve failure Check non return valve and replace if defective.
Page 3/4
Transmitter failure PT11 Check transmitter and replace if defective.
Delivery pressure sensor Delivery pressure
SA20
error shutdown, AI1 transmitter failure
Cables connection failure Fix or change cables / connectionsFKHFNSRODULW\
Page 4/4