EMERGENCY & T&P TESTING

(3050X1750) EMERGENCY & T&P TESTING


(3050X1750)
12250 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
6500 5050 BATTERY OTHERWISE MENTIONED.
(5050X2000) BATTERY
V1 V1 V1 V1 (5050X2000) 2. ALL LIGHT FITTINGS, SHALL BE ADEQUATELY EARTHED
V1 V1 V1 V1 IN CONFORMITY WITH IE RULES.
3. LDBs & PDBs SHALL BE MOUNTED AT 1500 MM FROM

SDB-C2

SDB-C2
SDB-C1 SDB-C2 FLOOR LEVEL .
SDB-C4

4. FOR FALSE CEILING AREAS. FRLS CABLES/WIRES RUN


SB-2
THROUGH 25MMØ & PVC CONDUITS.
SB-2 5. LOCATION OF LIGHT, FAN, OTHER FITTINGS, LDBs
INDICATED ARE TENTATIVE ONLY AN SHALL BE
SDB-C4
SDB-C2 ADJUSTED TO SUIT AT SITE CONDITIONS, IF REQUIRED.
SDB-C1 6. MOUNTING HEIGHT OF INDOOR LIGHT FIXTURES SHALL

SDB-C2
SDB-C8
SB-3 BATH TO SDB
SDB-C1 SDB-C2 (1550X1150) SB-3 BATH BE 2600 MM AND MOUNTING HEIGHT OF PERIPHERY
SDB-C9 SDB-C6 SB-5 (1550X1150) STREET
SDB-C5 SB-5
SDB-C2 LIGHT FIXTURES SHALL BE 3200 MM.
8460 SDB-C3 TO SDB 7. FOR OHE/CIVIL/ARCHITECTURAL RELATED QUARRIES
SDB-C1
SB-6 W.C.
SDB-C7 SB-6 REFER RESPECTIVE DRGS.
(1550X1300) TO SDB W.C.
SDB-C4 SDB-C2 (1550X1300) 8. IF ANY ITEM DIFFER FROM CONTRACT AGREEMENT THE
SDB-C3
SAME WILL BE CONSIDERED AS NON-SCHEDULED ITEM.
SDB SDB-C3 9. ALL WORKS WILL BE EXECUTED AS PER IE RILES & RVNL
SB-4
SDB-C1 SDB SB-4 SPECIFICATIONS.
SDB-C3 10. WIRES FROM LDB TO LIGHT/ FAN/5A SOCKET SHALL BE
1C X 1.5 SQ.MM CU. FLEXIBLE WIRE THROUGH 20MMØ PVC
SDB-C3 CONDUIT WIRE FROM PDB TO 16A SOCKET SHALL BE 1C X
4SQ.MM TO AC/GEYSER SHALL BE 6.0 SQ .MM. CU.FLEXIBLE
SDB-C1 SB-1 SDB-C3
SDB-C5 WIRE THRUOGH 25MMØ CONDUIT.
SB-1

V1 V1
SDB-C3 SDB-C3 V1 V1 CLIENT:- NORTH WESTERN RAILWAY
CONTROL ROOM
(6500X6500 CONTROL ROOM
STORE (6500X6500
(5050X2250) STORE
TO SDB TO SDB (5050X2250)

ELECTRICAL FITTING & CIRCUIT LAYOUT ELECTRICAL LOOPING LAYOUT PROJECT MANAGEMENT CONSULTANCY
(PMC) RITES LTD.
EMERGENCY & T&P TESTING
(3050X1750) LOOPING FROM SWITCH BOARD TO POINT
BATTERY
(5050X2000) LOOPING BETWEEN PP5A SOCKETS
V1 V1 V1 V1 CERTIFICATION:-
LOOPING BETWEEN SWITCH BORADS IT IS CERTIFIED THAT THE DRAWING PREPAREDIS COMPLIED WITH
CL:3.500 KW THE TERM & CONDITION OFCONTRACTOR AND WE OWN
RESPONSIBILITY FOR DESIGN. ADEQUACY & MEETING FUNCTIONAL
CONDUITS FROM SDB TO SWITCH BOARD 32A PERFORMANCE AND OPERATIONAL REQUIREMENT INCLUDING
CONSIDERATION FOR INTERFACE REQUIREMENT OF OTHER
CONDUITS FROM SWITCHBOARD TO LIGHTING FIXTURE CONCERNEDDESIGNER/CONTRACTOR AND COMPLIANCE TO
STANDARDS,NORMS,SAFETY AND STATUTORY RULES &
REGULATIONS.
PROJECT NAME:-
BATH
(1550X1150)
RAILWAY ELECTRIFICATION OF 25 KV OHE WORKS INCLUDING TSS
GENERAL ELECTRIFICATION CIVIL ENGINEERING WORKS
INCLUDING TOWER WAGON SHED, SERVICE BUILDING,STAFF
QUARTERSTRACK WORK AND SIGNALLING & TELECOMMINICATION
W.C.
(1550X1300)
WORKS ON EXISTING TRACKOF SINGLE LINE SECTION OF UDAIUR
04 CITY (EXCL.)-HIMMATNAGAR(EXCL.)210RKM(234.99TKM)SECTION
OF AJMER DIVISION OF NORTH WESTERN RAILWAY.
SDB 09 CONTRACTOR: M/S SALASAR TECHNO ENGINEERING LIMITED
03 7

04

EMERGENCY & T&P TESTING


04

02 DRAWN BY CHECKED BY APPD.BY CPM/STEL ISSUED BY


V1 V1
03 PROJECT:UDAIPUR CITY(EXCL.)-HIMMATNAGAR(RXCL.)

CONTROL ROOM

BATTERY ROOM
CONTROL ROOM
(6500X6500 STORE

STORE ROOM

BATH ROOM
(5050X2250) 06

W.C. ROOM
SWITCH BOARD 06 GENERAL ELECTRICAL LAYOUT DRAWING OF

SPARE
01
UMRA TSS CONTROL BUILDING
32 A DP FOR INCOMING
ELECTRICAL CONDUITING LAYOUT 16 A SPN FOR 15A SOCKET 07 REF NO.ETI/DRG/PSI/TSSLO/RSDO/00008/02/0
5-16A,SPN FOR LP/FP/TL/ DRAWING NO. REV SIZE SCALE SHEET NO.
09
\PP 5A
RITES- TSS UMRA 01 01