BBH Boiler Plan-Model

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

A B A B

5000 mm 3600 mm
2455 mm 1252 mm
ANCHOR BOLT
508 mm 508 mm
203 mm 808 mm 250 mm

WELL COMPACTED GROUND


76 mm 76 mm

1650 mm

1650 mm
BOILER FOUNDATION DETAIL
STEAM HEADERS
BRINE TANK

300 mm FOUNDATION COMPUTATION:


30 mm
G.I. GRATING COVER
SIMPLEX WATER SOFTENER DETAIL "A"
FIN. FLR. LINE
FIN. FLR. LINE

NOSING WT. OF FOUNDATION


60HP 3 PASS WETBACK BOILER 200 mm WF = 3.6m x 1.96m x 0.25 x 2400 kg/cu.m
FEED WATER TANK ( 330 gal ) SUPPORT SPCD
10 mm diam. REINF. BAR
= 4,233 kg
76 mm
76 mm
452 mm WT. OF BOILER W/ WATER Wbt

TRENCH

TRENCH

60HP WB3 BOILER


Wbt = 4,200 kg + 3,200 kg
7500 mm

3600 mm

3600 mm
DETAIL "A" SECTION thru TRENCH

7500 mm
= 7,400 kg
TOTAL LOAD IN SOIL, WS
FUEL OIL DAY TANK ( 330 gal ) 150 75
mmmm
16 mm diam. ANCHOR BOLT
300
75mm
mm WS = 4,200 kg + 7,400 kg
= 11,633 kg

400 mm
10 mm diam. VERTICAL BARS

300 mm
150 mm FLOOR LINE
75 mm ACTUAL SOIL BEARING PRESSURE, Asbp
100 mm 150 mm
100 6,09
mm Asbp = 11,633 kg / (3.6m x 1.96m)
75 mm
10 mm diam. RE. BAR
= 1,646.33 kg/sq.m
WELL COMPACTED GROUND
236 mm 50 mm 200 mm 50 mm FACTOR OF SAFETY
300 mm
FS = 12,225 kg/sq.m / 1,646.33 kg/sq.m
= 7.425

2250 mm

2250 mm
742 mm SECTION ELEVATION PLAN VIEW
1330 mm 1960 mm

BOILER FOUNDATION DATA


WEIGHT OF BOILER : 4,200 kgs
FIVE ( 5 ) METERS CLEARANCE FOR
BOILER TUBE REMOVAL WEIGHT OF WATER (full) : 3,200 kgs
FOUNDATION LAYOUT WEIGHT OF FOUNDATION : 4,233 kgs
TOTAL LOAD ON SOIL : 11,633 kgs
ACTUAL SOIL BEARING PRESSURE : 1,646.33 kg / sq. m
ALLOWABLE SOIL BEARING PRESSURE : 12,225 kg / sq. m
TOP VIEW FACTOR OF SAFETY : 7.425 (SAFE)

A B

EQUIPMENT DATA
ELEV. + 12268 mm

TYPE : 60 HP 3-PASS WETBACK FIRE BOILER


FUEL OIL DAY TANK ( 330 gal ) USE : STEAM GENERATION
SMOKE STACK ( 30 ft high )
FUEL OIL DAY TANK
FEED WATER TANK ( 330 gal )

ELEV. + 2557 mm
300HP 3 PASS WETBACK BOILER
BOILER
DISTRIBUTOR : NINGBO UNIMED IMP. & EXP. CO. LTD.
ELEV. + 2924 mm MODEL: WNS1 - 1.0 - YQ
SIMPLEX WATER SOFTENER MANUFACTURER DATE : 2020
BOILER CONFIGURATION : FIRE TUBE
STEAM HEADERS FUEL TYPE : DIESEL FUEL
WATER TREATMENT : WATER SOFTENER (simplex)
BRINE TANK ( 33 gal ) I.C. BURNER

OPERATIONAL DATA
USE : STEAM FOR PROCESS
236 mm 742 mm946 mm 1996 mm 4280 mm ( CIRCULATE IN STEAM JACKETED KETTLE )
8200 mm STEAM GENERATION : 1,000 kg / hr
DESIGN PRESSURE : 1.0 MPa (10bar)
OPERATING PRESSURE : 100 psig
ELEVATION THRU A - A ELEVATION THRU B - B

RONNEL IGNACIO

PLAN, ELEVATION AND DETAIL 1


CENTRALIZED BOILER UNIT
SECTION OF BOILER 1
OWNER / REPRESENTATIVE