Professional Documents
Culture Documents
Product Data Sheet ch88 in Situ Flue Gas Oxygen Transmitter Rosemount en 1508434
Product Data Sheet ch88 in Situ Flue Gas Oxygen Transmitter Rosemount en 1508434
CH88
In Situ Flue Gas Oxygen Transmitter
• World-ClassTM performance
• Outstanding accuracy
– ±1% full scale
• Boilers • Kilns
• Incinerators • Process heaters
• Industrial heating furnaces
Industrial
Steam
Lime/Cemen
t
Steel
2 Emerson.cn/zh-cn/automation/rosemount
July 2018 CH88 Combustion Flue Gas Oxygen Analyzer System
Emerson.cn/zh-cn/automation/rosemount 3
CH88 Combustion Flue Gas Oxygen Analyzer System July 2018
Specifications
System measurement specifications Installation Specifications
Net O2 range Probe
Variable 0-10% to 0-50%
Probe mounting flange
Accuracy in oxidizing conditions Vertical or horizontal — 2" 150# (4.75" (121mm) bolt circle)
±1% full scale for 0-10% range and above and DIN145
Lowest detectable limit Note: Flanges are flat-faced, and for mounting only. Flanges
0.05% are not pressure-rated. A 2.5" diameter hole in the process is
required.
Process temperature effect
Spool piece P/N 3D39761G02 is available, to offset
less than 0.05% O2 from 100 to 700 °C (212 to 1292 °F)
probe housing from hot ductwork.
System speed of response to calibration gas
Many adapter flanges are available to mate to existing
Initial response in less than 3 seconds, T90 in less than
flanges.
8 seconds. Response to process gas changes will vary
depending on process gas velocity and particulate Probe lengths and approximate shipping weights
loading of the diffuser .5 m (19.68 in.) package: 7.3 kg (16 lb)
1 m (39.37 in.) package: 9.5 kg (21 lb)
Calibration validity 2 m (78.74 in.) package: 12.2 kg (27 lb)
Presentation of calibration gases matches the bottle
Reference air
value to within ±0.1% O2
No instrument air required. Ambient air diffuses into the
probe passively. Ensure that ambient air is fresh (20.95% O2)
Environmental specifications
Calibration
Probe
Semi-automatic manual gas switching. New calibration
Probe values are calculated in the 1056 Combustion electronics.
Process-wetted materials are 304 stainless steel Cal gases
Process temperature limits .4% and 8% O2, balance N2 recommended.
Instrument air may be used as a high cal gas, but is
-40 to 705 °C (-40 to 1300 °F)
not recommended.
optional bypass and jacket accessories permit operation to 100% nitrogen cannot be used as the low cal gas.
1050 °C (1922 °F)
Calibration gas flow
Probe terminations 5scfh (2.5l/min)
4 Emerson.cn/zh-cn/automation/rosemount
July 2018 CH88 Combustion Flue Gas Oxygen Analyzer System
Specifications
Installation specifications
1056 combustion electronics
Analog output
4-20 mA. max load 550 ohms
Heater cable
12-18 ga. power cable
Emerson.cn/zh-cn/automation/rosemount 5
CH88 Combustion Flue Gas Oxygen Analyzer System July 2018
Dimensional drawings
Probe installation dimensions
Note: All dimensions are in meters with inches in parentheses.
Removal/installation
Probe length Removal envelope
.5 m (19.68 in.) 750 mm (30 in.)
1 m (39.37 in.) 1250 mm (49 in.)
2 m (78.74 in.) 2250 mm (89 in.)
6 Emerson.cn/zh-cn/automation/rosemount
July 2018 CH88 Combustion Flue Gas Oxygen Analyzer System
Dimensional drawings
CH88 probe installation dimensions
Note: All dimensions are in meters with inches in parentheses
Mounting flange
ANSI DIN
Flange dia 185 mm
(7.28
Hold dia in.)
19.1 mm
(.75 in.)
(4) Holes Eq 120.7 mm 145 mm
Sp on BC (4.75 in.) (5.71 in.)
Emerson.cn/zh-cn/automation/rosemount 7
CH88 Combustion Flue Gas Oxygen Analyzer System July 2018
Dimensional drawings
Xi Enhanced Interface - Panel Mounting Details
8 Emerson.cn/zh-cn/automation/rosemount
July 2018 CH88 Combustion Flue Gas Oxygen Analyzer System
Ordering information
Probe Length Part # Weight
0.5 m (19.68 in) 6A00507G01 7.3 Kg (16 lbs)
1 m (39.37 in) 6A00507G02 9.5 Kg (21 lbs)
2 m (78.74 in) 6A00507G03 12.2 Kg (27 lbs)
Electronics Part #
1056 Combustion 24490-00
Accessory Part #
Calibration flowmeter 771B635H01
Cal gas adaptor kit to mate
to a 1/4" female fitting on the 1A98771H07
probe.
Replacement sensor board 6A00493G01
Replacement power supply
24248-03
board
Replacement display board 24361-00-
Emerson.cn/zh-cn/automation/rosemount 9
CH88 Combustion Flue Gas Oxygen Analyzer System July 2018
CH88 Accessories
Bypass Packages
The specially designed Rosemount Analytical Bypass Package
for oxygen analyzers has proven to withstand the high
temperatures (to 1050°C/1922°F) in process heaters while
providing the same advantages offered by the in situ sensor.
Inconel tubes provide effective resistance to corrosion, and the
other components common to other sampling systems.
10 Emerson.cn/zh-cn/automation/rosemount
July 2018 CH88 Combustion Flue Gas Oxygen Analyzer System
Emerson.cn/zh-cn/automation/rosemount 11
CH88 Combustion Flue Gas Analyzer System Product Data Sheet
00813-0100-4896, Rev AA July 2018
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
Gas.CSC@Emerson.com