Part II
Investigate Defective Units.
Part III
Activity on field.
Part II Trouble shooting
1. Introduction of Inverter.
2. Troubleshooting single-zone.
3. Troubleshooting Multi-zone.
4. Test board review.
What is an inverter?
3 phase AC
Makes AC of approximate sine
Decreases ripples waves by dividing DC
Reactor
IPM
Electrical
Supply
Inverter
Compressor
Capacitors
Rectifier
1.Time to reach pre-set temp. Relatively long due to fixed capacity. Short because of increase capacity.
2. Fluctuations after reach pre- Major fluctuations due to start/stop Minor fluctuations due to load-
set temp. operations. adaptable operations
3. Sudden current flow when the 5 ~ 6 times rated value. 1.5 times rated value due to gradual
compressor is started frequency increase at the start.
4. Low temp. range during Decrease in capacity. Decrease in capacity compensated by
heating increased rotational speed.
5. Defrosting time Relatively long due to fixed capacity. Short due to maximum capacity
operations
6. Unit composition Relatively simple. Extra parts required.
Bulb (25-40W)
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
Operation Description
Abbreviations
KΩ
Td (T5)
℃
R – T Conversion Table
Main Protection
• 1 Three Minutes Delay at restart for compressor.
• ---- 1min delay on the 1st start-up and 3 minutes delay after.
• 2 Temperature protection of compressor top.
• ---- Top temp. protector cut off for 30s and restart the compressor with 3 minutes
delay. (Hardware function) (120/105)
• 3 Temperature protection of compressor discharge.
• When the compressor discharge temp. is getting higher, the running frequency will be
limited as below rules:
• ----Compressor discharge temp. T5>115℃ for 5s, compressor stops.
• ---- 108<T5<115℃, decrease the frequency to the lower level every 3 minutes.
• ---90<T5<105℃, keep running as the current frequency.
• ----T5<90℃, cancel the frequency limit control or restart compressor
• 4 Inverter module Protection.
• ----Inverter module protection does have a protection function against current, voltage
and temperature. If these protections happened, the corresponding code will display
on indoor unit LED and A/C will stop. The unit will recover 3min delay after the
protection disappeared.
Main Protection
5 Indoor fan delayed open function
----When the system starts the louver will open and the indoor fan will operate 10s later.
----If the system runs in heating mode, the anti-cold wind function has priority.
6 Compressor preheating functions.
----Preheating permitting condition:
If the main relay closed, T4<3℃ and the machine is first power on and compressor
has stopped for over 3 hours.
----Preheating mode:
From the wiring terminal of the compressor, a weak current flows through the
compressor coil, the compressor is heated without functioning .
----Preheating release condition:
If T4>5℃ or user turns on the machine and compressor runs, preheating function will
stop.
---- Crankcase Heater
Single zone inverter, compressor stop and T4 < 3 ℃ active,>=8℃ inactive.
Multi-zone inverter, compressor stop and T4< 3 ℃ active,>=5℃ inactive.
Error Code Overview (IDU)
Note: ☀=2.5Hz flash / ☆=0.2Hz flash/ ●= light on/ ○=off / E4 & P3: Reserved function
Failure code Error code display timing Priority Recovery
EEPROM parameter error E0 display if Error 1 NO
Zero-crossing signal error E2 Power on for 4 minute 2 NO
Indoor fan speed out of control E3 Fan operating for 1 minute 3 NO
Turn off the power supply, after 5 Return to normal Maybe the AC has
seconds , connect the power supply electromagnetic
and turn on the unit. interference.
E1 after 8 munities
Yes
Is all the wiring between terminal and
Indoor PCB connect ok? Reconnect and
No
retest
Yes
Yes
Yes
YES
Indoor PCB is defective.
Replace the indoor PCB.
E3/E7 Fan(indoor/outdoor) Speed Out of Control (RPG/DC motor)
Yes
No
YES
NO
Replace the sensors
YES
Replace YES
compressor
P1 Over voltage or too low voltage protection
Is the power NO
supply correct Be sure the power
and in good supply is normal when
condition? using the units
NO
YES
Charge refrigerant Replace the outdoor
PCB.
Is it ok after
refrigerate change?
NO
Check refrigerant system
(such as clogging of
capillary, etc)
P3 Low temperature protection (-15℃)
Outdoor temperature <= -15 °C, the unit will stop running, the indoor
display will show the error code "P3“. The unit will still receive remote
control signals.
If the outdoor >= -12 °C for 10 minutes, the compressor stops
running more than one hour, or the outdoor temperature>= 5 ℃ for
10 minutes, then reboot to enter the running before the last
shutdown.
P4 Inverter Compressor Drive Error
Is the connection of
compressor good? Is the NO
Reconnect and retry
wiring sequence right?
The voltage range proper?
YES
check coil
NO
resistance of
inverter Replace inverter compressor
Retry, is it error still?
compressor correct
or not?
YES
YES
LED1 Slow On
flashing
LED4 on on
LED1
(yellow)
LED4 (red)
LED 6 and 5 are two lights for controlling the compressor. the below is meanings for those lights.
IU
Problems Green Red Fast Judgment
No. display
1 standby for normal ● ○
2 Operation normally ○ ●
Peak current>30.7 A. comp.
IGBT over current ☀: ○ P0 wiring/IPM/PCB/COMP NG
3 Cooling system NG
Vol<120 or >400V.check the
DC wiring over-high voltage or
● ● P1 power, rectifier voltage. If ok,
over-low voltage
4 change the ODU PCB
MCE problems (DC wiring over-
Voltage protection as above,
high voltage or over-low voltage ● ☀: P1
but this is set by IC hardware.
5 may lead to this problem)
Power to IC failure, change the
MCE start problem ○ ☀: P4
6 outdoor PCB
MCE phrase lost problem.MCE
Wrong wiring UVW or outdoor
zero speed protection. PWM ☀: ● P4
PCB defective
7 synchronization error.
control speed IC and system
Communication EEROR ☀: ☀: P4 IC communication failure,
8 change the outdoor PCB
MCE-Motion Control Engine
PWM-Pulse-Width Modulation
IGBT-Insulated Gate Bipolar Transistor
Note: ☀=2.5Hz flash / ☆=0.2Hz flash/ ●= light on/ ○=off / E4 & P3: Reserved function