MRV II

Design Manual
R410A HEAT PUMP 50HZ

AV08NMVERA AV28NMVERA
AV10NMVERA AV30NMVERA
AV12NMVERA AV32NMVERA
AV14NMVERA AV34NMVERA
AV16NMVERA AV36NMVERA
AV18NMVERA AV38NMVERA
AV20NMVERA AV40NMVERA
AV22NMVERA AV42NMVERA
AV24NMVERA AV44NMVERA
AV26NMVERA AV46NMVERA
AV28NMVERA AV48NMVERA

SYJS-001-08REV.0 Aug. 2008

Downloaded from www.Manualslib.com manuals search engine


CONTENTS

1. Lineup of MRVII system 03


2. Combination of outdoor units 06
3. Products code explanation 07
4. Capacity range 08
5. Features 09
6. Control system 13
7. Specifications 16
8. Dimensions 42
9. Air flow and static pressure curves 74
10. Capacity calculation due to capacity modification coefficient 84
11. Refrigerant piping design 89
12. Wiring design 101
13. Management system H-CACS 110

G R U P A
d.o.o.

Downloaded from www.Manualslib.com manuals search engine


1. Lineup of MRVII system
1.1 Indoor/outdoor models
Indoor units

Type Model
4-way cassette type
PB-700IB AB*MCERA 092 122 162
4-way cassette type 282 302
AB*MCERA 182 242 382 482
PB-950JB
4-way cassette type
AB*MEERA 182 242 282 302 382 482
PB-950IB

Low ESP duct type AD*MLERA 072 092 122 162 182 242

Med ESP duct type AD*MMERA 182 242 282 302 382 482

High ESP duct type AD*MHERA 182 242 282 302 382 482 722 962

Convertible type AC*MC/FERA 092 122 162 182 242 382 482

Wall mounted type AS*MC/AERA 072 092 122 162 182 242

Console type AF*MAERA 072 092 122 182

G R U P A
Outdoor units

Type Model

d.o.o.
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 28HP 30HP
AV*MVERA
08N 10N 12N 14N 16N 18N 20N 22N 24N 28N 30N

Type Model

32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP


AV*MVERA
32N 34N 36N 38N 40N 42N 44N 46N 48N

03

Downloaded from www.Manualslib.com manuals search engine


1.2 External appearance

AV08NMVERA AV10NMVERA AV12NMVERA AV14NMVERA AV16NMVERA

AV18/20NMVERA AV22/24/26NMVERA
Outdoor

AV28/30/32NMVERA AV34/36NMVERA

G R U P A
AV38/40/42NMVERA AV44/46/48NMVERA

d.o.o.

04

Downloaded from www.Manualslib.com manuals search engine


4-WAY CASSETTE TYPE / PB-700IB 4-WAY CASSETTE TYPE / PB-950IB
AB092MCERA AB182MEERA
AB242MEERA
AB122MCERA
AB282MEERA
AB162MCERA AB302MEERA
AB382MEERA
AB482MEERA

4-WAY CASSETTE TYPE / PB-950JB CONVERTIBLE TYPE


AB182MCERA AC092MCERA
AB242MCERA AC122MCERA
AB282MCERA AC162MCERA
AC182MCERA
AC242MCERA
AB302MCERA
AB382MCERA AC382MFERA
AB482MCERA AC482MFERA

LOW ESP DUCT TYPE MED ESP DUCT TYPE


AD072MLERA AD182MMERA
AD092MLERA
Indoor

AD242MMERA
AD122MLERA AD282MMERA
AD162MLERA
AD182MLERA AD302MMERA
AD242MLERA AD382MMERA
AD482MMERA

G R U P A
HIGH ESP DUCT TYPE WALL MOUNTED TYPE
AD182MHERA
AS072MCERA
AD242MHERA AS092MCERA
AD282MHERA AS122MCERA

d.o.o.
AD302MHERA
AD382MHERA AS162MCERA
AD482MHERA AS182MCERA
AS242MAERA
AD722MHERA
AD962MHERA

HRV(heat reclaimed ventilation)


CONSOLE TYPE
ERV0150ANN
ERV0200ANN
AF072MAERA ERV0260ANN
AF092MAERA ERV0350ANN
ERV0800ANN
AF122MAERA
ERV1000ANN
AF182MAERA ERV1200ANN
ERV1500ANN

05

Downloaded from www.Manualslib.com manuals search engine


2. Combination of outdoor units
QTY of Outdoor unit
Capacity(100W) HP Total QTY
AV08 AV10 AV12 AV14 AV16
226 08 1 0 0 0 0 1

280 10 0 1 0 0 0 1

335 12 0 0 1 0 0 1

400 14 0 0 0 1 0 1

450 16 0 0 0 0 1 1

506 18 1 1 0 0 0 2

560 20 0 2 0 0 0 2

615 22 0 1 1 0 0 2

680 24 0 1 0 1 0 2

730 26 0 1 0 0 1 2

800 28 0 0 0 2 0 2

850 30 0 0 0 1 1 2

900 32 0 0 0 0 2 2

G R U P A
960 34 0 2 0 1 0 3

1010 36 0 2 0 0 1 3

1080 38 0 1 0 2 0 3

d.o.o.
1130 40 0 1 0 1 1 3

1180 42 0 1 0 0 2 3

1235 44 0 0 1 0 2 3

1300 46 0 0 0 1 2 3

1350 48 0 0 0 0 3 3

06

Downloaded from www.Manualslib.com manuals search engine


3. Products code explanation
Outdoor unit:
Model: A V 10 N M V E R A
Climate type: T1
Design number:
A stands for fixed frequency type,
H stands for inverter type,
R stands for DC inverter and R410A type
Cooling or heating, and refrigerant: E stands for heat
pump type, refrigerant is R410a
Appearance character
Product series: M stands for MRV II R410A
Applicable voltage:
2 stands for 220~230V/50Hz,
N stand for 380~400VAC/50Hz
Capacity,10=10HP
Product type : "V" stands for MRVII R410A outdoor

Haier Air Conditioner


Indoor unit:
Model: A B 09 2 M C E R A
Climate type: T1
Design number:

G R U P A
A stands for fixed frequency type,
H stands for inverter type,
R stands for DC inverter and R410A type
Cooling or heating, and refrigerant: E stands for heat

d.o.o.
pump type, refrigerant is R410a
Appearance character
Product series: M stands for MRV II R410A
Applicable voltage:
2 stands for 220~230V/50Hz,
N stand for 380~400VAC/50Hz
Capacity,09=9000BTU/h, 12=12000BTU/h
Product type :
"B" stands for cassette type,
"C" stands for convertible type,
"D" stands for duct type,
"S" stands for wall mounted type,
"F" stands for console type
Haier Air Conditioner

07

Downloaded from www.Manualslib.com manuals search engine


HRV:

Model: ERV 1000 A N N

W: with humidifier
N: without humidifier
H: with healthy module
N: without healthy module
A: 220~240V, 50Hz
B: 220~240V, 60Hz
C: 380V, 50Hz
D: 380V, 60Hz
E: 110V, 50Hz
F: 110V, 60Hz
Air flow: m3/h
Heat reclaimed ventilation unit

4. Capacity range
outdoor capacity 8HP 10HP 12HP 14HP 16HP Indoor20HP
18HP unit 22HP

max. indoor unit


quantity 13 16 19 23 26 29 33 36

total indoor 113~ 140~ 168~ 200~ 226~ 253~ 280~ 308~
capacity range 294 364 436 520 588 658 728 800
(*100W)

G R U P A
outdoor capacity 24HP 26HP 28HP 30HP 32HP Indoor36HP
34HP unit 38HP

max. indoor unit 39 43 46 50 53 56 59 63

d.o.o.
quantity

total indoor 340~ 365~ 400~ 425~ 450~ 480~ 505~ 540~
capacity range 884 949 1040 1105 1170 1248 1313 1404
(*100W)

outdoor capacity 40HP 42HP 44HP 46HP 48HP

max. indoor unit 64 64 64 64 64


quantity

total indoor 565~ 590~ 618~ 650~ 675~


capacity range 1469 1534 1606 1690 1755
(*100W)

08

Downloaded from www.Manualslib.com manuals search engine


5. Features
5.1 Adopt the high efficiency compressor
The compressor is scroll type and hermetically-sealled. It is driven by the DC bruchless motor,
and it is protected by the electric control, such as the discharging temperature, the suction
temperature, the oil temperature, the discharging pressure, the running current, etc.
Compressor shall be equipped with the inverter controller and able to change the rotation rate to
follow variation in cooling and heating mode. The outdoor unit shall have the multi-step of
capacity control to meet load fluctuation and indoor unit individual control.

5.2 Large diameter fan blade


The 3-blade fan on outdoor unit is 700mm diameter. And the built-in part
is made of Aluminum. The large-blade fan is running stably and silently.

5.3 High efficiency DC fan motor


The DC fan motor is high efficiency and low noise. Stable operation and reliable performance.

G R U P A
d.o.o.
5.4 Intelligent electric control, with heat expelling fan to reduce the electric control box
temperature and keep the electric safe.

09

Downloaded from www.Manualslib.com manuals search engine


5.5 Heat exchanger adopts the subcooling technology, to keep the refrigerant
in indoor unit flowing normally, further to enhance the unit efficiency greatly.
Outdoor adopts the sub-cooling heat exchanger. In cooling mode, the refrigerant will be cooled further
after being condensed to enhance the over cooling state. Thus the refrigerant will be prevented
changing into gas-liquid mixture in the long pipe and high drop system, and the liquid refrigerant
will flow into the indoor unit evenly to ensure the effect of every indoor unit is normal. Thoroughly
prevent the gas refrigerant flowing into indoor installed at higher place because of the instant
evaporation.

12\14\16HP subcooler
8\10HP subcooler

5.6 Flexible installation and design


Indoor quantity can be up to 64 sets in maximum. And the indoor total capacity can be 50%~130%
of outdoor capacity.
If there are multiple outdoors, the outdoors will be in running by turns, much longer life.
Multiple types of indoor can be chosen for different requirements.

G R U P A
up to 64 sets of indoor

d.o.o.

5.7 More optional outdoor capacity


The basic outdoor unit AV08/10/12/14/16NMVERA can be combined as the standard modular.The
combined outdoors will get the capacity at the interval of 2HP, such as AV18/20/22/24/26/28...etc..

10

Downloaded from www.Manualslib.com manuals search engine


5.8 Long piping length and high drop
The max. high drop can be up to 50m when outdoor is lower than indoor. And the max. single way
total pipe length can be up to 300m.
5.9 Easier maintenance
a. Auto diagnose function
The PCB will check the unit automatically, if there is error such as compressor wiring, sensor,
communication etc., the PCB will indicate failure code via the LED or the wired controller. Many
test modes or backup running modes are possible for easier test running and troubleshooting.
b. Auto restart function
The unit has memory function, when the power is cut off, the unit will memorize the operation state
at the moment, when the power comes again, the unit will run as the previous state.
5.10 Reliable performance
a. High COP
High efficiency and great energy saving are the purchased aim for every air conditioning
manufacturer. Haier MRVII has been designed to get high COP from the reasonable structure and
the excellent electric system.

HEATING COOLING

8HP COP 4.24 EER 4.28

10HP COP 3.95 EER 3.80

12HP COP 4.12 EER 3.90

G R U P A
14HP COP 3.85 EER 3.25

16HP COP 3.90 EER 3.20

d.o.o.
Cooling operation condition: indoor temp is 270CDB/190CWB; outdoor temp is 350CDB/240CWB;
Heating operation condition: indoor temp is 200DB, outdoor temp is 70CDB/60CWB.
b. Approved for RoHS certificate
All the parts in the unit have been approved for RoHS certificate. The parts are in conformance
with RoHS directive. Thus Haier MRVII will be environmental for human and nature.

The directive is to approximate the laws of the Member States on the restrictions of the use of
hazardous substances in electrical and electronics equipment and to contribute to the protection of
human health and the environmentally sound recovery and disposal of waste electrical and
electronic equipment.
c. Less chance of refrigerant leakage
The connection type of outdoor gas stop valve is brazed, therefore it is not easy to leak any
refrigerant.

11

Downloaded from www.Manualslib.com manuals search engine


5.11 Super comfortable
a. High efficiency compressor
The compressor is hermetically scroll type with brushless internal motor, which runs faster,
much more stable. Furthermore, the compressor is with the protection when temperature,
current etc occur error. The compressor will help the unit run normally.

5.12 Multiple indoor types


There are multiple indoor types to meet the variable request. The outdoor can be suitable for
mix-match connection of following indoor types:
< Cassette type
< Convertible type
< Ceiling concealed type
< Med static pressure duct type
< High static pressure duct type
< Wall mounted type
< Console type

G R U P A
d.o.o.

12

Downloaded from www.Manualslib.com manuals search engine


6. Control system
a. Individual control system
Wired controller YR-E12
Yqcb rm qcr rfc QSHI2 JER2 W[MRK2 LIEPXL2 XIQT42 XMQIV cra4

Large LCD is easy to read the data; set the temp. at interval of 10C.

8:3fmsp rgkcp dslargml@ rm qcr rfc qafcbsjc gl _ ufmjc b_w

Hcqgelcb rm afcai rfc qwqrck d_gjspc _srmk_rga_jjw `w npcqqgle GLIGO


`srrml4 Ejqm rfc d_gjspc ambc ugjj bgqnj_w ml PGH
[fcl rfc dgjrcp lccbq rm `c ajc_lcb _lb glbmmp ugjj qclb qgel_j rm rfc
amlrpmjjcp2 JMPXIV gaml ugjj bgqnj_w ml PGH4
G_l bgqnj_w rfc glbmmp aclrp_j _bbpcqq ml PGH
G_l oscpw rfc k_jdslargml fgqrmpw `w npcqqgle GLIGO `srrml
G_l af_lec rfc amlrpmjjcp rwncq `cruccl k_qrcp _lb qj_tc mlc `w
_bhsqrgle rfc hskncp qr_rc
G_l pc_jgxc bs_j amlrpmjjcpq rm amlrpmj mlc slgr2 mp mlc amlrpmjjcp rm amlrpmj
ksjrgnjc glbmmp slgrq
Iosgnncb ugrf rfc glbmmp _k`gclr rckn4 qclqmp gl rfc amlrpmjjcp2 ufgaf
k_icq rfc glbmmp rckn4 kmpc amkdmpr_`jc

G R U P A
controller master controller slave controller group control method

d.o.o.
Infrared remote controller YR-H71, YR-H65

Used to set the MODE, FAN, SWING, HEALTH, TEMP., TIMER etc.

Large LCD is easy to read the data; set the temp. at 10C.

24-hour timer function: to set the schedule in a whole day

Can be combined with the individual remote receiver.

Electric heating button can realize the electric heating function if the unit is
with this function.

remote receiver RE-01

13

Downloaded from www.Manualslib.com manuals search engine


b. Central control system

Group controller: Realize to control 16 indoor units ON/OFF synchronously. Set indoor
units at the same mode.
Note: When the indoor unit is in group control, it CAN NOT be
controlled by its individual controller (wired cotroller or infrared
controller).

Indoor unit

YR-E12
Power

Group controller

G R U P A
d.o.o.

14

Downloaded from www.Manualslib.com manuals search engine


Central controller(1:64)
Can monitor max.64 groups of indoor unit state: running mode, fan
speed, set temp., swing and vent. etc, also will display indoor filter
icon; can set below three modes: the later entering indoor in priority,
central control and lock;
Can monitor indoor failure and save the failure to be checked.
Receive the external signal such as the fire alarm, make the interconnect
control;
Receive the external timing signal to make TIMER ON/OFF control.
ICR01

Connection Outdoor unit


board IGU04 (master unit)

Indoor unit
Wired controller
Unit
Unit Unit (group control)
No. 1
Connection Outdoor unit No. 2 No. 3
board (master unit)

Indoor unit
Unit
Unit Unit
No. 4
Connection Outdoor unit No. 5 No. 6
board (master unit)

Indoor unit
Unit Unit Unit

G R U P A
Connection Outdoor unit No. 7 No. 8 No. 9
board (master unit)

Indoor unit
Unit
Unit Unit

d.o.o.
No. 62
No. 63 No. 64

Central controller(1:64)

15

Downloaded from www.Manualslib.com manuals search engine


7. Specifications
Indoor units
4-way cassette type
Model AB092MCERA AB122MCERA AB162MCERA AB182MEERA
Nominal cooling capacity(KW) 2.8 3.6 4.5 5.6
Nominal heating capacity(KW) 3.2 4.0 5.0 6.3
Electrical heating power(KW)
/Current(A) ---- ---- ---- (2.1/9.55)
Heating capacity at low temp.(KW) 2.5 3.2 4.0 5.0
Electri- Power source(PH,V,Hz) 1,220~230,50 1,220~230,50 1,220~230,50 1,220~230,50
cal
chara- Operating current(A) 0.47 0.47 0.47 0.47
cteris-
tics Power consumption(KW) 0.08 0.08 0.08 0.08

Fan type and Qty centrifugal*1 centrifugal*1 centrifugal*1 centrifugal*1


0.04 0.04 0.04 0.04
Fan Fan motor output(KW)
chara- 700 700 700 1020
cteris- Standard airflow(m /h)
3

tics Standard static pressure(Pa) 0 0 0 0


Max. static pressure(Pa) ---- ---- ---- ----
Exterior dimensions(mm) 660*570*260 660*570*260 660*570*260 840*840*240
Panel exterior dimensions(mm) 700*700*60 700*700*60 700*700*60 950*950*80
Weight(unit,net/gross, Kg) 19/21.6 19/21.6 19/21.6 30/36
Weight(panel, net/gross, Kg) 2.8/4.8 2.8/4.8 2.8/4.8 6/9
Expansion mode Electronic expansion valve

G R U P A
Controller Wired controller/ wireless controller (optional)
Gas piping(mm) 9.52 12.7 12.7 12.7
Piping
dimension Liquid piping(mm) 6.35 6.35 6.35 6.35
Drain hose(mm) 32 32 32 32

d.o.o.
Noise level(dB(A)) H/M/L 32/30/29 32/30/29 33/30/29 34/32/30

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

16

Downloaded from www.Manualslib.com manuals search engine


Indoor units
4-way cassette type
Model AB242MEERA AB282MEERA AB302MEERA AB382MEERA AB482MEERA
Nominal cooling capacity(KW) 7.1 8.0 9.0 11.2 14.0
Nominal heating capacity(KW) 8.0 9.0 10.0 12.5 16.0
Electrical heating power(KW)
/Current(A) (2.1/9.55) (2.1/9.55) (2.7/12.3) (2.7/12.3) (2.7/12.3)
Heating capacity at low temp.(KW) 6.3 7.1 8.0 10.0 12.5
Electri- Power source(PH,V,Hz) 1,220~230,50 1,220~230,50 1,220~230,50 1,220~230,50 1,220~230,50
cal
chara- Operating current(A) 0.47 0.47 0.76 0.76 0.76
cteris-
tics Power consumption(KW) 0.08 0.08 0.15 0.15 0.15

Fan type and Qty centrifugal*1 centrifugal*1 centrifugal*1 centrifugal*1 centrifugal*1


0.04 0.04 0.14 0.14 0.14
Fan Fan motor output(KW)
chara- 1020 1020 1920 1920 1920
cteris- Standard airflow(m /h)
3

tics Standard static pressure(Pa) 0 0 0 0 0


Max. static pressure(Pa) ---- ---- ---- ---- ----
Exterior dimensions(mm) 840*840*240 840*840*240 840*840*295 840*840*295 840*840*295
Panel exterior dimensions(mm) 950*950*80 950*950*80 950*950*80 950*950*80 950*950*80
Weight(unit,net/gross, Kg) 30/36 30/36 38/44 38/44 38/44
Weight(panel, net/gross, Kg) 6/9 6/9 6/9 6/9 6/9
Expansion mode Electronic expansion valve
Controller Wired controller/ wireless controller (optional)

G R U P A
Gas piping(mm) 15.88 15.88 15.88 15.88 15.88
Piping
dimension Liquid piping(mm) 9.52 9.52 9.52 9.52 9.52
Drain hose(mm) 32 32 32 32 32
Noise level(dB(A)) H/M/L 35/34/31 37/35/31 37/35/31 37/35/31 42/39/35

d.o.o.
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

17

Downloaded from www.Manualslib.com manuals search engine


Indoor units
4-way cassette type
Model AB182MCERA AB242MCERA AB282MCERA AB302MCERA
Nominal cooling capacity(KW) 5.6 7.1 8 9
Nominal heating capacity(KW) 6.3 8 9 10
Electrical heating power(KW)
/Current(A) ---- ---- ---- /
Heating capacity at low temp.(KW) 5 6 7.0 8.0
Electri- Power source(PH,V,Hz) 1,220~230,50 1,220~230,50 1,220~230,50 1,220~230,50
cal
chara- Operating current(A) 0.45 0.51 0.51 0.76
cteris-
tics Power consumption(KW) 0.09 0.1 0.1 0.15

Fan type and Qty centrifugal*1 centrifugal*1 centrifugal*1 centrifugal*1


0.05 0.05 0.05 0.09
Fan Fan motor output(KW)
chara- 1200 1200 1200 1800
cteris- Standard airflow(m /h)
3

tics Standard static pressure(Pa) 0 0 0 0


Max. static pressure(Pa) ---- ---- ---- ----
Exterior dimensions(mm) 840*840*240 840*840*240 840*840*240 840*840*280
Panel exterior dimensions(mm) 950*950*80 950*950*80 950*950*80 950*950*80
Weight(unit,net/gross, Kg) 30/36 30/36 30/36 30/36
Weight(panel, net/gross, Kg) 6/9 6/9 6/9 6/9
Expansion mode Electronic expansion valve
Controller Wired controller/ wireless controller (optional)

G R U P A
Gas piping(mm) 12.7 15.88 15.88 15.88
Piping
dimension Liquid piping(mm) 6.35 9.52 9.52 9.52
Drain hose(mm) 32 32 32 32
Noise level(dB(A)) H/M/L 34/32/30 35/34/31 37/35/31 37/35/31

d.o.o.
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

18

Downloaded from www.Manualslib.com manuals search engine


Indoor units
4-way cassette type
Model AB382MCERA AB482MCERA
Nominal cooling capacity(KW) 11.2 14
Nominal heating capacity(KW) 12.5 16
Electrical heating power(KW)
/Current(A) / /
Heating capacity at low temp.(KW) 10 12.5
Electri- Power source(PH,V,Hz) 1,220~230,50 1,220~230,50
cal
chara- Operating current(A) 0.76 0.76
cteris-
tics Power consumption(KW) 0.15 0.15

Fan type and Qty centrifugal*1 centrifugal*1


0.09 0.09
Fan Fan motor output(KW)
chara- 1800 1800
cteris- Standard airflow(m /h)
3

tics Standard static pressure(Pa) 0 0


Max. static pressure(Pa) ---- ----
Exterior dimensions(mm) 840*840*280 840*840*280
Panel exterior dimensions(mm) 950*950*80 950*950*80
Weight(unit,net/gross, Kg) 38/40 38/40
Weight(panel, net/gross, Kg) 6/9 6/9
Expansion mode Electronic expansion valve
Controller Wired controller/ wireless controller (optional)

G R U P A
Gas piping(mm) 15.88 15.88
Piping
dimension Liquid piping(mm) 9.52 9.52
Drain hose(mm) 32 32
Noise level(dB(A)) H/M/L 37/35/31 44/40/36

d.o.o.
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

19

Downloaded from www.Manualslib.com manuals search engine


Indoor units
Ceiling concealed type
Model AD072MLERA AD092MLERA AD122MLERA

Nominal cooling capacity(KW) 2.2 2.8 3.6


Nominal heating capacity(KW) 2.5 3.2 4.0
Electrical heating power(KW) 0.8/3.6 0.8/3.6 1.0/4.6
/Current(A)
Heating capacity at low temp.(KW) 2.0 2.5 3.2
Electri- Power source 1PH, 220~230V, 50Hz
cal
chara- Operating current(A) 0.15 0.15 0.25
cteris-
tics Power consumption(KW) 0.03 0.03 0.045

Fan type centrifugal*1


Fan characteristic

Fan motor output(KW) 0.012 0.012 0.02


Standard airflow(m3/h) 400 400 500
Standard static pressure(Pa) 0 0 0
Max. static pressure(Pa) 20 20 20

610*483.5 610*483.5 610*483.5


Exterior dimensions(mm)
*220 *220 *220
Air outlet dimensions(mm) 418*131 418*131 418*131
Air return dimensions(mm) 480*218 480*218 480*218
Weight(Kg) 13/13.5 13/13.5 14/14.5
Electronic expansion valve

G R U P A
Expansion mode
Controller Wired controller/ wireless controller (optional)
Gas piping(mm) 9.52 9.52 12.7
Piping 6.35 6.35 6.35
dimension Liquid piping(mm)
Drain hose(mm) 24/20 24/20 24/20

d.o.o.
Noise level(dB(A)) H/M/L 35/32/30 35/32/30 35/32/30

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

20

Downloaded from www.Manualslib.com manuals search engine


Indoor units
Ceiling concealed type
Model AD162MLERA AD182MLERA AD242MLERA

Nominal cooling capacity(KW) 4.5 5.6 7.1


Nominal heating capacity(KW) 5.0 6.3 8.0
Electrical heating power(KW)
/Current(A) 1.8/8.2 1.8/8.2 1.8/8.2
Heating capacity at low temp.(KW) 4.0 5.0 6.3
Electri- Power source 1PH, 220~230V, 50Hz
cal
chara- Operating current(A) 0.27 0.55 0.55
cteris-
tics Power consumption(KW) 0.05 0.11 0.11

Fan type centrifugal*2


Fan characteristic

Fan motor output(KW) 0.04 0.04 0.1


Standard airflow(m3/h) 850 1250 1250
Standard static pressure(Pa) 0 0 0
Max. static pressure(Pa) 20 20 20

Exterior dimensions(mm) 1105*483.5* 1105*483.5* 1105*483.5*220


220 220
Air outlet dimensions(mm) 880*131 880*131 880*131
Air return dimensions(mm) 1064*218 1064*218 1064*218

Weight(Kg) 25/26 28/29 28/29


Expansion mode Electronic expansion valve

G R U P A
Controller Wired controller/ wireless controller (optional)
Gas piping(mm) 12.7 12.7 15.88
Piping 9.52
dimension Liquid piping(mm) 6.35 6.35
Drain hose(mm) 24/20 24/20 24/20

d.o.o.
Noise level(dB(A)) H/M/L 36/33/31 36/33/31 39/37/35

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

21

Downloaded from www.Manualslib.com manuals search engine


Indoor units
Med static pressure duct type
Model AD182MMERA AD242MMERA AD282MMERA
Nominal cooling capacity(KW) 5.6 7.1 8.0
Nominal heating capacity(KW) 6.3 8.0 9.0
Electrical heating power(KW) /
/Current(A) / /
Heating capacity at low temp.(KW) 5.0 6.3 7.1
Electri- Power source 1PH, 220V, 50Hz
cal
chara- Operating current(A) 0.51
cteris-
tics Power consumption(KW) 0.1
Fan type and Qty centrifugal*3 centrifugal*3 centrifugal*3

Fan Fan motor output(KW) 0.15 0.15 0.15


chara-
cteris- Standard airflow(m /h)
3
1200 1200 1470
tics Standard static pressure(Pa) 50
Max. static pressure(Pa) 96
Exterior dimensions(mm) 990*650*300
Air outlet dimensions(mm) 200*3
Weight(Kg) 39/40.4
Controller Wired controller/ wireless controller (optional)
Accessories Use for installation
Gas piping(mm) 12.7 15.88
Piping Liquid piping(mm) 6.35 9.52
dimension

G R U P A
Drain hose(mm) 32 32
Noise level(dB(A)) H/M/L 43/37/35 43/37/35

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB

d.o.o.
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

22

Downloaded from www.Manualslib.com manuals search engine


Indoor units
Med static pressure duct type
Model AD302MMERA AD382MMERA AD482MMERA
Nominal cooling capacity(KW) 9.0 11.2 14.0
Nominal heating capacity(KW) 10.0 12.5 16.0
Electrical heating power(KW)
/Current(A) 2.4/10.91 2.4/10.91 2.4/10.91
Heating capacity at low temp.(KW) 8.0 10.0 12.5
Electri- Power source 1PH, 220~230V, 50Hz
cal
chara- Operating current(A) 0.51
cteris-
tics Power consumption(KW) 0.1
Fan type and Qty centrifugal*3 centrifugal*3 centrifugal*3

Fan Fan motor output(KW) 0.15 0.15 0.15


chara-
cteris- Standard airflow(m /h)
3
1900 1900 2100
tics Standard static pressure(Pa) 50
Max. static pressure(Pa) 96
Exterior dimensions(mm) 1410*645*350
Air outlet dimensions(mm) 200*4
Weight(Kg) 55/57
Controller Wired controller/ wireless controller (optional)
Accessories Use for installation
Gas piping(mm) 15.88
Piping Liquid piping(mm) 9.52
dimension
Drain hose(mm) 32

G R U P A
Noise level(dB(A)) H/M/L 43/37/35 44/40/36

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB

d.o.o.
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

23

Downloaded from www.Manualslib.com manuals search engine


Indoor units
High static pressure duct type
Model AD182MHERA AD242MHERA AD282MHERA
Nominal cooling capacity(KW) 5.6 7.1 8
Nominal heating capacity(KW) 6.3 8 9
Electrical heating power(KW)
/Current(A) 2.6/11.9 2.6/11.9 2.6/11.9
Heating capacity at low temp.(KW) 6.3 7.1
5.0
Electri- Power source 1PH, 220~230V, 50Hz
cal
chara- Operating current(A) 1.4 1.4 1.4
cteris-
tics Power consumption(KW) 0.28 0.28 0.28
Fan type and Qty centrifugal*2 centrifugal*2 centrifugal*2
Fan Fan motor output(KW) 0.23 0.23 0.23
chara-
cteris- Standard airflow(m /h) 900~1500 900~1500
3
900~1500
tics Standard static pressure(Pa) 100 100 100
Max. static pressure(Pa) 196 196 196
Exterior dimensions(mm) 970*875*360 970*875*360 970*875*360
Air outlet dimensions(mm) 600*250 600*250 600*250
Weight(net/gross, Kg) 48/56 48/56 48/56
Controller Wired controller/ wireless controller (optional)
Accessories Use for installation
Gas piping(mm) 12.7 15.88 15.88
Piping Liquid piping(mm) 6.35 9.52 9.52
dimension
Drain hose(mm) 32 32 32

G R U P A
Noise level(dB(A)) H/L 42/40 42/40 42/40

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB

d.o.o.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

24

Downloaded from www.Manualslib.com manuals search engine


Indoor units
High static pressure duct type
Model AD302MHERA AD382MHERA AD482MHERA
Nominal cooling capacity(KW) 9.0 11.2 14.0
Nominal heating capacity(KW) 10.0 12.5 16.0
Electrical heating power(KW)
/Current(A) ---- ---- ----
Heating capacity at low temp.(KW) 10.0 12.5
8.0
Electri- Power source 1PH, 220~230V, 50Hz
cal
chara- Operating current(A) 1.5 1.6 1.8
cteris-
tics Power consumption(KW) 0.3 0.32 0.36
Fan type and Qty centrifugal*2 centrifugal*2 centrifugal*2
Fan Fan motor output(KW) 0.27 0.27 0.27
chara-
cteris- Standard airflow(m /h) 1600 2100
3
1560
tics Standard static pressure(Pa) 100 100 100
Max. static pressure(Pa) 196 196 196
Exterior dimensions(mm) 1350*875*360 1350*875*360 1350*875*360
Air outlet dimensions(mm) 850*250 850*250 850*250
Weight(net/gross, Kg) 62/77 62/77 62/77
Controller Wired controller/ wireless controller (optional)
Accessories Use for installation
Gas piping(mm) 15.88 15.88 15.88
Piping Liquid piping(mm) 9.52 9.52 9.52
dimension
Drain hose(mm) 32 32 32

G R U P A
Noise level(dB(A)) H/L 45/40 45/40 45/40

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB

d.o.o.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

25

Downloaded from www.Manualslib.com manuals search engine


Indoor units
High static pressure duct type
Model AD722MHERA AD962MHERA
Nominal cooling capacity(KW) 22.6 28
Nominal heating capacity(KW) 25 31
Electrical heating power(KW)
/Current(A) --- ---
Heating capacity at low temp.(KW) --- ---
Electri- Power source 1PH, 220~230V, 50Hz
cal
chara- Operating current(A) 3 3
cteris-
tics Power consumption(KW) 0.6 0.6
Fan type and Qty centrifugal*4 centrifugal*4
Fan Fan motor output(KW) 0.27 0.27
chara-
cteris- Standard airflow(m /h)
3 4050/3600/3000 4050/3600/3000
tics Standard static pressure(Pa) 100 100
Max. static pressure(Pa) 196 196
Exterior dimensions(mm) 1570*830*360 1570*830*360
Air outlet dimensions(mm) 1515*250 1515*250
Weight(net/gross, Kg) 92/100 92/100
Controller Wired controller/ wireless controller (optional)
Accessories Use for installation
Gas piping(mm) 15.88 15.88
Piping Liquid piping(mm) 9.52 9.52
dimension

G R U P A
Drain hose(mm) 32 32
Noise level(dB(A)) H/L 54/49 54/49

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB

d.o.o.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

26

Downloaded from www.Manualslib.com manuals search engine


Indoor units
Convertible type
Model AC092MCERA AC122MCERA AC162MCERA AC182MCERA
Nominal cooling capacity(KW) 2.8 3.6 4.5 5.6
Nominal heating capacity(KW) 3.2 4 5 6.3
Electrical heating power(KW)
/Current(A) / / / /
Heating capacity at low temp.(KW) 2.5 3.2 4 5
Electri- Power source 1PH, 220V, 50Hz
cal
chara- Operating current(A) 0.3 0.3 0.3 0.3
cteris-
tics Power consumption(KW) 0.06 0.06 0.06 0.06
Fan type and Qty centrifugal*2 centrifugal*2 centrifugal*2 centrifugal*2
Fan Fan motor output(KW) 0.05 0.05 0.05 0.05
chara-
cteris- Standard airflow(m /h)
3 750 750 750 750
tics Standard static pressure(Pa) /
Max. static pressure(Pa) /
Exterior dimensions(mm) 990*655*199 990*655*199 990*655*199 990*655*199
Air outlet dimensions(mm) -- -- -- --
Weight(Kg) 28.3/34.3 28.3/34.3 28.3/34.3 28.3/34.3
Controller Wired controller/ wireless controller (optional)
Accessories Use for installation
Gas piping(mm) 9.52 12.7
Piping Liquid piping(mm) 6.35 6.35
dimension
Drain hose(mm) 20

G R U P A
20
Noise level(dB(A)) H/M/L 48/46/44 48/46/44 48/46/44 48/46/44

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB

d.o.o.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

27

Downloaded from www.Manualslib.com manuals search engine


Indoor units
Convertible type
Model AC242MCERA AC382MFERA AC482MFERA
Nominal cooling capacity(KW) 7.1 11.2 14
Nominal heating capacity(KW) 8 12.5 16
Electrical heating power(KW)
/Current(A) / / /
Heating capacity at low temp.(KW) 6.3 8 10
Electri- Power source 1PH, 220V, 50Hz
cal
chara- Operating current(A) 0.5 0.5 0.5
cteris-
tics Power consumption(KW) 0.1 0.1 0.1
Fan type and Qty centrifugal*4 centrifugal*4 centrifugal*4
Fan Fan motor output(KW) 0.09 0.09 0.09
chara-
cteris- Standard airflow(m /h)
3
800 1500 1800
tics Standard static pressure(Pa) /

Max. static pressure(Pa) /


Exterior dimensions(mm) 990*655*199 1580*700*240 1580*700*240
Air outlet dimensions(mm) -- -- --
Weight(Kg) 28.3/34.3 54/61 54/61
Controller Wired controller/ wireless controller (optional)
Accessories Use for installation
Gas piping(mm) 15.88
Piping Liquid piping(mm) 9.52
dimension

G R U P A
Drain hose(mm) 20 25
Noise level(dB(A)) H/M/L 51/49/47 53/51/49 53/51/49

Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB

d.o.o.
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

28

Downloaded from www.Manualslib.com manuals search engine


Indoor units
Wall mounted type
Model AS072MCERA AS092MCERA AS122MCERA
Nominal cooling capacity(KW) 2.2 2.8 3.6
Nominal heating capacity(KW) 2.5 3.2 4.0
Heating capacity at low temp.(KW) 2.0 2.5 3.2
Electri- Power source 1PH, 220~230V, 50Hz
cal
chara- Operating current(A) 0.2 0.2 0.2
cteris-
tics Power consumption(KW) 0.04 0.04 0.04
Fan type and Qty cross*1 cross*1 cross*1
Fan Fan motor output(KW) 0.025 0.025 0.025
chara- Standard airflow(m3/h)
cteris- 600 600 630
tics Standard static pressure(Pa) 0 0 0
Max. static pressure(Pa) 0 0 0
Exterior dimensions(mm) 795*265*197 795*265*197 795*265*197
Air outlet dimensions(mm) 600*85 600*85 600*85
Weight(Kg) 10 10 10
Controller Wireless controller
Gas piping(mm) 12.7 12.7 12.7

Piping Liquid piping(mm) 6.35 6.35 6.35


dimension Drain hose(mm) 16.5 16.5 16.5
Noise level(dB(A)) H/M/L 34/30/29 34/30/29 35/32/29

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

d.o.o.

29

Downloaded from www.Manualslib.com manuals search engine


Lg^hhj mgclk
X[ee fhmgl_^ lqi_
Qmbcj EW7<8QGIVE EW7>8QGIVE EW8:8QEIVE
Rmkgl_j ammjgle a_n_agrw.O[/ :4; ;4< =47
Rmkgl_j fc_rgle a_n_agrw.O[/ ;46 <49 >46
Lc_rgle a_n_agrw _r jmu rckn4.O[/ :46 ;46 <49
Ijcarpg3 Tmucp qmspac 7TL2 886Zy2 ;6Lx
a_j
af_p_3 Sncp_rgle asppclr.E/ 648; 648; 647;
arcpgq3
rgaq Tmucp amlqsknrgml.O[/ 646; 646; 6468=
J_l rwnc _lb Urw apmqq07 apmqq07 apmqq07
J_l J_l kmrmp msrnsr.O[/ 6469 6469 646:
af_p_3 Wr_lb_pb _gpdjmu.k95f/ =<6
arcpgq3 =<6 7766
rgaq Wr_lb_pb qr_rga npcqqspc.T_/ 6 6 6
Q_v4 qr_rga npcqqspc.T_/ 6 6 6
Ivrcpgmp bgkclqgmlq.kk/ ?8>07?=08<; ?8>07?=08<; 77;;088:096>
Egp msrjcr bgkclqgmlq.kk/ >;60>; >;60>; ?;;4;0=8
[cgefr.Oe/ 79 79 15
Gmlrpmjjcp [gpcjcqq amlrpmjjcp
K_q ngngle.kk/ 784= 7;4>> 7;4>>
Pgosgb ngngle.kk/ <49; ?4;8 ?4;8
Tgngle
bgkclqgml Hp_gl fmqc.kk/ 7<4; 7<4; 7<4;

Rmgqc jctcj.bF.E// L5Q5P 9>59<598 9>59<598 :<5:859;

Qmbcj EJ6=8QEIVE EJ6?8QEIVE EJ788QEIVE EJ7>8QEIVE


Rmkgl_j ammjgle a_n_agrw.O[/ 848 84> 94< ;46

G R U P A
Rmkgl_j fc_rgle a_n_agrw.O[/ 84; 948 :46 <46
Lc_rgle a_n_agrw _r jmu rckn4.O[/ 846 84; 948 :4;
Ijcarpg3 Tmucp qmspac 7TL2 886y896Z2 ;6Lx
a_j
af_p_3 Sncp_rgle asppclr.E/ 64:; 64:; 64:; 64:;
arcpgq3 Tmucp amlqsknrgml.O[/

d.o.o.
rgaq 646> 646> 646> 646>
J_l rwnc _lb Urw apmqq08 apmqq08 apmqq08 apmqq08
J_l Ynncp kmrmp msrnsr.O[/ 64686 64686 64686 64686
af_p_3 64677 64677
arcpgq3 Pmucp kmrmp msrnsr.O[/ 64677 64677
rgaq Wr_lb_pb _gpdjmu.k95f/ :<6 :<6 ;86 ;>6
Wr_lb_pb qr_rga npcqqspc.T_/ 6 6 6 6
Q_v4 qr_rga npcqqspc.T_/ 6 6 6 6
Ivrcpgmp bgkclqgmlq.kk/ =8608;;0<:6 =8608;;0<:6 =8608;;0<:6 =8608;;0<:6
Wfgnngle bgkclqgmlq.kk/ ==808?80=6: ==808?80=6: ==808?80=6: ==808?80=6:
[cgefr.Oe/ 7=4;586 7=4;586 7=4;586 7=4;586
Gmlrpmjjcp [gpcjcqq amlrpmjjcp
K_q ngngle.kk/ 784= 784= 784= 784=
Tgngle <49; <49;
bgkclqgml Pgosgb ngngle.kk/ <49; <49;
Hp_gl fmqc.kk/ 7<4; 7<4; 7<4; 7<4;
Rmgqc jctcj.bF.E// L5Q5P :959?59< :959?59< :959?59< :>5:<5:8

30

Downloaded from www.Manualslib.com manuals search engine


Outdoor units
Equivalent HP 8 10
Model AV08NMVERA AV10NMVERA
Combination mode ** **
Nominal cooling capacity(KW) 22.6 28.0
Nominal heating capacity(KW) 25.0 31.5
Heating capacity at low temp.(KW) 21.2 25.6
Power source 3N~, 380~400V, 50Hz
Operating/Max. current(A)
Cooling Heating

12.2/15.6
Electrical characteristics

8.7/10.5
Operating/Max. consumption(kw) 5.28/6.34 7.36/9.45
Operating/Max. current(A) 9.7/11.3 13.2/15.8
Operating/Max. consumption(kw) 5.89/6.85 7.97/10.2
Power consumption when heating at low temp.(kw) 5.57 6.73
Output power of outdoor motor(KW) 0.7 0.7
Exterior dimensions (mm) 990*750*1750 990*750*1750
Weight (Kg) 235 235
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 10000 10000
Refrigerant (R410A) charge (Kg) 10.0 10.0
Gas piping(mm) 19.05 22.22
Piping dimension

Liquid piping(mm) 9.52 9.52


Equipoise/Oil equalization piping(mm) 9.52 9.52
Noise level(dB(A)) 57.0 58.0
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB

G R U P A
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

compressor HNB71FB-YJHC, Mitsubishi Electric

d.o.o.
oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

31

Downloaded from www.Manualslib.com manuals search engine


Outdoor units
Equivalent HP 12 14
Model AV12NMVERA AV14NMVERA
Combination mode ** **
Nominal cooling capacity(KW) 33.5 40.0
Nominal heating capacity(KW) 37.5 45.0
Heating capacity at low temp.(KW) 28.7 36.7
Power source 3N~, 380~400V, 50Hz
Operating/Max. current(A)
Cooling Heating

14.2/17.0 20.3/24.4
Electrical characteristics

Operating/Max. consumption(kw) 8.58/10.3 12.31/14.8


Operating/Max. current(A) 15.1/18.4 19.3/23.2
Operating/Max. consumption(kw) 9.1/11.3 11.69/14.10
Power consumption when heating at low temp.(kw) 7.55 9.65
Output power of outdoor motor(KW) 1.1 1.1
Exterior dimensions (mm) 1390*750*1750 1390*750*1750
Weight (Kg) 275 275
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 12000 12000
12.0 12.0
Refrigerant (R410A) charge (Kg)
Gas piping(mm) 25.4 25.4
Piping dimension

Liquid piping(mm) 12.7 12.7


Equipoise/Oil equalization piping(mm) 9.52 9.52
Noise level(dB(A)) 60.0 60.0
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB

G R U P A
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

compressor HNB71FB-YJHC, Mitsubishi Electric

d.o.o.
oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

32

Downloaded from www.Manualslib.com manuals search engine


Outdoor units
Equivalent HP 16
Model AV16NMVERA
Combination mode **
Nominal cooling capacity(KW) 45.0
Nominal heating capacity(KW) 50.0
Heating capacity at low temp.(KW) 39.1
Power source 3N~, 380~400V, 50Hz
Operating/Max. current(A)
Cooling Heating

23.2/28.1
Electrical characteristics

Operating/Max. consumption(kw) 14.06/17.0


Operating/Max. current(A) 21.2/25.6
Operating/Max. consumption(kw) 12.82/15.38
Power consumption when heating at low temp.(kw) 10.28
Output power of outdoor motor(KW) 1.1
Exterior dimensions (mm) 1390*750*1750
Weight (Kg) 300
Exterior colour ivory
Compressor type scroll
Outdoor airflow (m3/h) 12000
16.0
Refrigerant (R410A) charge (Kg)
Gas piping(mm) 28.58
Piping dimension

Liquid piping(mm) 12.7


Equipoise/Oil equalization piping(mm) 9.52
Noise level(dB(A)) 60.0
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

compressor

d.o.o.
HNB71FB-YJHC, Mitsubishi Electric

oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

33

Downloaded from www.Manualslib.com manuals search engine


Outdoor units(combination)
Equivalent HP 18 20
Model AV18NMVERA AV20NMVERA
Combination mode AV08+AV10 AV10+AV10
Nominal cooling capacity(KW) 50.6 56.0
Nominal heating capacity(KW) 56.5 63.0
Heating capacity at low temp.(KW) 46.8 51.2
Power source 3N~, 380~400V, 50Hz
Operating/Max. current(A) 20.9/26.1
Cooling Heating
Electrical characteristics

24.4/31.2
Operating/Max. consumption(kw) 12.64/15.79 14.72/18.90
Operating/Max. current(A) 22.9/27.1 26.4/31.6
Operating/Max. consumption(kw) 13.86/17.05 15.94/20.4
Power consumption when heating at low temp.(kw) 12.3 13.46
Output power of outdoor motor(KW) 1.4 1.4
Exterior dimensions (mm) 990*750*1750 990*750*1750
+990*750*1750 +990*750*1750
Weight (Kg) 470 470
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 20000 20000
Refrigerant (R410A) charge (Kg) 20 20
28.58
Piping dimension

Gas piping(mm) 28.58


Liquid piping(mm) 15.88 15.88
Equipoise/Oil equalization piping(mm) 9.52 9.52
Noise level(dB(A)) 61 61
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric

oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

34

Downloaded from www.Manualslib.com manuals search engine


Outdoor units(combination)
Equivalent HP 22 24
Model AV22NMVERA AV24NMVERA
Combination mode AV10+AV12 AV10+AV14
Nominal cooling capacity(KW) 61.5 68
Nominal heating capacity(KW) 69 76.5
Heating capacity at low temp.(KW) 54.3 62.3
Power source 3N~, 380~400V, 50Hz
26.4/32.6
Cooling Heating
Electrical characteristics

Operating/Max. current(A) 32.5/40


Operating/Max. consumption(kw) 15.94/19.75 19.67/24.25
Operating/Max. current(A) 28.3/34.2 32.5/39
Operating/Max. consumption(kw) 17.07/21.33 19.66/24.3
Power consumption when heating at low temp.(kw) 14.28 16.38
Output power of outdoor motor(KW) 1.8 1.8
Exterior dimensions (mm) 990*750*1750+1390*750*1750 990*750*1750+
1390*750*1750
Weight (Kg) 510 510
Exterior colour ivory ivory
Compressor model scroll scroll
Outdoor airflow (m3/h) 22000 22000
Refrigerant (R410a) charge (Kg) 22 22
Piping dimension

Gas piping(mm) 28.58 28.58


Liquid piping(mm) 15.88 15.88
Equipoise/Oil equalization piping(mm) 9.52
Noise level(dB(A)) 62 62

Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric

oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

35

Downloaded from www.Manualslib.com manuals search engine


Outdoor units(combination)
Equivalent HP 26 28
Model AV26NMVERA AV28NMVERA
Combination mode AV10+AV16 AV14+AV14
Nominal cooling capacity(KW) 73 80
Nominal heating capacity(KW) 81.5 90
Heating capacity at low temp.(KW) 64.7 73.4
Power source 3N~, 380~400V, 50Hz
Operating/Max. current(A)
Cooling Heating
Electrical characteristics

35.4/43.7 40.6/48.8
Operating/Max. consumption(kw) 21.42/26.45 24.62/29.6
Operating/Max. current(A) 34.4/41.4 38.6/46.4
Operating/Max. consumption(kw) 20.79/25.58 23.38/28.2
Power consumption when heating at low temp.(kw) 17.01 19.3
Output power of outdoor motor(KW) 1.8 2.2
Exterior dimensions (mm) 990*750*1750 1390*750*1750
+1390*750*1750 +1390*750*1750
Weight (Kg) 535 550
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 22000 24000
Refrigerant (R410A) charge (Kg) 26 24
31.8
Piping dimension

Gas piping(mm) 31.8


Liquid piping(mm) 19.05 19.05
Equipoise/Oil equalization piping(mm) 9.52 9.52
Noise level(dB(A)) 62 63
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric

oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

36

Downloaded from www.Manualslib.com manuals search engine


Outdoor units(combination)
Equivalent HP 30 32
Model AV30NMVERA AV32NMVERA
Combination mode AV14+AV16 AV16+AV16
Nominal cooling capacity(KW) 85 90
Nominal heating capacity(KW) 95 100
Heating capacity at low temp.(KW) 75.8 78.2
Power source 3N~, 380~400V, 50Hz
Operating/Max. current(A) 43.5/52.5
Cooling Heating
Electrical characteristics

46.4/56.2
Operating/Max. consumption(kw) 26.37/31.8 28.12/34
Operating/Max. current(A) 40.5/48.8 42.4/51.2
Operating/Max. consumption(kw) 24.51/29.48 25.64/30.76
Power consumption when heating at low temp.(kw) 19.93 20.56
Output power of outdoor motor(KW) 2.2 2.2
Exterior dimensions (mm) 1390*750*1750 1390*750*1750
+1390*750*1750 +1390*750*1750
Weight (Kg) 575 600
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 24000 24000
Refrigerant (R410A) charge (Kg) 28 32
31.8
Piping dimension

Gas piping(mm) 31.8


Liquid piping(mm) 19.05 19.05
Equipoise/Oil equalization piping(mm) 9.52 9.52
Noise level(dB(A)) 63 63
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

compressor HNB71FB-YJHC, Mitsubishi Electric

d.o.o.
oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

37

Downloaded from www.Manualslib.com manuals search engine


Outdoor units(combination)
Equivalent HP 34 36
Model AV34NMVERA AV36NMVERA
Combination mode AV10+AV10+AV14 AV10+AV10+AV16
Nominal cooling capacity(KW) 96 101
Nominal heating capacity(KW) 108 113
Heating capacity at low temp.(KW) 87.9 90.3
Power source 3N~, 380~400V, 50Hz
44.7/55.6
Cooling Heating
Electrical characteristics

Operating/Max. current(A) 47.6/59.3


Operating/Max. consumption(kw) 27.03/35.4 28.78/35.9
Operating/Max. current(A) 45.7/54.8 47.6/57.2
Operating/Max. consumption(kw) 27.63/34.5 28.76/35.78
Power consumption when heating at low temp.(kw) 23.11 23.78
Output power of outdoor motor(KW) 2.5 2.5
Exterior dimensions (mm) (990*750*1750)*2 (990*750*1750)*2
+1390*750*1750 +1390*750*1750
Weight (Kg) 745 770
Exterior colour ivory ivory
Compressor model scroll scroll
Outdoor airflow (m3/h) 32000 32000
Refrigerant (R410a) charge (Kg) 32 36
Piping dimension

Gas piping(mm) 31.8 38.1


Liquid piping(mm) 19.05 19.05
Equipoise/Oil equalization piping(mm) 9.52
Noise level(dB(A)) 63 63

Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric

oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

38

Downloaded from www.Manualslib.com manuals search engine


Outdoor units(combination)
Equivalent HP 38 40
Model AV38NMVERA AV40NMVERA
Combination mode AV10+AV14+AV14 AV10+AV14+AV16
Nominal cooling capacity(KW) 108 113
Nominal heating capacity(KW) 121.5 126.5
Heating capacity at low temp.(KW) 99 101.4
Power source 3N~, 380~400V, 50Hz
Operating/Max. current(A) 52.8/64.4
Cooling Heating
Electrical characteristics

55.7/68.1
Operating/Max. consumption(kw) 31.98/39.05 33.73/41.25
Operating/Max. current(A) 51.8/62.2 53.7/64.6
Operating/Max. consumption(kw) 31.35/38.4 32.48/39.68
Power consumption when heating at low temp.(kw) 24.75 26.66
Output power of outdoor motor(KW) 2.9 2.9
Exterior dimensions (mm) 990*750*1750 990*750*1750
+(1390*750*1750)*2 +(1390*750*1750)*2
Weight (Kg) 785 810
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 34000 34000
Refrigerant (R410A) charge (Kg) 34 38
Piping dimension

Gas piping(mm) 38.1 38.1


Liquid piping(mm) 19.05 19.05
Equipoise/Oil equalization piping(mm) 9.52 9.52
Noise level(dB(A)) 63 63
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

compressor HNB71FB-YJHC, Mitsubishi Electric

d.o.o.
oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

39

Downloaded from www.Manualslib.com manuals search engine


Outdoor units(combination)
Equivalent HP 42 44
Model AV42NMVERA AV44NMVERA
Combination mode AV10+AV16+AV16 AV12+AV16+AV16
Nominal cooling capacity(KW) 118 123.5
Nominal heating capacity(KW) 131.5 137.5
Heating capacity at low temp.(KW) 103.8 106.9
Power source 3N~, 380~400V, 50Hz
Cooling Heating
Electrical characteristics

Operating/Max. current(A) 58.6/71.8 60.6/73.2


Operating/Max. consumption(kw) 35.48/43.45 36.7/44.3
Operating/Max. current(A) 55.6/67 57.5/69.6
Operating/Max. consumption(kw) 33.61/40.96 34.74/41.89
Power consumption when heating at low temp.(kw) 27.29 28.11
Output power of outdoor motor(KW) 2.9 3.3
Exterior dimensions (mm) 990*750*1750 (1390*750*1750)*3
+(1390*750*1750)*2
Weight (Kg) 835 875
Exterior colour ivory ivory
Compressor model scroll scroll
Outdoor airflow (m3/h) 34000 36000
Refrigerant (R410a) charge (Kg) 42 44
Piping dimension

Gas piping(mm) 38.1 38.1


Liquid piping(mm) 19.05 19.05
Equipoise/Oil equalization piping(mm) 9.52
Noise level(dB(A)) 64 64

Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric

oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

40

Downloaded from www.Manualslib.com manuals search engine


Outdoor units(combination)
Equivalent HP 46 48
Model AV46NMVERA AV48NMVERA
Combination mode AV14+AV16+AV16 AV16+AV16+AV16
Nominal cooling capacity(KW) 130 135
Nominal heating capacity(KW) 145 150
Heating capacity at low temp.(KW) 114.9 117.3
Power source 3N~, 380~400V, 50Hz
Cooling Heating

Operating/Max. current(A)
Electrical characteristics

66.7/80.6 69.6/84.3
Operating/Max. consumption(kw) 40.43/48.8 42.18/51
Operating/Max. current(A) 61.7/74.4 63.6/76.8
Operating/Max. consumption(kw) 37.33/44.86 38.46/46.14
Power consumption when heating at low temp.(kw) 30.21 30.84
Output power of outdoor motor(KW) 3.3 3.3
Exterior dimensions (mm) (1390*750*1750)*3 (1390*750*1750)*3

Weight (Kg) 875 900


Exterior colour ivory
Compressor model scroll
Outdoor airflow (m3/h) 36000 36000
Refrigerant (R410a) charge (Kg) 44 48
Gas piping(mm)
Piping dimension

38.1 38.1
Liquid piping(mm) 19.05 19.05
Equipoise/Oil equalization piping(mm) 9.52
Noise level(dB(A)) 64 64

Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.

G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.

d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric

oil type MEL32

oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator

41

Downloaded from www.Manualslib.com manuals search engine


120
90 80
overlaped distance between the ceiling
gas pipe
and the panel: 25mm
57 drainage pipe liquid pipe suspension holder
65 75
8. Dimensions
Cassette type indoor:

Downloaded from www.Manualslib.com manuals search engine


320mm

150mm
60mm

700mm (panel dimension)


ceiling panel

570mm (indoor unit dimension)


650mm (ceiling opening dimension)
AB092MCERA, AB122MCERA,AB162MCERA

42
95
180
535mm (between suspension poles)

570mm (indoor unit dimension) fresh air hole

650mm (ceiling opening dimension)

700mm (panel dimension)


140

VIEW A VIEW A

145 100 80

d.o.o. G R U P A
AB182MEERA, AB242MEERA, AB282MEERA

(mm)
860-890 155

680

35
air discharge hole

106

103
345
860-890 (ceiling hole)
680 (hang position)

85
30

85
57

57

35
180

950

G R U P A
260
160
135

d.o.o.
260
270
315
950

840

80
140
295

200

180
20 30
240 50

43

Downloaded from www.Manualslib.com manuals search engine


(mm)
AB302MEERA, AB382MEERA, AB482MEERA

860-890 155

680

35
air discharge hole

106

103
860-890 (ceiling hole)
680 (hang position)

345

85
30

85
57

57

35
220

950
310

G R U P A
160
135

d.o.o.
260
270
315
950

840

80
140
295

200

220

30
290 50

44

Downloaded from www.Manualslib.com manuals search engine


AB182MCERA, AB242MCERA, AB282MCERA

(mm)
860-890 155

680

35
air discharge hole

106

103
345
860-890 (ceiling hole)
680 (hang position)

85
30

85
57

57

35
180

950

G R U P A
260
160
135

d.o.o.
260
270
315
950

840

80
140
295

200

180
20 30
240 50

45

Downloaded from www.Manualslib.com manuals search engine


AB302MCERA, AB382MCERA, AB482MCERA

(mm)
860-890 155

680

35
air discharge hole

106

103
860-890 (ceiling hole)
680 (hang position)

345

85
30

85
57

57

35
220

950

G R U P A
310
160
135

d.o.o.
260
270
315
950

840

80
140
295

200

220

30
290 50

46

Downloaded from www.Manualslib.com manuals search engine


Ceiling concealed type indoor:

Model a b c d e f g h i J

AD07~122MLERA 418 538 483 220 255 508 610 131 24


AD16~242MLERA 1002 483.5 131 1105 255 105 880 970 220 24

DG7>{899POHUD
Hvaporators of DG7>3 DG7@ are 94row typeB evaporator of DG89 is :4row type5

;7
877

89<

G R U P A
9>7
8:7

;>? d.o.o.

997

47

Downloaded from www.Manualslib.com manuals search engine


AD16~242MLERA
Evaporators of AD16,18 are 2-row type; evaporator of AD24 is 3-row type.

;7
877
9>7

89<
8:7

G R U P A
@;7

d.o.o.
997

48

Downloaded from www.Manualslib.com manuals search engine


Med static pressure duct type indoor:
AD182MMERA, AD242MMERA, AD282MMERA
200

(mm)
170
drainage pipe

32

A-A
265
liquid pipe

200

890
150
gas pipe
235

100
165

120

200

130
A

300 635
210 545

70

G R U P A
80

270 305
30

20
85

d.o.o.
10

R100

986
960
890
260
275
35

49

Downloaded from www.Manualslib.com manuals search engine


AD302MMERA, AD382MMERA, AD482MMERA

(mm)
240
drainage pipe

32
265
A-A
liquid pipe

1280
150
235

gas pipe

100
165

120
A

350
85

655

85
545

G R U P A
d.o.o.
1406

1370
R100
260
275

electric control box

105 210
70
35

260 68 275
275

50

Downloaded from www.Manualslib.com manuals search engine


High static pressure duct type indoor:

AD182MHERA, AD242MHERA, AD282MHERA

(mm)
250
30

210
32
290
60

30
750

electric control box

830

800
345 145
365 80
100

G R U P A
15
130

120

d.o.o.
205

960

185
840

170

51

Downloaded from www.Manualslib.com manuals search engine


AD302MHERA, AD382MHERA, AD482MHERA

(mm)
250

45
32

210 290

30
1105

60

electric control box

830

365 800
345 145
80
100

G R U P A
15
250

d.o.o.
270

185
1200

170

1320

52

Downloaded from www.Manualslib.com manuals search engine


AD722MHERA, AD962MHERA (mm)

830
18 794 18
25

60
M5x20pcs Air inlet

138
13
250
1570
1690

1640

13 200 13

138
13
65
163 6x200=1200 163
35 1500 35
100
80
25

95
60

Control Box

Liquid pipe Gas pipe


12.7(1/2") 28.58(1-1/8")

M10x4pcs

80 510 25 M5x20pcs Air outlet

138

250
25

13
25

G R U P A
205
310
360

A
49

245
30
106

138

77
13
185 170 45 200

530 13 13

d.o.o.
DRAIN PIPE VP25 138 6X200=1200 138

60 1450 60

Installation dimension
Over 900 Over 900 (900x1730) Over 100 Over 300
35

Check Hole
(600x600)
900

Ceiling
35

100 60
Over 200
over 400

53

Downloaded from www.Manualslib.com manuals search engine


Convertible type indoor:
AC092MCERA,AC122MCERA,AC162MCERA, AC182MCERA, AC242MCERA

(mm)
240
100 200 back plate bottom plate
880

900

990

100 100

100
100
10

20
655

30
30

199

G R U P A
100 30
100

d.o.o.
25

right side
620
605
600

30
35
35
40

54

Downloaded from www.Manualslib.com manuals search engine


AC382MFERA, AC482MFERA

1580

700
598
495
285

36

55 114 240
90

25

440 300 47 200

G R U P A
47 47 47
150
95
40
60

d.o.o.
47
47
50 200 224 155
47 47

90

570
640
30 200
130

55

Downloaded from www.Manualslib.com manuals search engine


Wall mounted type indoor:

Haie
r

b
model a b c
AS072/092/122MCERA 795
265 182
AS162/182MCERA 928
c

60
50
60

50
55 200
45

200 55
60 70
bottom side
right side left side

AS242MAERA

G R U P A
d.o.o.

56

Downloaded from www.Manualslib.com manuals search engine


Console type indoor:

Outdoor unit
Single unit
Note:
A There should be no obstacles in 2000mm above the top of outdoor unit;
B Obstacles around outdoor should be less than 800mm to the bottom of unit.

8, 10HP:
4-15*20
990
Gas pipe
100 80
Liquid pipe
Oil pipe
65 55 125

G R U P A
755
630

750
790
125
168
143

138

62

173 92 100 80
700 700

d.o.o.
90
300mm

1550mm

1750

More than
500mm

100mm More than


1560

100mm
Top side
700

Oil pipe
Liquid pipe
Gas pipe
245

190 235
88

2-60*150 500

57

Downloaded from www.Manualslib.com manuals search engine


12, 14, 16HP:
100

80

over 300

over 1550
790
750
630

755

over 500
over 100 over 100
100

80

front
700 700

90
1560
1750

700

500

G R U P A
88

1390

d.o.o.

58

Downloaded from www.Manualslib.com manuals search engine


Combined outdoor unit

18,20HP:

990 over 200 990

over 300

over 1550
750
790
over 200 over 100

over 500
over 100
front

700 700 over 2380


90
1750
1560

G R U P A
700
88

over 2180

d.o.o.
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall
can be increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.

59

Downloaded from www.Manualslib.com manuals search engine


22, 24, 26HP:

990 over 200 1390

over 300

over 1550
750

790
over 200 over 100

over 500
over 100
700 700
front
over 2780
90
1750
1560
700
88

over 2580

G R U P A
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall

d.o.o.
can be increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.

60

Downloaded from www.Manualslib.com manuals search engine


28, 30, 32HP:

over 200

over 300
1390 1390

over 1550
750
790

over 500
over 100 over 100
over 200
front
over 3180
700 700

90
1560
1750

700
88

over 2980

G R U P A
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall

d.o.o.
can be increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.

61

Downloaded from www.Manualslib.com manuals search engine


34, 36HP:
over 1550

over 100
over 200

over 3970
front
over 200
over 100

over 300 over 500

over 3770
790
750
1390

700
over 200

G R U P A
90 700 88
990

700

1560
1750
over 200

d.o.o.
990

700

Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall can be
increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.

62

Downloaded from www.Manualslib.com manuals search engine


38, 40, 42HP:
over 1550

over 100
over 200

over 4370
over 200
front
over 100

over 300 over 500

790
750

over 4170
1390

700
over 200

G R U P A
1390

700

90 700 88
1560
1750
over 200

d.o.o.
990

700

Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall can be
increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.

63

Downloaded from www.Manualslib.com manuals search engine


44, 46, 48HP:
over 1550

over 100
over 200

over 4770
front
over 200
over 100
over 300 over 500

790
750

over 4570
1390

700
over 200

G R U P A
1390

700

90 700 88
1560
over 200

d.o.o.
1750
1390

700

Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall can be
increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.

64

Downloaded from www.Manualslib.com manuals search engine


Installation space

(1) When outer wall is lower than the outdoor condenser


A. Sites for one-row layout
The distance between two outdoor units in the same line and the distance from unit to the wall can
be increased for easy maintenance if there is enough space.
More than
300mm
More than
500mm

Front side

More than More than More than


100mm 200mm 200mm

G R U P A
d.o.o.
Less than
800mm

65

Downloaded from www.Manualslib.com manuals search engine


B. Sites for two-row layout
The distance between two outdoor units in the same line and the distance from unit to the wall can
be increased for easy maintenance if there is enough space.

More than
300mm
More than

Front side
600mm

Front side
More than
300mm

More than More than More than


100mm 200mm 200mm

G R U P A
d.o.o.
Less than
800mm

66

Downloaded from www.Manualslib.com manuals search engine


C. Sites for three-row layout
The distance between two outdoor units in the same line and the distance from unit to the wall can
be increased for easy maintenance if there is enough space.

More than More than


300mm

Front side
600mm

Front side
More than
600mm
More than
500mm

Front side

More More More


than than than
100mm
200mm 200mm

G R U P A
d.o.o.
Less than
800mm

67

Downloaded from www.Manualslib.com manuals search engine


D. Piping

piping

500
piping More than
500mm

(2) Wall higher than the outdoor unit


A. Place with air inlet hole
Notes:
1. Fan speed Vs at air inlet is 1.5m/s or below.
2. Air outlet height HD=H-h and below 1m.

air outlet
Above 600mm Above 300mm

G R U P A
HD

Front side

d.o.o.
H Above 1000mm

Above 100mm Above 200mm Above 200mm


h

Vs

68

Downloaded from www.Manualslib.com manuals search engine


B. Place without air inlet hole
Notes:
A. Set a 500~1000mm bracket.
B. Air outlet height HD=H-h and below 1m.
air outlet
Above 600mm Above 300mm

HD

H
Front side

500-1000mm
h

Above 100mm Above 200mm Above 200mm

G R U P A
d.o.o.

69

Downloaded from www.Manualslib.com manuals search engine


FQG-B730A FQG-B506A FQG-B335A

Gas

Gas
Pipe

Pipe

Gas

Pipe

Pipe
Pipe
Pipe
Side

Liquid

Liquid

Liquid
ID9.7 ID28.8
ID28.8
ID9.7 ID6.5 ID16.1
ID12.9
ID12.9 ID9.7
ID25.6 ID19.3
ID25.6
ID16.1

ID22.4
OD19.05 OD22.2
OD22.2

ID6.5
ID25.4

ID16.1

ID12.9
ID19.3
ID22.4

ID16.1

ID12.9
ID19.3
ID22.4
ID6.5
ID9.7
ID12.9
OD22.22*1.5
ID9.7

OD22.22*1.5

ID6.5
OD22.22

ID9.7
ID12.9
ID16.1
238

388
238
OD19.05

323

323
ID12.9
ID16.1
OD19.05
384

OD12.7

Downloaded from www.Manualslib.com manuals search engine


OD12.7

OD25.4 OD25.4
OD25.4

ID12.9
ID25.6
ID25.6
ID9.7 OD25.4
ID16.1

ID28.8
ID28.8 ID22.4

ID19.3

ID16.1

OD12.7
OD28.58

OD6.35

70
OD28.58
OD6.35 OD6.35
ID25.6

ID25.6
55
100

55
ID22.4

55
ID22.4
180

180
ID19.3
ID19.3
ID9.7
ID9.7
ID9.7 ID16.1 ID16.1
Branch pipe(unit: mm, ID: inner diameter; OD: outer diameter)

ID9.7

ID12.9
ID12.9
OD6.35
OD15.88

ID12.9
55
104

ID9.7
OD12.7

OD12.7

ID9.7
100
Connection of manifold pipe

OD15.88

100
ID12.9
104

ID9.7
ID9.7 ID9.7

d.o.o. G R U P A
FQG-B1350A

ID38.3

ID9.7
ID12.9
ID32
ID16.1

ID19.3
OD31.75

ID28.8
ID22.4

OD28.6
366

ID6.5
ID9.7
ID12.9
ID16.1
405
OD19.05

OD31.75

OD25.4
ID32

Downloaded from www.Manualslib.com manuals search engine


ID22.4
ID38.3

ID19.3

OD28.58

OD6.35
ID25.6

ID22.4

71
180

55
ID19.3

ID16.1

ID12.9

ID9.7 OD31.75

ID28.8
140

ID25.6

ID22.4

OD22.22

ID19.3

ID16.1
138
Connection of manifold pipe

ID12.9

OD12.7
100

ID9.7

d.o.o. G R U P A
HZG-30/A HZG-20/A

side

side
side
Gas
side
Gas

Liquid

Liquid
E
D
C
B
A
Model Side Mark
+0.25 +0.25 +0.25
ID38.1

10
10
+0.1 ID15.88
+0.1 +0.2 ID15.88
+0.1 +0.2
ID28.6
+0.05 +0.05
ID28.6
+0.25 +0.05
ID31.8+0.2 +0.25 +0.05
31.8+0.2

30
ID19.05
+0.1 +0.2 ID19.05
+0.1 +0.2

40
40
+0.05
ID38.1 ID38.1
+0.05

550
640
465
640
465

Double

Downloaded from www.Manualslib.com manuals search engine


Gather pipe dimensions:

424
424

667
Manifold pipe

+0.2 +0.2
+0.25 +0.25 +0.05
ID28.6 +0.25 +0.25
ID28.6
+0.05

15
15
+0.1
ID19.05 +0.1
ID19.05 +0.1
ID19.05 ID19.05
+0.1
+0.2 +0.2
ID28.6

40
40
40
40
ID28.6
+0.05 +0.05
+0.2 +0.2

12
+0.25
ID15.88 +0.25 ID25.4
+0.05 +0.25 +0.25
ID15.88 ID25.4
+0.05
+0.1 ID15.88
+0.1 ID15.88
+0.1 +0.1

40
40

40
40
+0.05
ID28.6+0.2 +0.2 +0.2
+0.25 +0.05
ID22.22 ID12.7+0.25 ID22.22
+0.05
ID12.7+0.25
+0.1 +0.1
ID12.7 +0.1 +0.1
ID12.7+0.25

15
40
40

40
40
+0.2 +0.2
+0.25 ID19.1 +0.05 +0.25 +0.25 +0.05
ID19.1
ID9.52 ID9.52
unit:mm, ID: inner diameter; OD: outer diameter

+0.2 +0.1 ID9.52+0.25


+0.1 +0.1 ID9.52
+0.1
+0.05
ID38.1
132

10
10

10
10
132
189 94.5 94.5
Gather pipe is used for combination of outdoor unit

72
material
Insulation
HZG-20/A(for 2 basic modules); HZG-30/A(for 3 basic modules)

side
side
Gas

side
Gas

Liquid
Side

¢
¢
¢

¢
Mark
Note: Cut off the pipe from its middle when

200 200

120
12 40 40 12 40 40
using

120
ID19.1

ID19.1
ID25.4

ID25.4

14
+0.2

+0.2
ID22.22
ID22.22
+0.2

+0.2
+0.05

+0.05
+0.05

+0.05

+0.2

14
+0.2

+0.05
+0.05

+0.2
ID38.1
+0.05 +0.2
ID35.1
+0.05
Connection of manifold pipe

Double

Double

d.o.o. G R U P A
Controller dimensions:

TEMP

ON
132mm

HEALTH

124mm
SWING
OFF FAN

C
SET RECOVERY

CHECK

18mm
126mm
25mm
48mm

infrared controller YR-H71 wired controller YR-E12

65 92
180

49
R
136
MONITOR GROUP RUN CENTRAL SLAVE STANDBY
SET TOTAL UNIT STOP LOCK TIMER FILTER

MODE FAN SET FAILURE CHECK


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 SPEED
FAN
AUTO 1
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 COOL
HIGH 2
DRY
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

G R U P A
HEAT MID

70 121 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 AUTO LOW


RECOVERY SWING
AUTO NORMAL HRV 86 70

d.o.o.
(mm)
central controller ICR01

IGU04

73

Downloaded from www.Manualslib.com manuals search engine


MRV II Commercial Air Conditioning

9. Air flow and static pressure curves

AD072MLERA air flow and static pressure curves

550

500

450
air flow (m3/h)

400 super high


high
350
med
300 low
250

200

150
0 10 20

static pressure (Pa)

AD092MLERA air flow and static pressure curves

G R U P A
550

500

d.o.o.
450
air flow (m3/h)

400 super high


high
350
med
300 low
250

200

150
0 10 20
static pressure (Pa)

96
74

Downloaded from www.Manualslib.com manuals search engine


AD122MLERA air flow and static pressure curves

650
600 super
550 high
air flow (m3/h)

high
500
med
450
400 low

350
300
250
0 10 20
static pressure (Pa)

AD162MLERA air flow and static pressure curves

G R U P A
1000
950
900
air flow (m3/h)

d.o.o.
850 super high
high
800
med
750 low
700
650
600
0 10 20
static pressure (Pa)

97
75

Downloaded from www.Manualslib.com manuals search engine


AD182MLERA air flow and static pressure curves

1400
1350
1300
air flow (m3/h)

1250 super high


high
1200
med
1150 low
1100
1050
1000
0 10 20
static pressure (Pa)

AD242MLERA air flow and static pressure curves

G R U P A
1400
1350
1300
air flow (m3/h)

d.o.o.
1250 super high
high
1200 med
1150 low
1100
1050
1000
0 10 20
static pressure (Pa)

98
76

Downloaded from www.Manualslib.com manuals search engine


AD182MMERA air flow and static pressure curves

1400

1300
air flow(m3/h)

1200 super high


high
1100
med
1000 low

900

800
40 50 60 70 80 90 100

static pressure(Pa)

AD242MMERA air flow and static pressure curves

G R U P A
1400

1300
air flow(m3/h)

1200 super high

d.o.o.
high
1100
med
1000 low

900

800
40 50 60 70 80 90 100

static pressure(Pa)

77
Downloaded from www.Manualslib.com manuals search engine
AD282MMERA air flow and static pressure curves

1700

1600
air flow(m3/h)

1500 super high


high
1400
med
1300 low

1200

1100
40 50 60 70 80 90 100

static pressure(Pa)

AD302MMERA air flow and static pressure curves

2300

G R U P A
2200
air flow(m3/h)

2100 super high


high

d.o.o.
2000
med
1900 low

1800

1700
40 50 60 70 80 90 100
static pressure(Pa)

78
Downloaded from www.Manualslib.com manuals search engine
AD382MMERA air flow and static pressure curves

2300

2200
air flow(m3/h)

2100 super high


high
2000
med
1900 low

1800

1700
40 50 60 70 80 90 100

static pressure(Pa)

AD482MMERA air flow and static pressure curves

2300

G R U P A
2200
air flow(m3/h)

2100 super high

d.o.o.
high
2000
med
1900 low

1800

1700
40 50 60 70 80 90 100
static pressure(Pa)

79
Downloaded from www.Manualslib.com manuals search engine
MRV II Commercial Air Conditioning

AD182MHERA air flow and static pressure curves

1400
1200
air flow (m3/h)

1000
super high
800 high
600 med
low
400
200
0
80 100 120 140 160 180 200

static pressure (Pa)

AD242MHERA air flow and static pressure curves

G R U P A
1400
1200
air flow (m3/h)

1000 super high

d.o.o.
800 high
600 med
low
400
200
0
80 100 120 140 160 180 200

static pressure (Pa)

141
80

Downloaded from www.Manualslib.com manuals search engine


AD282MHERA air flow and static pressure curves

1400
1200
air flow (m3/h)

1000
super high
800 high
600 med
low
400
200
0
80 100 120 140 160 180 200

static pressure (Pa)

AD302MHERA air flow and static pressure curves

G R U P A
2000

1800
air flow (m3/h)

1600 super high

d.o.o.
high
1400
med
1200 low

1000

800
80 100 120 140 160 180 200
static pressure (Pa)

81

Downloaded from www.Manualslib.com manuals search engine


AD382MHERA air flow and static pressure curves

2000

1800
air flow (m 3/h)

1600 super high


high
1400
med
1200 low

1000

800
80 100 120 140 160 180 200
static pressure (Pa)

AD482MHERA air flow and static pressure curves

2500

G R U P A
2300
air flow (m3/h)

2100 super high


high

d.o.o.
1900
med
1700 low

1500

1300
80 100 120 140 160 180 200
static pressure (Pa)

82

Downloaded from www.Manualslib.com manuals search engine


AD722MHERA, AD962MHERA:
1. The number in the circle stands for the step on the fan speed controller.
2. The red line shows the air flow and the static pressure varies due to the different
steps in high speed. The blue dashed line shows the air flow and the static pressure
varies due to the different steps in low speed.
High speed
Low speed
200

8 7
6 5
4
3

150
External static pressure Pa

3 8

7
100
6

50

G R U P A
0
55 60 65 70 75 80 8586
3
Upper limit air flow (m /min) lower limit

d.o.o.

83

Downloaded from www.Manualslib.com manuals search engine


109. Capacitycalculation
. Capacity calculationdue
duetoto capacity
capacity modification
modification coefficient
coefficient

(1) Calculation method of cooling capacity---Refrigerating capacity to be known


=Refrigerating capacity x (A x B x C x D x E) W

A. Capacity compensation coefficient of indoor B. Capacity compensation coefficient of outdoor air dry-bulb
air wet-bulb temperature condition temperature condition
1.2 1.2

Capacity modification coefficient


Capacity modification coefficient

1.1 1.1

1.0
1.0
0.9
0.9
-5 0 5 10 15 20 25 30 35 40 43
0.8
15 20 24 Outdoor air dry-bulb temperature
Indoor air wet-bulb temperature

C. Capacity modification coefficient D. Capacity compensation suitable for total capability


under airflow variation rate of indoor of indoor unit group (cooling)
unit group (only for duct unit) 120
Capacity modification coefficient
Capacity modification coefficient

100
1.1
80
1.0
60

0.9 40
80 90 100 110 120
capacity
airflow variation rate(%) 20 Standard

0 20 40 60 80 100 120 130

Total capacity of indoor unit group(%)

G R U P A
d.o.o.

84

Downloaded from www.Manualslib.com manuals search engine


E: Capacity compensation value at different piping length and drop
AV08NMVERA liquid pipe:φ12.7
AV10NMVERA liquid pipe:φ12.7
gas pipe:φ22.22 gas pipe:φ22.22

cooling compensation factor


cooling compensation factor
1.00 1.00
0.95 0.95
0.90 liquid pipe:φ9.52
0.90 liquid pipe:φ9.52
gas pipe:φ19.05 gas pipe:φ22.22
0.85 0.85
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)

AV12NMVERA AV14NMVERA liquid pipe:φ12.7


gas pipe:φ28.58
cooling compensation factor

cooling compensation factor


1.00 1.00
0.95 0.95
liquid pipe:φ12.7
0.90 gas pipe:φ28.58 0.90
0.85 liquid pipe:φ12.7
0.85 liquid pipe:φ12.7
gas pipe:φ25.4 gas pipe:φ25.4
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)

AV16NMVERA liquid pipe:φ12.7 AV18NMVERA


gas pipe:φ31.8
cooling compensation factor
cooling compensation factor

1.00 1.00

0.95 0.95

0.90 0.90
liquid pipe:φ15.88
0.85 liquid pipe:φ12.7 0.85 gas pipe:φ28.58
liquid pipe:φ15.88
gas pipe:φ28.58 gas pipe:φ31.8
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)

AV20NMVERA AV22NMVERA

G R U P A
cooling compensation factor
cooling compensation factor

1.00 1.00 liquid pipe:φ15.88


gas pipe:φ31.8
0.95 0.95
0.90 0.90
liquid pipe:φ15.88 liquid pipe:φ15.88 liquid pipe:φ15.88
0.85 0.85 gas pipe:φ28.58
gas pipe:φ28.58 gas pipe:φ31.8

d.o.o.
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)

AV24NMVERA liquid pipe:φ15.88 AV26NMVERA


cooling compensation factor

gas pipe:φ31.8
cooling compensation factor

1.00 1.00
0.95 0.95
0.90 0.90
0.85 liquid pipe:φ19.05 liquid pipe:φ19.05
0.85 liquid pipe:φ15.88
gas pipe:φ31.8
gas pipe:φ28.58 gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m)
pipe length of single way (m)

AV28NMVERA AV30NMVERA
cooling compensation factor
cooling compensation factor

1.00 1.00 liquid pipe:φ19.05


gas pipe:φ38.1
0.95 0.95
0.90 0.90
liquid pipe:φ19.05 liquid pipe:φ19.05
0.85 gas pipe:φ31.8
liquid pipe:φ19.05 0.85 gas pipe:φ31.8
gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)

85

Downloaded from www.Manualslib.com manuals search engine


AV32NMVERA AV34NMVERA

cooling compensation factor

cooling compensation factor


1.00 1.00
liquid pipe:φ19.05
gas pipe:φ38.1
0.95 0.95

0.90 0.90
liquid pipe:φ19.05
0.85 liquid pipe:φ19.05 liquid pipe:φ19.05 0.85 gas pipe:φ31.8
gas pipe:φ31.8 gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)

AV36NMVERA AV38NMVERA
cooling compensation factor

cooling compensation factor


1.00 1.00 liquid pipe:φ22.22
gas pipe:φ38.1
0.95 0.95
0.90 0.90
liquid pipe:φ19.05 liquid pipe:φ19.05
0.85 liquid pipe:φ22.22 0.85 gas pipe:φ38.1
gas pipe:φ38.1 gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)

AV40NMVERA cooling compensation factor AV42NMVERA


cooling compensation factor

1.00 liquid pipe:φ22.22 1.00


gas pipe:φ38.1
0.95 0.95
0.90 0.90
liquid pipe:φ19.05
0.85 gas pipe:φ38.1 0.85 liquid pipe:φ19.05 liquid pipe:φ22.22
gas pipe:φ38.1 gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)

AV44NMVERA AV46NMVERA

G R U P A
cooling compensation factor

1.00
cooling compensation factor

1.00 liquid pipe:φ22.22 liquid pipe:φ22.22


gas pipe:φ38.1 gas pipe:φ38.1
0.95 0.95
0.90 0.90
liquid pipe:φ19.05 0.85 liquid pipe:φ19.05
0.85 gas pipe:φ38.1

d.o.o.
gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)
AV48NMVERA
cooling compensation factor

1.00
0.95
0.90
liquid pipe:φ19.05
0.85 gas pipe:φ38.1
liquid pipe:φ22.22
gas pipe:φ38.1
0.80
0 20 40 60 80 100 120 140 160 180
pipe length of single way (m)
Note:
1. The refrigerant pipe should be thickened when the single way length is over 90m.
2. When in cooling mode, outdoor is lower than indoor; or when in heating mode, outdoor is higher
than indoor, the compensation factor should be decreased the below value from the above figure.
vertical height drop between indoor 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
and outdoor
adjustment factor 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024 0.027 0.030

86

Downloaded from www.Manualslib.com manuals search engine


(2) Calculation method of heating capacity---Heating capacity to be known
= Heating capacityx (A x B x C x D x E x F) W

A. Capacity modification value B. Capacity modification value under outdoor air wet-bulb C. Capacity modification value
temperature condition under airflow variation rate of
under indoor air dry-bulb 1.2
temperature condition indoor unit group
1.1
1.2

Capacity modification value


1.0 1.1
1.1
0.9 1.0
1.0 0.8
0.9
0.9 0.7 80 90 100 110 120
0.6 airflow variation rate(%)
0.8
15 20 24 0.5
-15 -10 -5 0 5 10 15
Indoor air dry-bulb
temperature Outdoor air wet-bulb temperature

D. Capacity compensation suitable for total


capability of indoor unit group (heating) E. Capacity compensation coefficient for defrost capability of
outdoor heat exchanger
Capacity modification coefficient

1.2
Capacity modification coefficient

1.0
1.0

0.8

0.6 0.9

0.4
capacity
Standard

G R U P A
0.2
0.8
-15 -10 -5 0 5 10
0 20 40 60 80 100 120 140
Outdoor air wet-bulb temperature
Total capacity of indoor unit group(%)
F. Heating compensation factor at different pipe length

d.o.o.
for all models
1.00
heating compensation factor

0.98
0.96
0.94
0.92
0.90
0 20 40 60 80 100 120 140 160 180
pipe length of single way (m)

(3) Calculation method of refrigerating capacity---Only one indoor unit running


standby indoor nominal capacity
Outdoor modified capacity with a single indoor running = outdoor modified capacity *
Indoor total nominal capacity
(Outdoor modified capacity: heating or cooling capacity after modify item 1 and 2)

87

Downloaded from www.Manualslib.com manuals search engine


(4) Operation limit

(Cooling)
45 (Heating)
40

35 15
Consecutive operation

30 10

Outdoor air WB (¡ )
Outdoor air DB (¡ )

Consecutive operation
25
5
20
0
15
-5
10
-10
5

0 -15

-5 -20
5 10 15 20 25 30
-10
10 15 20 25 30
Indoor air WB (¡ ) Indoor air DB(¡ )

G R U P A
d.o.o.

88

Downloaded from www.Manualslib.com manuals search engine


11. Refrigerant piping design
1. Piping branch system
Outdoor Outdoor

Branch pipe Branch pipe

Indoor

G R U P A
Controller

d.o.o.

89

Downloaded from www.Manualslib.com manuals search engine


Outdoor

Branch pipe
Indoor

Controller

G R U P A
d.o.o.
Note: 1. The indoor units in the system can be added or reduced at your will on the
condtion that the indoor capacity is in the allowable range
2. When the indoor total capacity is more than outdoor nominal capacity, the capacity
of running indoor will be relatively reduced. The capacity of running indoor will not
exceed outdoor capacity.

90

Downloaded from www.Manualslib.com manuals search engine


2. Equivalent pipe length of bend pipe and branch pipe (FYI)

Pipe size 6.35 9.52 12.7 15.88 19.1 31.8

0.16 0.18 0.20 0.25 0.35 0.55


bend pipe

0.5 0.5 0.5 0.5 0.5 0.5


branch pipe

3. Branch pipe selection:

Total capacity of indoor units(100W) Branch pipe model

Less than 335 FQG-B335A

Not less than 335 and less than 506 FQG-B506A

Not less than 506 and less than 730 FQG-B730A

Not less than 730 FQG-B1350A

G R U P A
d.o.o.

91

Downloaded from www.Manualslib.com manuals search engine


4. Pipe specifications and connection methods (unit: mm)
A. Outdoor unit
Model Gas pipe side Liquid pipe side Oil pipe side
Diameter Connecting Diameter Connecting Diameter Connecting
method method method
AV08NMVERA 19.05 Flared Flared
Brazing 9.52 9.52
AV10NMVERA 22.22 joint joint

AV12NMVERA 25.4
Flared Flared
AV14NMVERA 25.4 Brazing 12.7 9.52
joint joint
AV16NMVERA 28.58

B. Indoor unit
Model Gas pipe side Liquid pipe side
Capacity Connecting Connecting
Diameter method Diameter method
07 9.52 6.35
09 9.52 6.35
12 12.7 6.35
14 12.7 6.35 Flared joint
Flared joint
16 12.7 6.35
18 12.7 6.35
24 15.88 9.52
28 15.88 9.52
32 15.88 9.52
38 15.88 9.52
15.88 9.52

G R U P A
48

C. Pipe spec and the torque


diameter Thickness(mm) Torque(N.m)
6.35 0.8 16~20
9.52 0.8

d.o.o.
40~50
12.7 1.0
15.88 1.0 90~120
19.05 1.0 100~140
25.4 1.2 ---
Not less than 28.58 More than 1.4 ---

5. Refrigerant charging and additional charging


Diameter of
liquid pipe additonal refrigerant charging per meter(kg/m) charge when
Model out of factory
22.22 19.05 15.88 12.7 9.52 6.35
AV08NMVERA 10kg
AV10NMVERA
AV12NMVERA 0.35 0.25 0.17 0.11 0.054 0.022 12kg
AV14NMVERA
AV16NMVERA 16kg

92

Downloaded from www.Manualslib.com manuals search engine


Remarks:
A. Charging amount when out of factory excludes the refrigerant in the pipe.
B . Additional charging amount=actual length of liquid pipe*additional amount per meter liquid pipe
Additional charging amount=L1*0.35+L2*0.25+L3*0.17+L4*0.11+L5*0.054+L6*0.022
L1: total length of 22.22 liquid pipe L2: total length of 19.05 liquid pipe
L3: total length of 15.88 liquid pipe L4: total length of 12.7 liquid pipe
L5: total length of 9.52 liquid pipe L6:total length of 6.35 liquid pipe

6. Requestment of copper pipe specs and thickness


Exterior diameter(mm) Pipe thickness(mm) Remarks
6.35 more than 0.8
9.52 more than 0.8
12.7 more than 1.0 coil pipe
15.88 more than 1.0
19.05 more than 1.0(straight pipe) more than 1.0 (coil pipe)
22.22 more than 1.0
25.4 more than 1.0
28.58 more than 1.0
straight pipe
31.8 more than 1.1
34.9 more than 1.3
38.1 more than 1.4
41.8 more than 1.5

G R U P A
d.o.o.

93

Downloaded from www.Manualslib.com manuals search engine


7. Allowable refrigerant piping length and height difference

a. Allowable pipe length and height difference


Single way total pipe length 300m
Single way max. pipe length Max. 150m
st
Main pipe between outdoor to 1 branch Max. 90m
Pipe length between outdoors Less than 10m to 1st branch pipe
Height difference between indoor and Outdoor is upper Max. 50m
outdoor Outdoor is lower Max. 40m
Height difference between outdoors(in the same system) Within 5m (better be horizontal)
st
Max. pipe length from 1 branch pipe to indoor Max. 40m
Height difference between indoors Max. 15m
b. Pipe length between outdoors

outdoor1

G R U P A
outdoor2 outdoor3

d.o.o.
3 1st gather pipe
2st gather pipe
Gas/liquid pipe: L1<10m, L2+L3<10m
Oil equalization pipe: L5+L6<10m
height difference between outdoors: h<5m

Note: a. HZG-30/A includes HZG-20/A;


b. The connection pipe among outdoors can not be higher than the stop valve position;
c. The connection pipe among outdoors should be horizontal or be in a certain angle as
the below figure (less than 15degree).

94

Downloaded from www.Manualslib.com manuals search engine


outdoor1

outdoor2 outdoor3

outdoor1

outdoor3
outdoor2

G R U P A
d.o.o.
Installation at high difference:

outdoor1

outdoor2 outdoor3

95

Downloaded from www.Manualslib.com manuals search engine


outdoor2 outdoor3

outdoor1

Oil trap (upright projecting pipe, 200mm high), as the figure:

outdoor2 outdoor3

G R U P A
outdoor1

Below is forbidden (compressor oil will flow into the lowest outdoor).

d.o.o.

outdoor2 outdoor3

outdoor1

96

Downloaded from www.Manualslib.com manuals search engine


c. Allowable pipe length and height difference

outdoor1
when the distance between outdoors is over
2m, the oil trap must be set (upright projecting
pipe, 200mm high)
max. drop:5m
outdoor is uppper,max. drop is 50m

outdoor2 outdoor3
L2
L4

below 2m below 2m
L1
L3 L5
over 200mm
over 200mm

L1<10m L8
L6 L10
L2+L3<10m

max. drop:15m
L7+L14+L13 <40m L11
L9

outdoor is lower, max. drop is 40m


L12 L13
L7

L14 L15

Max. length Pipe in above figure G R U P A


d.o.o.

L1+L2+ L3+ L4+ L5+ L6+ L7+L8+ L9+ L10+


Single way total pipe length 300
L11+ L12+ L13+ L14+ L15
Single way max. pipe length 150 L1+L3+ L5+ L7+ L14+ L13
st
Max. pipe length after 1
40 L7+L13+L14
branch pipe
Main pipe actual length 90 L5
Height difference between
15 ————
indoors
Height difference between
5 ————
outdoors

97

Downloaded from www.Manualslib.com manuals search engine


(2) Pipe specification:

outdoor gather pipe

e e e
d

c
b
a a
the first branch

a a

a. Pipe “a” diameter (between indoor and branch pipe) (depends on indoor pipe, for wall
mounted unit, please refer to its specification)
Indoor(×100W) Gas pipe Liquid pipe
22~28 φ9.52 φ6.35
36~56 φ12.7 φ6.35
71~140 φ15.88 φ9.52

b. Pipe “b” diameter (between branch pipes)


Total indoor capacity after the
Gas pipe Liquid pipe
branch pipe

G R U P A
14.0KW《<16.8KW Φ15.88 Φ9.52
16.8KW《X<22.4KW Φ19.05 Φ9.52
22.4KW《X<33.0KW Φ22.22 Φ9.52
33.0KW《X<47.0KW Φ12.7
Φ28.58

d.o.o.
47.0KW《X<71.0KW Φ15.88
71.0KW《X<101.0KW Φ31.88
Φ19.05
》101.0KW Φ38.1

When the later indoor capacity is less than 14.0KW, the specification of pipe b should refer
to the data in table a.
c. Pipe “c” diameter (main pipe, between outdoor gather pipe and the first branch pipe)
Outdoor Main pipe Enlarged main pipe
capacity Gas pipe Liquid pipe Gas pipe Liquid pipe
22.6KW φ19.05 φ9.52 φ22.2 φ12.7
28.0KW φ22.2 φ9.52 φ25.4 φ12.7
33.5KW φ25.4 φ12.7 φ28.58 φ12.7
40.0KW φ25.4 φ12.7 φ28.58 φ12.7
45.0KW φ28.58 φ12.7 φ31.8 φ12.7
50.6KW φ28.58 φ15.88 φ31.8 φ15.88
56.0KW φ28.58 φ15.88 φ31.8 φ15.88
98

Downloaded from www.Manualslib.com manuals search engine


61.5KW φ28.58 φ15.88 φ31.8 φ15.88
68.0KW φ28.58 φ15.88 φ31.8 φ15.88
73.0KW φ31.8 φ19.05 φ38.1 φ19.05
80.0KW φ31.8 φ19.05 φ38.1 φ19.05
85.0 KW φ31.8 φ19.05 φ38.1 φ19.05
90.0 KW φ31.8 φ19.05 φ38.1 φ19.05
96.0 KW φ31.8 φ19.05 φ38.1 φ19.05
101.0KW φ38.1 φ19.05 φ38.1 φ22.22
106.5KW φ38.1 φ19.05 φ38.1 φ22.2
113.0KW φ38.1 φ19.05 φ38.1 φ22.2
118.0KW φ38.1 φ19.05 φ38.1 φ22.2
123.5KW φ38.1 φ19.05 φ38.1 φ22.2
130.0 KW φ38.1 φ19.05 φ38.1 φ22.2
135.0KW φ38.1 φ19.05 φ38.1 φ22.2
Note: When the distance from outdoor to the longest indoor is over 90m, the main pipe
diameter should be enlarged.
d. Pipe “d” diameter (between gather pipes)
Total outdoor capacity
Liquid pipe (a, c) Gas pipe (b, d)
before the gather pipe
~68.0KW φ15.88 φ28.58
69.0~96.0KW φ19.05 Φ31.8
97.0KW~ φ19.05 Φ38.1

G R U P A
e. Pipe “e” diameter (between outdoor and the gather pipe)
outdoor capacity Gas pipe Liquid pipe Oil equalization pipe
8HP φ19.05
φ9.52
10HP φ22.2

d.o.o.
φ9.52
12, 14 HP φ25.4 φ12.7
16HP φ28.58 φ12.7

Copper pipe selection:


hardness softness Half-hardness
Outer
φ6.35 φ9.52 φ12.7 φ15.88 φ19.05 φ22.2 φ25.4 φ28.58 φ31.8 φ34.9 φ38.1 φ41.3
diameter
Min.
0.8 0.8 1.0 1.0 1.0 1.1 1.2 1.4 1.4 1.4 1.4 1.43
thickness
Note: If the copper pipe with outer diameter φ19.05 is coil pipe, the thickness should be
over 1.1.

99

Downloaded from www.Manualslib.com manuals search engine


8. Pipe dimension among outdoors

(1) Outdoor pipe dimension

18~32HP 34~48HP

a Liquid pipe a c Liquid pipe


b Gas pipe
b d Gas pipe

The pipe “a, b, c, d” should be confirmed as to the below table.

Former outdoor capacity Liquid pipe (a, c) Gas pipe (b, d)

~68.0KW φ15.88 φ28.58

69.0KW~96.0KW φ19.05 φ31.8

Over 97.0KW φ19.05 φ38.1

G R U P A
Note: When the single pipe length is over 90m, the above pipe should be enlarged as the
former information.

(2) Oil equalization pipe connection

d.o.o.
18~32HP 34~48HP

T-shape
oil equalization 3-way pipe oil equalization
pipeφ9.52 pipeφ9.52

100

Downloaded from www.Manualslib.com manuals search engine


12. Wiring design
Warning :In European Market :local 3 phase isolator (power switch) must be fitted locally to
the unit (Legal requirement for EU).
For other area, pls. comply with local regulation requirement.
Electric wiring should be executed by the specialized well-trained person.
Warnings:
A. Do not take the other wire except for copper wire as the power cable.
B. All indoor/outdoor units must be connected with the earthing wire of power cable. The earthing wire can not be
connected onto the earthing wire of coal gas pipe, water pipe, lightning rod, or telephone. Or the electric shock or
fire will occur.
C. Must install the leakage breaker and the over current breaker, or electric shock will occur.
D. Before finishing electric installation, do not electrify the unit.
E. Indoor and outdoor use their individual power source. All indoors use one power source.
F. The communication wire and the power cable must be individual and can not use one multi-core cable, or
the communication wire will be interfered to cause abnormal.
Note: When one wired controller controls multiple indoors, the connected indoor units must use the
common phase of power source, or the communication will be abnormal.For example, the power source
is L1,L2,L3,and N, all the indoor units must use L1/N or L2/N or L3/N.
1. Wiring system:
(1) Power wiring figure

outdoor 1 outdoor 2 outdoor 3

L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N

leakage breaker leakage breaker leakage breaker


over current breaker over current breaker over current breaker

G R U P A
power source: 3PH, 380V, 50Hz power source: 3PH, 380V, 50Hz power source: 3PH, 380V, 50Hz

indoor 1 (wall mounted unit) indoor 2 (wall mounted unit) indoor 3 (non wall mounted unit)

Tw3 1 2 L N Tw3 1 2 L N L

d.o.o.
TW1 TW1 N

leakage breaker leakage breaker leakage breaker


over current breaker over current breaker over current breaker

power source: 1PH, 220V, 50Hz power source: 1PH, 220V, 50Hz power source: 1PH, 220V, 50Hz

101

Downloaded from www.Manualslib.com manuals search engine


(2) Communication wiring figure

outdoor 1 outdoor 2 outdoor 3

P QA B C ABC AB C

communication wire with polarity

indoor 1 indoor 2 indoor 3 indoor 4 indoor 5

P QA B C PQ A B C PQ A B C PQA B C PQA BC

control wire for wired controller with polarity

ABC
wired controller

indoor 6 indoor 7 indoor 8 indoor 9 indoor 10


PQAB C PQ A B C P QA B C PQA B C PQA BC

ABC A BC ABC ABC


wired controller wired controller wired controller wired controller
A BC
wired controller

indoor 11 indoor 12 indoor 13 indoor 14 indoor 15

PQAB C PQ A B C P QA B C PQA B C PQA BC

ABC A BC ABC ABC


wired controller wired controller wired controller wired controller
A BC
wired controller

indoor 16 indoor 17 indoor 18 indoor 19 indoor 20

PQAB C PQ A B C P QA B C PQA B C PQA BC

G R U P A
ABC A BC ABC ABC
wired controller wired controller wired controller wired controller
ABC A BC
wired controller wired controller

d.o.o.
Outdoor untis are in parallel through 3 polar wires. The outdoor and all indoor units are in parallel through 2
non-polar wires.
Three wiring methods between wired controller and indoor unit:
A. 1 to multi (group control): one wired controller controls 2~16 indoors, as shown in above figure, indoor
1~indoor 5: indoor 5 is wired control master unit, the others are wired control slave units. Wired controller and
the master indoor (directly connected to wired controller) is connected by 3 polar wires; the other indoors and
the master indoors are connected by 2 polar wires.B. 1 to 1 (one wired controller controls one indoor): as
shown in above figure, indoor 6~ indoor 19, indoor and wired controller are connected by 3 polar wires.
C. 2 to 1 (two wired controller controls one indoor): as shown in above figure, indoor 20. Either of wired controllers
can be set as master wired controller, and the other is slave wired controller. Master/slave wired controller,
and master/indoor are connected by 3 polar wires.
When indoor is controlled by remote controller, refer to the "wired control master unit/wired control slave
unit/remote control unit table".A, B, C on signal terminal block need not wires and not connect the wired controller.

102

Downloaded from www.Manualslib.com manuals search engine


3. Specs for power cable and communication wire
(1) Outdoor power source and power cable
power power cable section wire length circuit breaker(A) earthing wire
item
model source (mm2) (m) section(mm2) screw
individual AV10NMVERA 3N~, 10 60 40
380V, 3.5 M5
power AV16NMVERA 50Hz 18 60 70

a. Power cable must be fixed firmly.


b. Each outdoor must be earthed well.
c. When power cable exceeds the range, thichen it appropriately.
(2) Indoor power source, communication wire between indoor and outdoor, among indoors
rated current of residual communication wire section
item power cable wire length rated current current circuit breaker(A)
section (m) of overcurrent outdoor/indoor indoor/indoor
indoor total (mm2) breaker(A) leakage current (mA)
current (A) response time(s) (mm2) (mm2)

< 10 2 23 20 20A, 30mA, below 0.1s


¡ 10 and <15 3.5 24 30 30A, 30mA, below 0.1s 2-core * (0.75-2.0mm2)
¡ 15 and <22 5.5 shielded wire
27 40 40A, 30mA, below 0.1s
¡ 22 and <27 10 42 50 50A, 30mA, below 0.1s

a. Power cable and communication wire must be fixed firmly.


b. Each indoor must be earthed well.
c. When power cable exceeds the range, thichen it appropriately.
d. Shielded layer of communication wires must be connected together and be earthed at single point.
e. Communication wire total length cannot exceed 1000m.
(3) Communication wire for wired controller
wire length(m) wire spec wire length(m) wire spec
0.3mm2 * (3-core) shielded wire ¡ 300 and <400 1.25mm2 * (3-core) shielded wire

G R U P A
¡·100
¡ 100 and <200 0.5mm2 * (3-core) shielded wire ¡ 400 and <600 2mm2 * (3-core) shielded wire
¡ 200 and <300 0.75mm2 * (3-core) shielded wire

a. Shielded layer of communication wire must be earthed at one end.


b. The total length cannot exceed 600m.

d.o.o.
(4) Control type and the switchover
a) Indoor unit can be controlled by wired controller or remote controller.
b) When installation, the installer must set the unit due to the control type and wiring type.
Switchover between wired control master/slave unit /remote control unit, set when installation:
control type
wired control wired control
socket remote control
master unit slave unit
/dip switch
CN23 short connected disconnected disconnected
CN30 short connected short connected disconnected

CN21 blank blank to remote receiver

SW08-[6] ON ON OFF
signal terminal block A,B,C to wired controller B,C to wired controller A,B,C not to wired controller

103

Downloaded from www.Manualslib.com manuals search engine


Note:
1. In the above figure, the state in the frame is set when out of factory.
2. The indoor controlled by master/slave wired controller and the indoor controlled by individual wired
controller are all wired controlled master indoor.
3. The remote receiver is equipped with a multi-wire which can be inserted in CN21.

4. Central control system

connecting board
iGU04 outdoor (master unit)

indoor unit

Wired controller
Unit
Unit Unit (group control, 1:16)
No. 1
No. 2 No. 3

iGU04 outdoor (master unit)

indoor unit
Unit
No. 4
Unit Unit
No. 5 No. 6

iGU04 outdoor (master unit)

indoor unit

Unit
No. 7
Unit Unit
No. 8 No. 9

¡£¡£¡£¡£¡£¡£¡£¡£¡£¡£¡£¡£
iGU04 outdoor (master unit)

indoor unit

Unit

G R U P A
No. 62
Unit Unit
No. 63 No. 64
Central controller (64 units)

Can set the central control unit as a group, and the max. 64 units of indoor can be set a group.

d.o.o.
After setting unit, the indoor in one group can be controlled the same operation (when out of factory, one
unit is regarded as one group).

connecting board IGU04

unit 1 unit 2 unit 3 unit 1 unit 2 unit 3

˙ł 1 ˙ł 2 ˙ł 3
central controller

Figure 2 Central unit and group diagram

When the central controller connects one outdoor unit, the connecting board IGU04 is unnecessary.

104

Downloaded from www.Manualslib.com manuals search engine


Communication wire specs
The wire between connecting board to the central controller is the dual-core STP (shielded twisted pair).
The detailed specs are as below:

wire length(m) Specs


<100 0.3mm2 * 2-core STP
¡ 100 and <200 0.5mm2 * 2-core STP
¡ 200 and <300 0.75mm2 * 2-core STP
¡ 300 and <400 1.25mm2 * 2-core STP
¡ 400 and <600 2mm2 * 2-core STP
¡ø Shielded layer of communication wire must be earthed on one end.

5. Electric characteristic

units power supply indoor fan motor power input(W)

model phase voltage volt. MCA FLA


FQY range MFA W cooling heating

AB092MCERA 1 50 220 198~242 0.5 1.6 20 0.4 80 80

AB122MCERA 1 50 220 198~242 0.5 1.6 20 0.4 80 80

AB162MCERA 1 50 220 198~242 0.5 1.6 20 0.4 80 80

AB182MEERA 1 50 220 198~242 0.69 2.2 45 0.55 90 90

AB242MEERA 1 50 220 198~242 0.69 2.2 45 0.55 100 100

G R U P A
AB282MEERA 1 50 220 198~242 0.69 2.2 45 0.55 100 100

AB302MEERA 1 50 220 198~242 1.38 4.4 60 1.1 150 150

d.o.o.
AB382MEERA 1 50 220 198~242 1.38 4.4 60 1.1 150 150

AB482MEERA 1 50 220 198~242 1.38 4.4 60 1.1 150 150

AB182MCERA 1 50 220 198~242 0.69 2.2 45 0.55 90 90

AB242MCERA 1 50 220 198~242 0.69 2.2 45 0.55 100 100

AB282MCERA 1 50 220 198~242 0.69 2.2 45 0.55 100 100

AB302MCERA 1 50 220 198~242 1.38 4.4 53 1.1 150 150

AB382MCERA 1 50 220 198~242 1.38 4.4 53 1.1 150 150

AB482MCERA 1 50 220 198~242 1.38 4.4 53 1.1 150 150

105

Downloaded from www.Manualslib.com manuals search engine


units power supply indoor fan motor power input(W)

model phase voltage volt. MCA FLA


FQY range MFA W cooling heating

AD072MLERA 1 50 220 198~242 0.31 1 16 0.25 30 30

AD092MLERA 1 50 220 198~242 0.31 1 16 0.25 30 30

AD122MLERA 1 50 220 198~242 0.44 1.2 30 0.35 45 45

AD162MLERA 1 50 220 198~242 0.4 1.28 30 0.32 50 50

AD182MLERA 1 50 220 198~242 1.25 4 80 1 110 110

AD242MLERA 1 50 220 198~242 1.25 4 80 1 110 110

AD182MMERA 1 50 220 198~242 1.79 3.8 75 0.95 100 100

AD242MMERA 1 50 220 198~242 1.79 3.8 75 0.95 100 100

AD282MMERA 1 50 220 198~242 1.79 3.8 75 0.95 100 100

AD302MMERA 1 50 220 198~242 2.42 5.8 100 1.45 200 200

AD382MMERA 1 50 220 198~242 2.42 5.8 100 1.45 200 200

G R U P A
AD482MMERA 1 50 220 198~242 2.42 5.8 100 1.45 200 200

AD182MHERA 1 50 220 198~242 3.5 8 240 2 280 280

d.o.o.
AD242MHERA 1 50 220 198~242 3.5 8 240 2 280 280

AD282MHERA 1 50 220 198~242 3.4 9 240 2.3 280 280

AD302MHERA 1 50 220 198~242 3.375 10.8 270 2.7 300 300

AD382MHERA 1 50 220 198~242 3.375 10.8 270 2.7 320 320

AD482MHERA 1 50 220 198~242 3.375 10.8 270 2.7 360 360

AD722MHERA 1 50 220 198~242 1.88 6 270 1.5 600 600

AD962MHERA 1 50 220 198~242 1.88 6 270 1.5 600 600

106

Downloaded from www.Manualslib.com manuals search engine


units power supply indoor fan motor power input(W)

model phase voltage volt. MCA FLA


FQY range MFA W cooling heating

AC162MCERA 1 50 220 198~242 0.45 1.44 26 0.36 60 60

AC182MCERA 1 50 220 198~242 0.45 1.44 26 0.36 60 60

AC242MCERA 1 50 220 198~242 0.45 1.44 26 0.36 100 100

AC382MFERA 1 50 220 198~242 1.69 5.4 100 1.35 100 100

AC482MFERA 1 50 220 198~242 1.69 5.4 100 1.35 100 100

AS072MCERA 1 50 220 198~242 0.3 0.96 15 0.24 27 27

AS092MCERA 1 50 220 198~242 0.3 0.96 15 0.24 27 27

AS122MCERA 1 50 220 198~242 0.3 0.96 15 0.24 27 27

AS162MCERA 1 50 220 198~242 0.35 1.12 26 0.28 45 45

AS182MCERA 1 50 220 198~242 0.35 1.12 26 0.28 45 45

AF072MCERA 1 50 220 198~242 0.28 0.88 20 0.22 27 27

G R U P A
AF092MCERA 1 50 220 198~242 0.28 0.88 20 0.22 27 27

AF122MCERA 1 50 220 198~242 0.28 0.88 20 0.22 27 27

AF182MCERA 1 50 220 198~242 0.32 45 45


1.00 30 0.25

Symbols: Notes: d.o.o.

MCA: Min. circuit amps (A) 1. Voltage range


MFA: Max. fuse amps of circuit The units are applicable for the electrical systems
breaker where voltage supplied to unit is in the range.
KW: Fan motor rated output 2. Maximum allowable voltage unbalance between
(KW) phases is 2%.
FLA: Full load amps(A) 3. MCA=1.25*FLA
IFM: Indoor fan motor MFA 4*FLA
4. Power supply uses the circuit breaker

107

Downloaded from www.Manualslib.com manuals search engine


Outdoor unit:
units power supply compressor OFM

model phase volt. MCA TOCA RLA KW FLA


FQY voltage range MFA

AV08NMVERA 3 50 380 342-418 21.3 29.5 25 15 0.75 2


AV10NMVERA 3 50 380 342-418 23.5 32.9 25 17 0.75 2
AV12NMVERA 3 50 380 342-418 26.3 36.8 30 19 0.75 2
AV14NMVERA 3 50 380 342-418 29.8 41.7 35 21 0.75 2
AV16NMVERA 3 50 380 342-418 32.2 45 35 23 0.75 2
AV18NMVERA 3 50 380 342-418 44.8 62.4 50 15+17 0.75 2
AV20NMVERA 3 50 380 342-418 47 65.8 50 17+17 0.75 2
AV22NMVERA 3 50 380 342-418 49.8 69.7 55 17+19 0.75 2
AV24NMVERA 3 50 380 342-418 53.3 74.6 60 17+21 0.75 2
AV26NMVERA 3 50 380 342-418 55.7 77.9 60 17+23 0.75 2
AV28NMVERA 3 50 380 342-418 59.6 83.4 70 21+21 0.75 2
AV30NMVERA 3 50 380 342-418 62 86.7 70 21+23 0.75 2
AV32NMVERA 3 50 380 342-418 64.4 90 70 23+23 0.75 2
AV34NMVERA 3 50 380 342-418 76.8 107.5 85 17+17+21 0.75 2
AV36NMVERA 3 50 380 342-418 79.2 110.8 85 17+17+23 0.75 2
AV38NMVERA 3 50 380 342-418 83.1 116.3 95 17+21+21 0.75 2
AV40NMVERA 3 50 380 342-418 85.5 119.6 95 17+21+23 0.75 2
AV42NMVERA 3 50 380 342-418 87.9 122.9 95 17+23+23 0.75 2
AV44NMVERA 3 50 380 342-418 90.7 126.8 105 19+23+23 0.75 2

G R U P A
AV46NMVERA 3 50 380 342-418 94.2 131.7 105 21+23+23 0.75 2
AV48NMVERA 3 50 380 342-418 96.6 135 105 23+23+23 0.75 2

d.o.o.
Symbols: Notes:
MCA: Min. circuit amps. (A) 1. RLA is based on the nominal condition
TOCA: Total over-current amps.(A) 2. Voltage range
MFA: Max. fuse amps of circuit The units are applicable for the electrical systems
breaker where voltage supplied to unit is in the range.
MSC: Max. starting current 3. Maximum allowable voltage unbalance between
RLA: Rated load amps.(A) phases is 2%.
OFM: Outdoor fan motor 4. Power supply uses the circuit breaker

KW: Rated motor output(KW)


FLA: Full load amps(A)

108

Downloaded from www.Manualslib.com manuals search engine


6. Wiring of indoor and outdoor
Wiring of indoor units (for example)

1(L) 2(N) P Q A B C 1(L) 2(N) P Q A B C

To wired controller(A,B,C)

To other
indoor unit

Communication cable
(Shielded wire)
LN PQ
Power cable
To power cable To outdoor unit

Wiring of outdoor units (for example)

Rutdoor unit 9 Rutdoor unit 8

G R U P A
O8 O9 O: S T D E F O8 O9 O: S T D E F

d.o.o.

Wo other
outdoor
Wo other unit
outdoor
unit

Fommunication cable O8O9O:Q ST


Wo power cable Wo indoor
/Vhielded wire0
communication
Sower cable

109

Downloaded from www.Manualslib.com manuals search engine


13. Management system H-CACS
1. General information
This management system suits for MRV II series air conditioner.
1.1 Gateway(Model:iGU01)
Function:Communication BUS for indoor &Outdoor ,adopt the running status parameters,transmit the
control signal .And convert the comminucaition protocal from Homebus to LONKWORKS .Each system
need one set ,that is the gateway quantity equals to Inverter outdoor unit quantity and every gateway
can connect max. 40 sets of indoor in one system.
1.2 Network server(Model:iSERVER)
Function:Convert the communication protocol from Lonwokrs to TCP/IP.
Each Network server can connect 256 management ports(Each indoor unit ,outdoor unit is regarded
as one management port) in theory ,But in fact ,the system can not be more than 200 management
ports, and each management system can connect 4 sets network server maximum by HUB.
1.3 Network side software:Each software can control 20000 sets parameter ports
1.4 PC, HBU, internet wire, electric box, pulse ammeter are common devices, which will not be supplied
by Haier and be purchased by the distributor or the buyer.
Herein,
PC is the engineer computer or the server with the current standard configuration.
HUB is required with the enough ports.
Pulse ammeter is required with high precision.

For example:
10 sets of indoor (20HP), 20 sets of indoor (30HP), 30 sets of indoor (40HP), MRV II outdoor. To realize

G R U P A
monitor, control and count function.
The required devices are as follows:
3 gateways; 3 pieces of communication wire, one internet server, one set of network side software,
internet wire, one set of PC.

d.o.o.

110

Downloaded from www.Manualslib.com manuals search engine


2. Gateway exterior appearance & installation method

No. item Remarks


1 AC 13.8V, non-polar
2 AC
3 NC
4 NC
5 5V When ammeter connects external power supply,
there should be a resistor 10K between 5 and 7
6 GND
7 M1
8 GND
9 SUB1
Signal of slave unit 1

G R U P A
10 GND
11 SUB2 Signal of slave unit 2
12 GND
13 SUB3
Signal of slave unit 3

d.o.o.
14 GND
15 HB1 Communication bus line between indoor and
16 HB2 outdoor
17 LONA Communication bus line of LonWorks
18 LONB
19 LONA
20 LONB

B.Installation place of gateway


Install the gateway near the master unit, because the gateway gets HOMEBUS data and slave
data from outdoor inverter master unit(KMR-280W/BP), you could install the unit as follows:
Install the gateway on the cover of the electrical box right side of Master unit, drilling a
hole on the site. Adopt the flat head tapping screw to fix the gateway, to prevent the wires
punctured by the wires in the electric box.

111

Downloaded from www.Manualslib.com manuals search engine


MRV II Commercial Air Conditioning

2. Installation instruction
2.1 Structure figure

PC on client side
install network side software

internet or intranet or LAN

PC on field (server installed network side software)

switch
LAN

internet server

LonWorks

pulse ammeter gateway(iGU01)

2. 2 System diagram:

G R U P A
Ammeter Ammeter

Outdoor Outdoor Outdoor Outdoor


Gateway master slave Gateway master slave
unit unit

d.o.o.
unit unit
Ammeter Ammeter

Outdoor Outdoor Outdoor


Computer Gateway master slave Gateway Outdoor slave
master
unit unit unit unit
Ammeter Ammeter
Local area switch
network(LAN) Outdoor Outdoor Outdoor Outdoor
Gateway master slave
Gateway master slave
unit unit
iSERVER iSERVER unit unit

Ammeter Ammeter

Outdoor Outdoor Outdoor Outdoor


Gateway master slave Gateway master slave
unit unit unit unit
LONWORKS network (adopts end-to-end type
connection)

112

Downloaded from www.Manualslib.com manuals search engine


MRV II Commercial Air Conditioning

C. Wiring connection of gateway:

Gateway Electrical box of


Master unit

To pulse ammeter
To other gateway and server

PCB of master unit

CN44

CN19 CN36

when there is no To CN44 of slave unit 1 communication P Q X


terminal block Y A B C
proper power when there is no
supply from 5V signal from
PCB, connect pulse ammeter, To CN44 of slave unit 2

G R U P A
it to external use the port.
power: 13.8VAC To indoor unit To outdoor slave unit
200mA.
Remarks:
1) Power: The power of gateway is AC12V and could be getted from port A and B on the
communication terminal block of outdoor master unit and slave unit. There cannt be

d.o.o.
any error when connecting, or the gateway will be burnt off.
2) LON/LON(LONWORKS communication) connector: connect with the gateway of other
master unit and LONWORKS communication connector of internet server, no polarity
requirement.
3) HBS/earth wire(serial signal of master unit) wiring: connect with the output port of
serial signal (CN35 ) of the master uint PCB, get the parameter of slave unit from serial
signal, could not detect slave unit data when in reverse connection. Polarity is
required. When using communication wire 0010450044, black wire is connected to the
HBS terminal of gateway, and white wire is connected to the earth wire on the right of HBS.
4) Count/ earth wire(pulse signal) wiring: connect pulse ammeter to get the power
consumption recorded in the ammeter. Polarity is required.
Connect the earth wire terminal of pulse output of ammeter to the earth wire terminal on
the right of count terminal of gateway, and the other terminal of pulse output of ammeter
connects to the count terminal of gateway.
HBM/HBM (HOMEBUS communication) port: connect ports P&Q of the communication
terminal block of outdoor master unit and indoor unit, no polarity requirement..

113

Downloaded from www.Manualslib.com manuals search engine


MRV II Commercial Air Conditioning

Spec of cable:
1) Power: Two-core RVV, the section area is 0.5mm2, there is no polarity requirement when connection.
2) LON(LONWORKS communication) port: Two-core STP, the section area is 1.5mm2, there is no
polarity requirement when connection.
3) HBS(master unit serial signal): get state signal of slave units.
4) Count (pulse signal): use two-core RVVP shielded wire, the section area is1.0mm2, there is polarity
requirement when connection.
5) HBM (HOMEBUS communication): use two-core RVVP shielded wire, the section area is1.0mm2,
there is no polarity requirement when connection.
2.4 Connection among gateways, between gateway and server
The gateways are interconnected with two-core STP (the section is 1.5mm2) to make LONWORKS
control network. The spec of signal wire is as above. The wiring of signal wires adopts bus type
(identical with the communication wires connection between indoor and outdoor).
If it is very far from gateway to server, the wires must be shielded and be heat insulated well;
and the shielded layer must be connected to the earth wire terminal of the server.
2.5 Exterior appearance & installation method of internet server
A. External appearance and definition of port
To server bus line 17, 18 connect
with server bus line (LON);19
Connect with computer
connect with shield layer.

G R U P A
d.o.o.

earth N L
wire
114

Downloaded from www.Manualslib.com manuals search engine


MRV II Commercial Air Conditioning

s w itc h

The other communication ports are no used.


A: External dimension and installation space requirement:
Because the internet server is a precise electronic device, it should be installed in the control room
to connect computers conveniently.

G R U P A
d.o.o.

115

Downloaded from www.Manualslib.com manuals search engine


5. Management system H-CACSII
BMS system H-CACS transfer the data of air conditioner to the computer through the inverter
protocol adapter (IGU02), and the user can monitor the working state and the power consumption
of indoor and outdoor on real time at the computer. Set the parameter of system in time; start or
stop a certain indoor individually, or in group as the request; receive the alarm and make some
measures on real time; deal with the data and make some cost account tables.

Part 1: brief
1.1 Applicable for MRV II (R22 & R410A) system.
1.2 System combination
1. Inverter protocol adapter (IGU02): Transform the air conditioner protocol into protocol 485;
receive ammeter pulse signal; account and save the power cost of the connected system, then
transfer it to the computer.
2. Software: parameter display and human-computer operation surface, and account and save
the power cost, output the cost table.
3. RS 485&232 Converter (hardware), Item 2 & 3 name is HCM1.
1.3 Control range
1. If the H-CACSII is necessary, pay attention that the indoor quantity of every system cannot
be over 40 sets. Or the adapter can not work normally.
2. Every system needs one protocol adapter.
3. One Microsoft can control indoors within 400 sets.
1.4 Applicable range and relative certificate
1) Applicable range

G R U P A
Temp. range: -30¡ ¡«52¡
Ambient temperature of controller: -30¡ ¡«52¡
Ambient humidity of controller: -30¡ ¡«52¡
Save temp. range of controller: -30¡ ¡«52¡
Altitude: 0¡«6000m

d.o.o.
Voltage: 220Vac±10£¥
Frequency: 50Hz
2£'Safe certificate: Conform with HR and CCC
3£'Environment certificate: conform with ROHS
1.5 Reliable request
1£'Application standards£”QB1238-91, GB4706.1-92, GB4706.12-95
2£'Special requirement:

116

Downloaded from www.Manualslib.com manuals search engine


Part 2: Scheme of H-CACSII

Part 3: Appearance and dimension of protocol adapter

G R U P A
Appearance:

d.o.o.

Dimension: 2000*1300*430(mm)

Part 4: Wiring request


1. Protocol adapter needs 220V AC power supply.
2. The communication line between indoor and outdoor and the bus line 485 among the protocol
adapters should be through steel wire sleeve in the H-CACSII.
3. Set the indoor central address and the indoor/outdoor unit address by hand.
The system with H-CACSII should not set the group function of wired controller.

117

Downloaded from www.Manualslib.com manuals search engine


Dip switch setting: ON: 0; OFF: 1

left: 4 right: 4
Shows address of IGU02, address range: 1-32.
Communication lamp definition:

RUN SAVE ACCOUNT SLAVE1 SLAVE2 SLAVE3

POWER homebus receiver homebus send RS485+ RS485-

Wiring terminal:

G R U P A
d.o.o.

118

Downloaded from www.Manualslib.com manuals search engine


Part 5: install the software
1. Install database
Firstly install Mysql Database,

G R U P A
d.o.o.
Next:

119

Downloaded from www.Manualslib.com manuals search engine


Next:

Next:

G R U P A
d.o.o.
Next:

120

Downloaded from www.Manualslib.com manuals search engine


Then click "Finish", installation succeeds.

Note: No need to change the default setting, just click "next" all the way.
2. ODBC installation and setting
ODBC installation:

G R U P A
d.o.o.
Continue

121

Downloaded from www.Manualslib.com manuals search engine


Select mysql, then click "ok"

Then click "close"

G R U P A
ODBC setting:

d.o.o.
Open ODBC database in the route: control panel/manage tool

122

Downloaded from www.Manualslib.com manuals search engine


Select "system DNS"

G R U P A
Click and add

d.o.o.

123

Downloaded from www.Manualslib.com manuals search engine


Select "mysql", then click "finish"
Input according to the below information in the page:

Password is 1

G R U P A
d.o.o.

Click OK.

124

Downloaded from www.Manualslib.com manuals search engine


3. Software installation

G R U P A
Next

d.o.o.

125

Downloaded from www.Manualslib.com manuals search engine


Next

G R U P A
d.o.o.

Click finish.

Software startup:
1. Startup of database
In the folder C:\mysql\bin, look for winmysqladmin.exe and click twice to open it.

126

Downloaded from www.Manualslib.com manuals search engine


Note: Install mysql for the first time, open it, then you need enter username and password, username
is "sa", password is "a".
Problems in installation:
If problem occurs, the system needs to be re-installed. Firstly stop "mysqld-nt.exe".

G R U P A
d.o.o.

127

Downloaded from www.Manualslib.com manuals search engine


Search the file “my.ini” in disk C, and then cancel it.
If it cannot be found, modify the search item, as the following:

Choose the three items (search system folder, search hidden file and folder, search sub-folder) as the
figure.

G R U P A
Stop "mysql" in "service" in the manage tool folder, if it is already stopped, you need not change it.

d.o.o.

128

Downloaded from www.Manualslib.com manuals search engine


G R U P A
d.o.o.

129

Downloaded from www.Manualslib.com manuals search engine