MRV Ii: Design Manual R410A Heat Pump 50Hz
MRV Ii: Design Manual R410A Heat Pump 50Hz
Design Manual
R410A HEAT PUMP 50HZ
AV08NMVERA AV28NMVERA
AV10NMVERA AV30NMVERA
AV12NMVERA AV32NMVERA
AV14NMVERA AV34NMVERA
AV16NMVERA AV36NMVERA
AV18NMVERA AV38NMVERA
AV20NMVERA AV40NMVERA
AV22NMVERA AV42NMVERA
AV24NMVERA AV44NMVERA
AV26NMVERA AV46NMVERA
AV28NMVERA AV48NMVERA
G R U P A
d.o.o.
Type Model
4-way cassette type
PB-700IB AB*MCERA 092 122 162
4-way cassette type 282 302
AB*MCERA 182 242 382 482
PB-950JB
4-way cassette type
AB*MEERA 182 242 282 302 382 482
PB-950IB
Low ESP duct type AD*MLERA 072 092 122 162 182 242
Med ESP duct type AD*MMERA 182 242 282 302 382 482
High ESP duct type AD*MHERA 182 242 282 302 382 482 722 962
Convertible type AC*MC/FERA 092 122 162 182 242 382 482
Wall mounted type AS*MC/AERA 072 092 122 162 182 242
G R U P A
Outdoor units
Type Model
d.o.o.
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 28HP 30HP
AV*MVERA
08N 10N 12N 14N 16N 18N 20N 22N 24N 28N 30N
Type Model
03
AV18/20NMVERA AV22/24/26NMVERA
Outdoor
AV28/30/32NMVERA AV34/36NMVERA
G R U P A
AV38/40/42NMVERA AV44/46/48NMVERA
d.o.o.
04
AD242MMERA
AD122MLERA AD282MMERA
AD162MLERA
AD182MLERA AD302MMERA
AD242MLERA AD382MMERA
AD482MMERA
G R U P A
HIGH ESP DUCT TYPE WALL MOUNTED TYPE
AD182MHERA
AS072MCERA
AD242MHERA AS092MCERA
AD282MHERA AS122MCERA
d.o.o.
AD302MHERA
AD382MHERA AS162MCERA
AD482MHERA AS182MCERA
AS242MAERA
AD722MHERA
AD962MHERA
05
280 10 0 1 0 0 0 1
335 12 0 0 1 0 0 1
400 14 0 0 0 1 0 1
450 16 0 0 0 0 1 1
506 18 1 1 0 0 0 2
560 20 0 2 0 0 0 2
615 22 0 1 1 0 0 2
680 24 0 1 0 1 0 2
730 26 0 1 0 0 1 2
800 28 0 0 0 2 0 2
850 30 0 0 0 1 1 2
900 32 0 0 0 0 2 2
G R U P A
960 34 0 2 0 1 0 3
1010 36 0 2 0 0 1 3
1080 38 0 1 0 2 0 3
d.o.o.
1130 40 0 1 0 1 1 3
1180 42 0 1 0 0 2 3
1235 44 0 0 1 0 2 3
1300 46 0 0 0 1 2 3
1350 48 0 0 0 0 3 3
06
G R U P A
A stands for fixed frequency type,
H stands for inverter type,
R stands for DC inverter and R410A type
Cooling or heating, and refrigerant: E stands for heat
d.o.o.
pump type, refrigerant is R410a
Appearance character
Product series: M stands for MRV II R410A
Applicable voltage:
2 stands for 220~230V/50Hz,
N stand for 380~400VAC/50Hz
Capacity,09=9000BTU/h, 12=12000BTU/h
Product type :
"B" stands for cassette type,
"C" stands for convertible type,
"D" stands for duct type,
"S" stands for wall mounted type,
"F" stands for console type
Haier Air Conditioner
07
W: with humidifier
N: without humidifier
H: with healthy module
N: without healthy module
A: 220~240V, 50Hz
B: 220~240V, 60Hz
C: 380V, 50Hz
D: 380V, 60Hz
E: 110V, 50Hz
F: 110V, 60Hz
Air flow: m3/h
Heat reclaimed ventilation unit
4. Capacity range
outdoor capacity 8HP 10HP 12HP 14HP 16HP Indoor20HP
18HP unit 22HP
total indoor 113~ 140~ 168~ 200~ 226~ 253~ 280~ 308~
capacity range 294 364 436 520 588 658 728 800
(*100W)
G R U P A
outdoor capacity 24HP 26HP 28HP 30HP 32HP Indoor36HP
34HP unit 38HP
d.o.o.
quantity
total indoor 340~ 365~ 400~ 425~ 450~ 480~ 505~ 540~
capacity range 884 949 1040 1105 1170 1248 1313 1404
(*100W)
08
G R U P A
d.o.o.
5.4 Intelligent electric control, with heat expelling fan to reduce the electric control box
temperature and keep the electric safe.
09
12\14\16HP subcooler
8\10HP subcooler
G R U P A
up to 64 sets of indoor
d.o.o.
10
HEATING COOLING
G R U P A
14HP COP 3.85 EER 3.25
d.o.o.
Cooling operation condition: indoor temp is 270CDB/190CWB; outdoor temp is 350CDB/240CWB;
Heating operation condition: indoor temp is 200DB, outdoor temp is 70CDB/60CWB.
b. Approved for RoHS certificate
All the parts in the unit have been approved for RoHS certificate. The parts are in conformance
with RoHS directive. Thus Haier MRVII will be environmental for human and nature.
The directive is to approximate the laws of the Member States on the restrictions of the use of
hazardous substances in electrical and electronics equipment and to contribute to the protection of
human health and the environmentally sound recovery and disposal of waste electrical and
electronic equipment.
c. Less chance of refrigerant leakage
The connection type of outdoor gas stop valve is brazed, therefore it is not easy to leak any
refrigerant.
11
G R U P A
d.o.o.
12
Large LCD is easy to read the data; set the temp. at interval of 10C.
G R U P A
controller master controller slave controller group control method
d.o.o.
Infrared remote controller YR-H71, YR-H65
Used to set the MODE, FAN, SWING, HEALTH, TEMP., TIMER etc.
Large LCD is easy to read the data; set the temp. at 10C.
Electric heating button can realize the electric heating function if the unit is
with this function.
13
Group controller: Realize to control 16 indoor units ON/OFF synchronously. Set indoor
units at the same mode.
Note: When the indoor unit is in group control, it CAN NOT be
controlled by its individual controller (wired cotroller or infrared
controller).
Indoor unit
YR-E12
Power
Group controller
G R U P A
d.o.o.
14
Indoor unit
Wired controller
Unit
Unit Unit (group control)
No. 1
Connection Outdoor unit No. 2 No. 3
board (master unit)
Indoor unit
Unit
Unit Unit
No. 4
Connection Outdoor unit No. 5 No. 6
board (master unit)
Indoor unit
Unit Unit Unit
G R U P A
Connection Outdoor unit No. 7 No. 8 No. 9
board (master unit)
Indoor unit
Unit
Unit Unit
d.o.o.
No. 62
No. 63 No. 64
Central controller(1:64)
15
G R U P A
Controller Wired controller/ wireless controller (optional)
Gas piping(mm) 9.52 12.7 12.7 12.7
Piping
dimension Liquid piping(mm) 6.35 6.35 6.35 6.35
Drain hose(mm) 32 32 32 32
d.o.o.
Noise level(dB(A)) H/M/L 32/30/29 32/30/29 33/30/29 34/32/30
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
16
G R U P A
Gas piping(mm) 15.88 15.88 15.88 15.88 15.88
Piping
dimension Liquid piping(mm) 9.52 9.52 9.52 9.52 9.52
Drain hose(mm) 32 32 32 32 32
Noise level(dB(A)) H/M/L 35/34/31 37/35/31 37/35/31 37/35/31 42/39/35
d.o.o.
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
17
G R U P A
Gas piping(mm) 12.7 15.88 15.88 15.88
Piping
dimension Liquid piping(mm) 6.35 9.52 9.52 9.52
Drain hose(mm) 32 32 32 32
Noise level(dB(A)) H/M/L 34/32/30 35/34/31 37/35/31 37/35/31
d.o.o.
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
18
G R U P A
Gas piping(mm) 15.88 15.88
Piping
dimension Liquid piping(mm) 9.52 9.52
Drain hose(mm) 32 32
Noise level(dB(A)) H/M/L 37/35/31 44/40/36
d.o.o.
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
19
G R U P A
Expansion mode
Controller Wired controller/ wireless controller (optional)
Gas piping(mm) 9.52 9.52 12.7
Piping 6.35 6.35 6.35
dimension Liquid piping(mm)
Drain hose(mm) 24/20 24/20 24/20
d.o.o.
Noise level(dB(A)) H/M/L 35/32/30 35/32/30 35/32/30
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
20
G R U P A
Controller Wired controller/ wireless controller (optional)
Gas piping(mm) 12.7 12.7 15.88
Piping 9.52
dimension Liquid piping(mm) 6.35 6.35
Drain hose(mm) 24/20 24/20 24/20
d.o.o.
Noise level(dB(A)) H/M/L 36/33/31 36/33/31 39/37/35
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
21
G R U P A
Drain hose(mm) 32 32
Noise level(dB(A)) H/M/L 43/37/35 43/37/35
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
d.o.o.
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
22
G R U P A
Noise level(dB(A)) H/M/L 43/37/35 44/40/36
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
d.o.o.
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
23
G R U P A
Noise level(dB(A)) H/L 42/40 42/40 42/40
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
d.o.o.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
24
G R U P A
Noise level(dB(A)) H/L 45/40 45/40 45/40
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
d.o.o.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
25
G R U P A
Drain hose(mm) 32 32
Noise level(dB(A)) H/L 54/49 54/49
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
d.o.o.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
26
G R U P A
20
Noise level(dB(A)) H/M/L 48/46/44 48/46/44 48/46/44 48/46/44
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
d.o.o.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
27
G R U P A
Drain hose(mm) 20 25
Noise level(dB(A)) H/M/L 51/49/47 53/51/49 53/51/49
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
d.o.o.
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
28
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
29
G R U P A
Rmkgl_j fc_rgle a_n_agrw.O[/ 84; 948 :46 <46
Lc_rgle a_n_agrw _r jmu rckn4.O[/ 846 84; 948 :4;
Ijcarpg3 Tmucp qmspac 7TL2 886y896Z2 ;6Lx
a_j
af_p_3 Sncp_rgle asppclr.E/ 64:; 64:; 64:; 64:;
arcpgq3 Tmucp amlqsknrgml.O[/
d.o.o.
rgaq 646> 646> 646> 646>
J_l rwnc _lb Urw apmqq08 apmqq08 apmqq08 apmqq08
J_l Ynncp kmrmp msrnsr.O[/ 64686 64686 64686 64686
af_p_3 64677 64677
arcpgq3 Pmucp kmrmp msrnsr.O[/ 64677 64677
rgaq Wr_lb_pb _gpdjmu.k95f/ :<6 :<6 ;86 ;>6
Wr_lb_pb qr_rga npcqqspc.T_/ 6 6 6 6
Q_v4 qr_rga npcqqspc.T_/ 6 6 6 6
Ivrcpgmp bgkclqgmlq.kk/ =8608;;0<:6 =8608;;0<:6 =8608;;0<:6 =8608;;0<:6
Wfgnngle bgkclqgmlq.kk/ ==808?80=6: ==808?80=6: ==808?80=6: ==808?80=6:
[cgefr.Oe/ 7=4;586 7=4;586 7=4;586 7=4;586
Gmlrpmjjcp [gpcjcqq amlrpmjjcp
K_q ngngle.kk/ 784= 784= 784= 784=
Tgngle <49; <49;
bgkclqgml Pgosgb ngngle.kk/ <49; <49;
Hp_gl fmqc.kk/ 7<4; 7<4; 7<4; 7<4;
Rmgqc jctcj.bF.E// L5Q5P :959?59< :959?59< :959?59< :>5:<5:8
30
12.2/15.6
Electrical characteristics
8.7/10.5
Operating/Max. consumption(kw) 5.28/6.34 7.36/9.45
Operating/Max. current(A) 9.7/11.3 13.2/15.8
Operating/Max. consumption(kw) 5.89/6.85 7.97/10.2
Power consumption when heating at low temp.(kw) 5.57 6.73
Output power of outdoor motor(KW) 0.7 0.7
Exterior dimensions (mm) 990*750*1750 990*750*1750
Weight (Kg) 235 235
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 10000 10000
Refrigerant (R410A) charge (Kg) 10.0 10.0
Gas piping(mm) 19.05 22.22
Piping dimension
G R U P A
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
oil type MEL32
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
31
14.2/17.0 20.3/24.4
Electrical characteristics
G R U P A
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
oil type MEL32
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
32
23.2/28.1
Electrical characteristics
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
compressor
d.o.o.
HNB71FB-YJHC, Mitsubishi Electric
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
33
24.4/31.2
Operating/Max. consumption(kw) 12.64/15.79 14.72/18.90
Operating/Max. current(A) 22.9/27.1 26.4/31.6
Operating/Max. consumption(kw) 13.86/17.05 15.94/20.4
Power consumption when heating at low temp.(kw) 12.3 13.46
Output power of outdoor motor(KW) 1.4 1.4
Exterior dimensions (mm) 990*750*1750 990*750*1750
+990*750*1750 +990*750*1750
Weight (Kg) 470 470
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 20000 20000
Refrigerant (R410A) charge (Kg) 20 20
28.58
Piping dimension
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
34
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
35
35.4/43.7 40.6/48.8
Operating/Max. consumption(kw) 21.42/26.45 24.62/29.6
Operating/Max. current(A) 34.4/41.4 38.6/46.4
Operating/Max. consumption(kw) 20.79/25.58 23.38/28.2
Power consumption when heating at low temp.(kw) 17.01 19.3
Output power of outdoor motor(KW) 1.8 2.2
Exterior dimensions (mm) 990*750*1750 1390*750*1750
+1390*750*1750 +1390*750*1750
Weight (Kg) 535 550
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 22000 24000
Refrigerant (R410A) charge (Kg) 26 24
31.8
Piping dimension
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
36
46.4/56.2
Operating/Max. consumption(kw) 26.37/31.8 28.12/34
Operating/Max. current(A) 40.5/48.8 42.4/51.2
Operating/Max. consumption(kw) 24.51/29.48 25.64/30.76
Power consumption when heating at low temp.(kw) 19.93 20.56
Output power of outdoor motor(KW) 2.2 2.2
Exterior dimensions (mm) 1390*750*1750 1390*750*1750
+1390*750*1750 +1390*750*1750
Weight (Kg) 575 600
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 24000 24000
Refrigerant (R410A) charge (Kg) 28 32
31.8
Piping dimension
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
oil type MEL32
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
37
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
38
55.7/68.1
Operating/Max. consumption(kw) 31.98/39.05 33.73/41.25
Operating/Max. current(A) 51.8/62.2 53.7/64.6
Operating/Max. consumption(kw) 31.35/38.4 32.48/39.68
Power consumption when heating at low temp.(kw) 24.75 26.66
Output power of outdoor motor(KW) 2.9 2.9
Exterior dimensions (mm) 990*750*1750 990*750*1750
+(1390*750*1750)*2 +(1390*750*1750)*2
Weight (Kg) 785 810
Exterior colour ivory ivory
Compressor type scroll scroll
Outdoor airflow (m3/h) 34000 34000
Refrigerant (R410A) charge (Kg) 34 38
Piping dimension
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
oil type MEL32
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
39
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
40
Operating/Max. current(A)
Electrical characteristics
66.7/80.6 69.6/84.3
Operating/Max. consumption(kw) 40.43/48.8 42.18/51
Operating/Max. current(A) 61.7/74.4 63.6/76.8
Operating/Max. consumption(kw) 37.33/44.86 38.46/46.14
Power consumption when heating at low temp.(kw) 30.21 30.84
Output power of outdoor motor(KW) 3.3 3.3
Exterior dimensions (mm) (1390*750*1750)*3 (1390*750*1750)*3
38.1 38.1
Liquid piping(mm) 19.05 19.05
Equipoise/Oil equalization piping(mm) 9.52
Noise level(dB(A)) 64 64
Connection type of gas stop valve is brazed, while those of liquid stop valve and oil stop valve are flared.
G R U P A
Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB
Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time
Analyser calibrated sound intensity meter. It is a sound pressure noise level.
d.o.o.
compressor HNB71FB-YJHC, Mitsubishi Electric
oil charging amount 3 litre with compressor, additional charging 1 litre to gas-liquid segregator
41
150mm
60mm
42
95
180
535mm (between suspension poles)
VIEW A VIEW A
145 100 80
d.o.o. G R U P A
AB182MEERA, AB242MEERA, AB282MEERA
(mm)
860-890 155
680
35
air discharge hole
106
103
345
860-890 (ceiling hole)
680 (hang position)
85
30
85
57
57
35
180
950
G R U P A
260
160
135
d.o.o.
260
270
315
950
840
80
140
295
200
180
20 30
240 50
43
860-890 155
680
35
air discharge hole
106
103
860-890 (ceiling hole)
680 (hang position)
345
85
30
85
57
57
35
220
950
310
G R U P A
160
135
d.o.o.
260
270
315
950
840
80
140
295
200
220
30
290 50
44
(mm)
860-890 155
680
35
air discharge hole
106
103
345
860-890 (ceiling hole)
680 (hang position)
85
30
85
57
57
35
180
950
G R U P A
260
160
135
d.o.o.
260
270
315
950
840
80
140
295
200
180
20 30
240 50
45
(mm)
860-890 155
680
35
air discharge hole
106
103
860-890 (ceiling hole)
680 (hang position)
345
85
30
85
57
57
35
220
950
G R U P A
310
160
135
d.o.o.
260
270
315
950
840
80
140
295
200
220
30
290 50
46
Model a b c d e f g h i J
DG7>{899POHUD
Hvaporators of DG7>3 DG7@ are 94row typeB evaporator of DG89 is :4row type5
;7
877
89<
G R U P A
9>7
8:7
;>? d.o.o.
997
47
;7
877
9>7
89<
8:7
G R U P A
@;7
d.o.o.
997
48
(mm)
170
drainage pipe
32
A-A
265
liquid pipe
200
890
150
gas pipe
235
100
165
120
200
130
A
300 635
210 545
70
G R U P A
80
270 305
30
20
85
d.o.o.
10
R100
986
960
890
260
275
35
49
(mm)
240
drainage pipe
32
265
A-A
liquid pipe
1280
150
235
gas pipe
100
165
120
A
350
85
655
85
545
G R U P A
d.o.o.
1406
1370
R100
260
275
105 210
70
35
260 68 275
275
50
(mm)
250
30
210
32
290
60
30
750
830
800
345 145
365 80
100
G R U P A
15
130
120
d.o.o.
205
960
185
840
170
51
(mm)
250
45
32
210 290
30
1105
60
830
365 800
345 145
80
100
G R U P A
15
250
d.o.o.
270
185
1200
170
1320
52
830
18 794 18
25
60
M5x20pcs Air inlet
138
13
250
1570
1690
1640
13 200 13
138
13
65
163 6x200=1200 163
35 1500 35
100
80
25
95
60
Control Box
M10x4pcs
138
250
25
13
25
G R U P A
205
310
360
A
49
245
30
106
138
77
13
185 170 45 200
530 13 13
d.o.o.
DRAIN PIPE VP25 138 6X200=1200 138
60 1450 60
Installation dimension
Over 900 Over 900 (900x1730) Over 100 Over 300
35
Check Hole
(600x600)
900
Ceiling
35
100 60
Over 200
over 400
53
(mm)
240
100 200 back plate bottom plate
880
900
990
100 100
100
100
10
20
655
30
30
199
G R U P A
100 30
100
d.o.o.
25
right side
620
605
600
30
35
35
40
54
1580
700
598
495
285
36
55 114 240
90
25
G R U P A
47 47 47
150
95
40
60
d.o.o.
47
47
50 200 224 155
47 47
90
570
640
30 200
130
55
Haie
r
b
model a b c
AS072/092/122MCERA 795
265 182
AS162/182MCERA 928
c
60
50
60
50
55 200
45
200 55
60 70
bottom side
right side left side
AS242MAERA
G R U P A
d.o.o.
56
Outdoor unit
Single unit
Note:
A There should be no obstacles in 2000mm above the top of outdoor unit;
B Obstacles around outdoor should be less than 800mm to the bottom of unit.
8, 10HP:
4-15*20
990
Gas pipe
100 80
Liquid pipe
Oil pipe
65 55 125
G R U P A
755
630
750
790
125
168
143
138
62
173 92 100 80
700 700
d.o.o.
90
300mm
1550mm
1750
More than
500mm
100mm
Top side
700
Oil pipe
Liquid pipe
Gas pipe
245
190 235
88
2-60*150 500
57
80
over 300
over 1550
790
750
630
755
over 500
over 100 over 100
100
80
front
700 700
90
1560
1750
700
500
G R U P A
88
1390
d.o.o.
58
18,20HP:
over 300
over 1550
750
790
over 200 over 100
over 500
over 100
front
G R U P A
700
88
over 2180
d.o.o.
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall
can be increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.
59
over 300
over 1550
750
790
over 200 over 100
over 500
over 100
700 700
front
over 2780
90
1750
1560
700
88
over 2580
G R U P A
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall
d.o.o.
can be increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.
60
over 200
over 300
1390 1390
over 1550
750
790
over 500
over 100 over 100
over 200
front
over 3180
700 700
90
1560
1750
700
88
over 2980
G R U P A
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall
d.o.o.
can be increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.
61
over 100
over 200
over 3970
front
over 200
over 100
over 3770
790
750
1390
700
over 200
G R U P A
90 700 88
990
700
1560
1750
over 200
d.o.o.
990
700
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall can be
increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.
62
over 100
over 200
over 4370
over 200
front
over 100
790
750
over 4170
1390
700
over 200
G R U P A
1390
700
90 700 88
1560
1750
over 200
d.o.o.
990
700
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall can be
increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.
63
over 100
over 200
over 4770
front
over 200
over 100
over 300 over 500
790
750
over 4570
1390
700
over 200
G R U P A
1390
700
90 700 88
1560
over 200
d.o.o.
1750
1390
700
Note:
A. There should be no obstacles in 2000mm above the top of outdoor unit;
B. Obstacles around outdoor should be less than 800mm to the bottom of unit.
C. The distance between two outdoor units in the same line and the distance from unit to the wall can be
increased for easy maintenance if there is enough space.
D. The sequence and the position of every outdoor can be at will.
64
Front side
G R U P A
d.o.o.
Less than
800mm
65
More than
300mm
More than
Front side
600mm
Front side
More than
300mm
G R U P A
d.o.o.
Less than
800mm
66
Front side
600mm
Front side
More than
600mm
More than
500mm
Front side
G R U P A
d.o.o.
Less than
800mm
67
piping
500
piping More than
500mm
air outlet
Above 600mm Above 300mm
G R U P A
HD
Front side
d.o.o.
H Above 1000mm
Vs
68
HD
H
Front side
500-1000mm
h
G R U P A
d.o.o.
69
Gas
Gas
Pipe
Pipe
Gas
Pipe
Pipe
Pipe
Pipe
Side
Liquid
Liquid
Liquid
ID9.7 ID28.8
ID28.8
ID9.7 ID6.5 ID16.1
ID12.9
ID12.9 ID9.7
ID25.6 ID19.3
ID25.6
ID16.1
ID22.4
OD19.05 OD22.2
OD22.2
ID6.5
ID25.4
ID16.1
ID12.9
ID19.3
ID22.4
ID16.1
ID12.9
ID19.3
ID22.4
ID6.5
ID9.7
ID12.9
OD22.22*1.5
ID9.7
OD22.22*1.5
ID6.5
OD22.22
ID9.7
ID12.9
ID16.1
238
388
238
OD19.05
323
323
ID12.9
ID16.1
OD19.05
384
OD12.7
OD25.4 OD25.4
OD25.4
ID12.9
ID25.6
ID25.6
ID9.7 OD25.4
ID16.1
ID28.8
ID28.8 ID22.4
ID19.3
ID16.1
OD12.7
OD28.58
OD6.35
70
OD28.58
OD6.35 OD6.35
ID25.6
ID25.6
55
100
55
ID22.4
55
ID22.4
180
180
ID19.3
ID19.3
ID9.7
ID9.7
ID9.7 ID16.1 ID16.1
Branch pipe(unit: mm, ID: inner diameter; OD: outer diameter)
ID9.7
ID12.9
ID12.9
OD6.35
OD15.88
ID12.9
55
104
ID9.7
OD12.7
OD12.7
ID9.7
100
Connection of manifold pipe
OD15.88
100
ID12.9
104
ID9.7
ID9.7 ID9.7
d.o.o. G R U P A
FQG-B1350A
ID38.3
ID9.7
ID12.9
ID32
ID16.1
ID19.3
OD31.75
ID28.8
ID22.4
OD28.6
366
ID6.5
ID9.7
ID12.9
ID16.1
405
OD19.05
OD31.75
OD25.4
ID32
ID19.3
OD28.58
OD6.35
ID25.6
ID22.4
71
180
55
ID19.3
ID16.1
ID12.9
ID9.7 OD31.75
ID28.8
140
ID25.6
ID22.4
OD22.22
ID19.3
ID16.1
138
Connection of manifold pipe
ID12.9
OD12.7
100
ID9.7
d.o.o. G R U P A
HZG-30/A HZG-20/A
side
side
side
Gas
side
Gas
Liquid
Liquid
E
D
C
B
A
Model Side Mark
+0.25 +0.25 +0.25
ID38.1
10
10
+0.1 ID15.88
+0.1 +0.2 ID15.88
+0.1 +0.2
ID28.6
+0.05 +0.05
ID28.6
+0.25 +0.05
ID31.8+0.2 +0.25 +0.05
31.8+0.2
30
ID19.05
+0.1 +0.2 ID19.05
+0.1 +0.2
40
40
+0.05
ID38.1 ID38.1
+0.05
550
640
465
640
465
Double
424
424
667
Manifold pipe
+0.2 +0.2
+0.25 +0.25 +0.05
ID28.6 +0.25 +0.25
ID28.6
+0.05
15
15
+0.1
ID19.05 +0.1
ID19.05 +0.1
ID19.05 ID19.05
+0.1
+0.2 +0.2
ID28.6
40
40
40
40
ID28.6
+0.05 +0.05
+0.2 +0.2
12
+0.25
ID15.88 +0.25 ID25.4
+0.05 +0.25 +0.25
ID15.88 ID25.4
+0.05
+0.1 ID15.88
+0.1 ID15.88
+0.1 +0.1
40
40
40
40
+0.05
ID28.6+0.2 +0.2 +0.2
+0.25 +0.05
ID22.22 ID12.7+0.25 ID22.22
+0.05
ID12.7+0.25
+0.1 +0.1
ID12.7 +0.1 +0.1
ID12.7+0.25
15
40
40
40
40
+0.2 +0.2
+0.25 ID19.1 +0.05 +0.25 +0.25 +0.05
ID19.1
ID9.52 ID9.52
unit:mm, ID: inner diameter; OD: outer diameter
10
10
10
10
132
189 94.5 94.5
Gather pipe is used for combination of outdoor unit
72
material
Insulation
HZG-20/A(for 2 basic modules); HZG-30/A(for 3 basic modules)
side
side
Gas
side
Gas
Liquid
Side
¢
¢
¢
¢
Mark
Note: Cut off the pipe from its middle when
200 200
120
12 40 40 12 40 40
using
120
ID19.1
ID19.1
ID25.4
ID25.4
14
+0.2
+0.2
ID22.22
ID22.22
+0.2
+0.2
+0.05
+0.05
+0.05
+0.05
+0.2
14
+0.2
+0.05
+0.05
+0.2
ID38.1
+0.05 +0.2
ID35.1
+0.05
Connection of manifold pipe
Double
Double
d.o.o. G R U P A
Controller dimensions:
TEMP
ON
132mm
HEALTH
124mm
SWING
OFF FAN
C
SET RECOVERY
CHECK
18mm
126mm
25mm
48mm
65 92
180
49
R
136
MONITOR GROUP RUN CENTRAL SLAVE STANDBY
SET TOTAL UNIT STOP LOCK TIMER FILTER
G R U P A
HEAT MID
d.o.o.
(mm)
central controller ICR01
IGU04
73
550
500
450
air flow (m3/h)
200
150
0 10 20
G R U P A
550
500
d.o.o.
450
air flow (m3/h)
200
150
0 10 20
static pressure (Pa)
96
74
650
600 super
550 high
air flow (m3/h)
high
500
med
450
400 low
350
300
250
0 10 20
static pressure (Pa)
G R U P A
1000
950
900
air flow (m3/h)
d.o.o.
850 super high
high
800
med
750 low
700
650
600
0 10 20
static pressure (Pa)
97
75
1400
1350
1300
air flow (m3/h)
G R U P A
1400
1350
1300
air flow (m3/h)
d.o.o.
1250 super high
high
1200 med
1150 low
1100
1050
1000
0 10 20
static pressure (Pa)
98
76
1400
1300
air flow(m3/h)
900
800
40 50 60 70 80 90 100
static pressure(Pa)
G R U P A
1400
1300
air flow(m3/h)
d.o.o.
high
1100
med
1000 low
900
800
40 50 60 70 80 90 100
static pressure(Pa)
77
Downloaded from www.Manualslib.com manuals search engine
AD282MMERA air flow and static pressure curves
1700
1600
air flow(m3/h)
1200
1100
40 50 60 70 80 90 100
static pressure(Pa)
2300
G R U P A
2200
air flow(m3/h)
d.o.o.
2000
med
1900 low
1800
1700
40 50 60 70 80 90 100
static pressure(Pa)
78
Downloaded from www.Manualslib.com manuals search engine
AD382MMERA air flow and static pressure curves
2300
2200
air flow(m3/h)
1800
1700
40 50 60 70 80 90 100
static pressure(Pa)
2300
G R U P A
2200
air flow(m3/h)
d.o.o.
high
2000
med
1900 low
1800
1700
40 50 60 70 80 90 100
static pressure(Pa)
79
Downloaded from www.Manualslib.com manuals search engine
MRV II Commercial Air Conditioning
1400
1200
air flow (m3/h)
1000
super high
800 high
600 med
low
400
200
0
80 100 120 140 160 180 200
G R U P A
1400
1200
air flow (m3/h)
d.o.o.
800 high
600 med
low
400
200
0
80 100 120 140 160 180 200
141
80
1400
1200
air flow (m3/h)
1000
super high
800 high
600 med
low
400
200
0
80 100 120 140 160 180 200
G R U P A
2000
1800
air flow (m3/h)
d.o.o.
high
1400
med
1200 low
1000
800
80 100 120 140 160 180 200
static pressure (Pa)
81
2000
1800
air flow (m 3/h)
1000
800
80 100 120 140 160 180 200
static pressure (Pa)
2500
G R U P A
2300
air flow (m3/h)
d.o.o.
1900
med
1700 low
1500
1300
80 100 120 140 160 180 200
static pressure (Pa)
82
8 7
6 5
4
3
150
External static pressure Pa
3 8
7
100
6
50
G R U P A
0
55 60 65 70 75 80 8586
3
Upper limit air flow (m /min) lower limit
d.o.o.
83
A. Capacity compensation coefficient of indoor B. Capacity compensation coefficient of outdoor air dry-bulb
air wet-bulb temperature condition temperature condition
1.2 1.2
1.1 1.1
1.0
1.0
0.9
0.9
-5 0 5 10 15 20 25 30 35 40 43
0.8
15 20 24 Outdoor air dry-bulb temperature
Indoor air wet-bulb temperature
100
1.1
80
1.0
60
0.9 40
80 90 100 110 120
capacity
airflow variation rate(%) 20 Standard
G R U P A
d.o.o.
84
1.00 1.00
0.95 0.95
0.90 0.90
liquid pipe:φ15.88
0.85 liquid pipe:φ12.7 0.85 gas pipe:φ28.58
liquid pipe:φ15.88
gas pipe:φ28.58 gas pipe:φ31.8
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)
AV20NMVERA AV22NMVERA
G R U P A
cooling compensation factor
cooling compensation factor
d.o.o.
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)
gas pipe:φ31.8
cooling compensation factor
1.00 1.00
0.95 0.95
0.90 0.90
0.85 liquid pipe:φ19.05 liquid pipe:φ19.05
0.85 liquid pipe:φ15.88
gas pipe:φ31.8
gas pipe:φ28.58 gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m)
pipe length of single way (m)
AV28NMVERA AV30NMVERA
cooling compensation factor
cooling compensation factor
85
0.90 0.90
liquid pipe:φ19.05
0.85 liquid pipe:φ19.05 liquid pipe:φ19.05 0.85 gas pipe:φ31.8
gas pipe:φ31.8 gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)
AV36NMVERA AV38NMVERA
cooling compensation factor
AV44NMVERA AV46NMVERA
G R U P A
cooling compensation factor
1.00
cooling compensation factor
d.o.o.
gas pipe:φ38.1
0.80 0.80
0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 160 180
pipe length of single way (m) pipe length of single way (m)
AV48NMVERA
cooling compensation factor
1.00
0.95
0.90
liquid pipe:φ19.05
0.85 gas pipe:φ38.1
liquid pipe:φ22.22
gas pipe:φ38.1
0.80
0 20 40 60 80 100 120 140 160 180
pipe length of single way (m)
Note:
1. The refrigerant pipe should be thickened when the single way length is over 90m.
2. When in cooling mode, outdoor is lower than indoor; or when in heating mode, outdoor is higher
than indoor, the compensation factor should be decreased the below value from the above figure.
vertical height drop between indoor 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
and outdoor
adjustment factor 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024 0.027 0.030
86
A. Capacity modification value B. Capacity modification value under outdoor air wet-bulb C. Capacity modification value
temperature condition under airflow variation rate of
under indoor air dry-bulb 1.2
temperature condition indoor unit group
1.1
1.2
1.2
Capacity modification coefficient
1.0
1.0
0.8
0.6 0.9
0.4
capacity
Standard
G R U P A
0.2
0.8
-15 -10 -5 0 5 10
0 20 40 60 80 100 120 140
Outdoor air wet-bulb temperature
Total capacity of indoor unit group(%)
F. Heating compensation factor at different pipe length
d.o.o.
for all models
1.00
heating compensation factor
0.98
0.96
0.94
0.92
0.90
0 20 40 60 80 100 120 140 160 180
pipe length of single way (m)
87
(Cooling)
45 (Heating)
40
35 15
Consecutive operation
30 10
Outdoor air WB (¡ )
Outdoor air DB (¡ )
Consecutive operation
25
5
20
0
15
-5
10
-10
5
0 -15
-5 -20
5 10 15 20 25 30
-10
10 15 20 25 30
Indoor air WB (¡ ) Indoor air DB(¡ )
G R U P A
d.o.o.
88
Indoor
G R U P A
Controller
d.o.o.
89
Branch pipe
Indoor
Controller
G R U P A
d.o.o.
Note: 1. The indoor units in the system can be added or reduced at your will on the
condtion that the indoor capacity is in the allowable range
2. When the indoor total capacity is more than outdoor nominal capacity, the capacity
of running indoor will be relatively reduced. The capacity of running indoor will not
exceed outdoor capacity.
90
G R U P A
d.o.o.
91
AV12NMVERA 25.4
Flared Flared
AV14NMVERA 25.4 Brazing 12.7 9.52
joint joint
AV16NMVERA 28.58
B. Indoor unit
Model Gas pipe side Liquid pipe side
Capacity Connecting Connecting
Diameter method Diameter method
07 9.52 6.35
09 9.52 6.35
12 12.7 6.35
14 12.7 6.35 Flared joint
Flared joint
16 12.7 6.35
18 12.7 6.35
24 15.88 9.52
28 15.88 9.52
32 15.88 9.52
38 15.88 9.52
15.88 9.52
G R U P A
48
d.o.o.
40~50
12.7 1.0
15.88 1.0 90~120
19.05 1.0 100~140
25.4 1.2 ---
Not less than 28.58 More than 1.4 ---
92
G R U P A
d.o.o.
93
outdoor1
G R U P A
outdoor2 outdoor3
d.o.o.
3 1st gather pipe
2st gather pipe
Gas/liquid pipe: L1<10m, L2+L3<10m
Oil equalization pipe: L5+L6<10m
height difference between outdoors: h<5m
94
outdoor2 outdoor3
outdoor1
outdoor3
outdoor2
G R U P A
d.o.o.
Installation at high difference:
outdoor1
outdoor2 outdoor3
95
outdoor1
outdoor2 outdoor3
G R U P A
outdoor1
Below is forbidden (compressor oil will flow into the lowest outdoor).
d.o.o.
outdoor2 outdoor3
outdoor1
96
outdoor1
when the distance between outdoors is over
2m, the oil trap must be set (upright projecting
pipe, 200mm high)
max. drop:5m
outdoor is uppper,max. drop is 50m
outdoor2 outdoor3
L2
L4
below 2m below 2m
L1
L3 L5
over 200mm
over 200mm
L1<10m L8
L6 L10
L2+L3<10m
max. drop:15m
L7+L14+L13 <40m L11
L9
L14 L15
97
e e e
d
c
b
a a
the first branch
a a
a. Pipe “a” diameter (between indoor and branch pipe) (depends on indoor pipe, for wall
mounted unit, please refer to its specification)
Indoor(×100W) Gas pipe Liquid pipe
22~28 φ9.52 φ6.35
36~56 φ12.7 φ6.35
71~140 φ15.88 φ9.52
G R U P A
14.0KW《<16.8KW Φ15.88 Φ9.52
16.8KW《X<22.4KW Φ19.05 Φ9.52
22.4KW《X<33.0KW Φ22.22 Φ9.52
33.0KW《X<47.0KW Φ12.7
Φ28.58
d.o.o.
47.0KW《X<71.0KW Φ15.88
71.0KW《X<101.0KW Φ31.88
Φ19.05
》101.0KW Φ38.1
When the later indoor capacity is less than 14.0KW, the specification of pipe b should refer
to the data in table a.
c. Pipe “c” diameter (main pipe, between outdoor gather pipe and the first branch pipe)
Outdoor Main pipe Enlarged main pipe
capacity Gas pipe Liquid pipe Gas pipe Liquid pipe
22.6KW φ19.05 φ9.52 φ22.2 φ12.7
28.0KW φ22.2 φ9.52 φ25.4 φ12.7
33.5KW φ25.4 φ12.7 φ28.58 φ12.7
40.0KW φ25.4 φ12.7 φ28.58 φ12.7
45.0KW φ28.58 φ12.7 φ31.8 φ12.7
50.6KW φ28.58 φ15.88 φ31.8 φ15.88
56.0KW φ28.58 φ15.88 φ31.8 φ15.88
98
G R U P A
e. Pipe “e” diameter (between outdoor and the gather pipe)
outdoor capacity Gas pipe Liquid pipe Oil equalization pipe
8HP φ19.05
φ9.52
10HP φ22.2
d.o.o.
φ9.52
12, 14 HP φ25.4 φ12.7
16HP φ28.58 φ12.7
99
18~32HP 34~48HP
G R U P A
Note: When the single pipe length is over 90m, the above pipe should be enlarged as the
former information.
d.o.o.
18~32HP 34~48HP
T-shape
oil equalization 3-way pipe oil equalization
pipeφ9.52 pipeφ9.52
100
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
G R U P A
power source: 3PH, 380V, 50Hz power source: 3PH, 380V, 50Hz power source: 3PH, 380V, 50Hz
indoor 1 (wall mounted unit) indoor 2 (wall mounted unit) indoor 3 (non wall mounted unit)
Tw3 1 2 L N Tw3 1 2 L N L
d.o.o.
TW1 TW1 N
power source: 1PH, 220V, 50Hz power source: 1PH, 220V, 50Hz power source: 1PH, 220V, 50Hz
101
P QA B C ABC AB C
P QA B C PQ A B C PQ A B C PQA B C PQA BC
ABC
wired controller
G R U P A
ABC A BC ABC ABC
wired controller wired controller wired controller wired controller
ABC A BC
wired controller wired controller
d.o.o.
Outdoor untis are in parallel through 3 polar wires. The outdoor and all indoor units are in parallel through 2
non-polar wires.
Three wiring methods between wired controller and indoor unit:
A. 1 to multi (group control): one wired controller controls 2~16 indoors, as shown in above figure, indoor
1~indoor 5: indoor 5 is wired control master unit, the others are wired control slave units. Wired controller and
the master indoor (directly connected to wired controller) is connected by 3 polar wires; the other indoors and
the master indoors are connected by 2 polar wires.B. 1 to 1 (one wired controller controls one indoor): as
shown in above figure, indoor 6~ indoor 19, indoor and wired controller are connected by 3 polar wires.
C. 2 to 1 (two wired controller controls one indoor): as shown in above figure, indoor 20. Either of wired controllers
can be set as master wired controller, and the other is slave wired controller. Master/slave wired controller,
and master/indoor are connected by 3 polar wires.
When indoor is controlled by remote controller, refer to the "wired control master unit/wired control slave
unit/remote control unit table".A, B, C on signal terminal block need not wires and not connect the wired controller.
102
G R U P A
¡·100
¡ 100 and <200 0.5mm2 * (3-core) shielded wire ¡ 400 and <600 2mm2 * (3-core) shielded wire
¡ 200 and <300 0.75mm2 * (3-core) shielded wire
d.o.o.
(4) Control type and the switchover
a) Indoor unit can be controlled by wired controller or remote controller.
b) When installation, the installer must set the unit due to the control type and wiring type.
Switchover between wired control master/slave unit /remote control unit, set when installation:
control type
wired control wired control
socket remote control
master unit slave unit
/dip switch
CN23 short connected disconnected disconnected
CN30 short connected short connected disconnected
SW08-[6] ON ON OFF
signal terminal block A,B,C to wired controller B,C to wired controller A,B,C not to wired controller
103
connecting board
iGU04 outdoor (master unit)
indoor unit
Wired controller
Unit
Unit Unit (group control, 1:16)
No. 1
No. 2 No. 3
indoor unit
Unit
No. 4
Unit Unit
No. 5 No. 6
indoor unit
Unit
No. 7
Unit Unit
No. 8 No. 9
¡£¡£¡£¡£¡£¡£¡£¡£¡£¡£¡£¡£
iGU04 outdoor (master unit)
indoor unit
Unit
G R U P A
No. 62
Unit Unit
No. 63 No. 64
Central controller (64 units)
Can set the central control unit as a group, and the max. 64 units of indoor can be set a group.
d.o.o.
After setting unit, the indoor in one group can be controlled the same operation (when out of factory, one
unit is regarded as one group).
˙ł 1 ˙ł 2 ˙ł 3
central controller
When the central controller connects one outdoor unit, the connecting board IGU04 is unnecessary.
104
5. Electric characteristic
G R U P A
AB282MEERA 1 50 220 198~242 0.69 2.2 45 0.55 100 100
d.o.o.
AB382MEERA 1 50 220 198~242 1.38 4.4 60 1.1 150 150
105
G R U P A
AD482MMERA 1 50 220 198~242 2.42 5.8 100 1.45 200 200
d.o.o.
AD242MHERA 1 50 220 198~242 3.5 8 240 2 280 280
106
G R U P A
AF092MCERA 1 50 220 198~242 0.28 0.88 20 0.22 27 27
107
G R U P A
AV46NMVERA 3 50 380 342-418 94.2 131.7 105 21+23+23 0.75 2
AV48NMVERA 3 50 380 342-418 96.6 135 105 23+23+23 0.75 2
d.o.o.
Symbols: Notes:
MCA: Min. circuit amps. (A) 1. RLA is based on the nominal condition
TOCA: Total over-current amps.(A) 2. Voltage range
MFA: Max. fuse amps of circuit The units are applicable for the electrical systems
breaker where voltage supplied to unit is in the range.
MSC: Max. starting current 3. Maximum allowable voltage unbalance between
RLA: Rated load amps.(A) phases is 2%.
OFM: Outdoor fan motor 4. Power supply uses the circuit breaker
108
To wired controller(A,B,C)
To other
indoor unit
Communication cable
(Shielded wire)
LN PQ
Power cable
To power cable To outdoor unit
G R U P A
O8 O9 O: S T D E F O8 O9 O: S T D E F
d.o.o.
Wo other
outdoor
Wo other unit
outdoor
unit
109
For example:
10 sets of indoor (20HP), 20 sets of indoor (30HP), 30 sets of indoor (40HP), MRV II outdoor. To realize
G R U P A
monitor, control and count function.
The required devices are as follows:
3 gateways; 3 pieces of communication wire, one internet server, one set of network side software,
internet wire, one set of PC.
d.o.o.
110
G R U P A
10 GND
11 SUB2 Signal of slave unit 2
12 GND
13 SUB3
Signal of slave unit 3
d.o.o.
14 GND
15 HB1 Communication bus line between indoor and
16 HB2 outdoor
17 LONA Communication bus line of LonWorks
18 LONB
19 LONA
20 LONB
111
2. Installation instruction
2.1 Structure figure
PC on client side
install network side software
switch
LAN
internet server
LonWorks
2. 2 System diagram:
G R U P A
Ammeter Ammeter
d.o.o.
unit unit
Ammeter Ammeter
Ammeter Ammeter
112
To pulse ammeter
To other gateway and server
CN44
CN19 CN36
G R U P A
it to external use the port.
power: 13.8VAC To indoor unit To outdoor slave unit
200mA.
Remarks:
1) Power: The power of gateway is AC12V and could be getted from port A and B on the
communication terminal block of outdoor master unit and slave unit. There cannt be
d.o.o.
any error when connecting, or the gateway will be burnt off.
2) LON/LON(LONWORKS communication) connector: connect with the gateway of other
master unit and LONWORKS communication connector of internet server, no polarity
requirement.
3) HBS/earth wire(serial signal of master unit) wiring: connect with the output port of
serial signal (CN35 ) of the master uint PCB, get the parameter of slave unit from serial
signal, could not detect slave unit data when in reverse connection. Polarity is
required. When using communication wire 0010450044, black wire is connected to the
HBS terminal of gateway, and white wire is connected to the earth wire on the right of HBS.
4) Count/ earth wire(pulse signal) wiring: connect pulse ammeter to get the power
consumption recorded in the ammeter. Polarity is required.
Connect the earth wire terminal of pulse output of ammeter to the earth wire terminal on
the right of count terminal of gateway, and the other terminal of pulse output of ammeter
connects to the count terminal of gateway.
HBM/HBM (HOMEBUS communication) port: connect ports P&Q of the communication
terminal block of outdoor master unit and indoor unit, no polarity requirement..
113
Spec of cable:
1) Power: Two-core RVV, the section area is 0.5mm2, there is no polarity requirement when connection.
2) LON(LONWORKS communication) port: Two-core STP, the section area is 1.5mm2, there is no
polarity requirement when connection.
3) HBS(master unit serial signal): get state signal of slave units.
4) Count (pulse signal): use two-core RVVP shielded wire, the section area is1.0mm2, there is polarity
requirement when connection.
5) HBM (HOMEBUS communication): use two-core RVVP shielded wire, the section area is1.0mm2,
there is no polarity requirement when connection.
2.4 Connection among gateways, between gateway and server
The gateways are interconnected with two-core STP (the section is 1.5mm2) to make LONWORKS
control network. The spec of signal wire is as above. The wiring of signal wires adopts bus type
(identical with the communication wires connection between indoor and outdoor).
If it is very far from gateway to server, the wires must be shielded and be heat insulated well;
and the shielded layer must be connected to the earth wire terminal of the server.
2.5 Exterior appearance & installation method of internet server
A. External appearance and definition of port
To server bus line 17, 18 connect
with server bus line (LON);19
Connect with computer
connect with shield layer.
G R U P A
d.o.o.
earth N L
wire
114
s w itc h
G R U P A
d.o.o.
115
Part 1: brief
1.1 Applicable for MRV II (R22 & R410A) system.
1.2 System combination
1. Inverter protocol adapter (IGU02): Transform the air conditioner protocol into protocol 485;
receive ammeter pulse signal; account and save the power cost of the connected system, then
transfer it to the computer.
2. Software: parameter display and human-computer operation surface, and account and save
the power cost, output the cost table.
3. RS 485&232 Converter (hardware), Item 2 & 3 name is HCM1.
1.3 Control range
1. If the H-CACSII is necessary, pay attention that the indoor quantity of every system cannot
be over 40 sets. Or the adapter can not work normally.
2. Every system needs one protocol adapter.
3. One Microsoft can control indoors within 400 sets.
1.4 Applicable range and relative certificate
1) Applicable range
G R U P A
Temp. range: -30¡ ¡«52¡
Ambient temperature of controller: -30¡ ¡«52¡
Ambient humidity of controller: -30¡ ¡«52¡
Save temp. range of controller: -30¡ ¡«52¡
Altitude: 0¡«6000m
d.o.o.
Voltage: 220Vac±10£¥
Frequency: 50Hz
2£'Safe certificate: Conform with HR and CCC
3£'Environment certificate: conform with ROHS
1.5 Reliable request
1£'Application standards£”QB1238-91, GB4706.1-92, GB4706.12-95
2£'Special requirement:
116
G R U P A
Appearance:
d.o.o.
Dimension: 2000*1300*430(mm)
117
left: 4 right: 4
Shows address of IGU02, address range: 1-32.
Communication lamp definition:
Wiring terminal:
G R U P A
d.o.o.
118
G R U P A
d.o.o.
Next:
119
Next:
G R U P A
d.o.o.
Next:
120
Note: No need to change the default setting, just click "next" all the way.
2. ODBC installation and setting
ODBC installation:
G R U P A
d.o.o.
Continue
121
G R U P A
ODBC setting:
d.o.o.
Open ODBC database in the route: control panel/manage tool
122
G R U P A
Click and add
d.o.o.
123
Password is 1
G R U P A
d.o.o.
Click OK.
124
G R U P A
Next
d.o.o.
125
G R U P A
d.o.o.
Click finish.
Software startup:
1. Startup of database
In the folder C:\mysql\bin, look for winmysqladmin.exe and click twice to open it.
126
G R U P A
d.o.o.
127
Choose the three items (search system folder, search hidden file and folder, search sub-folder) as the
figure.
G R U P A
Stop "mysql" in "service" in the manage tool folder, if it is already stopped, you need not change it.
d.o.o.
128
129