Sequence Of Operation For Electrical,

Low Current & ELV Systems


Fire Alarm Panels Sequence
Location: Fire Alarm Panels: Various Locations (refer to Fire Alarm
Layout)

Each Fire alarm panel will be monitored by the DDC controller to


provide a system healthy, fault and alarm. All information shall be
displayed on the BMS Supervisor. All MCC and DDC control panels
will be linked to the Fire Alarm system such that in a Fire condition
the plant will either shut down or control to an agreed routine.

A graphical representation of the plant will be produced with all


status information, alarms etc. displayed with simple mouse clicks.
Access to the graphic will be through a system of site plans,
plantrooms and systems.

All values are to be historically recorded at controller level so that


locally any laptop or Portable operator’s terminal may retrieve the
data as well as the network BMS Supervisor.

Lighting Control
Lighting Control Panels (Internal): Various Locations (refer to Lighting
Layout)

Lighting Control Panels (External): Various Locations (refer to Lighting


Specialist Layout)

The BMS shall integrate to the FOH lighting control system via an EIB
interface and provide monitoring functionality.

A graphical representation of the system will be produced with all


status information, alarms schedules etc. displayed with simple
mouse clicks. Access to the graphic will be through a system of site
plans, plantrooms and systems.
All values are to be historically recorded at controller level so that
locally any laptop or Portable operator’s terminal may retrieve the
data as well as the network BMS Supervisor.

Lifts / Elevators
Provisions shall be made on the BMS to allow for monitoring all lifts
for:-

 Lift Alarm
 Lift Out Of Service

Electric Meters Monitoring


The BMS shall be interfaced and allowed for the receiving, recording
and presenting of current and historic information from the all
electric KWH meters.

LV Switchgear Monitoring
Location: LV Switchgear: Substation Room (Ground Floor Level)

The main ACB’s in all LV switchboard panels shall be monitored by


the BMS for the following:-

 Open
 Closed

Automatic Transfer Switch


Each automatic transfer switch will be monitored by the local DDC
controller to provide a change over fault and a common general fault.

A graphical representation of the plant will be produced with all


status information, alarms etc. displayed with simple mouse clicks.
Access to the graphic will be through a system of site plans,
plantrooms and systems.

All values are to be historically recorded at controller level so that


locally any laptop or Portable operator’s terminal may retrieve the
data as well as the network BMS Supervisor.
Security System
Security System will be monitored by the DDC controller to provide a
system healthy and Common alarm. All information shall be displayed
on the BMS Supervisor.

A graphical representation of the plant will be produced with all


status information, alarms etc. displayed with simple mouse clicks.
Access to the graphic will be through a system of site plans,
plantrooms and systems.

All values are to be historically recorded at controller level so that


locally any laptop or Portable operator’s terminal may retrieve the
data as well as the network BMS Supervisor.

Main Distribution Boards


Location: Main Distribution Board (MDB): Substation (Ground Floor
Level)

Each of the Main Distribution Boards Alarms will be monitored


through the DDC controller by thru VFC. All available information
shall be mapped into the local DDC controller for display on the
Building Management System and all connected computers on the
network. A common fault and ACB status indication will be hard
wired into the controller.

A graphical representation of the plant will be produced with all


status information, alarms etc. displayed with simple mouse clicks.
Access to the graphic will be through a system of site plans,
plantrooms and systems.

All values are to be historically recorded at controller level so that


locally any laptop or Portable operator’s terminal may retrieve the
data as well as the network BMS Supervisor.

UPS Systems
Location of UPS System: Various Locations (Refer to Electrical
Drawings)
The following systems shall be monitored by the BMS:-

 UPS System
 Battery Status
 Charger Status
 Mains Supply Tripped

A graphical representation of the plant will be produced with all


status information, alarms etc. displayed with simple mouse clicks.
Access to the graphic will be through a system of site plans,
plantrooms and systems.

All values are to be historically recorded at controller level so that


locally any laptop or Portable operator’s terminal may retrieve the
data as well as the network BMS Supervisor.

Central Battery System (CBS)


Location of Central Battery System (CBS): Various Locations (refer to
Electrical Drawings)

Each of the CBS Systems will be monitored through the DDC


controller by means of a VFC. All available information as per IO
Schedule shall be mapped into the local DDC controller for display on
the Building Management System and all connected computers on
the network.

A graphical representation of the plant will be produced with all


status information, alarms etc. displayed with simple mouse clicks.
Access to the graphic will be through a system of site plans, plant
rooms and systems.

All values are to be historically recorded at controller level so that


locally any laptop or Portable operator’s terminal may retrieve the
data as well as the network BMS Supervisor.

For more details please refer to I/O points schedule/ control


schematics/ riser drawings.
The details provided are minimum requirements and need to be
details as per the site requirement by BMS specialist.

Motor Control Centre (MCC)


All Motor Control Centres shall interface with the fire alarm system
described in the Electrical Specification.

All MCC room air conditioning (A/C) system (motorised smoke fire
dampers) shall be switched off thru the signal from Automatic Gas
Fire Suppresion System Panel. The Fan Coil Unit (FCU) serving the
MCC room shall be switched of thru BMS DDC.

Disabled Toilet Alarms


Location of Disabled Toilet Alarms: Various Locations (refer to
Electrical drawings)

The BMS shall receive individual alarm signals from manual call alarm
in each toilet through volt free contact (VFC) from panel to DDC.