Approval Code : ---

SLB PROJECT NUMBER - PF-0004


OTC
PF-0004-Sakarya Project

VENDOR DOCUMENT TITLE: I/O List – Effluent Treatment Plant

Tag No.Y0700

Vendor Document Number: PF-0004-517-IE-975-0001


Vendor Revision: D

Project Return Codes (For SLB Use Only - Mark up as appropriate)

D 20.07.2022 For Approval H.Basbug K.Memis U.Balaban


C 18.05.2022 For Approval H.Basbug K.Memis U.Balaban
B 01.04.2022 For Approval C.Namruk K.Memis U.Balaban
A 04.03.2022 For Approval C.Namruk K.Memis U.Balaban
Vendor Vendor Vendor
Date Purpose of Issue Originator Checker Approver
SLB
Rev

SLB Document Number: PF-0004-517-IE-975-0001


This document includes detailed design information that is confidential, proprietary and a trade secret of Schlumberger. This information is not meant for public dissemination
without the prior written permission of Schlumberger. Documents shall not be (1) copied, reproduced, or traced or (2) used to furnish any information for making any other
document or (3) loaned to any other party.

Schlumberger-Private
Approval Code : ---

CONTROL SYSTEM CABINET

EXTERNAL POWER SUPPLY


SIGNAL FROM LOCATION

NORMAL (AS SETPOINT)


CONTACT TYPE- NO/ NC
REFERENCE DRAWINGS

SUPPLY DETAILS (LOOP


SIGNAL TYPE , POWER

OPC DATA EXCHANGE


SYSTEM TAG NUMBER

POWERED, DRY/WET)

ALARM DESCRPTION

JB NO / RIO CABINET
ENG. RANGE OF INS.
P & ID NO / VENDOR
FIELD TAG NUMBER

INSTRUMENT TYPE

REVISION NUMBER
CONTROL SYSTEM

LINE MONITORING

SYSTEM PRIORITY

CONTROL ACTION
SIGNAL VOLTAGE

CAL. Range. LRL

TREND/REPORT
DRAWING / ANY

REVISION DATE
CAL. Range URL

SOE REQUIRED
LOOP NUMBER

TERMINAL NO
TIME DELAY

COMMENTS
INTERLOCK
ENGG UNIT

VALVE FAIL
LOCATION

REMARKS
SERVICE

IS/Non-IS

NUMBER
I/O TYPE

HHH

HH

LL
H

L
PF-0004-517-PE-960-0001 / SC26-OPF-PE- 2.1 - 66 TBD (by TBD (by
59-FT-1014-01 59-FT-1014-01 59-FT-1014-01 ETP Discharge Flow Analog Signal EM Flow Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 2.1 18 m³/h - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 m3/h SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- 2.1 - 66 TBD (by TBD (by
59-FT-1020A-01 59-FT-1020A-01 59-FT-1020A-01 59-T-1020A CPI Tank A Inlet Flow Analog Signal EM Flow Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 2.1 18 m³/h - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 3 of 6 m3/h SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- 2.1 - 66 TBD (by TBD (by
59-FT-1020B-01 59-FT-1020B-01 59-FT-1020B-01 59-T-1020B CPI Tank B Inlet Flow Analog Signal EM Flow Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 2.1 18 m³/h - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 3 of 6 m3/h SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- 0.54 - 18 TBD (by TBD (by
59-FT-1025-01 59-FT-1025-01 59-FT-1025-01 59-F-1025 Filter Press Sludge Inlet Flow Analog Signal EM Flow Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 0.54 4.5 m³/h - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 m3/h SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1025-01 59-LT-1025-01 59-LT-1025-01 59-T-1025 Treated W ater Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 1000 0 250 cm - - - - 2050 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1005-01 59-LT-1005-01 59-LT-1005-01 59-N-1005 Drain Pit Level Analog Signal Radar Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 750 0 100 cm - - - - 900 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1021-01 59-LT-1021-01 59-LT-1021-01 59-T-1021 Sludge Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 1000 0 150 cm - - - - 1200 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1022-01 59-LT-1022-01 59-LT-1022-01 59-T-1022 Oil Tank Level Analog Signal Radar Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 750 0 150 cm - - - - 1250 - 400 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1019-01 59-LT-1019-01 59-LT-1019-01 59-T-1019 Equalization Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 1000 0 300 cm - - - - 2600 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 3 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1023-01 59-LT-1023-01 59-LT-1023-01 59-T-1023 Filter Feed Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 1000 0 250 cm - - - - 2050 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1024-01 59-LT-1024-01 59-LT-1024-01 59-T-1024 Cat. Poly Preparation Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 100 0 100 cm - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-PT-1002A-01 59-PT-1002A-01 59-PT-1002A-01 59-F-1002A Filter A Inlet Pressure Analog Signal Pressure Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 10 0 10 bar - - - - 6 - - - - - - 1s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-PT-1002A-02 59-PT-1002A-02 59-PT-1002A-02 59-F-1002A Filter A Outlet Pressure Analog Signal Pressure Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 10 0 10 bar - - - - 6 - - - - - - 1s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-PT-1002A-03 59-PT-1002A-03 59-PT-1002A-03 59-F-1002B Filter B Inlet Pressure Analog Signal Pressure Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 10 0 10 bar - - - - 6 - - - - - - 1s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-PT-1002A-04 59-PT-1002A-04 59-PT-1002A-04 59-F-1002B Filter B Outlet Pressure Analog Signal Pressure Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 10 0 10 bar - - - - 6 - - - - - - 1s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-01 59-ZSO-1002A-01 59-ZSO-1002A-01 59-F-1002A Filter A Inlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-01 59-ZSC-1002A-01 59-ZSC-1002A-01 59-F-1002A Filter A Inlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-01 59-XY-1002A-01 59-XY-1002A-01 59-F-1002A Filter A Inlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-02 59-ZSO-1002A-02 59-ZSO-1002A-02 59-F-1002A Filter A Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-02 59-ZSC-1002A-02 59-ZSC-1002A-02 59-F-1002A Filter A Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-02 59-XY-1002A-02 59-XY-1002A-02 59-F-1002A Filter A Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-03 59-ZSO-1002A-03 59-ZSO-1002A-03 59-F-1002A Filter A Backwash Inlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-03 59-ZSC-1002A-03 59-ZSC-1002A-03 59-F-1002A Filter A Backwash Inlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-03 59-XY-1002A-03 59-XY-1002A-03 59-F-1002A Filter A Backwash Inlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-04 59-ZSO-1002A-04 59-ZSO-1002A-04 59-F-1002A Filter A Backwash Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-04 59-ZSC-1002A-04 59-ZSC-1002A-04 59-F-1002A Filter A Backwash Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-04 59-XY-1002A-04 59-XY-1002A-04 59-F-1002A Filter A Backwash Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-05 59-ZSO-1002A-05 59-ZSO-1002A-05 59-F-1002A Filter A Air Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-05 59-ZSC-1002A-05 59-ZSC-1002A-05 59-F-1002A Filter A Air Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-05 59-XY-1002A-05 59-XY-1002A-05 59-F-1002A Filter A Air Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-06 59-ZSO-1002A-06 59-ZSO-1002A-06 59-F-1002A Filter A Drain Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-06 59-ZSC-1002A-06 59-ZSC-1002A-06 59-F-1002A Filter A Drain Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-06 59-XY-1002A-06 59-XY-1002A-06 59-F-1002A Filter A Drain Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-01 59-ZSO-1002B-01 59-ZSO-1002B-01 59-F-1002B Filter B Inlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-01 59-ZSC-1002B-01 59-ZSC-1002B-01 59-F-1002B Filter B Inlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-01 59-XY-1002B-01 59-XY-1002B-01 59-F-1002B Filter B Inlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-02 59-ZSO-1002B-02 59-ZSO-1002B-02 59-F-1002B Filter B Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-02 59-ZSC-1002B-02 59-ZSC-1002B-02 59-F-1002B Filter B Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-02 59-XY-1002B-02 59-XY-1002B-02 59-F-1002B Filter B Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-03 59-ZSO-1002B-03 59-ZSO-1002B-03 59-F-1002B Filter B Backwash Inlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-03 59-ZSC-1002B-03 59-ZSC-1002B-03 59-F-1002B Filter B Backwash Inlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-03 59-XY-1002B-03 59-XY-1002B-03 59-F-1002B Filter B Backwash Inlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-04 59-ZSO-1002B-04 59-ZSO-1002B-04 59-F-1002B Filter B Backwash Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-04 59-ZSC-1002B-04 59-ZSC-1002B-04 59-F-1002B Filter B Backwash Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-04 59-XY-1002B-04 59-XY-1002B-04 59-F-1002B Filter B Backwash Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-05 59-ZSO-1002B-05 59-ZSO-1002B-05 59-F-1002B Filter B Air Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-05 59-ZSC-1002B-05 59-ZSC-1002B-05 59-F-1002B Filter B Air Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-05 59-XY-1002B-05 59-XY-1002B-05 59-F-1002B Filter B Air Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-06 59-ZSO-1002B-06 59-ZSO-1002B-06 59-F-1002B Filter B Drain Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-06 59-ZSC-1002B-06 59-ZSC-1002B-06 59-F-1002B Filter B Drain Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-06 59-XY-1002B-06 59-XY-1002B-06 59-F-1002B Filter B Drain Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1020A-01 59-ZSO-1020A-01 59-ZSO-1020A-01 59-T-1020A CPI Tank A Sludge Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1020A-01 59-ZSC-1020A-01 59-ZSC-1020A-01 59-T-1020A CPI Tank A Sludge Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1020A-01 59-XY-1020A-01 59-XY-1020A-01 59-T-1020A CPI Tank A Sludge Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1020B-01 59-ZSO-1020B-01 59-ZSO-1020B-01 59-T-1020B CPI Tank B Sludge Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1020B-01 59-ZSC-1020B-01 59-ZSC-1020B-01 59-T-1020B CPI Tank B Sludge Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1020B-01 59-XY-1020B-01 59-XY-1020B-01 59-T-1020B CPI Tank B Sludge Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
TBD (by TBD (by
59-HS-1019A-01 59-HS-1019A-01 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-02 59-HS-1019A-02 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-03 59-HS-1019A-03 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-04 59-HS-1019A-04 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-05 59-HS-1019A-05 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-06 59-HS-1019A-06 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-07 59-HS-1019A-07 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-01 59-HS-1019B-01 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-02 59-HS-1019B-02 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-03 59-HS-1019B-03 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-04 59-HS-1019B-04 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-05 59-HS-1019B-05 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-06 59-HS-1019B-06 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-07 59-HS-1019B-07 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-01 59-HS-1019C-01 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-02 59-HS-1019C-02 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-03 59-HS-1019C-03 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-04 59-HS-1019C-04 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)

# Schlumberger-Private
Approval Code : ---

CONTROL SYSTEM CABINET

EXTERNAL POWER SUPPLY


SIGNAL FROM LOCATION

NORMAL (AS SETPOINT)


CONTACT TYPE- NO/ NC
REFERENCE DRAWINGS

SUPPLY DETAILS (LOOP


SIGNAL TYPE , POWER

OPC DATA EXCHANGE


SYSTEM TAG NUMBER

POWERED, DRY/WET)

ALARM DESCRPTION

JB NO / RIO CABINET
ENG. RANGE OF INS.
P & ID NO / VENDOR
FIELD TAG NUMBER

INSTRUMENT TYPE

REVISION NUMBER
CONTROL SYSTEM

LINE MONITORING

SYSTEM PRIORITY

CONTROL ACTION
SIGNAL VOLTAGE

CAL. Range. LRL

TREND/REPORT
DRAWING / ANY

REVISION DATE
CAL. Range URL

SOE REQUIRED
LOOP NUMBER

TERMINAL NO
TIME DELAY

COMMENTS
INTERLOCK
ENGG UNIT

VALVE FAIL
LOCATION

REMARKS
SERVICE

IS/Non-IS

NUMBER
I/O TYPE

HHH

HH

LL
H

L
TBD (by TBD (by
59-HS-1019C-05 59-HS-1019C-05 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-06 59-HS-1019C-06 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-07 59-HS-1019C-07 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-01 59-HS-1019D-01 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-02 59-HS-1019D-02 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-03 59-HS-1019D-03 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-04 59-HS-1019D-04 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-05 59-HS-1019D-05 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-06 59-HS-1019D-06 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-07 59-HS-1019D-07 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-01 59-HS-1020A-01 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-02 59-HS-1020A-02 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-03 59-HS-1020A-03 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)

# Schlumberger-Private
Approval Code : ---

CONTROL SYSTEM CABINET

EXTERNAL POWER SUPPLY


SIGNAL FROM LOCATION

NORMAL (AS SETPOINT)


CONTACT TYPE- NO/ NC
REFERENCE DRAWINGS

SUPPLY DETAILS (LOOP


SIGNAL TYPE , POWER

OPC DATA EXCHANGE


SYSTEM TAG NUMBER

POWERED, DRY/WET)

ALARM DESCRPTION

JB NO / RIO CABINET
ENG. RANGE OF INS.
P & ID NO / VENDOR
FIELD TAG NUMBER

INSTRUMENT TYPE

REVISION NUMBER
CONTROL SYSTEM

LINE MONITORING

SYSTEM PRIORITY

CONTROL ACTION
SIGNAL VOLTAGE

CAL. Range. LRL

TREND/REPORT
DRAWING / ANY

REVISION DATE
CAL. Range URL

SOE REQUIRED
LOOP NUMBER

TERMINAL NO
TIME DELAY

COMMENTS
INTERLOCK
ENGG UNIT

VALVE FAIL
LOCATION

REMARKS
SERVICE

IS/Non-IS

NUMBER
I/O TYPE

HHH

HH

LL
H

L
TBD (by TBD (by
59-HS-1020A-04 59-HS-1020A-04 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-05 59-HS-1020A-05 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-06 59-HS-1020A-06 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-07 59-HS-1020A-07 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-01 59-HS-1020B-01 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-02 59-HS-1020B-02 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-03 59-HS-1020B-03 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-04 59-HS-1020B-04 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-05 59-HS-1020B-05 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-06 59-HS-1020B-06 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-07 59-HS-1020B-07 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-01 59-HS-1016A-01 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-02 59-HS-1016A-02 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-03 59-HS-1016A-03 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-04 59-HS-1016A-04 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-05 59-HS-1016A-05 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-06 59-HS-1016A-06 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-07 59-HS-1016A-07 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-01 59-HS-1016B-01 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-02 59-HS-1016B-02 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-03 59-HS-1016B-03 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-04 59-HS-1016B-04 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-05 59-HS-1016B-05 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-06 59-HS-1016B-06 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-07 59-HS-1016B-07 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-01 59-HS-1022A-01 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-02 59-HS-1022A-02 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-03 59-HS-1022A-03 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-04 59-HS-1022A-04 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-05 59-HS-1022A-05 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-06 59-HS-1022A-06 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-07 59-HS-1022A-07 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-01 59-HS-1022B-01 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-02 59-HS-1022B-02 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-03 59-HS-1022B-03 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-04 59-HS-1022B-04 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-05 59-HS-1022B-05 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-06 59-HS-1022B-06 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-07 59-HS-1022B-07 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-01 59-HS-1021-01 59-A-1021 59-A-1021 Sludge Tank Agitator A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-02 59-HS-1021-02 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-03 59-HS-1021-03 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-04 59-HS-1021-04 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-05 59-HS-1021-05 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-06 59-HS-1021-06 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-07 59-HS-1021-07 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-01 59-HS-1021A-01 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-02 59-HS-1021A-02 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-03 59-HS-1021A-03 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-04 59-HS-1021A-04 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-05 59-HS-1021A-05 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-06 59-HS-1021A-06 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-07 59-HS-1021A-07 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-01 59-HS-1021B-01 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-02 59-HS-1021B-02 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-03 59-HS-1021B-03 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-04 59-HS-1021B-04 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-05 59-HS-1021B-05 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-06 59-HS-1021B-06 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-07 59-HS-1021B-07 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-01 59-HS-1024-01 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-02 59-HS-1024-02 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-03 59-HS-1024-03 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-04 59-HS-1024-04 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-05 59-HS-1024-05 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-06 59-HS-1024-06 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-07 59-HS-1024-07 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-01 59-HS-1024A-01 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-02 59-HS-1024A-02 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-03 59-HS-1024A-03 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-04 59-HS-1024A-04 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-05 59-HS-1024A-05 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-06 59-HS-1024A-06 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-07 59-HS-1024A-07 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-HS-1024A-08 59-HS-1024A-08 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Dosing Reference from DCS AO Non-IS 4-20 mA DCS FIELD TBD (by SLB) 24 VDC - - - 100 0 100 - (%) - - - - - - - - - 10 s TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
TBD (by TBD (by
59-HS-1024B-01 59-HS-1024B-01 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-02 59-HS-1024B-02 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-03 59-HS-1024B-03 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-04 59-HS-1024B-04 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-05 59-HS-1024B-05 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-06 59-HS-1024B-06 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)

# Schlumberger-Private
Approval Code : ---

CONTROL SYSTEM CABINET

EXTERNAL POWER SUPPLY


SIGNAL FROM LOCATION

NORMAL (AS SETPOINT)


CONTACT TYPE- NO/ NC
REFERENCE DRAWINGS

SUPPLY DETAILS (LOOP


SIGNAL TYPE , POWER

OPC DATA EXCHANGE


SYSTEM TAG NUMBER

POWERED, DRY/WET)

ALARM DESCRPTION

JB NO / RIO CABINET
ENG. RANGE OF INS.
P & ID NO / VENDOR
FIELD TAG NUMBER

INSTRUMENT TYPE

REVISION NUMBER
CONTROL SYSTEM

LINE MONITORING

SYSTEM PRIORITY

CONTROL ACTION
SIGNAL VOLTAGE

CAL. Range. LRL

TREND/REPORT
DRAWING / ANY

REVISION DATE
CAL. Range URL

SOE REQUIRED
LOOP NUMBER

TERMINAL NO
TIME DELAY

COMMENTS
INTERLOCK
ENGG UNIT

VALVE FAIL
LOCATION

REMARKS
SERVICE

IS/Non-IS

NUMBER
I/O TYPE

HHH

HH

LL
H

L
TBD (by TBD (by
59-HS-1024B-07 59-HS-1024B-07 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-HS-1024B-08 59-HS-1024B-08 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Dosing Reference from DCS AO Non-IS 4-20 mA DCS FIELD TBD (by SLB) 24 VDC - - - 100 0 100 - (%) - - - - - - - - - 10 s TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
TBD (by TBD (by
59-HS-1023A-01 59-HS-1023A-01 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-02 59-HS-1023A-02 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-03 59-HS-1023A-03 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-04 59-HS-1023A-04 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-05 59-HS-1023A-05 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-06 59-HS-1023A-06 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-07 59-HS-1023A-07 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-01 59-HS-1023B-01 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-02 59-HS-1023B-02 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-03 59-HS-1023B-03 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-04 59-HS-1023B-04 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-05 59-HS-1023B-05 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-06 59-HS-1023B-06 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-07 59-HS-1023B-07 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-01 59-HS-1023C-01 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-02 59-HS-1023C-02 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-03 59-HS-1023C-03 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-04 59-HS-1023C-04 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-05 59-HS-1023C-05 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-06 59-HS-1023C-06 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-07 59-HS-1023C-07 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-01 59-HS-1015A-01 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-02 59-HS-1015A-02 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-03 59-HS-1015A-03 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-04 59-HS-1015A-04 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-05 59-HS-1015A-05 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-06 59-HS-1015A-06 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-07 59-HS-1015A-07 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-01 59-HS-1015B-01 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-02 59-HS-1015B-02 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-03 59-HS-1015B-03 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-04 59-HS-1015B-04 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-05 59-HS-1015B-05 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-06 59-HS-1015B-06 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-07 59-HS-1015B-07 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-01 59-HS-1014A-01 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-02 59-HS-1014A-02 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-03 59-HS-1014A-03 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-04 59-HS-1014A-04 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-05 59-HS-1014A-05 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-06 59-HS-1014A-06 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-07 59-HS-1014A-07 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-01 59-HS-1014B-01 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-02 59-HS-1014B-02 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-03 59-HS-1014B-03 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-04 59-HS-1014B-04 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-05 59-HS-1014B-05 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-06 59-HS-1014B-06 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-07 59-HS-1014B-07 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)