SLB Project Number - Pf-0004 OTC PF-0004-Sakarya Project - Effluent Treatment Plant
SLB Project Number - Pf-0004 OTC PF-0004-Sakarya Project - Effluent Treatment Plant
Tag No.Y0700
Schlumberger-Private
Approval Code : ---
POWERED, DRY/WET)
ALARM DESCRPTION
JB NO / RIO CABINET
ENG. RANGE OF INS.
P & ID NO / VENDOR
FIELD TAG NUMBER
INSTRUMENT TYPE
REVISION NUMBER
CONTROL SYSTEM
LINE MONITORING
SYSTEM PRIORITY
CONTROL ACTION
SIGNAL VOLTAGE
TREND/REPORT
DRAWING / ANY
REVISION DATE
CAL. Range URL
SOE REQUIRED
LOOP NUMBER
TERMINAL NO
TIME DELAY
COMMENTS
INTERLOCK
ENGG UNIT
VALVE FAIL
LOCATION
REMARKS
SERVICE
IS/Non-IS
NUMBER
I/O TYPE
HHH
HH
LL
H
L
PF-0004-517-PE-960-0001 / SC26-OPF-PE- 2.1 - 66 TBD (by TBD (by
59-FT-1014-01 59-FT-1014-01 59-FT-1014-01 ETP Discharge Flow Analog Signal EM Flow Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 2.1 18 m³/h - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 m3/h SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- 2.1 - 66 TBD (by TBD (by
59-FT-1020A-01 59-FT-1020A-01 59-FT-1020A-01 59-T-1020A CPI Tank A Inlet Flow Analog Signal EM Flow Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 2.1 18 m³/h - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 3 of 6 m3/h SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- 2.1 - 66 TBD (by TBD (by
59-FT-1020B-01 59-FT-1020B-01 59-FT-1020B-01 59-T-1020B CPI Tank B Inlet Flow Analog Signal EM Flow Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 2.1 18 m³/h - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 3 of 6 m3/h SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- 0.54 - 18 TBD (by TBD (by
59-FT-1025-01 59-FT-1025-01 59-FT-1025-01 59-F-1025 Filter Press Sludge Inlet Flow Analog Signal EM Flow Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 0.54 4.5 m³/h - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 m3/h SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1025-01 59-LT-1025-01 59-LT-1025-01 59-T-1025 Treated W ater Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 1000 0 250 cm - - - - 2050 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1005-01 59-LT-1005-01 59-LT-1005-01 59-N-1005 Drain Pit Level Analog Signal Radar Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 750 0 100 cm - - - - 900 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1021-01 59-LT-1021-01 59-LT-1021-01 59-T-1021 Sludge Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 1000 0 150 cm - - - - 1200 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1022-01 59-LT-1022-01 59-LT-1022-01 59-T-1022 Oil Tank Level Analog Signal Radar Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 750 0 150 cm - - - - 1250 - 400 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1019-01 59-LT-1019-01 59-LT-1019-01 59-T-1019 Equalization Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 1000 0 300 cm - - - - 2600 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 3 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1023-01 59-LT-1023-01 59-LT-1023-01 59-T-1023 Filter Feed Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 1000 0 250 cm - - - - 2050 - 250 - - - - 5s TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-LT-1024-01 59-LT-1024-01 59-LT-1024-01 59-T-1024 Cat. Poly Preparation Tank Level Analog Signal Hydrostatic Level Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 100 0 100 cm - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-PT-1002A-01 59-PT-1002A-01 59-PT-1002A-01 59-F-1002A Filter A Inlet Pressure Analog Signal Pressure Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 10 0 10 bar - - - - 6 - - - - - - 1s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-PT-1002A-02 59-PT-1002A-02 59-PT-1002A-02 59-F-1002A Filter A Outlet Pressure Analog Signal Pressure Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 10 0 10 bar - - - - 6 - - - - - - 1s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-PT-1002A-03 59-PT-1002A-03 59-PT-1002A-03 59-F-1002B Filter B Inlet Pressure Analog Signal Pressure Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 10 0 10 bar - - - - 6 - - - - - - 1s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-PT-1002A-04 59-PT-1002A-04 59-PT-1002A-04 59-F-1002B Filter B Outlet Pressure Analog Signal Pressure Signal to DCS AI Non-IS 4-20 mA HART DCS 59-JBA-1104-DCS TBD (by SLB) 24 VDC - - - 10 0 10 bar - - - - 6 - - - - - - 1s TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-01 59-ZSO-1002A-01 59-ZSO-1002A-01 59-F-1002A Filter A Inlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-01 59-ZSC-1002A-01 59-ZSC-1002A-01 59-F-1002A Filter A Inlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-01 59-XY-1002A-01 59-XY-1002A-01 59-F-1002A Filter A Inlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-02 59-ZSO-1002A-02 59-ZSO-1002A-02 59-F-1002A Filter A Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-02 59-ZSC-1002A-02 59-ZSC-1002A-02 59-F-1002A Filter A Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-02 59-XY-1002A-02 59-XY-1002A-02 59-F-1002A Filter A Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-03 59-ZSO-1002A-03 59-ZSO-1002A-03 59-F-1002A Filter A Backwash Inlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-03 59-ZSC-1002A-03 59-ZSC-1002A-03 59-F-1002A Filter A Backwash Inlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-03 59-XY-1002A-03 59-XY-1002A-03 59-F-1002A Filter A Backwash Inlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-04 59-ZSO-1002A-04 59-ZSO-1002A-04 59-F-1002A Filter A Backwash Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-04 59-ZSC-1002A-04 59-ZSC-1002A-04 59-F-1002A Filter A Backwash Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-04 59-XY-1002A-04 59-XY-1002A-04 59-F-1002A Filter A Backwash Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-05 59-ZSO-1002A-05 59-ZSO-1002A-05 59-F-1002A Filter A Air Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-05 59-ZSC-1002A-05 59-ZSC-1002A-05 59-F-1002A Filter A Air Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-05 59-XY-1002A-05 59-XY-1002A-05 59-F-1002A Filter A Air Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-06 59-ZSO-1002A-06 59-ZSO-1002A-06 59-F-1002A Filter A Drain Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002A-06 59-ZSC-1002A-06 59-ZSC-1002A-06 59-F-1002A Filter A Drain Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002A-06 59-XY-1002A-06 59-XY-1002A-06 59-F-1002A Filter A Drain Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1101-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-01 59-ZSO-1002B-01 59-ZSO-1002B-01 59-F-1002B Filter B Inlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-01 59-ZSC-1002B-01 59-ZSC-1002B-01 59-F-1002B Filter B Inlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-01 59-XY-1002B-01 59-XY-1002B-01 59-F-1002B Filter B Inlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-02 59-ZSO-1002B-02 59-ZSO-1002B-02 59-F-1002B Filter B Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-02 59-ZSC-1002B-02 59-ZSC-1002B-02 59-F-1002B Filter B Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-02 59-XY-1002B-02 59-XY-1002B-02 59-F-1002B Filter B Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-03 59-ZSO-1002B-03 59-ZSO-1002B-03 59-F-1002B Filter B Backwash Inlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-03 59-ZSC-1002B-03 59-ZSC-1002B-03 59-F-1002B Filter B Backwash Inlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-03 59-XY-1002B-03 59-XY-1002B-03 59-F-1002B Filter B Backwash Inlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-04 59-ZSO-1002B-04 59-ZSO-1002B-04 59-F-1002B Filter B Backwash Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-04 59-ZSC-1002B-04 59-ZSC-1002B-04 59-F-1002B Filter B Backwash Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-04 59-XY-1002B-04 59-XY-1002B-04 59-F-1002B Filter B Backwash Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-05 59-ZSO-1002B-05 59-ZSO-1002B-05 59-F-1002B Filter B Air Outlet Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-05 59-ZSC-1002B-05 59-ZSC-1002B-05 59-F-1002B Filter B Air Outlet Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-05 59-XY-1002B-05 59-XY-1002B-05 59-F-1002B Filter B Air Outlet Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-06 59-ZSO-1002B-06 59-ZSO-1002B-06 59-F-1002B Filter B Drain Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1002B-06 59-ZSC-1002B-06 59-ZSC-1002B-06 59-F-1002B Filter B Drain Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1002B-06 59-XY-1002B-06 59-XY-1002B-06 59-F-1002B Filter B Drain Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1102-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 5 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1020A-01 59-ZSO-1020A-01 59-ZSO-1020A-01 59-T-1020A CPI Tank A Sludge Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1020A-01 59-ZSC-1020A-01 59-ZSC-1020A-01 59-T-1020A CPI Tank A Sludge Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1020A-01 59-XY-1020A-01 59-XY-1020A-01 59-T-1020A CPI Tank A Sludge Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1020B-01 59-ZSO-1020B-01 59-ZSO-1020B-01 59-T-1020B CPI Tank B Sludge Valve Control Signal Opened Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-ZSO/ZSC-1020B-01 59-ZSC-1020B-01 59-ZSC-1020B-01 59-T-1020B CPI Tank B Sludge Valve Control Signal Closed Status to DCS DI Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
According to "PF-0004-V517-TRANS-OUT-0016 / PF-0004-517-EE-975-0001
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-XY-1020B-01 59-XY-1020B-01 59-XY-1020B-01 59-T-1020B CPI Tank B Sludge Valve Control Signal Open Signal from DCS DO Non-IS DRY CONTACT DCS 59-JBD-1103-DCS TBD (by SLB) 24 VDC - NO - - - - - - - - - - - - - - - - - TBC NO - Rev A (Code 3)", output signal of DCS is sent to actuator through an isolation E 20.7.2022
PID-271455-000 Sheet 4 of 6 SLB) SLB)
relay. Kindly refer to wiring diagram of valve panel
TBD (by TBD (by
59-HS-1019A-01 59-HS-1019A-01 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-02 59-HS-1019A-02 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-03 59-HS-1019A-03 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-04 59-HS-1019A-04 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-05 59-HS-1019A-05 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-06 59-HS-1019A-06 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019A-07 59-HS-1019A-07 59-P-1019A 59-P-1019A CPI Feed Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-01 59-HS-1019B-01 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-02 59-HS-1019B-02 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-03 59-HS-1019B-03 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-04 59-HS-1019B-04 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-05 59-HS-1019B-05 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-06 59-HS-1019B-06 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019B-07 59-HS-1019B-07 59-P-1019B 59-P-1019B CPI Feed Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-01 59-HS-1019C-01 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-02 59-HS-1019C-02 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-03 59-HS-1019C-03 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-04 59-HS-1019C-04 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
# Schlumberger-Private
Approval Code : ---
POWERED, DRY/WET)
ALARM DESCRPTION
JB NO / RIO CABINET
ENG. RANGE OF INS.
P & ID NO / VENDOR
FIELD TAG NUMBER
INSTRUMENT TYPE
REVISION NUMBER
CONTROL SYSTEM
LINE MONITORING
SYSTEM PRIORITY
CONTROL ACTION
SIGNAL VOLTAGE
TREND/REPORT
DRAWING / ANY
REVISION DATE
CAL. Range URL
SOE REQUIRED
LOOP NUMBER
TERMINAL NO
TIME DELAY
COMMENTS
INTERLOCK
ENGG UNIT
VALVE FAIL
LOCATION
REMARKS
SERVICE
IS/Non-IS
NUMBER
I/O TYPE
HHH
HH
LL
H
L
TBD (by TBD (by
59-HS-1019C-05 59-HS-1019C-05 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-06 59-HS-1019C-06 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019C-07 59-HS-1019C-07 59-P-1019C 59-P-1019C CPI Feed Pump C Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-01 59-HS-1019D-01 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-02 59-HS-1019D-02 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-03 59-HS-1019D-03 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-04 59-HS-1019D-04 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-05 59-HS-1019D-05 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-06 59-HS-1019D-06 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1019D-07 59-HS-1019D-07 59-P-1019D 59-P-1019D CPI Feed Pump D Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-01 59-HS-1020A-01 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-02 59-HS-1020A-02 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-03 59-HS-1020A-03 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
# Schlumberger-Private
Approval Code : ---
POWERED, DRY/WET)
ALARM DESCRPTION
JB NO / RIO CABINET
ENG. RANGE OF INS.
P & ID NO / VENDOR
FIELD TAG NUMBER
INSTRUMENT TYPE
REVISION NUMBER
CONTROL SYSTEM
LINE MONITORING
SYSTEM PRIORITY
CONTROL ACTION
SIGNAL VOLTAGE
TREND/REPORT
DRAWING / ANY
REVISION DATE
CAL. Range URL
SOE REQUIRED
LOOP NUMBER
TERMINAL NO
TIME DELAY
COMMENTS
INTERLOCK
ENGG UNIT
VALVE FAIL
LOCATION
REMARKS
SERVICE
IS/Non-IS
NUMBER
I/O TYPE
HHH
HH
LL
H
L
TBD (by TBD (by
59-HS-1020A-04 59-HS-1020A-04 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-05 59-HS-1020A-05 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-06 59-HS-1020A-06 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020A-07 59-HS-1020A-07 59-O-1020A 59-O-1020A CPI Oil Skimmer A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-01 59-HS-1020B-01 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-02 59-HS-1020B-02 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-03 59-HS-1020B-03 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-04 59-HS-1020B-04 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-05 59-HS-1020B-05 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-06 59-HS-1020B-06 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1020B-07 59-HS-1020B-07 59-O-1020B 59-O-1020B CPI Oil Skimmer B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-01 59-HS-1016A-01 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-02 59-HS-1016A-02 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-03 59-HS-1016A-03 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-04 59-HS-1016A-04 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-05 59-HS-1016A-05 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-06 59-HS-1016A-06 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016A-07 59-HS-1016A-07 59-P-1016A 59-P-1016A Drain Pit Sump Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-01 59-HS-1016B-01 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-02 59-HS-1016B-02 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-03 59-HS-1016B-03 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-04 59-HS-1016B-04 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-05 59-HS-1016B-05 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-06 59-HS-1016B-06 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1016B-07 59-HS-1016B-07 59-P-1016B 59-P-1016B Drain Pit Sump Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-01 59-HS-1022A-01 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-02 59-HS-1022A-02 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-03 59-HS-1022A-03 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-04 59-HS-1022A-04 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-05 59-HS-1022A-05 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-06 59-HS-1022A-06 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022A-07 59-HS-1022A-07 59-P-1022A 59-P-1022A Oil Transfer Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-01 59-HS-1022B-01 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-02 59-HS-1022B-02 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-03 59-HS-1022B-03 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-04 59-HS-1022B-04 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-05 59-HS-1022B-05 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-06 59-HS-1022B-06 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1022B-07 59-HS-1022B-07 59-P-1022B 59-P-1022B Oil Transfer Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-01 59-HS-1021-01 59-A-1021 59-A-1021 Sludge Tank Agitator A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-02 59-HS-1021-02 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-03 59-HS-1021-03 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-04 59-HS-1021-04 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-05 59-HS-1021-05 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-06 59-HS-1021-06 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021-07 59-HS-1021-07 59-A-1021 59-A-1021 Sludge Tank Agitator Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-01 59-HS-1021A-01 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-02 59-HS-1021A-02 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-03 59-HS-1021A-03 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-04 59-HS-1021A-04 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-05 59-HS-1021A-05 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-06 59-HS-1021A-06 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021A-07 59-HS-1021A-07 59-P-1021A 59-P-1021A Sludge Transfer Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-01 59-HS-1021B-01 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-02 59-HS-1021B-02 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-03 59-HS-1021B-03 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-04 59-HS-1021B-04 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-05 59-HS-1021B-05 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-06 59-HS-1021B-06 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1021B-07 59-HS-1021B-07 59-P-1021B 59-P-1021B Sludge Transfer Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-01 59-HS-1024-01 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-02 59-HS-1024-02 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-03 59-HS-1024-03 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-04 59-HS-1024-04 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-05 59-HS-1024-05 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-06 59-HS-1024-06 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024-07 59-HS-1024-07 59-A-1024 59-A-1024 Poly Preparation Tank Agitator Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-01 59-HS-1024A-01 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-02 59-HS-1024A-02 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-03 59-HS-1024A-03 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-04 59-HS-1024A-04 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-05 59-HS-1024A-05 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-06 59-HS-1024A-06 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024A-07 59-HS-1024A-07 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-HS-1024A-08 59-HS-1024A-08 59-P-1024A 59-P-1024A Cat. Poly Dosing Pump A Motor Control Signal Dosing Reference from DCS AO Non-IS 4-20 mA DCS FIELD TBD (by SLB) 24 VDC - - - 100 0 100 - (%) - - - - - - - - - 10 s TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
TBD (by TBD (by
59-HS-1024B-01 59-HS-1024B-01 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-02 59-HS-1024B-02 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-03 59-HS-1024B-03 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Command E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-04 59-HS-1024B-04 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-05 59-HS-1024B-05 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1024B-06 59-HS-1024B-06 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - E 20.7.2022
SLB) SLB)
# Schlumberger-Private
Approval Code : ---
POWERED, DRY/WET)
ALARM DESCRPTION
JB NO / RIO CABINET
ENG. RANGE OF INS.
P & ID NO / VENDOR
FIELD TAG NUMBER
INSTRUMENT TYPE
REVISION NUMBER
CONTROL SYSTEM
LINE MONITORING
SYSTEM PRIORITY
CONTROL ACTION
SIGNAL VOLTAGE
TREND/REPORT
DRAWING / ANY
REVISION DATE
CAL. Range URL
SOE REQUIRED
LOOP NUMBER
TERMINAL NO
TIME DELAY
COMMENTS
INTERLOCK
ENGG UNIT
VALVE FAIL
LOCATION
REMARKS
SERVICE
IS/Non-IS
NUMBER
I/O TYPE
HHH
HH
LL
H
L
TBD (by TBD (by
59-HS-1024B-07 59-HS-1024B-07 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - E 20.7.2022
SLB) SLB)
PF-0004-517-PE-960-0001 / SC26-OPF-PE- TBD (by TBD (by
59-HS-1024B-08 59-HS-1024B-08 59-P-1024B 59-P-1024B Cat. Poly Dosing Pump B Motor Control Signal Dosing Reference from DCS AO Non-IS 4-20 mA DCS FIELD TBD (by SLB) 24 VDC - - - 100 0 100 - (%) - - - - - - - - - 10 s TBC NO - E 20.7.2022
PID-271455-000 Sheet 6 of 6 SLB) SLB)
TBD (by TBD (by
59-HS-1023A-01 59-HS-1023A-01 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-02 59-HS-1023A-02 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-03 59-HS-1023A-03 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-04 59-HS-1023A-04 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-05 59-HS-1023A-05 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-06 59-HS-1023A-06 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023A-07 59-HS-1023A-07 59-P-1023A 59-P-1023A Filter Feed Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-01 59-HS-1023B-01 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-02 59-HS-1023B-02 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-03 59-HS-1023B-03 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-04 59-HS-1023B-04 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-05 59-HS-1023B-05 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-06 59-HS-1023B-06 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023B-07 59-HS-1023B-07 59-P-1023B 59-P-1023B Filter Feed Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-01 59-HS-1023C-01 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-02 59-HS-1023C-02 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-03 59-HS-1023C-03 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-04 59-HS-1023C-04 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-05 59-HS-1023C-05 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-06 59-HS-1023C-06 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1023C-07 59-HS-1023C-07 59-P-1023C 59-P-1023C Filter Feed Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-01 59-HS-1015A-01 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-02 59-HS-1015A-02 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-03 59-HS-1015A-03 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-04 59-HS-1015A-04 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-05 59-HS-1015A-05 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-06 59-HS-1015A-06 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015A-07 59-HS-1015A-07 59-P-1015A 59-P-1015A Filter Backwash Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-01 59-HS-1015B-01 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-02 59-HS-1015B-02 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-03 59-HS-1015B-03 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-04 59-HS-1015B-04 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-05 59-HS-1015B-05 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-06 59-HS-1015B-06 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1015B-07 59-HS-1015B-07 59-P-1015B 59-P-1015B Filter Backwash Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-01 59-HS-1014A-01 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-02 59-HS-1014A-02 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-03 59-HS-1014A-03 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-04 59-HS-1014A-04 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-05 59-HS-1014A-05 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-06 59-HS-1014A-06 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014A-07 59-HS-1014A-07 59-P-1014A 59-P-1014A Treated W ater Discharge Pump A Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-01 59-HS-1014B-01 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Local / Remote Selection from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-02 59-HS-1014B-02 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Start Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-03 59-HS-1014B-03 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Stop Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - 3s Pulse Signal D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-04 59-HS-1014B-04 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Motor Available to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-05 59-HS-1014B-05 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Running Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-06 59-HS-1014B-06 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Fault Status to DCS PF-0004-01Z-EE-985-0024 Rev B DI Non-IS DRY CONTACT DCS MCC TBD (by SLB) 230 VAC - NO - - - - - - - - - - - - - - - - - TBC NO - D 25.5.2022
SLB) SLB)
TBD (by TBD (by
59-HS-1014B-07 59-HS-1014B-07 59-P-1014B 59-P-1014B Treated W ater Discharge Pump B Motor Control Signal Trip Command from DCS PF-0004-01Z-EE-985-0024 Rev B DO Non-IS DRY CONTACT MCC DCS TBD (by SLB) 230 VAC - NC - - - - - - - - - - - - - - - - - TBC NC - D 25.5.2022
SLB) SLB)