PERFECT ENGINEERING AND TRADING COMPANY

19/3-Temple Road, Ground Floor, Behind Farid Tower, Lahore.


Phone: 0345-9225313, Cell: 0300-6734529, E-mail: Perfectengg@hotmail.com

M/S Unilever, Pakistan Date 20-07-2022


Lab Code 001-0722 Sampling Point After UV
Location Drinking Water Filtration Plant, Canteen Unilever.

PHYSIOCHEMICAL ANALYSIS OF WATER


Water Quality Permissible Results Water Quality Permissible Results
Parameter Limits Parameter Limits
Alkalinity (mg/l) 300 (WHO) 180 Conductivity (µs/cm) NGVS 760

Arsenic (ppb) 10 (WHO) 0 Iron (mg/l) 0.3 (WHO) 0.05

Total Hardness (mg/l) 250 (PSQCA) 250 Magnesium (mg/l) 100(PSQCA) 32

Calcium (mg/l) 200 (PSQCA) 46 pH 6.5-8.5 (WHO) 7.8

Carbonate (mg/l) NGVS 0 Turbidity (NTU) 5 (WHO) NA

Chloride (mg/l) 250 (WHO) 68 Sulphate (mg/l) 250 (WHO) 63

Free Chlorine (mg/l) 0.6 (WHO) 0.0 TDS (mg/l) 100-500 (PSQCA) 380

BACTERIOLOGICAL ANALYSIS OF WATE


Micro Species Limits Results
TVC (cfu/100ml) <50 (WHO 70
Total Coliform (MPN/100ml Nil (WHO) Nil

Abbreviations: WHO: World Health Organization PSQCA: Pakistan Standards Quality Control Authority
EC: European Community MPN: Maximum Probable Number NTU: Nephelometric Turbidity Unit ppb: Parts Per Billion NA:
Not Analyzed NGVS: No Guideline Value Set

Analyzed & Verified By: Mohammad Ahmed


(Service Engineer)