Job Title: STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY

Client: LIMA CORPORATION

Engineer: TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan


STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 05-May-22
JOB NAME STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY
JOB CLIENT LIMA CORPORATION
ENGINEER NAME TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER KN
JOINT COORDINATES
1 7.30001 0 0; 2 14.6 0 0; 3 7.30001 0 7.30001; 4 14.6 0 7.30001;
9 9.25002 19.5 5.35001; 17 9.25002 19.5 1.95; 18 12.65 19.5 5.35001;
19 12.65 19.5 1.95; 20 7.94682 6.46807 0.646807; 21 7.94682 6.46807 6.65321;
22 13.9532 6.46807 6.65321; 23 13.9532 6.46807 0.646807;
24 8.59363 12.9361 1.29361; 25 8.59363 12.9361 6.0064;
26 13.3064 12.9361 6.0064; 27 13.3064 12.9361 1.29361;
28 7.62342 3.23404 0.323404; 29 7.62342 3.23404 6.97661;
30 14.2766 3.23404 6.97661; 31 14.2766 3.23404 0.323404;
32 8.27022 9.70211 0.970211; 33 8.27022 9.70211 6.3298;
34 13.6298 9.70211 6.3298; 35 13.6298 9.70211 0.970211;
36 8.92182 16.2181 1.62181; 37 8.92182 16.2181 5.67821;
38 12.9782 16.2181 5.67821; 39 12.9782 16.2181 1.62181;
40 7.62342 3.23404 3.65001; 41 10.95 3.23404 6.97661; 42 14.2766 3.23404 3.65;
43 10.95 3.23404 0.323404; 46 7.46207 1.62055 1.82899;
47 7.46207 1.62055 5.47102; 48 9.12901 1.62055 7.13796;
49 12.779 1.61348 7.13867; 50 14.438 1.62055 5.47102;
51 14.4387 1.61348 1.82101; 52 12.771 1.62055 0.162055;
53 9.12103 1.61348 0.161348; 60 7.78477 4.84753 2.15168;
61 7.78547 4.85458 5.15488; 62 9.45169 4.84753 6.81526;
63 12.4549 4.85458 6.81456; 64 14.1153 4.84753 5.14833;
65 14.1146 4.85458 2.14513; 66 12.4483 4.84753 0.484753;
67 9.44515 4.85458 0.485458; 68 8.27022 9.70211 3.65001;
69 10.95 9.70211 6.3298; 70 13.6298 9.70211 3.65001; 71 10.95 9.70211 0.970211;
76 8.10845 8.08441 2.14777; 77 8.10859 8.08578 5.15097;
78 9.44778 8.08441 6.49157; 79 12.451 8.08578 6.49144;
80 13.7916 8.08441 5.15224; 81 13.7915 8.08578 2.14904;
82 12.4523 8.0844 0.80844; 83 9.44906 8.08578 0.808578;
88 8.43193 11.3191 2.47181; 89 8.43193 11.3191 4.8282;
90 9.77182 11.3191 6.1681; 91 12.1282 11.3191 6.1681;
92 9.77183 11.3191 1.13191; 93 12.1282 11.3191 1.13191;
94 13.4681 11.3191 2.47181; 95 13.4681 11.3191 4.82821;
100 8.92182 16.2181 3.65; 101 10.95 16.2181 5.67821;
102 12.9782 16.2181 3.65001; 103 10.95 16.2181 1.62181;
104 8.75773 14.5771 2.47181; 105 9.77182 14.5771 1.45771;
106 8.75773 14.5771 4.8282; 107 9.77182 14.5771 5.8423;
108 12.1282 14.5771 5.8423; 109 13.1423 14.5771 4.82821;
110 13.1423 14.5771 2.47181; 111 12.1282 14.5771 1.45771;
116 9.08592 17.8591 2.8; 117 9.08592 17.8591 4.50001; 118 10.1 17.8591 5.51411;
119 11.8 17.8591 5.51411; 120 12.8141 17.8591 4.50001;
121 12.8141 17.8591 2.80001; 122 11.8 17.8591 1.78591;

D:\balmaceda\4th Year\2nd Semester\DSS\138kV_TRANSMISSION TOWER.std [05/06/2022 2:38 pm] Page 1 of 8


Job Title: STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY

Client: LIMA CORPORATION

Engineer: TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan


123 10.1 17.8591 1.78591; 124 9.25002 20.5 1.95; 125 12.65 20.5 1.95;
126 9.25002 20.5 5.35001; 127 12.65 20.5 5.35001; 128 9.25002 21.5 1.95;
129 12.65 21.5 1.95; 130 9.25002 21.5 5.35001; 131 12.65 21.5 5.35001;
132 9.25002 22.5 1.95; 133 12.65 22.5 1.95; 134 9.25002 22.5 5.35001;
135 12.65 22.5 5.35001; 136 9.25002 23.5 1.95; 137 12.65 23.5 1.95;
138 9.25002 23.5 5.35001; 139 12.65 23.5 5.35001; 140 9.25002 24.5 1.95;
141 12.65 24.5 1.95; 142 9.25002 24.5 5.35001; 143 12.65 24.5 5.35001;
144 9.25002 25.5001 1.95; 145 12.65 25.5001 1.95; 146 9.25002 25.5001 5.35001;
147 12.65 25.5001 5.35001; 148 9.25002 26.5001 1.95; 149 12.65 26.5001 1.95;
150 9.25002 26.5001 5.35001; 151 12.65 26.5001 5.35001;
152 9.25002 27.5001 1.95; 153 12.65 27.5001 1.95; 154 9.25002 27.5001 5.35001;
155 12.65 27.5001 5.35001; 160 10.95 20 7.85002; 161 10.1 19.75 6.60002;
162 10.1 20.25 6.60001; 163 11.8 19.75 6.60002; 164 11.8 20.25 6.60002;
165 10.95 22 7.85002; 166 10.1 21.75 6.60002; 167 10.1 22.25 6.60001;
168 11.8 21.75 6.60002; 169 11.8 22.25 6.60002; 170 10.95 24 7.85002;
171 10.1 23.75 6.60002; 172 10.1 24.2501 6.60001; 173 11.8 23.75 6.60002;
174 11.8 24.25 6.60002; 181 10.95 20 -0.550001; 182 11.8 20.25 0.700005;
183 10.1 20.25 0.700005; 184 10.1 19.75 0.700005; 185 11.8 19.75 0.700005;
186 10.95 22 -0.550001; 187 11.8 22.25 0.700005; 188 10.1 22.25 0.700005;
189 10.1 21.75 0.700005; 190 11.8 21.75 0.700005; 191 10.95 24 -0.550001;
192 11.8 24.2501 0.700005; 193 10.1 24.2501 0.700005; 194 10.1 23.75 0.700005;
195 11.8 23.75 0.700005; 202 10.95 29.5001 3.65001; 203 10.1 28.5001 2.80001;
204 10.1 28.5001 4.50001; 205 11.8 28.5001 4.50001; 206 11.8 28.5001 2.80001;
207 10.525 29.0001 3.22501; 208 10.525 29.0001 4.07501;
209 11.375 29.0001 3.22501; 210 11.375 29.0001 4.07501;
213 10.95 27.5001 6.65001; 214 11.8 27.5001 6.00001; 215 11.8 27.0001 6.00001;
216 10.1 27.5001 6.00001; 217 10.1 27.0001 6.00001; 220 10.95 27.5001 0.650001;
221 11.8 27.5001 1.3; 222 11.8 27.0001 1.3; 223 10.1 27.5001 1.3;
224 10.1 27.0001 1.3;
MEMBER INCIDENCES
13 3 29; 24 1 28; 27 4 30; 31 20 32; 32 21 33; 33 22 34; 34 2 31; 35 20 21;
36 21 22; 37 23 35; 38 23 22; 39 20 23; 40 24 36; 41 25 37; 42 26 38; 43 27 39;
44 24 25; 45 25 26; 46 27 26; 47 24 27; 72 28 20; 73 29 21; 74 30 22; 75 31 23;
76 28 40; 77 29 41; 78 42 30; 79 43 31; 80 32 24; 81 33 25; 82 32 68; 83 34 26;
84 33 69; 85 35 27; 86 70 34; 87 71 35; 88 36 17; 89 37 9; 90 38 18; 91 39 19;
92 36 100; 93 37 101; 94 102 38; 95 103 39; 96 40 29; 97 41 30; 98 31 42;
99 28 43; 100 1 46; 102 3 48; 103 41 49; 104 50 4; 105 51 42; 106 52 2;
107 53 43; 109 47 3; 112 46 40; 113 40 47; 116 48 41; 118 49 4; 119 42 50;
120 2 51; 121 43 52; 122 1 53; 130 46 28; 131 53 28; 132 47 29; 133 48 29;
134 49 30; 135 50 30; 136 51 31; 137 52 31; 138 60 20; 139 40 61; 140 62 21;
141 41 63; 142 64 22; 143 42 65; 144 66 23; 145 43 67; 150 40 60; 151 61 21;
152 41 62; 153 63 22; 154 42 64; 155 65 23; 156 43 66; 157 67 20; 166 28 60;
167 61 29; 168 29 62; 169 63 30; 170 64 30; 171 66 31; 172 31 65; 173 28 67;
174 68 33; 175 69 34; 176 35 70; 177 32 71; 178 20 76; 179 77 68; 180 21 78;
181 79 69; 182 22 80; 183 81 70; 184 23 82; 185 83 71; 190 76 68; 191 21 77;
192 78 69; 193 22 79; 194 80 70; 195 23 81; 196 82 71; 197 20 83; 206 76 32;
207 83 32; 208 77 33; 209 78 33; 210 80 34; 211 79 34; 212 81 35; 213 82 35;
214 88 24; 215 68 89; 216 90 25; 217 69 91; 218 95 26; 219 70 94; 220 93 27;
221 71 92; 226 68 88; 227 89 25; 228 69 90; 229 91 26; 230 92 24; 231 71 93;
232 94 27; 240 32 88; 241 32 92; 242 33 89; 243 33 90; 244 34 91; 245 35 94;

D:\balmaceda\4th Year\2nd Semester\DSS\138kV_TRANSMISSION TOWER.std [05/06/2022 2:38 pm] Page 2 of 8


Job Title: STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY

Client: LIMA CORPORATION

Engineer: TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan


246 35 93; 247 70 95; 249 34 95; 254 100 37; 255 101 38; 256 39 102;
257 36 103; 258 24 104; 259 106 100; 260 25 107; 261 108 101; 262 26 109;
263 110 102; 264 27 111; 265 105 103; 266 104 100; 267 24 105; 270 104 36;
271 105 36; 272 25 106; 273 107 101; 274 26 108; 275 109 102; 276 27 110;
277 111 103; 284 106 37; 285 107 37; 286 108 38; 287 109 38; 288 110 39;
289 111 39; 290 116 17; 291 117 9; 292 118 9; 293 119 18; 294 120 18;
295 121 19; 296 122 19; 297 123 17; 302 100 116; 303 100 117; 304 101 118;
305 101 119; 306 102 120; 307 102 121; 308 103 122; 309 103 123; 318 36 116;
319 37 117; 320 37 118; 321 38 119; 322 38 120; 323 39 122; 324 39 121;
325 36 123; 330 17 124; 331 9 126; 332 18 127; 333 19 125; 342 124 128;
343 125 129; 344 126 130; 345 127 131; 358 128 132; 359 129 133; 360 130 134;
361 131 135; 382 132 136; 383 133 137; 384 134 138; 385 135 139; 406 136 140;
407 137 141; 408 138 142; 409 139 143; 430 140 144; 431 141 145; 432 142 146;
433 143 147; 454 144 148; 455 145 149; 456 146 150; 457 147 151; 478 148 152;
479 149 153; 480 150 154; 481 151 155; 506 9 161; 507 160 162; 508 18 163;
509 127 164; 510 161 160; 511 162 126; 512 163 160; 513 164 160; 514 161 162;
515 163 164; 516 162 9; 517 164 18; 518 162 164; 519 161 163; 520 164 126;
521 161 18; 522 130 166; 523 165 167; 524 131 168; 525 135 169; 526 166 165;
527 167 134; 528 168 165; 529 169 165; 530 166 167; 531 168 169; 532 167 130;
533 169 131; 534 167 169; 535 166 168; 536 169 134; 537 166 131; 538 138 171;
539 170 172; 540 139 173; 541 143 174; 542 171 170; 543 172 142; 544 173 170;
545 174 170; 546 171 172; 547 173 174; 548 172 138; 549 174 139; 550 172 174;
551 171 173; 552 174 142; 553 171 139; 562 181 184; 563 181 183; 564 181 182;
565 181 185; 566 182 125; 567 183 124; 568 184 17; 569 185 19; 570 184 183;
571 183 182; 572 182 185; 573 185 184; 574 182 124; 575 184 19; 576 186 189;
577 186 188; 578 186 187; 579 186 190; 580 187 133; 581 188 132; 582 189 128;
583 190 129; 584 189 188; 585 188 187; 586 187 190; 587 190 189; 588 187 132;
589 189 129; 590 191 194; 591 191 193; 592 191 192; 593 191 195; 594 192 141;
595 193 140; 596 194 136; 597 195 137; 598 194 193; 599 193 192; 600 192 195;
601 195 194; 602 192 140; 603 194 137; 616 152 203; 617 154 204; 618 153 206;
619 155 205; 620 203 207; 621 204 208; 622 205 210; 623 206 209; 624 203 204;
625 204 205; 626 205 206; 627 206 203; 628 152 204; 629 154 203; 630 154 205;
631 155 204; 632 155 206; 633 153 205; 634 153 203; 635 152 206; 636 207 202;
637 208 202; 638 209 202; 639 210 202; 640 203 208; 641 204 207; 642 206 207;
643 203 209; 644 206 210; 645 205 209; 646 205 208; 647 204 210; 650 150 217;
651 213 216; 652 213 215; 653 213 214; 654 214 155; 655 215 151; 656 216 154;
657 217 213; 658 215 214; 659 214 216; 660 216 217; 661 217 215; 664 153 221;
665 220 223; 666 148 224; 667 149 222; 668 221 220; 669 222 220; 670 223 152;
671 224 220; 672 221 223; 673 223 224; 674 224 222; 675 222 221; 676 150 216;
677 151 214; 678 148 223; 679 149 221; 680 221 152; 681 224 149; 682 214 154;
683 217 151; 712 17 130; 713 9 128; 714 128 138; 715 130 136; 716 136 146;
717 138 144; 718 144 154; 719 146 152; 720 19 131; 721 18 129; 722 129 139;
723 131 137; 724 137 147; 725 139 145; 726 145 155; 727 147 153; 772 152 153;
773 154 155; 774 134 135; 775 142 143; 777 138 139; 779 140 141; 780 150 151;
781 136 137; 782 132 133; 783 128 129; 784 130 131; 785 148 149; 786 146 147;
787 144 145; 788 18 19; 789 9 17; 790 19 17; 791 18 9; 792 155 153;
793 152 154; 794 153 148; 795 148 145; 796 145 140; 797 140 137; 798 137 132;
799 132 129; 800 155 150; 801 150 147; 802 147 142; 803 142 139; 804 139 134;
805 134 131; 806 131 126; 807 126 18; 808 129 124; 809 124 19; 810 124 125;
811 127 126;

D:\balmaceda\4th Year\2nd Semester\DSS\138kV_TRANSMISSION TOWER.std [05/06/2022 2:38 pm] Page 3 of 8


Job Title: STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY

Client: LIMA CORPORATION

Engineer: TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan


START GROUP DEFINITION
MEMBER
_LEGS1 13 24 27 31 TO 34 37 40 TO 43 72 TO 75 80 81 83 85 88 TO 91
_LEGS2 330 TO 333 342 TO 345 358 TO 361 382 TO 385 406 TO 409 430 TO 433 454 -
455 TO 457 478 TO 481
_BRACE1 76 TO 79 96 TO 100 102 TO 107 109 112 113 116 118 TO 122 130 TO 137
_BRACE2 35 36 38 39 138 TO 145 150 TO 157 166 TO 173
_BRACE3 82 84 86 87 174 TO 185 190 TO 197 206 TO 213
_BRACE4 44 TO 47 214 TO 221 226 TO 232 240 TO 247 249
_BRACE5 92 TO 95 254 TO 267 270 TO 277 284 TO 289
_BRACE6 290 TO 297 302 TO 309 318 TO 325
_WINGS 506 TO 553 562 TO 603 616 TO 647 650 TO 661 664 TO 683
_LOWERBRACE 35 36 38 39 44 TO 47 76 TO 79 82 84 86 87 92 TO 100 102 TO 107 -
109 112 113 116 118 TO 122 130 TO 145 150 TO 157 166 TO 185 190 TO 197 206 -
207 TO 221 226 TO 232 240 TO 247 249 254 TO 267 270 TO 277 284 TO 297 302 -
303 TO 309 318 TO 325
_DIAGONALS 35 36 38 39 44 TO 47 100 102 TO 107 109 112 113 116 118 TO 122 -
138 TO 145 150 TO 157 178 TO 185 190 TO 197 214 TO 221 226 TO 232 247 258 -
259 TO 267 272 TO 277 290 TO 297 302 TO 309
_BRACEINNER 130 TO 137 166 TO 173 206 TO 213 240 TO 246 249 270 271 -
284 TO 289 318 TO 325
_BRACING_DIAG 712 TO 727
_BRACING_DIAG2 794 TO 809
_BRACING_HOR 772 TO 775 777 779 TO 793 810 811
_FAILED 361 721 807 809
JOINT
END GROUP DEFINITION
DEFINE MATERIAL START
ISOTROPIC STEEL
E 2.05e+08
POISSON 0.3
DENSITY 76.8195
ALPHA 1.2e-05
DAMP 0.03
G 7.88462e+07
TYPE STEEL
STRENGTH FY 0 FU 0 RY 1.5 RT 1.2
ISOTROPIC STEEL_275_NMM2
E 2.05e+08
POISSON 0.3
DENSITY 76.8195
ALPHA 1.2e-05
DAMP 0.03
TYPE STEEL
STRENGTH FY 0 FU 0 RY 1.5 RT 1.2
END DEFINE MATERIAL
MEMBER PROPERTY AMERICAN
76 TO 79 96 TO 99 138 139 142 143 150 151 154 155 178 179 182 183 190 191 -
194 195 TABLE LD L25255
82 84 86 87 92 TO 95 174 TO 177 214 215 218 219 226 227 232 247 254 TO 267 -

D:\balmaceda\4th Year\2nd Semester\DSS\138kV_TRANSMISSION TOWER.std [05/06/2022 2:38 pm] Page 4 of 8


Job Title: STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY

Client: LIMA CORPORATION

Engineer: TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan


272 TO 277 290 TO 297 302 TO 309 TABLE ST L40406
130 TO 137 166 TO 173 206 TO 213 240 TO 246 249 270 271 284 TO 289 -
318 TO 325 TABLE ST L25253
712 713 720 721 TABLE LD L30306
102 103 106 107 116 118 121 122 140 141 144 145 152 153 156 157 180 181 184 -
185 192 193 196 197 216 217 220 221 228 TO 231 TABLE ST L40406
13 24 27 34 72 TO 75 TABLE ST L808012
507 509 511 513 TO 519 523 525 527 529 TO 535 539 541 543 545 TO 551 563 564 -
566 567 570 TO 573 577 578 580 581 584 TO 587 591 592 594 595 598 TO 601 -
616 TO 627 636 TO 647 650 TO 661 664 TO 679 TABLE ST L20203
31 TO 33 37 80 81 83 85 TABLE ST L808010
40 TO 43 88 TO 91 TABLE ST L606010
330 TO 333 342 TO 345 382 TO 385 406 TO 409 430 TO 433 TABLE ST L404012
358 TO 361 454 TO 457 478 TO 481 TABLE ST L40407
772 TO 775 777 779 TO 793 810 811 TABLE LD L25253
794 TO 797 800 TO 803 TABLE LD L25253
714 TO 719 722 TO 727 TABLE LD L30304
44 TO 47 TABLE ST L50508
35 36 38 39 TABLE LD L40406
798 799 804 TO 809 TABLE ST L40408
100 104 105 109 112 113 119 120 TABLE LD L25254
506 508 510 512 520 TO 522 524 526 528 536 TO 538 540 542 544 552 553 562 -
565 568 569 574 TO 576 579 582 583 588 TO 590 593 596 597 602 603 630 631 -
634 635 680 TO 683 TABLE ST L30303
628 629 632 633 TABLE LD L20202
CONSTANTS
BETA 45 MEMB 44 45 92 93 133 135 137 206 209 210 213 214 218 226 231 241 242 -
244 245 247 254 255 259 261 263 265 267 270 272 274 276 285 287 290 292 294 -
296 302 304 306 308 319 321 324 325 331 344 360 384 408 432 456 480
BETA 135 MEMB 82 84 86 87 130 174 TO 177 332 345 361 385 409 433 457 481
BETA 315 MEMB 46 47 94 95 207 208 211 212 215 219 227 232 240 243 246 249 -
256 258 260 262 264 266 271 273 275 277 284 286 288 291 293 295 297 303 305 -
307 309 318 320 322 323 330 342 358 382 406 430 454 478
BETA 225 MEMB 131 132 134 136 166 TO 173 333 343 359 383 407 431 455 479
MATERIAL STEEL_275_NMM2 MEMB 214 TO 221 226 TO 232 240 TO 247 249
MATERIAL STEEL ALL
SUPPORTS
1 TO 4 FIXED
DEFINE REFERENCE LOADS
LOAD R1 LOADTYPE Dead TITLE D
SELFWEIGHT Y 1
JOINT LOAD
160 165 170 181 186 191 213 220 FY -2.865
160 165 170 181 186 191 213 220 FX 10.84
160 165 170 181 186 191 213 220 FX -10.84
202 FX 4.725
202 FX -4.725
202 FY -1.26
202 FZ 18.475
160 165 170 181 186 191 213 220 FZ 23.327

D:\balmaceda\4th Year\2nd Semester\DSS\138kV_TRANSMISSION TOWER.std [05/06/2022 2:38 pm] Page 5 of 8


Job Title: STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY

Client: LIMA CORPORATION

Engineer: TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan


LOAD R2 LOADTYPE Dead TITLE BROKEN WIRE
JOINT LOAD
160 165 170 181 186 191 213 220 FY -1.4325
160 165 170 181 186 191 213 220 FX 10.84
202 FX 4.725
202 FY -1.26
202 FZ 9.2375
160 165 170 181 186 191 213 220 FZ 11.6635
END DEFINE REFERENCE LOADS
DEFINE WIND LOAD
TYPE 1 WIND X
<! STAAD PRO GENERATED DATA DO NOT MODIFY !!!
ASCE-7-2010:PARAMS 270.000 KMPH 5 1 1 0 0.000 FT 0.000 FT 0.000 FT 1 1 -
29.100 M 7.300 M 60.000 2.577 0.010 0 0 0 1 0.974 1.000 1.000 0.850 0 1 0 0 -
0.850 1.900 -0.550
!> END GENERATED DATA BLOCK
INT 2.72195 2.72195 2.95514 3.14968 3.3181 3.4675 3.60235 3.72564 3.8395 -
3.94549 4.04481 4.13837 4.22693 4.31108 4.39131 4.46804 4.54161 4.61231 HEIG -
0 4.572 6.096 7.62 9.144 10.668 12.192 13.716 15.24 16.764 18.288 19.812 -
21.336 22.86 24.384 25.908 27.432 28.956
TYPE 2 WIND Z
<! STAAD PRO GENERATED DATA DO NOT MODIFY !!!
ASCE-7-2010:PARAMS 270.000 KMPH 5 1 1 0 0.000 FT 0.000 FT 0.000 FT 1 1 -
29.100 M 8.100 M 60.000 2.580 0.010 0 0 0 1 0.974 1.000 1.000 0.850 0 1 0 0 -
0.850 1.900 -0.550
!> END GENERATED DATA BLOCK
INT 2.72195 2.72195 2.95514 3.14968 3.3181 3.4675 3.60235 3.72564 3.8395 -
3.94549 4.04481 4.13837 4.22693 4.31108 4.39131 4.46804 4.54161 4.61231 HEIG -
0 4.572 6.096 7.62 9.144 10.668 12.192 13.716 15.24 16.764 18.288 19.812 -
21.336 22.86 24.384 25.908 27.432 28.956
<! STAAD PRO GENERATED DATA DO NOT MODIFY !!!
!> END GENERATED DATA BLOCK
<! STAAD PRO GENERATED DATA DO NOT MODIFY !!!
!> END GENERATED DATA BLOCK
LOAD 1 LOADTYPE Dead TITLE D
REFERENCE LOAD
R1 1.0
REFERENCE LOAD
R2 1.0
LOAD 2 LOADTYPE Wind TITLE WX
WIND LOAD X 1 TYPE 1 YR 0 29.1 ZR -1 8.1 OPEN
WIND LOAD -X 0.3 TYPE 1 YR 0 29.1 ZR -1 8.1 OPEN
WIND LOAD -Z 0.7 TYPE 1 XR 7.3 14.6 YR 0 29.1 OPEN
WIND LOAD -Z -0.7 TYPE 1 XR 7.3 14.6 YR 0 29.1 OPEN
LOAD 3 LOADTYPE Wind TITLE WZ
WIND LOAD Z 1 TYPE 1 XR 7.3 14.6 YR 0 29.1 OPEN
WIND LOAD -Z -0.3 TYPE 1 XR 7.3 14.6 YR 0 29.1 OPEN
WIND LOAD -X 0.7 TYPE 1 YR 0 29.1 ZR -1 8.1 OPEN
WIND LOAD -X -0.7 TYPE 1 YR 0 29.1 ZR -1 8.1 OPEN
LOAD COMB 101 1.4(D + F)

D:\balmaceda\4th Year\2nd Semester\DSS\138kV_TRANSMISSION TOWER.std [05/06/2022 2:38 pm] Page 6 of 8


Job Title: STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY

Client: LIMA CORPORATION

Engineer: TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan


1 1.4
LOAD COMB 102 1.2(D + F + T) + 1.6(L + H) + 0.5LR
1 1.2
LOAD COMB 103 1.2D + 1.6(LR OR R) + 0.5WX
1 1.2 2 0.5
LOAD COMB 104 1.2D + 1.6(LR OR R) + 0.5WZ
1 1.2 2 0.5
LOAD COMB 105 1.2D + 1.6(LR OR R) - 0.5WX
1 1.2 2 -0.5
LOAD COMB 106 1.2D + 1.6(LR OR R) - 0.5WZ
1 1.2 3 -0.5
LOAD COMB 107 1.2D + 1.0WX + F1L + 0.5(LR OR R)
1 1.2 2 1.0
LOAD COMB 108 1.2D + 1.0WZ + F1L + 0.5(LR OR R)
1 1.2 3 1.0
LOAD COMB 109 1.2D - 1.0WX + F1L + 0.5(LR OR R)
1 1.2 2 -1.0
LOAD COMB 110 1.2D - 1.0WZ + F1L + 0.5(LR OR R)
1 1.2 3 -1.0
LOAD COMB 111 1.2D + 1.0EX + F1L
1 1.2
LOAD COMB 112 (1.2D+0.5CALD) +- 1.0EX +- 0.3EZ + F1L
1 1.4312
LOAD COMB 113 0.9D + 1.0WX + 1.6H
1 0.9 2 1.0
LOAD COMB 114 0.9D + 1.0WZ + 1.6H
1 0.9 3 1.0
LOAD COMB 115 0.9D - 1.0WX + 1.6H
1 0.9 2 -1.0
LOAD COMB 116 0.9D - 1.0WZ + 1.6H
1 0.9 3 -1.0
LOAD COMB 117 0.9D + 1.0EX + 1.6H
1 0.9
LOAD COMB 118 (0.90D-0.5CALD) +- 1.0EX +- 0.30EZ
1 0.6688
LOAD COMB 119 (0.90D-0.5CALD) +- 1.0EZ +- 0.30EX
1 0.6688
LOAD COMB 201 W.D. WX 1.0D + 0.5L + 0.5LR + 1.0WX
1 1.0 2 1.0
LOAD COMB 202 W.D. WZ 1.0D + 0.5L + 0.5LR + 1.0WZ
1 1.0 3 1.0
LOAD COMB 301 D + F
1 1.0
LOAD COMB 302 D + H + F + 0.6WX
1 1.0 2 0.6
LOAD COMB 303 D + H + F + 0.6WZ
1 1.0 3 0.6
LOAD COMB 304 D + H + F - 0.6WX
1 1.0 2 -0.6
LOAD COMB 305 D + H + F - 0.6WZ

D:\balmaceda\4th Year\2nd Semester\DSS\138kV_TRANSMISSION TOWER.std [05/06/2022 2:38 pm] Page 7 of 8


Job Title: STRUCTURAL DESIGN OF 138 KV D/C TRANSMISSION TOWER IN BATANGAS CITY

Client: LIMA CORPORATION

Engineer: TEAM X - Balmaceda, Lumaad, Panaligan, Torres, Wagan


1 1.0 3 -0.6
PERFORM ANALYSIS
DEFINE ENVELOPE
101 TO 119 ENVELOPE 1 TYPE STRENGTH
201 202 ENVELOPE 2 TYPE STRENGTH
301 TO 305 ENVELOPE 3 TYPE SERVICEABILITY
END DEFINE ENVELOPE
PARAMETER 1
CODE AISC UNIFIED 2016
CHECK CODE ALL
FINISH