S-23 Push Button Token Less Block Instrument For Single Line
S-23 Push Button Token Less Block Instrument For Single Line
• Line Closed
(White): when lit,
indicates that the
section has been
closed.
Neutral Line
1 QN1 8F-8B 28
Relay
2 QL1 Latch relays 8F-6B 4
3 QB3 Biased relays 4F-2B 3
Electronic
4 ET -- 1
Timer
Condenser units with Q relay base (U-I,
5 4
U-II, U-III & U-IV)
Telephone
1. 3 V Battery
Circuit
24 V Battery with each battery 2 V 120 AH
cells 13 nos. are preferable as minimum 24
Local Circuit V on load is
2.
required for its reliable working.
External
4. 24 V battery
circuit
SCKR CIRCUIT
17 SCKR 43
SNR
ASR
SNR K
2. 2 K
SNR CIRCUIT
SNR relay picks up by proving SCKR front contact and other
conditions
5/4/2020 S-23 Tokenless block instrumets VER 1.0
ASTR: ADVANCE STARTER TRACK
RELAY
R ASTR
CANCEL CAR ASTR
P
TGBR ASCR
ASTR CIRCUIT
ASTR : It is a repeater for the FVT relay and can pick up whenever the
TGB is pressed and sticks once TGT is established. It drops once FVT is
actuated.
TAR
CIRCUIT
TAR:It is a magnetic latch relay and used for registering the arrival
of a train on line clear. It picks up through the external battery while
receiving a train on signals with Instrument in TCF-TOL/TGT-TOL
condition and de latches to normal through local battery once the
instrument assumes to lineS-23 closed position.
Tokenless block instrumets
5/4/2020
VER 1.0
RELAYS ENERGIZED FROM
LINE BATTERY
Whenever this relay picks up either +ve or _ve pulse will be on line
1 +
LCBR
PTR NTR
4 -
TOLTR
CTPR TGBR
CTPR BCBR
LPR
CTR
CIRCUIT
N N
NTR CIRCUIT
NTR : Negative transmission relay. when ever negative is connected to Line 1 this
relay is in pick up condition .initially it picks up with 1CR ,2CR and 3CR back
contact along with PTR back contact
5/4/2020 S-23 Tokenless block instrumets VER 1.0
LR
TAR
N PCR
PCR CIRCUIT
opp
LINE CIRCUIT
250
10W LCBR BCBR LPR CTPR RCKR CTR L1 CTR RCKR CTPR BCBR
Tele.
LINE CIRCUIT FOR BELL AND TELEPHONE 2f
Tele.
TCF.
After setting to TCF, triggers TGT Code to
Station A.
NTR
NTR
F/CF/C
PTR F/C
y
Supply
Suppl CRR( RD
Suppl
toto y to R) R
CRR(N)
CRR(R
CRR(
) R)
TOL
CRR( TCF
A
N) R
R
RCKR
TGT Code Transmission
StationA Station B
NNTTRRF/C
PTR F/C
F/C
Supply to
RD SSupp uppll
R CRR(N)
yyttoo
CCRR RR((
R)R)
TOL
A
R
TGT
R
TIMMING DIAGRAM FOR TGT CODE
LINE CLEAR CONDITION B/I RELAY
POSITION
STATION-A STATION-B
ASTR TOLAR
SNR TCFR
TCFPR
TOLAR
ASR
TGTR
TGTPR
StationA TOL Code Transmission Station B
NTR
NTR F/C
F/C
Suppl RD
Suppl
y to R
y to
CRR(
CRR(
R)
R)
TO
L TCF
R
AR
TOL
T
R
TIMMING DIAGRAM FOR TOL CODE
Auto TOL code transmission.
PTR
PNTTRRF/C
RD FF/CC
Supply
R SS
toupupplply
y to
CRR(N
)CCRR RR(
R)N)
P2
R
LCC
PR
TIMMING DIAGRAM FOR LC
CODE
S-23
PUSH BUTTON BLOCK
INSTRUMENT CIRCUITS
Tele.
LINE CIRCUIT FOR BELL AND TELEPHONE 2f
Tele.
LCCPR RCKR
SHKR: it will pick up through BCBR front contact along with LCBR
/TGBR front
contact, it Has five path
5/4/2020 S-23 Tokenless block instrumets VER 1.0
SCKR AND SNR CIRCUITS
EKT
36 SNR SHKR
SCKR
SCKR
SCKR CIRCUIT
17 SCKR 43
SNR
ASR
SNR K
2. 2 K
SNR CIRCUIT
SNR relay picks up by proving SCKR front contact and other
conditions
5/4/2020 S-23 Tokenless block instrumets VER 1.0
CTR CIRCUIT
3CR LR 1CR TOLTR TGB TGTPR
P
CTR CIRCUIT
N N
NTR CIRCUIT
NTR : Negative transmission relay. when ever negative is connected to Line 1 this
relay is in pick up condition .initially it picks up with 1CR ,2CR and 3CR back contact
along with PTR back contact
TCKR AND CRR LINE CIRCUIT
TOLTR
1 +
LCBR
PTR NTR
4 -
TOLTR
CTPR TGBR
CTPR BCBR
LPR
LCCPR CRR(R)
LR PTR
LR
TCKR NTR 47 470f
U II
LR CIRCUIT
LR - Coding Relay. This is the relay that is reacted on first by CRR(R) or TCKR while
the instrument is receiving or transmitting respectively. By picking up and dropping
alternately as required it activates progresses and terminates the functioning of the
coding circuit. So, the feeding circuits to this relay consists of two branches, one
with TCKR and PTR/NTR contacts and the other CRR(R), CRR(N) contacts .
LPR CIRCUIT
LR 1CR
U
III
1CR is coding relay with the
combination of 2CR and 3CR
arrange dc pulse code NTR on
and off and PTR on and off 1CR CIRCUIT
conditions
S-23 Tokenless block instrumets
5/4/2020
VER 1.0
CTPR CIRCUIT
CTPR CIRCUIT
CTPR - Repeater of CTR. This repeats the CTR while the instrument is
transmitting code, but remains energized till the complete answer back
code is received. A time delay circuit measures the time taken by the other
instrument to answer back. If the instrument does not respond within a
definite time, CTPR releases and reset all relays and code transmission is
initiated all over again.
S-23 Tokenless block instrumets
5/4/2020
VER 1.0
RDR CIRCUIT
CAR TAR LPR R1 R2
N RDR
LR RDR
• RDR - Receiving delivery relay – This stores the first pulse of any code when it is
negative and remains energized till code reception is complete and relay 3CR de-
energizes.
S-23 Tokenless block instrumets
5/4/2020
VER 1.0
RCKR CIRCUIT
RCKR CIRCUIT
RCKR - Code reception checking relay – This senses the progress of the coding
circuit at the receiving end and when picked up, terminates the pulse that is being
received by opening the line circuit. This relay prepares the instrument for automatic
answer back.
S-23 Tokenless block instrumets
5/4/2020
VER 1.0
2CR CIRCUIT
LPR LR 2 CR R1 R2
2 CR
U II
LPR 3CR R1 R2
3CR
U III
3CR CIRCUIT
3CR is coding relay with the combination of 2CR and 3CR arrange dc pulse
code NTR on and off and PTR on and off conditions
1CR TCKR RDR 2CR CRR(R) P2R TGTR TCFPR R1 TAR TOLAR
R2 CAR TGTPR PCR
N TCFR N R
R3 R4
CRR(N) ASR LCCPR P2R LCBR BCBR TGTPR SNR
TCFR CIRCUIT
R ASTR
CANCEL CAR ASTR
P
TGBR ASCR
ASTR CIRCUIT
ASTR : It is a repeater for the FVT relay and can pick up whenever the
TGB is pressed and sticks once TGT is established. It drops once FVT is
actuated.
TCFR
R
PCR TGTR TCFR
N N
2CR 3CR CTPR TOLTR PCR LCCPR
1CR 2CR 3CR TOLTR PCR TGTR TCFR NTR RDR RCKR CTR
N N PTR
PTR CIRCUIT
PTR – Positive Transmitting Relay. This relay switch on positive pulse on line by
connecting the line battery to line appropriately. Stick feed to these over TCKR front
contact ensures the presence of pulse on line till the line circuit is opened.
P2R/N2R CIRCUIT
• P2R & N2R - Second positive and second negative pulse receiving relays.
These store the polarity of the second pulse of a code that is received. Front
contacts of these are used in the circuit of the final relay.
S-23 Tokenless block instrumets
5/4/2020
VER 1.0
TOLAR CIRCUIT
P2R
TOLAR CIRCUIT
ASR CIRCUIT
LCCPR SHKR
LCCPR CIRCUIT
ASCR CIRCUIT
TCFPR/TGTPR CIRCUIT
R
TOLTR CIRCUIT
• TOLTR - TOL code transmitting relay. At the sending station, this relay picks
up when the ASTR and ASR drop successively due to the train occupying
the FVT while entering the block section. Consequently, CTR picks up to
transmit TOL code. At the receiving station, this picks up in response to TOL
code received from line. The buzzer sounds intermittently, when the SM
acknowledges the TOL code by pressing BCB to transmit a bell code, the
TOLAR at the sending station drops and causes TOLTR to drop to stop the
transmission of TOL Code.S-23 Tokenless block instrumets
5/4/2020
VER 1.0
TAR CIRCUIT
TAR
CIRCUIT
:
•TAR It is a magnetic latch relay and used for registering the arrival of a train on
line clear. It picks up through the external battery while receiving a train on
signals with Instrument in TCF-TOL/TGT-TOL condition and de latches to
normal through local battery once the instrument assumes to line closed
position.
S-23 Tokenless block instrumets
5/4/2020
VER 1.0
PCR CIRCUIT
TAR
N PCR
PCR CIRCUIT
CAR - Cancellation Relay. This picks up for cancellation of Line Clear when
the BCB and cancel buttons are pressed along with some more conditions .
This pushes the counter by one digit.
INDICATION CIRCUIT
INDICATION CIRCUIT gives various indications on the panel like line close
,TCF green and TGT green by proving the above conditions.
TCFPR
TOLAR TCFPR
N
TOL INDICATION CIRCUIT
INDICATION CIRCUIT TOL(R)k will lit when train enters the block section
by proving conditions TGTR latched and TGTPR front contact in one path
and other path is also available through TOLAR
14. Train arrival buzzer -do- TAR not picked up (or) not
failure holding.
Do,s
Operating department:
(1) Ensure SM’s key/ SHK /SCK “IN” for
taking Line Clear.
(2)Block competency Authorized person only
shall operate Block Instrument.
Operating department:
(1)Do not allow unauthorized person
to operate the Block Instrument.
(2)Do not allow to interfere with the Block
Instrument without proper
disconnection.