SUBMITTAL MCU-R4NEK0N Page 1 of 2

Samsung DVM S Eco Series, HR Changer

Job Name Location


Purchaser Engineer
Submitted to Reference Approval Construction
Unit Designation Schedule #

Specifications
Voltage (ø/V/Hz) 1 / 208-230 / 60 • Compatible with Samsung DVM S Eco Heat Recovery
(AM0**NXMDCR/AA) systems only.
Max Current A 1.6
Power 0.2 • Allows for simultaneous heating and cooling on a single system.
Rated Controller Current A
Minimum Circuit Ampacity A 2 • HR Changer is mandatory for DVM S Eco Heat Recovery systems
and must be connected to the outdoor unit before any additional
Max. Breaker MOP (A) 15
MCU's.
MCU total1 76,000
Maximum Btu/h • Serial connection capability to supply refrigerant to other MCU's thus
Each Port1 ≤ 19,0001 reducing Y-joint installation quantity (see example below).
Capacity
Number of Ports 4
• The HR Changer shall have pressure equalization valves (480 steps)
Quantity of Connectable Indoor Units2 1 - 12 to reduce refrigerant sounds during mode changing of connected
indoor units.
Liquid (braze) 3/8
Inlet Pipes From ODU
• Using solenoid valves, the HR Changer shall control the path of
and Outlet Pipes To Suction (braze) 3/4 refrigerant to the indoor unit(s) based on the mode of operation
Piping
Other MCU's required.
Connections HP Gas (braze) 5/8
(inches) • The unit shall contain internal subcoolers with an electronic expansion
Liquid (braze) 1/4 X 4
To Indoor Units valve to maximize performance of connected units and reduce
Suction (braze) 1/2 X 4 refrigerant sounds
Standard Operation High dB (A) 34 • If connecting an indoor unit > 19,000 Btu/h and ≤ 48,000 Btu/h, 2
Sound Level
Mode Switching High dB (A) 50 consecutive ports must be twinned.

Unit WXHXD Inches 28 11/16 X 7 13/16 X 18 7/16 • The HR Changer must be mounted indoors, level, with the pipes
Dimensions running horizontally in and out of unit.
Weight lbs. 46.96
• No drain connection required
Safety Certifications ETL (UL 1995)
1 Ifconnecting an indoor unit > 19,000 Btu/h and ≤ 48,000 Btu/h, 2 consecutive ports must be twinned using Y-Joint Construction
kit part number MXJ-YM1206R. Y-Joint kits are purchased separately. • Galvanized steel cabinet
2 Maximum of 3 indoor units allowed on a single port. Twinned ports cannot connect to multiple indoor units. Please

use DVM Pro design software for system design.


• Most internal devices can be serviced via bottom panel. The PCB
and wiring is accessible from the back.
Accessory Y-Joint - Combining Two Ports Controls
• The unit shall be operated via a DDC type signal

Connections to • Control wiring shall be 16 AWG X 2 shielded wire


outdoor unit
• Supports auto-pairing

Connect to an indoor unit > 19,000 Btu/h and ≤ 48,000 Btu/h Connection Example
(if less than 19,000 Btu/h connect direct to MCU without Y-
connector using a single set of ports)

outdoor unit can only


connect to one specific
side of HR Changer

(MCU-R4NEK0N)

(TOP) (TOP)
MXJ-YM1206R Sub MCU

Series connection

Connections to
sub MCU (if used)

TOP VIEW
(PICTURED WITHOUT COVER)

Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.
© 2020 Samsung HVAC www.SamsungHVAC.com
SHA-DVMS-04212020 888-699-6067
Page 2 of 2
SUBMITTAL MCU-R4NEK0N
Samsung DVM S Eco Series, HR Changer

TOP

32 1/8"
30 1/16"
28 5/8" Control Box

Suspension

2 5/8"
Point (X4)
Low pressure gas

High pressure gas


18 7/16"
8 13/16"

Liquid

3 15/16"
3 1/2"

5 1/16"
3 11/16"

FRONT SIDE
18 7/16"
2 9/16" 2 3/4" X 3= 8 1/4" 4"
5 1/8" 3 15/16" 2 5/8"
Control
Box
7 7/8"

7 3/4"

6 5/16"

2"
3 3/4" 2 3/4" X 3 = 8 1/4"

2 3/4"

6 1/4"
3 15/16"

Recommended Installation Clearances

16" or more Ceiling


28 5/8" 3" minimum
(recommended)

HR Changer
7 7/8"
18 7/16"

HR Changer
(TOP)

20" or more

20" or more 28" or more

www.SamsungHVAC.com