Professional Documents
Culture Documents
TR 149
TR 149
net/publication/282334141
CITATIONS READS
6 253
10 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Ramesh Joshi on 01 October 2015.
1
1. Introduction:
Ion Cyclotron Resonance Heating (ICRH) is a promising heating method for a
fusion device due to its localized power deposition profile, a direct ion heating at
high density, and established technology for high power handling at low cost. For
the same reason 1.5-Megawatt ICRH system is developed for steady state
superconducting tokamak (SST-1). (ref: 10.1)
SST-1 is a large aspect ratio tokamak with wide range of elongation (1.7-1.9) &
triangularity (0.4- 0.7). The maximum plasma current is expected to be 220kA.The
maximum toroidal magnetic field at the center is 3.0T. The major & minor radii are
1.1 meter & 0.2 meter. 1.5 MW of RF power is to be delivered to the plasma for
pulse lengths of upto 1000 second [1].
Slow on-line impedance matching (say in order of second) would be achieved with
the coarse-matching network. It consists of following components.
Coarse Stub: Mechanical shunt tuners are added at appropriate positions on the
main transmission line. The reactance of such shorted stub is varied by varying
length of the stub.
Coarse Phase-shifter: Mechanical phase shifters are added to the transmission line.
The reactance of such shorted stub is varied by varying length of the phase shifter.
As it involves mechanical movement, matching is expected to achieve in few
seconds.
AMN consists of two motorized 0.5-meter stubs & two motorized vacuum variable
capacitors (VVC) connected in parallel to each other. This network is located
between the generator & the coarse matching network. In the beginning of any
plasma shot operation AMN systems are kept in NULL position. At Null position
2
of the system, inductive reactance (XL) provided by the stub movement is equal in
magnitude but opposite in direction of capacitive reactance (XC) provided by the
VVC, thus net reactance in the system cancels out each other’s effect.
During tokamak operation plasma load impedance may be inductive and capacitive
depending on the plasma parameters & its position of plasma in vacuum vassal.
Hence, AMN system has to operate in such a way so it can match both inductive &
capacitive loads. Keeping the 0.5meter stub to lower limit position & VVC at its
6th turn of rotation ensures null position in the system. Movement of VVC motor
towards lower turn from its null position provides inductive reactance to the system
& towards higher turn provides capacitive reactance to the system. So in AMN
operation only VVC motor moves & stub remains static [1][2][3].
24 probe signals are taken out from the probe section of the ICRH-transmission
line. These signal are acquired, digitized in high speed analog board at the rate of
1ms. Software programming written in VME system does the calculation from
these signals as per the RF error signal equations & generates the directional signal
to motor-controller for the movement of the VVC motor in case of mismatched
load.
Figure 1: Real time feedback controlled ICRH – AMN System for SST-1
Magnitude of the probe signals change because of the new VVC movement &
again new error signal calculations are performed which causes new directional
3
signal to be generated to the motor-controller for the VVC movement. This keeps
continuing till the error signal becomes zero (it ensures that load is matched).
2. ICRH System overview: The block diagram of the ICRH system as shown
in the figure2 having following sub-systems.
Probe section: From this section 22 voltages probe signals are taken out for
VSWR plot. Two signals are used for error signal calculation of AMN & hence for
matching. The distance between two probe positions is 210 mm.
Direction Coupler: From direction coupler forward & reflected power signals are
taken out for error signal calculations of the AMN.
RF Automatic Coarse
source Tx. Probe Direction
Matching Matching Interface
Antenna
1.5 MW Line Hybrid
section coupler
Network Network
Port6
Coupler
Automatic Coarse
Dummy Load Probe Direction Antenna
Matching Matching Interface
section coupler Port14
Network Network
Interface:
Interface section provides the separation between the vacuum of the tokamak &
atmosphere pressure of the transmission line by two RF vacuum feed-throughs. It
also provides mechanical support to the antenna box.
3. Aim of Testing:
4
The main objective of this experiment is to optimize the response time of both
Automatic Matching Network (AMN) lying with each transmission line with the
following related sub-objectives.
Fiber Optic Tx/Rx cards: The entire motor driver control signal is fiber optic
based. It serves dual purpose of providing noise immunity & isolation to signals.
RF-Detector: It converts the RF signal (45.6 MHz) picked from the transmission
line through disc probe to DC signals.
VGD4 card (Analog Input): VME based card digitizes all probe signals obtained
from the signal conditioning cards.
VMIC –2528 DIO Card: VME based card used for Digital Input/Output signals.
VMIC-9660 Card: Carrier board for Timer card (IP-480) & Analog Output card
(IP-220).
5
VME Control Programming: The programming on the VME system includes
card driver programming, system integration programming for the ICRH-SST-1
operation & control. In this AMN control loop operates within 5ms.
Data Acquisition: MDS+ based data acquisition module has been implemented. It
can acquire data at the rate of 1ms for 1000-seconds operation.
Data Analysis: Jscope based Data analysis software module has been implemented
for off-line (post shot) analysis.
5. Test-setup:
The block diagram of the ICRH system for the testing & optimization of the AMN
system’s response time is shown in figure-3.
Hybrid coupler equally divides the input power to two ports if the load connected at
both port is of same value, otherwise all power will dump into the fourth port
(dummy load).
As the plasma environment is very dynamic in nature and keeps changing during
plasma formation, so to simulate the same condition as of plasma load, a very fast-
motorized variable load is made from the variable capacitor (35pf-1000pf with 48
6
rotation) & resistor (10 Ohm/ 1000W) as shown in figure4. To minimize the
radiation the load assembly is made to co-axial type. This variable load is
characterized at ICRH operating frequency of 45.6 MHz with the help of VNA.
35-1000pf
10 ohm
0 (C m in ) 018 + j106
4 137 + j490
8 040 - j64.8
12 031 - j34.4
16 030 - j25.6
20 029 - j21
24 28.7 - j18.9
VNA : :
44 27.8 - j13.8
4 8 (C m a x ) 27.7 - j13.2
7
Figure5 shows the block diagram of the DAC system integrated with both ICRH-
Transmission line section.
1 2 3 4 5 6 7 8 9 10 11 12
20pf 35pf 50pf 65pf 80pf 95pf 125pf 140pf 155pf 170pf 185pf 200pf
110pf
VVC provides capacitance of 20pf-200pf in full 12 rotations i.e. 15pf per rotation
as shown in the figure6.
8
As the plasma load may be inductive and capacitive, so the VVC has to operate
such that it can provide both inductive and capacitive reactance to the system when
load changes during plasma formation. For this purpose the AMN operation always
starts from the Null position of the system (Null position is ensured by keeping the
0.5meter stub to lower limit position & capacitor at its 6th turn of rotation). Thus in
the AMN operation only VVC motor moves and 0.5meter stub remains set at fixed
position.
6- 0 turn: movement of VVC motor will provide inductive reactance to the system.
6-12 turn: movement of VVC motor will provide capacitive reactance to the
system.
D-16000 D16000
-5 -3 -2 -1 +1 +2 +3 +5
-4 +4
m
om
Zoo
-6 0 +6
H/W Limit
9
• S/W Enable (SE): Enables the controller to drive the motor in program mode.
• Homing Enable (HO): Motor will travel towards the home (initial position /
null position / distance D0 counts) direction from any current position.
• CCW Direction (CCW): Motor will travel in CCW direction & in single sense
of same direction signal; the motor will travel distance to the set count value in
controller programmer (e.g. d-400, d-1600, d-4000).
• CW Direction (CW): Motor will travel in CW direction & in single sense of
same direction signal; the motor will travel distance to the set count value in
controller programmer (e.g. d400, d1600, d4000).
For the safety of the VVC, motor driver is programmed such that motor can move
maximum four rotations in one direction from its home position (system’s null
position). So software puts limit to the VVC of maximum eight rotations.
6-2 turn movement (110pf– 50pf): provides inductive reactance to the system.
6-10 turn movement (110pf – 170pf): provides capacitive reactance to the system.
The VVC motor makes one rotation (15pf capacitance
change) in d4000 counts of the driver. So to move 1/20 rotation (change of 0.75pf
capacitance) d200 count is needed.
7. Testing Procedure:
10
The entire probe signals are calibrated from the source end (RF detector) up to the
destination (VME Analog input terminal) end as shown in figure 8.
Tx Line
Probe Probe Probe Probe Probe Probe
disc disc disc disc disc disc
VGD4
RF Inverter Isolation
I/V Card AI
detector card card Terminal
Figure 8: Probe signal calibration in electronic cards
This is ensured by
1. By keeping the penetration depth of disc probe same for each signal.
2. Electronics card is calibrated.
VVC2 VVC1
COARSE
PHASE Dynamic
SHIFTER Load
RF
Source
T
COARSE
VNA STUB
11
Ea = (V1- Vf)* sin2bl2- (V2 -Vf) sin2bl1
Eg = (V1- Vf )* cos2bl2 - (V2 -Vf) cos2b l1
But it is observed that even in matched case the Error A (Ea) & Error G
(Eg) has non-zero values. So AMN motor will continuously rotate alternatively in
both directions. Effect of this on the AMN system is shown in appendix VII.
A M N S Y S TE M
VVC2 VVC1
RF
S ource P ow er
M eter PHASE
S H IFT ER
C O A R SE
STUB
D ynam ic
Load
Figure 10: Load impedance matching from the AMN
12
• Power meter value shows following reading.
Before AMN operation start: Pf = 350W, Pr = 240W
After AMN operation start: Pf = 650W, Pr = 10W
• Matching time: ~1.3second
CASE 2:
• Motor Parameter set in VVC (i.e. AMN) Driver
Velocity: 50rps
Acceleration: 2000 rev/sec/sec
One step count: d400-d4000
• Dynamic Load changes (by varying the capacitance) the impedance to
new impedance value
• Power meter value shows following reading.
Before AMN operation Start: Pf = 350W, Pr = 240W
After AMN operation Start: Pf = 650W, Pr = 10W
• Matching time: ~500msecond
So As the acceleration, velocity & move count increases, matching time decreases.
M O TO R
VM E DO
V M E S /W F O C T X /R X C A R D C O N T R O L LE R
C A R D T E R M IN A L
I/P S E N S O R
5 m s (N e w R e fre sh tim e )
After setting loop refresh time to 5ms, with same speed parameter in the motor
driver as in above-mentioned case-2 (8.a), matching time reduced to 200ms.
Matching time: ~300msecond
13
the motor controller input sensor section & its driver section of appx. 50ms .It is
observed that default setting of input debounce time in motor controller is 50ms as
shown in figure 11.
MOTOR
VME DO MOTOR
VME S/W FOC TX/RX CARD CONTROLLER
CARD TERMINAL DRIVER
I/P SENSOR
50mS debounce
5ms (VME Refresh time)
5mS debounce
As the step size in the motor controller changes from d1200 count (4.5pf / step)
count to d4800 count (18pf / step) keeping the other motions parameters same in
the motor controller, matching is not achieved for the same set value of variable
load, because AMN makes the system oscillate between matching & mismatching
region as shown appendix XII.
As the step size in the motor controller changes from d4800 count (18pf / step) to
d3600 count (13.5pf / step) keeping the other motion parameters same in the motor
controller. Matching time reduced to 45ms for the same set value of variable load
as shown in appendix XIII.
(8.e) Observation:
14
•It observed that load is set such that VVC has to rotate (9/10)th rotation
(d3600 count) to match it.
• At this setting of load, experimental matching time & calculated matching
time is same.
9. Conclusions:
In Previous report (ref 10.5) we had given the results of single transmission line
using automatic matching network. In this report we present the results of the total
transmission system which includes RF Generator, Hybrid coupler & two
transmission lines with two variable loads to be simultaneously using automatic
matching network unit.
The design, development & testing of the AMN is very important aspect for the
ICRH experiments in tokamak, where plasma impedance changes dynamically.
This report explains all the technical details of the matching achieved with dynamic
load in a very short duration. It is also observed that this matching time is shorter
than many matching systems in other tokamaks. Following are the important
conclusions.
• All the H/W and S/W delay from the DAC is optimized up to ~2ms.
• Mechanical inertia time of this VVC motor is negligible (~ .1ms)
• VVC motion is optimized to 1.5pf/15ms.
• Motor will move as fast as set acceleration & velocity in controller.
• Once the motor-controller get CW/CCW signal, motor will move one
set count value (d400/d4800).
• Small count can match the load but matching time will be more (d400
count preferably).
• Large count will make system oscillate.
• If time scale or magnitude of plasma impedance variation is known then
count value can be optimized further to minimize the matching time.
• Set count (distance) into motor controller from the VME system is not
possible, because controller has its own programming (compu-motor
15
S/W) which can be uploaded/downloaded from serial communications
only.
• Total matching time is 135 ms with d400 count of motor controller
program & vme response time for feedback loop is 2 ms.
10. References:
1. Engineering design report (EDR) of ICRH-SST1
SST-2.03-050199-RF Group
Appendix-I
Driver/Controller signals for Motor
16
Digital output signals:
S.N. Signals Name Signal Type Controller Logic No. Of Channel
1 Static Stub1 CW TTL Active High 1
2 Static Stub1 CCW TTL Active High 1
3 Static Stub1 CW TTL Active High 1
4 Static Stub1 CCW TTL Active High 1
5 Coarse Stub PULSE TTL Active High 1
1
6 Coarse Stub SIGN TTL Active High 1
7 Phase shifter PULSE TTL Active High 1
1
8 Phase shifter SIGN TTL Active High 1
2
9 Motor-1 H/W Enable TTL Active Low 1
10 Motor-1 S/W Enable TTL Active High 1
11 Motor-1 CW TTL Active High 1
12 Motor-1 CCW TTL Active High 1
13 Motor-1 Homing TTL Active High 1
2
14 Motor-2 H/W Enable TTL Active Low 1
15 Motor-2 S/W Enable TTL Active High 1
16 Motor-2 CW TTL Active High 1
17 Motor-2 CCW TTL Active High 1
18 Motor-2 Homing TTL Active High 1
1. Sign pin will be +5V for CW signal, 0V for CCW signal
2. To enable the signal, controller needs 0V(Active Low)
17
Appendix-II
Is CW Is CCW Is home
signal ? signal ? signal ?
yes
yes
yes
No CW VVC is in No CCW VVC is in
yes yes
movement CW Limit movement CCW Limit
18
Appendix-III
AMN START
NO
NO
NO
19
Appendix-IV
20
Appendix-V
21
Appendix-VI
Rota- Zload Zin before VSWR Return Stub Phase Zin after
tion matching Loss (From LL) Shifter matching
(From LL)
48 27.7 - j13.2 48.4 - j30.8 1.001 -58dB 465mm 894mm 50.031 –j.0823
(Cmax (Up) (Up)
pos)
44 27.8 - j13.8 49.99 -j92.7 1.01 -40.5 No No 49.99 – j0927
movement movement
40 27.9 - j14 49 – j1.22 1.03 -36.2 No No 49 – j1.22
movement movement
36 28 - j15.5 48.45 - j1.9 1.05 -31.9 No No 48.45 - j1.9
movement movement
32 28.2 - j16.0 48 - j3.09 1.078 -28.5 No No 48 - j3.09
movement movement
28 28.4 - j17.2 47 - j4.25 1.025 -25.5 No No 47 - j4.25
movement movement
24 28.7 - j18.9 45.7 – j5.8 1.162 -22.5 No No 45.7 – j5.8
movement movement
20 29 - j21 44.0 – j8.22 1.24/ -19.37 545mm 1028mm 49.9 – j.556
1.002 /-60dB (Up) (up)
16 30 - j25.6 46.7 - j3.6 1.1073 -25.8 No No 46.7 - j3.6
movement movement
12 31.7 -j34.4 41.3 - j10.8 1.354 -16.4 No No 41.3- j10.8
movement movement
8 40 - j64.8 31.3 - j30.21 2.38/ -7.74/- 872mm 810mm 50.06 – j.2
1.003 50 (Up) (Up)
4 137 + j490 60 - j132 7.69 -2.22 No No 27.8 - j13.8
movement movement
0 18 + j106 211 - j204 8.28/ -2.1/-46 1227mm 177mm 49.96 - j.5
(Cmin 1.00 (Up) (Up)
pos)
Variable load is replaced with .75ohm Resistive load and the coarse network does matching.
No movement: At this setting of the load, coarse matching network (stub & phase shifter)
is not operated for the matching of the load
Conclusion: Coarse matching network can match any load starting from milliohms range
to some ohm range obtained from the variable load.
22
Appendix-VII
Reflection coefficient curve shows it starts downing from value of 0.9 to 0.15 as AMN
Start-Stop Signal generated by the VME (hence VVC motor-1 controller received CW
pulse & VVC Motor-2 controller received CW/CCW Pulse). Now AMN motor should
ideally stop, as it is matched condition (ensured by the power meter reading at generator
side which showing Forward power is 700W & reflected power is 10W & before matching
it was 350W/240W).
Since even in perfect matched load some error signal will generate continuously, which
causes motor driver get receive direction signal from the VME system, hence motor will
alternatively rotate in both direction continuously.
23
Appendix-VIII
Reflection coefficient curve shows it is down from value of 0.9 to 0.15 as AMN Start-Stop
signal generated by the VME (hence VVC Motor-1 controller received CW pulse & VVC
Motor-2 controller received CW/CCW pulse).
As error signal window margin added in the VME programming & error signal not
crossing the putted window limit, so motor driver didn’t get any direction signal from
VME system for the same load (as in appendix-7), hence motor remain standstill. (Power
meter showing the reading 650W/10W).
24
Appendix-IX
Reflection coefficient curve shows that after adjusting the response time in VVC Motor
controller for the same case as shown in (appendix IX), it starting to reduce immediately
after receiving the AMN Start/Stop signal. It means VVC motor –1 start moving in CCW
direction as soon as its controller get CCW direction signal from the VME. That time is to
~ 300 msecond.
25
Appendix-X
Reflection coefficient curve shows that after adjusting the step size of count from d400 to
d1200 in VVC motor controller, keeping the other motion parameter & load condition
same as of in appendix X, the matching time reduces to ~90msecond.
26
Appendix-XI
VVC
0.5 Meter
STUB
VVC Motor Motor Controller Motor Connection with VVC VME Processor / Cards