UNITROL-F EXCITATION SYSTEM UNITROL

Power Supply Unit


UNS 0861a-P, V.1,2
Data sheet

FEATURES 1 11
2 AC 12
220VDC power supply unit with variable input voltage:
- Variant 1: For 24V ... 48VDC input voltage 5
+ +
17,18

- Variant 2: For 110V ... 250VDC input voltage DC


4 19,20
Connections for redundant AC voltage supply DC
-

Monitoring of the AC and DC output voltages 14


Galvanically isolated 24VDC contact interrogation voltage (6, 8) OK 15

Parallel connection of the 24V output of 2 power supply units allowed 6,7
Stand-alone device for assembly board installation DC
DC
+
8,9

SHORT DESCRIPTION
The external power supply unit UNS 0861a-P provides the voltage supply to the POW-1 module
integrated in the main unit. The device is responsible for adapting the battery voltages present on
the customer side to the DC input range of the POW-1 module.
The device is available in the following two variants:
- V1: for 24 ... 48VDC nominal input voltage
- V2: for 110 ... 250VDC nominal input voltage.
In order to achieve a redundant voltage supply, the 115V / 230VAC supply voltage is additionally
fed to the POW-1 module. The decoupling diodes belonging to the AC/DC redundant power supply
are located in the DC output 17-19. The AC and DC output voltages (11, 12 and 17 ... 20) are
monitored. If one of the two fails, the FAIL signal is generated at the outputs 14 and 15. The
presence of the AC and DC output voltages is indicated by means of the AC ON and DC ON
LEDs. The 220VDC output voltage is additionally fed to test terminals. With an external capacitor
on the outputs 18 and 20, the 220VDC output voltage can be supported in the event of brief
interruptions of the DC supply voltage. The fuse F1 in the DC input protects the device in the event
of internal defects.
In addition, the power supply unit UNS 0861 generates a galvanically isolated 24VDC contact
interrogation voltage. The parallel connection of this contact interrogation voltage with a second
UNS 0861a-P is allowed where 2-channel systems are used. A decoupling diode and the two
terminals 6,7 and 8,9 are provided for this purpose. The 24VDC output is short-circuit-proof.

1 11 X99/L
+
2 115/230VAC 12 X99/N -
ACON
5 F1 V2:110/250VDC 17 X95/2
+
V1: 24/48VDC 18
DCON
4 220VDC 19 X95/1
20
POW-1
6
7 14
+ + 24VDC 15
FAIL 15
8 isolated 16
9 UNS 0861a-P 17 UNS 1860

Issued: Document Format Language Page No. of


Rev.
a c 95-08-07 pages
Rev. Check 1:
b d
Department 1 Department 2
e Check 2: TA A4 E 1 8
Der. from / Repla.: Released:
IAEG Replaced by: HIEE 422029 E
-2- UNS 0861a-P, V.1,2

TABLE OF CONTENTS

FEATURES ....................................................................................................................................1
SHORT DESCRIPTION..................................................................................................................1
1. DEVICE BLOCK DIAGRAM.........................................................................................3
2. FUNCTIONAL DESCRIPTION .....................................................................................3
2.1 Schematic Diagram..................................................................................................3
2.2 Connections.............................................................................................................3
3. CONFIGURATION .......................................................................................................4
4. COMMISSIONING AND FUNCTION CHECK ..............................................................4
4.1 Variant Check ..........................................................................................................4
4.2 Setting AC Voltage Range .......................................................................................4
4.3 Function Check........................................................................................................4
5. TECHNICAL DATA......................................................................................................5
5.1 Input Values.............................................................................................................5
5.1.1 AC Supply Voltage (connection 1,2) ....................................................................5
5.1.2 DC Supply Voltage (connection 4,5)....................................................................5
5.2 Output Values ..........................................................................................................6
5.2.1 AC Output Voltage (connection 11,12) ................................................................6
5.2.2 DC Output Voltage (connection 17/18 - 19/20) ....................................................6
5.2.3 Contact Interrogation Voltage (connection 6/7 - 8/9)............................................6
5.3 Monitoring (connection 15,14)..................................................................................6
5.4 Environmental Values ..............................................................................................6
5.4.1 Permissible Temperature Range .........................................................................6
5.4.2 Climatic Stability ..................................................................................................6
5.4.3 Mechanical Stability.............................................................................................7
5.4.4 EMC (Electromagnetic Compatibility) ..................................................................7
5.4.5 Altitude of Installation ..........................................................................................7
5.4.6 Protection Means ................................................................................................7
5.4.7 Reliability.............................................................................................................7
6. CONSTRUCTION DATA..............................................................................................7
6.1 Dimensions ..............................................................................................................7
6.2 Weight .....................................................................................................................7
6.3 Indicator Elements ...................................................................................................7
6.4 Connectors ..............................................................................................................7
6.5 Location of Control Elements ...................................................................................8
7. ORDERING INFORMATION ........................................................................................8

HIEE 422029 E
-3- UNS 0861a-P, V.1,2

1. DEVICE BLOCK DIAGRAM


(see operating instructions)

2. FUNCTIONAL DESCRIPTION
2.1 Schematic Diagram

UNS 0861a-P, V1/V2 POW-1


11 X99/L F
1 +
115 or 230VAC 50/60Hz
12 X99/N
2 -
ACON X95/2 X95/1
3 13
+DC OUT
-F1 + V2: 110...250VDC U 17
5 V1: 24...48VDC
18
DCON
C1
220VDC -DC OUT
U
19
4 20

16
6 AC_DC_FAIL
+ 14 15 DI8
7 +24VDC 10W X1:2
8 isolated +15V
9 current limited 17

15 16

UNS 1860

2.2 Connections
2.5 mm2 spring-clamp terminals, type WAGO 231, are used for all connections.
Only one conductor (wire or strand) may be connected per terminal.
The connections are divided into 3 blocks:
Terminals 1,2,4,5 AC and DC supply voltage
Terminals 6,7,8,9,+24V contact interrogation voltage
Terminals 11....20Output voltages to POW-1 and UNS 1860

The 3 connection blocks can be pulled out.

HIEE 422029 E
-4- UNS 0861a-P, V.1,2

3. CONFIGURATION
Two-wire twisted cables must be used for the following associated input/output signals:

14,15 Fail signal of the voltage monitoring

The EMC protection is provided by means of the fixing bolts, if the assembly board is a grounded
surface. An additional ground connection (1 ... 4 mm2) is provided for the protective ground.

4. COMMISSIONING AND FUNCTION CHECK


4.1 Variant Check
Check the use of the device variants:
V1: input voltage at connection 5(+), 4(-): 24...48 VDC
V2: input voltage at connection 5(+), 4(-): 110..250 VDC

4.2 Setting AC Voltage Range


AC supply voltage (output 1,2)
The nominal input voltage must be set using the slide switch SW1 on the POW-1
module.

4.3 Function Check


The 220VDC output voltage is to be checked between the test terminals +DCOUT and
-DCOUT.
If the device is functioning correctly, the LEDs AC ON and DC ON which are assigned to the output
voltages must be activated.
The voltage between connection 15 (+) and 14 (-) must be between 0.1 and 2V.

The following procedure is recommended in the event of a malfunction:


Check for correct connections
Check size and polarity of the input voltages
Check fuse F1 in the UNS 0861
Check fuse F1 in the POW-1 module
Check output voltages

HIEE 422029 E
-5- UNS 0861a-P, V.1,2

5. TECHNICAL DATA
5.1 Input Values
5.1.1 AC Supply Voltage (connection 1,2)
Nominal input voltage Ι 115 VAC
Input voltage range 93 ... 127 VAC
The nominal input voltage must be set using the slide switch SW1
on the POW-1 module.

Nominal input voltage ΙΙ 220 VAC


Input voltage range 185 ... 260 VAC
The nominal input voltage must be set using the slide switch SW1
on the POW-1 module.

Minimum required voltage rise/drop 10 %/s


Nominal frequency 50/60 Hz
Maximum power consumption 70 VA
Test voltage (against all other connections and ground) 2263 VAC
50 Hz / 1 min
EMC data
Fast transient burst: IEC801-4 4 kV com. mode
Surge voltage: IEC801-5 2 kV com. mode
1 kV diff. mode
Performance criteria B

5.1.2 DC Supply Voltage (connection 4,5)


Variant 1:
Nominal input voltages 24/48 VDC
Max. permissible tolerance ± 25 %
Max. power consumption 50 W
Fuse: F1 (5x20 mm) 1.6 AT

Variant 2:
Nominal input voltages 110/250 VDC
Max. permissible tolerance ± 25 %
Max. power consumption 50 W
Test voltage (against all other connections and ground) 3200 VDC
3 pulse, 10 ms/5s
EMC data
Fast transient burst: IEC801-4 4 kV com. mode
Surge voltage: IEC801-5 2 kV com. mode
1 kV diff. mode
Performance criteria B

HIEE 422029 E
-6- UNS 0861a-P, V.1,2

5.2 Output Values


5.2.1 AC Output Voltage (connection 11,12)
The same as the input voltage in accordance with 5.1.1

5.2.2 DC Output Voltage (connection 17/18 - 19/20)


Nominal output voltage 220 VDC
Voltage tolerance ± 10 %
Max. ripple (peak-peak) 20 V
Output power 40 W
Required C1 capacity in the event of an interruption in supply 2.2 mF/s

5.2.3 Contact Interrogation Voltage (connection 6/7 - 8/9)


Nominal output voltage + 24 VDC
Voltage tolerance ± 10 %
Max. ripple (peak-peak) 1V
Output power 10 W
Effectiveness of current limitation 500 ... 600 mA

Test voltage (against inputs 4,5) 2263 VAC


50 Hz, 1 min

EMC data
Fast transient burst: IEC801-4 4 kV com. mode
Surge voltage: IEC801-5 2 kV com. mode
1 kV diff. mode
Performance criteria B

5.3 Monitoring (connection 15,14)


Voltage between connection 15 and 14 if:
AC and DC supply voltages are present ≤ 2 VDC
AC or DC supply voltage is not present 10..15 VDC

5.4 Environmental Values


5.4.1 Permissible Temperature Range
Keeping the technical data 0 ... + 55 °C
Operable within range 0 ... + 70 °C
Storage temperature - 25 ... + 85 °C

5.4.2 Climatic Stability


according to IEC 68-2-6 0 °C
according to IEC 68-2-2 70 °C
according to IEC 68-2-3 21 days
at (relative humidity) 93 %

HIEE 422029 E
-7- UNS 0861a-P, V.1,2

5.4.3 Mechanical Stability


Vibration according to IEC 68-2-6 10 ... 150 Hz
Acceleration 2 g in each axis
Earthquake test according to IEEE-STD 344 1 ... 33 Hz
Acceleration 5 g in each axis
Shock test according to IEC 68-2-29 10 g
Maximum pulse rate 1000

5.4.4 EMC (Electromagnetic Compatibility)


Radiated Interference Immunity
according to IEC 801-3 10 V/m
27 ... 1000 MHz
Performance Criteria A

5.4.5 Altitude of Installation


according to IEC 68-2-13 max. 2000 meters above sea-level

5.4.6 Protection Means


according to DIN 40050 IP 20
Condition: Compliance with installation regulations HIEE 405197.

5.4.7 Reliability
Failure rate 695 Fit
Condition: GB, 40 °C

6. CONSTRUCTION DATA
6.1 Dimensions
Dimensions (L x W x H) 175x150x55 mm
Mounting: PCB on standard aluminium board (see 6.5)

6.2 Weight
Mass 400 g

6.3 Indicator Elements


LED AC ON (green) AC voltage present
LED DC ON (green) DC voltage present

6.4 Connectors
Terminals 1,2,4,5 (AC/DC input) Type WAGO 231, 2.5 mm2
Terminals 6,7,8,9 (contact interrogation voltage) Type WAGO 231, 2.5 mm2
Terminals 11.....20 (output voltages) Type WAGO 231, 2.5 mm2
Cage spring clamp connections for one conductor (wire or strand)

HIEE 422029 E
-8- UNS 0861a-P, V.1,2

6.5 Location of Control Elements

17 +
18 +

20 -
19 -
11
12
13

15
16
14
AC OK 220VDC
Outputs

150 mm
UNS 0861

Inputs 24V Contact interrogation


AC DC

Fuse
1 2 3 4 5 6 7 8 9
+ + - -

Earthed
175 mm
aluminium board

7. ORDERING INFORMATION
Order number: UNS 0861a-P, V1 HIEE 305084 R1
Order number: UNS 0861a-P, V2 HIEE 305084 R2

HIEE 422029 E