Professional Documents
Culture Documents
Overall Thesis
Overall Thesis
on
DESIGN AND FABRICATION OF EARTH AIR HEAT
EXCHANGER
Project work submitted in partial fulfilment of the requirement for the award of the degree of
BACHELOR OF ENGINEERING
In
MECHANICAL ENGINEERING
Submitted By
NADERGUL, HYDERABAD-501510
Abstract………………………………………………………………….. ii
Acknowledgement………………………………………………………. iii
Table of contents……………………………………………………….…iv
List of figures……………………………………………………………...v
List of tables………………………………………………………………vi
Terminology………………………………………………………………vii
i
ABSTRACT
ii
ACKNOWLEDGEMENT
Thanking you,
iii
TABLE OF CONTENTS
CHAPTER 1................................................................................. 1
INTRODUCTION ............................................................................................... 1
1.1 EARTH AIR HEAT EXCHANGER (EAHE) .................................................................... 2
1.2 CLASSIFICATION OF EAHE ......................................................................................... 4
1.3 FACTORS INFLUENCING THE PERFORMANC OF EAHE ......................................... 7
1.4 ADVANTAGES AND DISADVANTAGES OF EAHE ...................................................... 7
CHAPTER 2................................................................................. 9
SCOPE OF STUDY ............................................................................................. 9
2.1 Objectives of the study:.................................................................................................. 9
CHAPTER 3............................................................................... 10
LITERATURE REVIEW ................................................................................. 10
3.1 Research conducted in India ....................................................................................... 10
3.2 Research conducted in other parts of the world: .......................................................... 19
CHAPTER 4............................................................................... 35
RESEARCH METHODOLOGY ..................................................................... 35
4.1 SELECTION OF PIPES LAYOUT AND GEOMETRY .................................................. 36
4.1.1 PIPE GEOMETRY ........................................................................................ 36
4.1.2 PIPE MATERIAL.......................................................................................... 36
4.2 DESIGN PARAMETERS ............................................................................................. 38
4.3 ASSUMPTIONS........................................................................................................... 39
4.4 CALCULATIONS ......................................................................................................... 40
4.4.1 Formulas for theoretical calculations ....................................................... 40
4.4.2 Input parameters ...................................................................................... 41
4.4.3 Sample Calculations .................................................................................. 42
CHAPTER 5............................................................................... 44
RESULTS AND DISCUSSION ........................................................................ 44
5.1 EXPERIMENTAL RESULTS ........................................................................................ 44
5.1.1 EXPERIMENTAL RESULTS 1: ...................................................................... 44
5.1.2 EXPERIMAENTAL RESULTS 2: .................................................................... 45
iv
5.2 THEORITICAL RESULTS............................................................................................ 46
5.2.1 Theoretical results for experimental results 1.......................................... 46
5.2.2 Theoretical results for experimental results 2.......................................... 46
CHAPTER 6............................................................................... 48
CONCLUSION .................................................................................................. 48
REFERENCES ........................................................................... 49
v
LIST OF FIGURES
vi
LIST OF TABLES
vii
TERMINOLOGY
Nomenclature
Units
m meter
°C Celsius
K kelvin
W watt
J joule
viii
CHAPTER 1
INTRODUCTION
1
exchangers is a passive way for thermal comforting which uses geothermal
energy of the earth.
As per the current scenario, energy saving has become one of the important
parameters for economic growth of developed and developing countries like
America, India, China, Japan, Russia etc. have taken initiatives for saving
energy. EAHE is now been used by many countries for achieving thermal
comfort in buildings and it is energy efficient. EAHE is a non-conventional
technique which uses underground soil temperature of earth and has
applications in green houses, residential and commercial buildings with air
conditioning system.
2
During summers, the temperature of the ambient air is higher depending on
the location. The hot air flows through the buried pipes, the EUT of soil
reduces the temperature of the air by conduction and delivers through outlet
to the required space. i.e., the temperature of the required space is lower than
outside.
During winters, the temperature of the ambient air is lower depending on the
location. The cool air flows through the buried pipes, the EUT of soil reduces
the temperature of the air by conduction and delivers through outlet to the
required space. i.e., the temperature of the required space is higher than
outside. For the continuous flow of air through the pipe’s mechanical devices
such as fans and blowers are used or passive methods such as wind towers
and wind catchers can be used to create sufficient pressure difference.
3
1.2 CLASSIFICATION OF EAHE
Open loop system: The ambient air from the atmosphere enters through inlet
and flows through buried pipes where pre heating or pre cooling of the air
takes place based on the temperature of ambient air and then it enters the
required space through outlet. The air which reaches the ambient temperature
gets out of the space through ventilation provided at top of the space.
Closed loop system: The air from the closed space enters inlet of the EAHE
system and flows through the buried pipes where the air is pre heated or
cooled based on the temperature of the air entering the pipes. The air which
is heated or cooled enters the room. There is no need of ventilation system
as the air inside the closed space is recirculated in the buried pipes.
Closed loops are more efficient than open loop system. Closed loop system
reduces the humidity problem in air.
4
Figure 1.3: Closed loop system
Hybrid systems: To improve the efficiency of EAHE, they are coupled with
active or passive cooling techniques for cooling and heating such as air
conditioners, heat recovery units, heat pumps, mechanical ventilation
systems and air handling units, evaporative cooling, air humidity control
devices, building integrated photovoltaic systems, solar air heaters and
heating ducts, solar chimneys, wind towers and phase change materials.
The EAHE are also classified based on the layout of the pipe in the ground
and according to the arrangement of the pipe.
• Vertical loop
• Slinky loop
• Helical loop
5
Figure 1.4: Horizontal loop
One tube system does not meet the requirements of air conditioning systems
in the building. This is because as the tube is large there will a pressure drop.
Hence parallel tube systems are used in order to reduce the pressure drop and
increase the thermal performance of the system. Parallel tube systems require
less place as compared to one tube systems.
6
Figure 1.6: One tube and Parallel tube system
• Geographic location
• Physical and chemical properties of soil
• Temperature and velocity of air
• Spacing between the pipes
• Pipe material, diameter, length and thickness
• Relative humidity of air
• Depth of burial
• Condensation inside the pipe
• Climatic conditions
Advantages of EAHE:
7
Disadvantages of EAHE:
8
CHAPTER 2
SCOPE OF STUDY
The efficiency of the EAHE is dependent on the depth of the pipe placed,
length of the pipe, diameter of the pipe, layout of the buried pipe, the ambient
air temperature of the specific area, the thermal conductivity of the pipe,
material of the pipe and the air flow velocity, thermal diffusivity of the soil
as stated previously. EAHE has previously been subjected to adequate
research based on the aforementioned factors. As of now there is no study of
EAHE in Hyderabad. This project focuses on the experimental setup of
EAHE and theoretical calculation based on the parameters of the
experimental setup. This project focuses on the experimental and theoretical
validation of earth air heat exchanger with certain setup parameters. For
theoretical calculation NTU method is used.
This is a novel technology that has received little attention. Based on the
energy in today’s context, green energy is supported in both developed and
developing countries, such as The United States, India, Russia and China etc.
This technology has the potential to be a green technology in the future that
uses energy source such as solar energy. The research is still in its early
stages. This field takes into account diverse properties, working fluids, and
so on as mentioned earlier. This have many applications; one such
application is snow melting. Therefore, experiments in cool places may be
undertaken, such that the snow is melted and warm water is provided during
winter. EAHE technology investigation is still in its early stages, with much
of room for advancement, yet this technology is still useful.
9
CHAPTER 3
LITERATURE REVIEW
The conventional air conditioning system is most often used system for
providing comfort in residential buildings, offices, and so on. The basis of
operation of an air conditioning system id to condition the air, convey it, and
introduce it into the conditioned room. Air conditioning system consumes a
lot of energy while also depleting the ozone layer owing to CFC emission.
The Kyoto protocol issued by the United Nations Framework Convention on
Climate Change (UNIFCCC), focuses on reducing greenhouse gas
emissions. Passive energy saving measures are being implemented in HVAC
installations to minimize energy usage. EAHE, which uses earth as a heat
sink, is one such passive approach. The transfer medium for summer cooling
and winter heating is air. This shows that the temperature at the outlet is
higher/lower than the ambient temperature.
Many Indian researchers have studied the potential of buried pipes. The
parameters for the studies are mentioned in table 1 and table 2 from both
theoretical and analytical studies.
Bisoniya et al. [87] to assess the thermal potential of EAHE created a model
to analyze the different parameters of pipe such as length of the pipe, depth
of the buried pipe, diameter of the pipe, and air flow rate. By providing the
description of the pipe, a relationship between input and output temperature
10
was determined for one dimensional model. This depicts EAHE’s
performance as a steady state 1D model. The ground temperature at 5
different depths is calculated using 2D models. Conduction problems are
also solved using finite element methods. The performance study is carried
out using 3D models, which allow for variety of grid geometry. For more
complex fluid flow problems in any heat exchanger CFD software alike
Ansys FLUENT, STAR CD, CFX, ADINA can be used.
Misra et al. [87] emphasizes the cooling potential of low-cost materials such
as PVC. This focuses on duct systems design. The experimental
configuration was created as a prototype model with a metal tray as the basis.
As previously stated, the performance of EAHE is dependent on the air
velocity and pipe material. As a result, a less expensive material can be
utilized for the analysis. The system’s minimal EER was found to be 3.78,
which is nearly equal to an energy star 5 rating. As a result, EAHE uses less
energy than traditional systems. The prototype model, according to this
research, can be utilized in small residences to keep the room temperature
lower than the outside temperature during the summer. The author suggests
using the EAHE to achieve thermal comfort in homes. As a result, when
compared to the energy rating system, EAHE is an energy efficient system.
Kaushal et al. [85] employed FVM to look into the thermal potential of
hybrid EAHE. The response surface method was also used in this study to
improve the process parameters using Ansys FLUENT. Individual EAHE
are compared to the numerical results. By combining the EAHE with a solar
air heater, the EAHE becomes hybrid. The temperature contours along the
length were analyzed, and it was discovered that the temperature rises as the
length grows. Only the EAHE results were compared to the data given by
Bansal [74]. The HEAHE results were compared to the outcomes of the
experiment. To evaluate the factors affecting the input variables, response
surface methodology employs the f-test and ANOVA techniques. The results
revel that as the temperature rises, the potential for solar heat gain decreases.
The results demonstrate that for hybrid EAHE, the temperature reduction is
greatest. As a result, HEAHE performs better than EAHE.
11
Khandelwal et al. [83] investigated the heating and cooling demand of
MNIT’s Jaipur library. A basic excel model was created. The library has 4
rooms with split air conditioning to which EAHE was attached. Total
sensible and latent heat, as well as infiltration load, were taken into account
while calculating the cooling load. The average comfort temperature was
28.6°C, according to a poll. The largest temperature decrease was 11.5°C,
and the pipe length was 72 meters. The installation cost was projected to be
Rs. 149380 based on the cost analysis. The cooling demand including
ventilation, was 77kW, and EAHE’s cooling capacity was 60781 kW.
Mathur et al. [82] investigate the thermal saturation on soil and its ability to
self-recover between distinct modes of an EAHE system installed at MNIT
Jaipur, India. Ansys FLUENT v14.5 was used to run the numerical
simulations. It was discovered that the measured and the simulated findings
were in good agreement. Following the validation of CFD model, a thorough
examination of the impact of soil temperature on EAHE was carried out. The
temperature of the soil drops during length of the experiment according to
the findings. As a result, ambient air temperature has a significant impact on
soil temperature. The temperature profile in radial direction was simulated
for the research of heat infiltrating the soil. The soil temperature drops as it
advances away from the EAHE surface, while the soil around the pipe
changes with the ambient air temperature, according to the findings. The soil
temperature can be recovered during non-working hours in intermittent
operation mode via heat conduction among the soil layers. Continuous
operation had a higher self-recovery temperature than intermittent operation.
Jakhar et al. [81] using TRNSYS v17.0 examined the operating temperature
of Photovoltaic panels that was responsible for their life span and
performance. The operating fluid was water. For a specific cooling
arrangement of concentrating photovoltaics, the simulated system was
compared to existing ones in the literature (CPV). Three different types of
pipe materials were evaluated in the investigation. Temperature was
measured along the depth of all three pipes while keeping the pipe length,
flow rate, and diameter constant. When the pipe material was taken into
account, a temperature of difference of 1.61° was discovered. HDEP was
used for the study because it is less expensive. It was discovered that depth
increases, so does the average temperature. Thus, it was concluded that at
12
3.5m was considered as optimum depth for further simulation. Also,
concluded that the pipe material does not affect the performance of EAHE.
But when the mass flow rate was increased the outlet temperature, Reynolds
number and Nusselt number was increased. Thus, mass flow rate affects the
outlet temperature.
Jakhar et al. [81] during the winter season calculated the performance of
EAHE with and without solar air heating duct (SAHD) using TRNSYS 17.
The findings were confirmed in Ajmer, India, using experimental setting.
Galvanized iron conduits were employed for the solar air heating. The
performance of EAHE was investigated in three situations in the study.
When the air velocity was altered, the results showed that the EAHE
combined with SAHD increased the outlet temperature by 6°-9°C. in
addition, it was discovered that when the EAHE was combined with solar air
heating duct, the heating capacity of the EAHE was increased. During the
error analysis, it was discovered that there was 3.9% error.
Soni et al. [81] experimented with lowering the power usage of a 1.5TR air
conditioner connected to EAHE. Three distinct layouts were examined for
the experiment. Economic analysis methodologies including simple payback
period, deferred payback period, and others were also assessed. The
condenser tube temperature in the arrangement II was 10% lower than the
condenser tube temperature in arrangement III, according to the
configurations. The power consumption in each of the three layouts was
calculated and compared to the basic mode. The results show that the
arrangement III was effective in reducing power consumption during
summer days. The EAHE configuration produced the best results when the
velocity was between 5 and 7 m/s. the EAHE layout produced the best
outcomes. The EPBT for the arrangement II is 604.3 days and for
arrangement III is 362 days for the energy matrices, while the CO2 emission
for arrangement II is 5425.92 kg and for arrangement III are 9043 kg. as a
result, arrangement II is a good option for lowering CO2 emissions.
Thakur et al. [79] created a model in Pro-e to investigate the influence of the
EAHE finned model. This was compared to an EAHE model without fins.
The ANSYS workbench meshing tool was employed, and the FLUENT was
used to study the complex heat transfer and air flow process. Mishra’s
13
experimental investigation was used to validate the computational model.
Different pipe inlet velocities were used in the simulations. When the data
was compared to the current experimental data, it was discovered that there
was 7.64 percent difference. The results of simulations for both finned and
finless EAHE systems were examined. According to the findings, adding
fins to the system allows it to perform efficiently even if the soil has poor
thermal conductivity. Also concluded that smaller length of the pipes can
also perform well thus lowering initial cost.
Kumar et al. [77] investigated the finite difference method and the FFT
(MATLAB) model as numerical approaches. The findings were compared to
experimental data from a comparable tunnel in Mathura (India). When the
length and the flow rate of the pipe are reduced, the outlet temperature rises
and falls, respectively. In addition, increasing the radius of the pipe raised
the temperature while lowering the convective heat transfer coefficient. As
a result, it may be stated that a greater tunnel length saves more cooling
energy. The arrangement has a cooling capacity of 456kWh, according to the
results. The outlet temperature and be increased by rising the pipe radius
above a certain point, which impacts the heating/ cooling potential. As a
result, it is determined that a large exit temperature can be attained by
employing larger diameter pipe.
14
Chel et al. [74] developed a thermal model of vault roof building with EAHE
that was solved using ranga kutta method. The adobe house has a room air
temperature that is 5-15°C warmer than ambient in the winter and lower than
ambient air in summer, increasing the energy saving potential. The adobe
house was examined under three situations (before renovation, after
renovation, with EAHE for 6 rooms). For all three situations, the total energy
saving potential ranged from 4183 to 10321 kWh/year, with co2 emissions
ranging from 7 to 16 tones/year. For heating, the average seasonal energy
efficiency ratio was 1.8, and for winters, it was 2.9. As a result, EAHE is
more efficient for heating than it is for cooling. As a result, it can be
concluded that EAHE is more efficient for heating than cooling.
Ghosal et al. [11] did analytical research. With a mass flowrate of 100 kg/h,
the pipes were organized in serpentine pattern. The performance was
measured in terms of pipe length and greenhouse air temperature over both
seasons. The findings show that as the length of the subterranean pipes is
increased, the air temperature within the greenhouse rises in the winter and
15
falls in the summer. As a result, the EAHE’s performance is the function of
the greenhouse’s length and temperature.
Bansal et al. [15] carried out the same experiment for the summer season
using identical input parameters. When the experimental data were
compared, there was a variation of 0-11.4%. it was discovered that when the
air velocity rises, the temperature at the outflow rises as well. A relative tiny
temperature differential exists at the pipe’s output for both materials. At 5
m/s, the greatest hourly energy gain was 3.1 MWh, while the COP was 1.9-
2.9 in the same velocity range. As a result, the pipe material has no bearing
on EAHE performance.
Jakhar et al. [31] in Ajmer, where the temperature ranges from 15-18°C in
winters, predicted the thermal performance of EAHE when paired with solar
air heating duct. The solar air heating duct’s entrance is connected to
EAHE’s outlet. To assess the thermal performance, three modes were
investigated in this study. Four 39-day intervals were used to test the three
modes: 14-16 January, 26-28 January, 1-3 February, and 13-15 February.
The results suggest that combining EAHE with solar heating duct raises the
temperature of room by 1.1-3.5°C. for mode II, heating capacity and cop
were 665.52 kW and 1.54 respectively, whereas for mode III, the heating
capacity was increased to 1976 kW and cop 4.57.
The results of all the above literature survey conducted by researches in India
are tabulated below. Table 1 represents the experimental results studied in
India. Table 2 represents the analytical results studied in India.
16
Table 3.1: Summary of experimental results in India
Author place/year season material Length Diameter Depth Ambient Temperature Velocity
of pipe of pipe (m) of pipe temperature variation range (m/s)
(m) (m) (°C) (°C)
Mishra et al. New Delhi,
[92] India 2009 summer PVC - - 3 34-44 20-22 -
Jakhar et al. Ajmer, Winter PVC 60 0.1 3.7 13.9-20.4 24.3-24.7 2.5,3.5,5.5
[91] India,2016 24.3-32.5
Soni et al. Bhopal Rainy Galvanize 11 0.05 2 37.5-46 35.5-42 -
[90] India, 2016 -d iron
summer
17
Table 3.2: Summary of analytical results in India
Author place/year season material Length Diameter Depth Ambient Temperature Velocity
of pipe of pipe (m) of pipe temperature variation range
(m) (m) (°C) (°C) (m/s)
Jakhar et al. Rajasthan summer HDEP 90 0.025 - 42 1.61 -
[87] India,2016 GI 22.5-27.7
Steel 31.9
Kaushal et al. India, 2015 - - 3 0.1 - 7 21-24 1.0-3.0
[86]
Mathur et al. Jaipur, summer HDPE - - - 26.39 27.27 -
[85] India, 2015
Khandelwal Jaipur, winter PVC 72 0.1524 4 - 11.5 4
Et al. [84] India, 2015
Singh et al. Punjab summer GI - 0.524 3.048 - 29.3 6.7
[83] India, 2015
Bisnoiya Bhopal Summer PVC 9.114 0.1016 2 25-40 12.9-11.3 0.4-2.5
Et al. [80] India, 2014
Bansal et al. Ajmer Summer Mild steel 23.42 0.15 2.7 8.0-12.7 12.7 12.0-5.0
[76] India, 2009 PVC 10.3
18
3.2 Research conducted in other parts of the world:
Chlela et al. [33] For three French climates, conducted a numerical analysis
to evaluate the energy performance of two distinct ventilation systems and
earth air heat exchangers. The structure in question is a home called "Mozart"
with a floor size of 101m2. Three French cities were included in the
simulations: Nancy (5°C), La Rochelle (8°C), and Nice (10°C). The
mechanical extract ventilation system and the balanced ventilation system
were also studied. Clay was suggested as a soil type. SIMBAD was used to
simulate the building's thermal behavior. Other building data was used to
confirm the findings [El Khouryet et al., 2005]. For all three cities, annual
simulations were conducted to assess the thermal performance of EAHE and
the balanced ventilation system. The ventilation system's heating demands
for the three cities were analyzed, and the heating demand was reduced.
Nice's results were quite intriguing. The house in Nice had a heating demand
of 13.2 kWh/m2, which was nearly equivalent to the annual heating demand.
With the mechanical extract ventilation system, EAHE's heating demand
was reduced. As a result, balanced ventilation with a heat recovery unit
outperforms EAHE. During the summer, the balanced system's heat
exchanger was bypassed. The cooling potential of the three cities was
assessed in three modalities. As a result, EAHE has a lot of cooling potential.
Li et al. [72] built an air-conditioning system for chilly places in the Harbin
area, which directly delivers the cold energy stored in the earth. The
operation took place during the summer of 2006. The cooling seasonal
performance factor (CSPF) and the average heat rejection rate unit depth of
borehole were explored as performance metrics. A ground heat exchanger
and an interior fan coil make up the system. Water was used as the circulating
fluid. The borehole was placed 7 meters outside the walls to limit the
building's thermal influence on the earth. The heat rejection rate per unit
borehole depth ranged from 40 to 100 W/m. Seasonal cooling characteristics
and daily cooling characteristics are the two types of cooling characteristics.
On a daily basis, the second day had the highest cooling capacity. The
temperature of the ground rises quickly at first, but then settles down. In the
last 45 days, there has been a cooling of 0.75°C. The highest cooling capacity
happened on the first hour and the minimum cooling capacity occurred on
19
the tenth hour, with a ratio of 0.81. As a result, the increase in ground
temperature begins slowly at different depths and then accelerates.
Jassim et al. [71] studied the efficacy of a wind catcher in an EAHE to reduce
energy usage in hot, arid places such as Iraq. A wind catcher is an air-pulling
and air-expelling device. Wind catcher towers are usually attached to a
structure to provide cooling. In two phases, the thermal performance was
investigated. Phase 1: Data loggers were used to record the temperature.
Phase 2: Computational fluid dynamics (CFD) simulation. The model was a
two-story structure with a 2m2 wind catcher. The experimental setup was
used to evaluate a CFD model that was developed. The results show that in
August, there was a greater variation in temperature. However, in June, these
variations were reduced, although relative humidity increased. This finding
also suggests that soil temperature is influenced by soil type and water table.
It was discovered that increasing the wind catcher space in phase 1 did not
improve thermal comfort. However, increasing the amount of space in phase
2 reduces the temperature by 18°C. It was also discovered that increasing the
velocity boosted the COP to 5.24. As a result, this revolutionary self-cooling
design uses less energy.
20
when the cooling capacity was calculated. The total cooling capacity was 1.1
kW/°C as a result.
Sansui et al. [68] looked studied the temperature of the soil at various depths
up to 5 meters to determine the potential of EAHE in Malaysia. The
experiment took place on the campus of the International Islamic University
in Malaysia, which was often exposed to sun radiation. The soil type is
sandy, and the grass is short. The research was divided into two phases: the
first measured temperatures up to 5 meters, while the second focused on
temperature at shallow depths. There was a small variation in temperature
for shallow depths, which was observed. The findings show that using EAHE
in a building is only practicable if the air temperature rises over 34°C. Also,
at a depth of 1 meter, the ideal temperature for the undisturbed soil
temperature was found.
Li et al. [66] investigated a hybrid EAHE that included a solar chimney. The
solar collector serves as a link between the solar chimney and the structure.
An EAHE pipe with one end exposed to the outside and the other end
exposed to the inside makes up the system. The experimental arrangement
was created at the University of Nebraska's testing laboratory. The solar
chimney was developed to compensate for the pressure losses caused by
EAHE. Figure 12 shows a schematic illustration of the configuration. Time
and date, indoor relative humidity (percent), outdoor relative humidity
(percent), supply air relative humidity (percent), supply airflow rate (m3 /s),
solar collector airflow rate (m3 /s), average indoor temperature (°C), supply
air temperature (°C), and outdoor temperature (°C) are the variables
investigated. The temperature of the underground earth was measured at
various depths. Less was discovered to be the case. For deeper depths,
temperature fluctuations were noticed. The highest temperature possible at
2.9m deep, there was a difference.
Niu et al. [69] The transient control volume technique was used by to
investigate the 2D heat transfer mechanism. Thermal balance was used to
divide the computational domain into control units. Continuous and
intermittent modes were used to conduct a self-recovery temperature
analysis. The data was compared to an experimental setup that was already
in place in Omaha, Nebraska. The measurements were taken to determine
21
the system's cooling capability. MATLAB 8 was used to run the simulations.
The outflow temperature rises as the soil air temperature rises, according to
the findings. During validation, it was discovered that the validation results
were in good agreement with the experimental results. The soil temperature
near the tube fluctuated more than the one further away. As a result, the
temperature difference between the soil and the air is greater than the
temperature at outlet. The night is the best time to reclaim your lost energy.
In order to analyze the recovery analysis, two modes were considered:
continuous modes and intermittent modes. The soil temperature was
recovered during non-working time in intermittent mode. With time and
distance, the ability to recuperate declines. In continuous mode, the recovery
temperature ranges between 19.5 and 21.7°C as the supply air temperature
rises.
22
during the summer season, and that thermal insulation was advantageous for
Cd. Juarez city during the winter season.
Hatraf et al. [61] To determine the depth of the pipe, looked at the soil ground
temperature profile. The soil's physical features were investigated, and a
mathematical model was developed. By considering different flow rates of
100, 150, and 200 m3 /s, a comparison was conducted between the computed
and experimental results. The performance of the 26 is influenced by the air
flow. The Nusselt number rises in tandem with the Reynolds number. As a
result, soil qualities have a significant impact on performance. The pipe's
depth is determined by the pipe's diffusivity.
23
Figure 3.1: Schematic diagram of EAHE coupled to wind catcher
Vaz et al. [58] studied the temperature fields' transient behavior in the
exterior air soil and underground ducts. Casa Ventura was used to test the
experimental setup. Temperature and humidity in the soil, air, and water
were also measured. This study is on fluid and heat flow. It was investigated
the thermal properties of Udult soil with a density of 1800 kg/m3. At various
depths, the variance in soil temperature was explored. The temperature rises
as the depth is increased, according to the findings.
Ariffin et al. [60] looked at the best pipe materials for predicting the ideal air
temperature for thermal comfort. For the environmental modelling tool, the
study employs Energy Plus. Polyethylene (PE), PVC (polyvinyl chloride),
steel, clay, concrete, and copper were the pipe materials studied. The
performance of three pipe materials systems was investigated: single pipe
material, hybrid pipes, and insulated hybrid pipes. Three polyethylene pipes
are buried at varying depths in the research. A parametric study of six
different pipe materials was conducted using Energy Plus software: PVC
(polyvinyl chloride), PE (polyethylene), steel, clay, concrete, and copper.
The results of the simulation were compared to those of an experiment done
in 2012. The study included four different sorts of tests, which are listed
below. Test 1: primary test, Test 2: individual material simulations, Test 3:
hybrid material (simulations of two different materials), and Test 4: hybrid
material and insulation simulations (Simulation of combination of 2
materials and insulation). The first test was used to standardize the factors
across the three simulations. Test 2: Each of the six pipe materials was
assessed. Pipes with a diameter of 50mm were not accessible in the
Malaysian market for the pipe materials clay and concrete, so they were
excluded from the study. In compared to the other three, the PE
24
(polyethylene) showed the greatest temperature drop of 6.23°C. Test 3: Two
pipes were simulated, one inside the other. The results showed that
combining metal and non-metal reduces temperature more effectively. Test
4: Two types of simulations were performed in this test: 4A: hybrid system
+ water and 4B: hybrid system + Rockwool insulation. The combination of
Steel and PE (ST+PE) is the best water-hybrid system, according to the
results. Although the metal+ nonmetal combination produces better results,
nonmetal+ nonmetal can also be used. As a result, PE + PE pipe is
recommended for use since it is more robust and less expensive. The
temperature reduction ranges between 6.03 to 6.23°C, according to
simulation data from 4B. As a result, this combination produces a greater
temperature difference.
Sansui et al. [57] investigated the ability of Malaysian soil to apply EAHE.
The goal of this study is to forecast soil temperature for various soil surface
conditions. The experiment was place on the International Islamic
University's Gombak campus in Malaysia. Three different types of soil
surface conditions were taken into account. The soil was bare and short grass,
and it was protected by layers of reclaimed wood palette and insulated by
layers of used tyres. To determine the suitable soil surface condition, a
parametric analysis was used to estimate the soil temperature at an optimum
depth. Energy Plus software was used to do the simulations for the
investigation. The temperature of the soil was measured, and it was
discovered that it ranged from 21.5 to 34.1°C. The soil temperature was the
coldest of all three types when shaded with a timber palette and insulated
with used tyres. When the simulation is conducted for all three soil surface
conditions while taking into account solar radiation, the soil shaded with a
timber palette and insulated with old tyres produces the best results. As a
result, a cooler soil temperature allows for improved heat exchange and
cooling. As a result, with Malaysia's climate, EAHE cooling is viable.
25
inside the corrugated pipe was assumed to be turbulent in a CFD model. The
dissection was carried out utilizing the PRESTO scheme. The examination
of soil temperature at various depths revealed that on a hot summer day, the
soil temperature rises as the depth decreases. The VEAHE was turned off to
measure the performance of HEAHE, and vice versa. The average room
temperature for HEAHE was Shipping ContainerAC AC Buried Pipes
Vegetation Shipping Container VEAHE, according to simulation data.
HEAHE Vegetation Ground 23 is slightly larger than VEAHE Vegetation
Ground 23. As a result, it was determined that the VEAHE provides a greater
reduction in temperature drop than the HEAHE. As a result, for Australian
weather, VEAHE is preferred.
Rodrigues et al. [54] For EAHE, used constructional design to get the highest
thermal potential. Ansys FLUENT was used to run the numerical simulation.
FLUENT was used to create the computational domains, which were then
discretized in Gambit. The numerical simulation was carried out in real time.
The validation was performed on a 22-experiment setup built in 2007. Adrain
Bejaan designed the constructional design in 1997. Five distinct EAHE
configurations were tested in this experiment. This design was used to
discover the best installation using volume fraction parameters. During
December, a high thermal potential was attained for installation I. Thermal
potential had a consistent behavior in Installation 2. The horizontal spacing
of pipe was increased in this arrangement, which increased the heat potential.
The issue of volume fraction was considered in installation 3. The months of
May, June, July, October, November, and December had the maximum
thermal potential. During January and February, there was no discernible
change in thermal potential. Thermal potential has an intermediate value in
installation 4. Installation 5 demonstrated outstanding heating and cooling
performance. Thus, a constant air volume fraction can be maintained by
increasing the number of ducts and decreasing the duct diameter.
26
disqualified by the central difference scheme. Three Mexican cities (Juarez
City, Mexico City, and Merida) and four Reynolds numbers (100, 500, 1000,
and 1500) are used in the analysis. It was determined that in extreme winter
conditions the EAHE has a high heating potential for all Reynolds numbers
in the cities of Juarez and Merida. For just Reynolds number 100, the EAHE
system for Mexico has a good heating and cooling potential.
Chiesa et al. [56] set out to investigate the effects of EAHE in an Imola, Italy
school building over the winter and summer seasons. The EAHE was
attached to a solar wall air collector constructed of polyethylene. GAEA
software (Graphische Auslegung von Erdwrme Austauschern) was used to
assess the EAHE system's energy efficiency. Using Parson and Koehler's
expression, the effectiveness of EAHE was discovered. This equation was
used to verify the data without taking into account the outlet temperature. To
predict the input, outflow, relative, and absolute humidity, a psychometric
analysis was performed. During the summer, there was a considerable drop
in temperature along with a rise in relative humidity. When the dew point
temperature is attained in the tubes, the absolute humidity rises. The
temperature rose dramatically during the winter, necessitating treatment of
the outlet air to bring it up to inside standards. The rate of heat transmission
was calculated using an energy balance. The pressure loss of the system was
also taken into account while calculating the COP of the EAHE. The results
of the monitoring were compared to those found in the literature. EAHE was
discovered to be an effective system that is dependent on the design
parameters.
27
Gan et al. [51] developed a FORTRAN model to investigate EAHE's thermal
performance. Two interfaces were examined for studying the heat and
moisture transfer 3D mass and energy equation: between the ground and the
atmosphere, and between the heat exchanger and the supply air. The current
study's simulation was done using FLUENT in two modes: continuous and
intermittent. The heat is transmitted from the earth to the air at any given
time in continuous mode. This occurs in intermittent mode for a certain time
period during which the air is preheated before heat transfer takes place.
Simulations were run at various lengths (10 to 40 m). The temperature of the
ambient air increased from 5-6.6°C. With a reduction in soil temperature, the
heat transmission rate reduces day by day. As a result, the rate of heat transfer
and temperature rise reduces as the length grows, but overall heat uptake
increases. Furthermore, the temperature and moisture interaction between
the heat exchanger atmosphere and the soil has a considerable impact on the
rate of heat transfer, according to the author.
Barakat et al. [49] investigated the use of EAHE as a gas turbine inlet. The
thermal performance of EAHE was investigated using a MATLAB-based
transient 1D model. An experiment study in Damietta Power Plant, North
Carolina, was used to validate a mathematical model. The output temperature
drops as the length decreases, according to the findings. As a result, a greater
pipe length allows for more heat exchange. It was also discovered that as
pipe diameter and velocity increase, the temperature at the exit increases and
lowers. The fuel consumption was calculated, and employing EAHE as a gas
turbine inlet resulted in a reduction of 4.4 percent. As a result, a longer tube,
a smaller diameter, a deeper placement, and a low inlet air velocity result in
a lower outlet temperature when using EAHE.
28
a result, as the output temperature rises, the soil temperature rises as well. In
addition, as pipe length is increased, the temperature inside the pipe rises
along its length but falls at the exit due to heat losses to the outside. During
the winter, the temperature rises with depth, and vice versa, according to
CFD models. Parametric research was also carried out to investigate the
design parameters used in simulation. The study's findings reveal that as the
pipe diameter grows larger, the air temperature drops, reducing convection
heat transmission. The effect of outlet temperature change was also
considered for three different pipe materials. It was discovered that all three-
pipe materials had equal output temperatures. As a result, the pipe material
has less of an impact on EAHE performance.
29
Yang et al. [45] The performance of EAHE in Harmonic heat conditions was
predicted In China, the experiment was carried out using a cylindrical
coordinate system. The numerical simulation took t=1000s to complete. It
was discovered that as the depth of the well increases, the temperature of the
output falls. The annual fluctuation amplitude diminishes with depth and
reaches a maximum value when the depth exceeds 7m. The results reveal
that as the radius expands, the outflow temperature lowers at first, then rises.
The capacity of cooling and heating is determined by the outlet temperature
and air flow rate. The cooling/heating capacity increases as the flow rate
rises.
Bojic et al. [36] In Athens, Greece, studied the performance of ATEHE over
the summer and winter seasons. During the winter, the space was heated with
a heater, and during the summer, it was cooled with an air conditioning
system. At a temperature of 20°C, the results show that as the length of the
pipe rises, the energy use ratio for the building increases. Summer days had
a greater energy use ratio than winter days, it was also discovered. During
the summer, the energy expenditure was 11d/MJ-s with a 10 m long pipe and
7d/MJ-s with two pipes for ATEHE. The author argues that when the pipe
length is L 17m, it is desirable to utilize four pipes rather than two, making
the ATEHE less expensive. Summer temperatures at the discharge were
30
found to be three times greater than winter temperatures. This clearly
demonstrates that the ATEHE is more energy efficient and less expensive in
the summer than in the winter.
Goswami et al. [40] For the experimental setting in Florida, employed plastic
corrugated pipe. The experiment was carried out on soil with a high moisture
content. The EAHE system was operational for 8-12 hours per day. The air
was circulated at the output using a heat pump. It was discovered that if air
was distributed evenly throughout the tunnel, the COP increased by 8%.
During the chilling period, the open loop tunnel utilized 14kWh of electricity
and 52kWh during the heating period. As a result, the EAHE uses less energy
than traditional air conditioning. The EAHE is also recommended for
agricultural structures, according to the author. The payback period was
likewise estimated to be around 20 years. As a result, adopting a multi-pipe
system rather than a single pipe is more cost effective.
Fard et al. [39] developed a system that consists of two parallel horizontal
pipes in Iran's north east. The goal of the experiment was to see how
parameters like burial depth, pipe length, air velocity, and pipe material
affected the results. The factorial design was used in the simulations. The
average relative humidity was 67 percent with an average temperature of
3.8°C (heating mode) and 14 percent with an average temperature of 36.5°C
(cooling mode), according to the results (cooling mode). In addition, for both
heating and cooling modes, the temperature of the soil and the length of the
pipe rise as the depth of the pipe increases. It was also discovered that the
differential temperature of galvanized pipe is higher than that of PVC, owing
to the fact that galvanized pipe has a higher heat transfer coefficient than
PVC. In the case of pipe material, there is no discernible effect because pipe
material does not alter with temperature.
Mongkon et al. [34] used three seasons in Chaing Mai for HETS cooling in
Thailand's tropical climate: winter, summer, and monsoon. The effectiveness
of the cooling system and the amount of condensation in the pipes were
assessed. As illustrated in figure 6, the experiment was completed using a
series of pipes arranged in a serpentine pattern to simulate fully developed
turbulent flow. Regression analysis is used to investigate the temperature
differential between the intake and output. During the summer, there was a
31
significant temperature variation. The saturation temperature drops as the
dew point temperature rises, according to condensation analysis. In
compared to the other two seasons, the results also show that summers have
the highest COP.
The results of all the above literature survey conducted by researches around
the world are tabulated below. Table 3 represents the experimental results
studied around the world. Table 4 represents the analytical results studied
around the world.
32
Table 3.3: Experimental results studied around the World
Author place/year season material Length Diameter Depth Ambient Temperature Velocity
of pipe of pipe (m) of pipe temperature variation range (m/s)
(m) (m) (°C) (°C)
Mongkon et Thailand, Summer Iron 38.5 0.08 1 24.5 20.88 9
al. [34] 2013
Winter 28.8 21.37
33
Table 3.4: Analytical results of EAHE studied around the world
Author place/year season material Length Diameter Depth Ambient Temperature Velocity
of pipe of pipe (m) of pipe temperature variation range (m/s)
(m) (m) (°C) (°C)
Niu et al. [61] USA, 2015 Summer Steel 57 0.45 3 26-34 13-16 -
Gan et al. [59] UK, 2015 Winter HDEP 0.2 1.5 10 17.6 2
Xamana et al. Mexico, Summer - 10 0.15 5 28 25.3 -
[60] 2015
Ariffin et al. Malaysia, summer PVC 30 0.076 1 36.46 30.3 0.5
[53] 2014 PE 30.2
Steel 30.24
Copper 30.25
Ahmed et al. Queensland Winter PVC 8 0.021 - 21.01 23-24 3.4
[52] 2014
Vaz et al. [51] Brazil, Summer, PVC A:0.11 - 1.6 30-18.8 20-12 -
2014 Winter B:0.11 0.6
C:0.10 0.5
Bojic et al. Greece, Winter PVC 50 0.15 2.4 8 - 8
[36] 1996 Summer 37 23-35
Mihalakakou 1994 Summer PVC 14.8 0.15 1.1 - 17-33.5 10.5
et al. [21]
34
CHAPTER 4
RESEARCH METHODOLOGY
The study intends to find the temperature difference between the inlet and
outlet of the air for both experimental setup and theoretical calculations of
EAHE. The theoretical calculations are calculated using NTU method. This
study also validates the experimental temperature difference with theoretical
temperature difference. The experimental setup is an open loop horizontal
system consisting of pipe of aluminum having outer diameter of 0.076m and
thickness of 0.0015m. the aluminum pipes are buried at a depth of 1.5m.
ambient air is sucked into the pipes by means of blower by a 18w, 240volts,
1350rpm motor. The blower is used to suck the hot air through pipes and
deliver the cool air in summer and vice versa in winter. The required results
will be in the form of temperature difference between the inlet and outlet of
the air passing in EAHE.
understanding the
principe of EAHE
design parameters
assumptions
calculations
extraction of results
validation of results
Figure 4.1: Flow chart of the research methodology
35
4.1 SELECTION OF PIPES LAYOUT AND GEOMETRY
36
Table 4.1: thermo physical properties of different materials
Material Density(kg/m3) Specific heat Thermal
capacity conductivity
(J/Kg K) (W/m K)
Aluminum 2719 871 204
PVC 1380 900 0.161
Steel 7833 465 54
Copper 8978 381 387.6
The most prevalent alloy for aluminum extrusion is 6063. It is used for
visible architectural applications such as window frames, door frames, roofs,
and sign frames, as well as heat exchangers, because it permits complex
shapes to be made with very smooth surfaces suitable for anodizing. 6061 or
6082 are commonly used in applications that require more strength.
37
Table 4.3 : Properties of A6063
Physical properties
Density (𝜌) 2.69 g/cm
Mechanical properties
Young's modulus (E) 68.3 GPa
Tensile strength (σt) 145-186 MPa
Elongation (ε) 18-33%
Poisson's ratio 0.3
Thermal properties
Melting point (Tm) 615 °C
Thermal conductivity (k) 201-218 W/mK
Specific heat capacity (C) 900 j/kgK
Electrical properties
Volume resistivity (ρ) 30-35 n Ohm.m
38
Figure 4.4: Experimental setup
4.3 ASSUMPTIONS
39
4.4 CALCULATIONS
𝜌𝑣𝐷𝑖
• Reynolds number (𝑅𝑒 ) = ... (4.2)
𝜇
𝜇𝐶𝑝
• Prandtl number (Pr)= … (4.3)
𝐾𝑎
𝑓
(8)(𝑅𝑒−1000)𝑃𝑟
• Nusselt number (Nu) = 1 … (4.4)
2
𝑓 2
1+12.7(8) (𝑃𝑟 3 −1)
𝑁𝑢 𝑘𝑎𝑖𝑟
• Convective heat transfer coefficient (he) = … (4.5)
𝐷𝑜
1 1 𝑟
• Overall heat transfer coefficient (Ut) = ( + ln ( 𝑜))−1 … (4.6)
ℎ𝑒 2𝜋𝑘𝑡 𝑟𝑖
𝑇𝑜𝑢𝑡 −𝑇𝑖𝑛
• Effectiveness (𝜖) =
𝑇𝑤𝑎𝑙𝑙 −𝑇𝑖𝑛
= 1 − 𝑒 −(𝑁𝑇𝑈) ... (4.7)
𝑈𝑡 𝐴 𝑈𝑡 𝐷𝑖 𝐿
• NTU = = … (4.8)
𝑚𝑎 𝐶𝑝 𝑚𝑎 𝐶𝑝
40
4.4.2 Input parameters
41
4.4.3 Sample Calculations
𝜋
• Mass flow rate (m) = (𝑣 ∗ 𝜌 ∗ ∗ 𝐷𝑖 2 )
4
𝜋
= (7.775 ∗ 1.1465 ∗ ∗ 0.07452 )
4
= 0.03886 𝑘𝑔/𝑠
𝜌𝑣𝐷𝑖
• Reynolds number (𝑅𝑒 ) =
𝜇
1.1465∗7.775∗0.0745
= −5
1.7∗10
= 39064.46
𝜇𝐶𝑝
• Prandtl number (Pr) =
𝐾𝑎
1.7∗10−5 ∗1006
=
0.0275
= 0.622
• 𝑓 = (0.79 ln(𝑅𝑒) − 1.64)−2
= 0.0222
𝑓
( )(𝑅𝑒−1000)𝑃𝑟
8
• Nusselt number (Nu) = 1 2
𝑓 2
1+12.7( ) (𝑃𝑟 3 −1)
8
0.0222
( )(39064.46−1000)∗0.622
8
= 1 2
0.0222 2
1+12.7( ) (0.6223 −1)
8
= 80.32
𝑁𝑢 𝑘𝑎𝑖𝑟
• Convective heat transfer coefficient (he) =
𝐷𝑜
42
80.32∗0.0275
=
0.076
= 29.1 W/m2K
1 1 𝑟
• Overall heat transfer coefficient (Ut) = ( + ln ( 𝑜 ))−1
ℎ𝑒 2𝜋𝑘𝑡 𝑟𝑖
1 1 0.038
=( + ln ( ))−1
29.1 2∗𝜋∗205 0.03725
=29.086 W/m2K
𝑈𝑡 𝐴 𝑈 𝐷𝑖 𝐿
• NTU (Number of Transfer Units) =
𝑚𝑎 𝐶𝑝
= 𝑚𝑡
𝑎 𝐶𝑝
29.086∗0.0745∗4
=
0.03886∗1006
= 0.7
= 0.03886*1006(37.1 - 33)
= 160.3
43
CHAPTER 5
In the present study the experimental results are found using a thermocouple,
thermometer, and anemometer. The thermocouple was coupled with the
outer wall of the pipe buried inside the ground. Digital thermometer is used
to find the ambient air temperature and outlet temperature of the air.
Anemometer is used to find the velocity of air.
5.1 EXPERIMENTAL RESULTS
45
5.2 THEORITICAL RESULTS
All the theoretical results remain same for both experimental values except
the values depending on temperature.
From the above results it has been observed that for the same input
parameters the outlet temperature in both experimental and theoretical
results are approximately equal. Hence both experimental and theoretical
results are validated.
46
velocity of air v/s outlet temperature air
33.5
33
33
32.5 32.3
outlet temperature °C 32 31.8
31.5
31
30.5 30.2
30
29.5
29
28.5
7.755 6 5 4
velocity of air in m/s
34 33.76
33
33
32.1
32
31
30
copper aluminium steel pvc
pipe material
47
CHAPTER 6
CONCLUSION
Buildings consume a lot of energy for thermal comfort; thus, several passive
heating and cooling systems and tactics have been devised to save energy.
EAHE, which employs geothermal energy, is one such passive technology.
The purpose of this work is to investigate the cooling potential of the EAHE
system. Also validates the experimental results with theoretical results. It has
been observed that the both theoretical and experimental results are
validated. The temperature difference was found to be 4-7°C between the
inlet and the outlet. From the literature review conducted it is found that the
material of the pipe does not show much effect on the performance of the
earth air heat exchanger, if other parameters are designed properly. And the
main parameters for are depth of burial, diameter of pipe, velocity of air and
length of the pipe.
As a result, we can conclude that earth-air heat exchangers are a viable
method for building space conditioning. If properly constructed, the EAHE
system can be a viable and cost-effective alternative to traditional air-
conditioning systems.
48
REFERENCES
49
[12] Ghosal et al, “An experimental validation of thermal modelling
of a greenhouse with an integrated earth to air heat exchanger”, 2004,
Vol. 36, pp. 219-227.
[13] V Bansal et al, “The effect of soil thermal conductivity and
operating time on the performance of the Earth Air Tunnel Heat
Exchanger in the short term”, 2013, vol. 103.
[14] O.P. Jakhar et al, “Earth Air Heat Exchanger CFD Thermal
Analysis for Hot and Dry Climates”, 2019.
[15] T. Choudhary et al, “using a simple and cost-effective earth to
air heat exchanger approach to reduce the effects of changing climate
on buildings”, 2014.
[16] M. Jamil Ahmad et al, “heating/cooling potential and carbon
percentage of earth air heat exchanger”, 2010.
[17] K.H. lee et al, “cooling/heating potential of an EAHE in
building”, 2008, vol 40.
[18] H.K. Dhruw et al, “Earth tube heat exchanger-a review paper”,
2015, vol. 3.
[19] A. Mathur et al, “The effect of soil thermal diffusivity on the
performance of the EATHE system in the short term”, 2014.
[20] R. Kumar et al, “Evaluation of the performance and energy-
saving possibilities of an earth-air-tunnel system in conjunction with
a non-air-conditioned building”, 2003, vol. 38, pp. 807-813.
[21] D.Y Goswami, “Using an underground air tunnel for heat
transfer analysis in environmental control”, 2015, vol 107.
[22] S. Barakat et al, “Earth to air heat exchanger (EAHE) cooling
system enhancement of gas turbine power output”, 2016, pp. 137-146.
[23] Nilesh et al, “A review on earth air heat exchanger”, 2016,
vol. 5, [IJERT].
50