ITER_D_7HKPGW v1.

1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

L 11-B1-01 L

1A
For testing Note 10
TCWS Drain Tanks Upper Level
S S
Note 9

VG-0237
Chilled water
Vent

26CHH2
L
CHWS-H2 supply
VG-2093 VG-2193
MFT
Valve
0231

PI-2093
DN150
MP MTE MTH
to Exhaust Filter

VG-0233

VG-0234

VG-0235
2154 2152 2130
K S (Vault) H K
HMS vents
x2 x2 24VPHM-PID-001/09 26CH_32_001-IFP-0013
MT MP

LC
1A From HX-0008
1E
24VPHM-PI-2030
0231 0231 L

DN15
DN15

DN25
VG-2030 VG-2130 Process gas outlet PI-0231 PI-0231 CHWS-H2 return
DN25 - 4-S3S0150-2 - CC DN25 - 4-S3S0150-2 - CC 26CH_32_001-IFP-0014
DI-0231
VK-0236

VG-0230
VG-2057
S S

PI-2091
N2 safe state purge
From VVPSS/HMS

VG-2092 VG-2192

PI-2057
J J
DN50

S S

Note 2
DN50
VG-2091 VG-2191
H2
x2 MAM
2093

PI-2091
H2
I x2 MAM HH I
PI 7879 2091 AH
ADT/DYS Vents
1A
-
VC-7515 VG-7515

DN25 - 4-S3S0150-2 - CC
x2
AL

PI-0230
DN15 MPD
2090
CVCS VP SWT vent PI 7629 LL
1A VG-2190
-
VG-7629 H Note 8
MPH
2090
H VVPSS Eva/Vent H
1A x2
- PI-0220
24VP_32DT_001-IFP-0001 DN50 - 4-S3S0150-2

Note 1
SDT Vac. Line PI 7953 Note 3
1A 1 2 2

VC-0212
- P P P
VK-7952 1
P
PV-0001 MP
26_32DT_001-IFP-0001
MP
HH
H MT H
HH
MP Note 4 Note 4
7800 0230 0210 0210
FH-0213

DN25

DN15

DN15
From WCT
G PI 7860 venting PI-0210 PI-0211 PI-0213 N1 PI-0214 PI-0214 32DT80-PID-1126/09
G
1I
DN65 32DT80-PI-0214
(DN 65) VG-7861 DN65 - 4-S3S0150-2 - PFP-61
VG-0210
DN65 - 4-S3S0150-2 - PFP-61 DN65 - 4-S3S0150-2 - PFP-61
VG-0215 VG-0216
DN100 - 4-S3S0150-2 - PFP-61

(SIV) Note 1 Note 1


PI 5507 Note 5
Air supply Note 1 Note 1 MPD
1A 0213
-
VG-5507

VC-0211
Note 6
N2 Supply PI 5032
1A
-
F VC-5032
VG-5032 F
N2 for Q2 VR-7005 DK-7876
dilution
N5 N1 N2
Vent Header PI 7816
1A
-
VC-7811 VG-7816

N4 N3
HX-0210
Relief Headers PI 7807 Note 7
1A
-
E MAG E
DN25

PI 1304 7850
Transfer- NB-DT
1A
-
VC-1304 VG-1304
VG-0232

VG-0222
LC

For drainage
TA-7850 and testing
WCT

D D
NOTE 11 PI 7807 PI-0212 Condensate return to WCT
VG-7859
DN15 DN20 - 4-S3S0150-2
VK-7859 26_32DT_001-IFP-0002
(SIV)

To sampling
and RadWaste
VG-7850
TTT-ISA conversion table PBS24/26/32
C C
Notes: Instrument TTT code Instrument ISA Code Instrument
1. Fire protection. MP-0230 PTAHH-0230 Pressure Transmitter with high and high high alarm
2. Thermal insulation with vapour barrier to avoid condensation along chilled water piping. MT-0210 TTAHH-0210 Temperature Transmitter with high and high high alarm Legal Owner
3. Inlet flow throttle valve for filter efficiency test, min 8-20 diameter upstream of 1st sampling point. Throttle MP-0210
MPD-0213
PT-0210
PDT-0213
Pressure Transmitter
Differential Pressure Transmitter
ITER ORGANIZATION
valve can also be used as aerosol injection point.
MFT-0231 FTAL-0231 Flow Transmitter for DI-0231 with low alarm
4. Sampling points (min 8 diameter upstream/downstream of filter, ISO-16170). In addition, these nozzles can be MT-0231 TTAH-0231 Temperature Transmitter with high alarm INTERNAL USE
used for flow measurement (Anemometer). MP-0231 PTAL-0231 Pressure Transmitter with low alarm Information contained in this drawing is not public.
5. Isolation valve in PBS32 side to stop collection of PBS 26 exhaust in off-normal operating conditions. MAG-7850 HE-7850 Hydrogen Detector It is reserved to an internal use and may be shared with third parties if a need-to-know is established
B B
6. The throttle valve VC-0211 shall be adjusted to pre-set positions depending upon the clients requirements and MP-7800 PT-7800 Pressure Transmitter Created By Technical Reference Approved By Version modifications
their mode of operation. RAULTG/
MP-2154 unknown Pressure Transmitter (redundant)
WAGNERR KUMARR/LEPETIL BELOGLS --
7. Condenser to be installed at adequate elevation (> 8.5 m from floor level) to provide enough water column MTE-2152 unknown Temperature Transmitter (redundant)
Document type
height to transfer condensate from condenser to WCT. MTH-2130 TSH-2130 High Temperature Switch (redundant)
8. The HMS safety vent, originates after HMS condenser and do not require moisture removal by DS (5PVPZU) . MAM-2093 unknown Hydrogen Detector (redundant) Piping and Instrumentation Diagram (P&ID)
MAM-2091 unknown Hydrogen Detector with alarm (redundant)
9. Flow transmitter FT 0231 may be removed if the Chilled water flow is monitored at the ChW supply-distribution Document title Sheet size
MPD-2090 unknown Differential Pressure Transmitter (redundant)
point. MPH-2090 PSH High Pressure Switch (redundant) 32DT80 Condensing and Filtration System (CFS) A1
10. Nozzle to remove trapped air if any from the chilled water circuit.
P&ID for HAZOP Sheet 1
A 11: The PBS 24 and 26 system parts are just for the reference and not under the scope of the P&ID review. of 2
A
Drawing number IDM number Date of issue Revision

7HKPGW 04 AUG 2022 V1.1