Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

THE ROYAL ATLANTIS RESORT AND RESIDENCES

Contract No : CN 0063 FCN No.: TRA-SBJ-FCN-EL-GEN-05564

EMPLOYER : ATLANTIS THE PALM LIMITED 2 Rev.00

CONTRACTOR : SSYANGYONG_BESIX J.V. DATE: 17/08/2022

FIELD CHANGE NOTICE


Civil Architectural
Electrical Electrical Mechanical Plumbing

SUBMITTAL No. :

DOCUMENT No. : TRA-TEC-EL-GEN-00148

DOCUMENT TITLE : GA Drawings for AHU-CA-02 Updated based on EI # 0481

STATUS OF SUBMITTAL : Approved As Noted

DESCRIPTION : GA Drawings for AHU-CA-02 Updated based on EI # 0481

SBJV Internal QA/QC Check


Refer to the EI # 0481, the manufacture drawing & control panel schedule for AHU-CA-02 Coordination
have been modified and enclosed for your review and approval . N/A
PACKAGE
TEAM INITIAL
INVOLVE

MEP

ARCHITECTURE

STRUCTURAL -
STEEL
STRUCTURAL -
CONCRETE

FAÇADE

OTH.(____,____,)

OTH.(____,____,)

Initiated By : Sarath DATE: 17/08/2022

Contractor Project Director : Received By DEC :

Signature/ Date : Signature/Date :

For Consultant :

Approved Approved as Noted Not Approved

COMMENTS :

Name Position Signature Date

NOTE : This info will be included in the revised shop drawing (where applicable)
TRA-SBJ-QCD-QA-GEN-00004 Rev.03 Date: 28/03/19
1 2 3 4 5 6 7 8

E E

D D

CLIENT: PANEL REF:

ATLANTIS THE PALM LIMITED 2 (ATP2) HT1-G00-CP-AHU-02


[ FED FROM : SMDB-H1-GR01-01 ]
C C
PROJECT: MAIN CONTRACTOR:

THE ROYAL ATLANTIS RESORT


AND RESIDENCES M/s. SsangYong - Besix Joint Venture (SBJV)
PALM JUMEIRAH CRESCENT, DUBAI, U.A.E.

CONSULTANT: MEP subcontractor:

B M/s. DYNAMIC ENGINEERING CONSULTANTS M/s. SPECON L.L.C. B

Design & Assembly By :


QTY. 01 No.
PACIFIC OCEAN ELECTRICAL QTN NO. 13295
3 08.07.19 FACTORY MOD. ASBUILT AQL AJMAL VENKATESH SWITCHGEAR INDUSTRIES L.L.C
A
JOB NO. 3397
P.O. BOX 62154, SHARJAH, U.A.E E-mail: sales@pacificocean.ae, poet7@eim.ae
2 31-03-19 FOR MODIFICATION AJMAL AJMAL VENKATESH
TEL. 06 - 5345334, FAX. 06 - 5347212 Web: www.pacificoceansg.com A
1 14-01-19 ASBUILT KANNAN AJMAL VENKATESH REV:

0 08-10-18 FIRST ISSUE AJMAL AJMAL VENKATESH 0 1 2 3 4


REV DATE NATURE OF REVISION DRAWN DESIGNED CHECKED DRAWING. No.: POET - 017 / 18 - 5 - 12 SHEET No. 01 / 07
1 2 3 4 5 6 7 8

ENCLOSURES POWER SUPPLY SUPPLY OF AUXILIARIES REMARKS

SUPPLY VOLTAGE : 400V/50Hz VOLTAGE CONTROL 230 V /50Hz


E ALFANAR
24 V AC E
SIGNALING 230 V/50Hz
NEUTRAL SYSTEM ORIGIN
PANEL MOUNTING DIRECT TO EARTH (TT) EXTERNAL
FROM BUS BAR
WALL MOUNTED ISOLATED (IT)
AUXILIARY TRANSFORMER
FLOOR MOUNTED EARTHED (IN) WIRING

SEPARATE (TN-S) VOLTAGE 1.5mm2


NEUTRAL & EARTH CURRENT 2.5mm2
PRESENTATION WITH WITHOUT

FIXED FRONT
D D
CONNECTIONS CIRCUIT MARKING
FUNCTIONAL DOOR
MOUNTING INC OUTG
PLAIN DOOR POWER
DIRECT TO DEVICE
TRANSPARENT DOOR TERMINALS (EXTN. LINK) RYB

WITH KEY THRU TERMINAL BLOCKS LABELS

OTHER ACCESS PVC

FRONT COLOR : BLACK LETTERS ON WHITE BACKGROUND


FORM OF CONST. REAR
LANGUAGE: ENGLISH
LEFT SIDE:RIGHT SIDE
C FORM - 1 C
ENTRY
FORM - 2 INC OUTG

FORM - 3 TOP
BOTTOM
FORM - 4 (TYPE-2)
SHROUDING

ALL LIVE PARTS


DEGREE OF PROTECTION IP-54

PAINT FINISH RAL 7035

B B

COMPONENTS MOUNTING

INC OUTG

FIXED

QTY. : 01 No.
A A
3 08.07.19 FACTORY MODIFICATION ASBUILT AQUIL AJMAL PANEL REF/DRG. TITLE : THE ROYAL ATLANTIS RESORT AND RESIDENCES
PROJECT:
2 31-03-19 FOR MODIFICATION AJMAL AJMAL PACIFIC OCEAN ELECTRICAL HT1-G00-CP-AHU-02 PALM JUMEIRAH CRESCENT, DUBAI, U.A.E.
1 14-01-19 ASBUILT KANNAN AJMAL
SWITCHGEAR INDUSTRIES L.L.C. [ FED FROM : SMDB-H1-GR01-01 ] MEP M/s. SPECON L.L.C.
CONTRACTOR:
0 08-10-18 FIRST ISSUE AJMAL AJMAL
REV DATE NATURE OF REVISION DRAWN DESIGNED SHARJAH: TEL.06 - 5345334, FAX 06 - 5347212 DRG. No. POET - 017/18-5-12 REV. : 4 SHEET NO. : 02 / 07
1 2 3 4 5 6 7 8

1
E E
FAN
Q0
INCOMER

1KAD1

1KAD2
TRX

1KAD

KAF1

KAF2
1KA1

1KA2

1KA3
1F01
N

F01
F02
F03
1X2

Q1
F1

ESC

>
>
D D

>
L OCAL
R EMOTE
>
OK > i

>
S TOP R UN
RES ET

VFD BYPASS
RUN TRIP RUN TRIP
1KM2
HOA V B START STOP

VFD1
1800

1800
1F2 30KW

1KM1 1KM3

C C

1X1

SH. GND
FILTER DEPTH: 400mm X1

DEPTH: 400mm
B B

800 800

FRONT VIEW INTERNAL LAYOUT LABELS


CABLE ENTRY:
INCOMING - TOP 1. HT1-G00-CP-AHU-02
2. SUPPLY FAN
OUTGOING - BOTTOM

QTY. : 01 No.
A A
3 08.07.19 FACTORY MODIFICATION ASBUILT AQUIL AJMAL PANEL REF/DRG. TITLE : THE ROYAL ATLANTIS RESORT AND RESIDENCES
PROJECT:
2 31-03-19 FOR MODIFICATION AJMAL AJMAL PACIFIC OCEAN ELECTRICAL HT1-G00-CP-AHU-02 PALM JUMEIRAH CRESCENT, DUBAI, U.A.E.
1 14-01-19 ASBUILT KANNAN AJMAL
SWITCHGEAR INDUSTRIES L.L.C. [ FED FROM : SMDB-H1-GR01-01 ] MEP M/s. SPECON L.L.C.
CONTRACTOR:
0 08-10-18 FIRST ISSUE AJMAL AJMAL
REV DATE NATURE OF REVISION DRAWN DESIGNED SHARJAH: TEL.06 - 5345334, FAX 06 - 5347212 DRG. No. POET - 017/18-5-12 REV. : 4 SHEET NO. : 03 / 07
1 2 3 4 5 6 7 8

E E
L1 L2 L3

Q1 I> I> I>

L1 L2 L3

1 2

F1
3
D D
N

1KM1
A1 1/L1 3/L2 5/L3

Q0 1KM2 2/T1 4/T2 6/T3


A2
A1 1/L1 3/L2 5/L3
4
A2 2/T1 4/T2 6/T3 L1 L2 L3

VFD1
WITH BUILT-IN
DC CHOKE

U V W
C C
1F1 1KM3 5
A1 1/L1 3/L2 5/L3

A2 2/T1 4/T2 6/T3


1W
1V

R Y B 1U

1X1
U V W

N N
E E

B FEEDER
B
DESIGNATION INCOMER SUPPLY FAN

PHASES 3PHASE 3PHASE


RATING &
TYPE
63A TP ISOLATOR 65A TP MPCB + 80A 300mA 4P RCCB

CABLE SIZE -- --
TOTAL CONNECTED
LOAD 30KW 30KW

QTY. : 01 No.
A A
3 08.07.19 FACTORY MODIFICATION ASBUILT AQUIL AJMAL PANEL REF/DRG. TITLE : THE ROYAL ATLANTIS RESORT AND RESIDENCES
PROJECT:
2 31-03-19 FOR MODIFICATION AJMAL AJMAL PACIFIC OCEAN ELECTRICAL HT1-G00-CP-AHU-02 PALM JUMEIRAH CRESCENT, DUBAI, U.A.E.
1 14-01-19 ASBUILT KANNAN AJMAL
SWITCHGEAR INDUSTRIES L.L.C. [ FED FROM : SMDB-H1-GR01-01 ] MEP M/s. SPECON L.L.C.
CONTRACTOR:
0 08-10-18 FIRST ISSUE AJMAL AJMAL
REV DATE NATURE OF REVISION DRAWN DESIGNED SHARJAH: TEL.06 - 5345334, FAX 06 - 5347212 DRG. No. POET - 017/18-5-12 REV. : 4 SHEET NO. : 04 / 07
1 2 3 4 5 6 7 8

L 1F01 100

1X1 1

EM. STOP
PROVISION

E 2 101 E
1X2 1 FIRE ALARM START
FUTURE INTERLOCK
51
11
1S11
KAF1
52
14 12

BYPASS
102
2

VFD
31
103 1S11
43

1S11 11
12 44
(BYPASS)
129

HAND

AUTO
32 23

OFF
24
112 31
13
14
31
32 115 11
1KA3 11 43
23 44 KAF2
24 34 32
STOP 51
33 1S3 12 52
41 12 14
34

1KAD
KAF1
1S1
43 131 133
44
113

44
41
44 42

D D
11
116 33
230V AC AFTER F1

1S1
106 105 1KA1 1S1
111A START
13
21
1X2 7 8 14 12 34
(HAND)
133A
1X1 3 1KAD2 FIRE ALARM START
1S2 FIRE ALARM START
START/STOP
14 24 FUTURE INTERLOCK 130 132 FUTURE INTERLOCK
FROM BMS
4 114 R1C R2C R3C
21 21

SINK INT.

SINK EXT.
SOURCE.
1KA3 1KA2

DI1

DI5

24V
DI2

DI4
DI3

DI6
P24

0V
24 22 24 22

VFD1

RS485
21 31 95 97
1F1 41
KAF1 KAF1 1F1
1KAD

STOB
STOA
98

COM
96

COM

AQ1
24 22 34 32 44

24V

AQ2
10V

AI1

AI3
AI2
R1B R1A
110 111 122 1X1 11
R2A R3A
21

1KM2
1X2 3 4 5 6 117 OPEN SIGNAL
FIRE ALARM START 137 138
22
FUTURE INTERLOCK 22
13 FROM DAMPER 135
1KM1 1KM2 134
107 14
12 1X2 140 139
21 136 9 10
+ - - + 21
+ -
11
121 1X1 5 6 8 7 1X1 10 9
C 118 123 KAF2 C
1KA2 124 125 0-10V DC PTC 0-10V DC
14
SPEED REFERENCE INPUT 22 24 FEED BACK
12 21
SIGNAL FROM BMS TO BMS
1KM3
FIRE ALARM START
108 22
119 FUTURE INTERLOCK
127 128
126

11 21

1KAD 1KAD
14 12 24 22 X1 X1 X1 X1

109 1H1 1H3 1H4


1H2
A1 A1 A1 A1 A1 A1 A1 A1 A1
1KA1 1KAD1 1KM1 1KM3 1KM2 1KAD2 X2 X2 1KAD 1KA2 1KA3 X2 X2
A2 A2 A2 A2 A2 A2 A2 A2 A2

TRIP RUN DAMPER OPEN VFD TRIP VFD RUN RUN TRIP
N
(YELLOW) (GREEN) RELAY RELAY RELAY (GREEN) (YELLOW)

B BYPASS VFD
B

141 143 145 147

TYPICAL 230V AC CONTROL CIRCUIT FOR SUPPLY FAN VFD - Q1 43


41 31 31 SEQUENCE OF OPERATION :
1KA3 1KA2 1KAD
1S1
44 44 42 34 32 34 32 HAND MODE: SUPPLY FAN shall operate through Manual START / STOP Push Button.
142 144 146 148
OFF MODE: SUPPLY FAN shall turn to OFF position manually through selector switch.
1X1
13 14 15 16 17 18 19 20
AUTO MODE: SUPPLY FAN shall operate from BMS.
AUTO STATUS VFD RUN STATUS VFD TRIP STATUS DAMPER OPEN STATUS
FOR BOTH MANUAL AND AUTO MODE FAN WILL OPERATE AFTER
TO BMS
RECEIVING DAMPER OPEN CONFIRMATION SIGNAL.

QTY. : 01 No.
A A
3 08.07.19 FACTORY MODIFICATION ASBUILT AQUIL AJMAL PANEL REF/DRG. TITLE : THE ROYAL ATLANTIS RESORT AND RESIDENCES
PROJECT:
2 31-03-19 FOR MODIFICATION AJMAL AJMAL PACIFIC OCEAN ELECTRICAL HT1-G00-CP-AHU-02 PALM JUMEIRAH CRESCENT, DUBAI, U.A.E.
1 14-01-19 ASBUILT KANNAN AJMAL
SWITCHGEAR INDUSTRIES L.L.C. [ FED FROM : SMDB-H1-GR01-01 ] MEP M/s. SPECON L.L.C.
CONTRACTOR:
0 08-10-18 FIRST ISSUE AJMAL AJMAL
REV DATE NATURE OF REVISION DRAWN DESIGNED SHARJAH: TEL.06 - 5345334, FAX 06 - 5347212 DRG. No. POET - 017/18-5-12 REV. : 4 SHEET NO. : 05 / 07
1 2 3 4 5 6 7 8

E E

L F01 F02 03 F03 05


L

04
01

11 11

1KAD1 1KAD2
D 14 12 14 12
D
AFTER INCOMER 230V AC

AFTER INCOMER 230V AC


11

1KA3
07
14 12 TRF X1 1
X1 3
230/24VAC FIRE ALARM
63VA SIGNAL 24V AC SUPPLY
PE (CLOSES ON FIRE) TO SUPPLY FAN DAMPER
2
4

C 02 C
06

N
A1 A1
KAF1 KAF2
A2 A2

N EV1 N
B FAN B

08
31

KAF2

34 32

09
X1
5 6
FIRE ALARM SIGNAL
STATUS TO BMS

QTY. : 01 No.
A A
3 08.07.19 FACTORY MODIFICATION ASBUILT AQUIL AJMAL PANEL REF/DRG. TITLE : THE ROYAL ATLANTIS RESORT AND RESIDENCES
PROJECT:
2 31-03-19 FOR MODIFICATION AJMAL AJMAL PACIFIC OCEAN ELECTRICAL HT1-G00-CP-AHU-02 PALM JUMEIRAH CRESCENT, DUBAI, U.A.E.
1 14-01-19 ASBUILT KANNAN AJMAL
SWITCHGEAR INDUSTRIES L.L.C. [ FED FROM : SMDB-H1-GR01-01 ] MEP M/s. SPECON L.L.C.
CONTRACTOR:
0 08-10-18 FIRST ISSUE AJMAL AJMAL
REV DATE NATURE OF REVISION DRAWN DESIGNED SHARJAH: TEL.06 - 5345334, FAX 06 - 5347212 DRG. No. POET - 017/18-5-12 REV. : 4 SHEET NO. : 06 / 07
1 2 3 4 5 6 7 8

MATERIAL SCHEDULE
E ITEM DESCRIPTION REF No. MAKE QTY E
ENCLOSURE 1800mm(H) x 800mm(W) x 400mm(D) - RAL 7035 1
047-SBX181040 ALFANAR
SHEET STEEL ENCLOSURE
I/C- Q0 63A TP ISOLATOR WITH EXTERNAL HANDLE INS63-28902 + LV428941 SCHNEIDER ELECTRIC 1
Q1 65A TP MOTOR PROTECTIVE CIRCUIT BREAKER GV3-L65 SCHNEIDER ELECTRIC 1
F1 80A 300mA 4P RCCB iID-A9R14480 SCHNEIDER ELECTRIC 1
1KM1-1KM3 50A TP CONTACTOR 230V AC COIL LC1 D50A SCHNEIDER ELECTRIC 2
1KM2 65A TP CONTACTOR 230V AC COIL LC1 D65A SCHNEIDER ELECTRIC 1
RC FILTER FOR LC1D CONTACTOR - D40A-D65A(3P) 110-240VAC LAD4RC3U SCHNEIDER ELECTRIC 3
D FOR (1KM1-1KM3) D
1F1 48-65A THERMAL OVER LOAD RELAY LRD 365 SCHNEIDER ELECTRIC 1
1S1 THREE POSITION (HOA) SELECTOR SWITCH XB5-AD33 + 2xZBE-101 SCHNEIDER ELECTRIC 1
1S11 TWO POSITION (VFD/BYPASS) SELECTOR SWITCH XB5-AD21+2xZBE-101+2xZBE-102 SCHNEIDER ELECTRIC 1
1S2 START PUSH BUTTON-GREEN XB7-NA31 SCHNEIDER ELECTRIC 1
1S3 STOP PUSH BUTTON-RED XB7-NA42 SCHNEIDER ELECTRIC 1
1H1,1H3 RUN INDICATION LAMP (GREEN) LED (230V AC) XB7-EV03MP SCHNEIDER ELECTRIC 2
1H2,1H4 TRIP INDICATION LAMP (YELLOW) LED (230V AC) XB7-EV05MP SCHNEIDER ELECTRIC 2
F01-F03,1F01 CONTROL FUSE CARRIER STI-A9N15636 SCHNEIDER ELECTRIC 4
C KAF1-KAF2 AUXILIARY RELAY 24V AC RXM 4AB1B7+RXZ E2S114M SCHNEIDER ELECTRIC 2 C
1KA1-1KA3,1KAD1-1KAD2, AUXILIARY RELAY 230V AC RXM 4AB1P7+RXZ E2S114M SCHNEIDER ELECTRIC 6
1KAD,1KAD1-1KAD2,
VARIABLE FREQUENCY DRIVE - 30KW + ATV630D30N4 + VW3A1112 +
VFD1 SCHNEIDER ELECTRIC 1
REMOTE MOUNTING KIT + REMOTE-MOUNTING CORDSET VW3A1104R30
FAN+FILTER - 250mmx250mm (Air flow with export filters : 170m3/h) SQ-5525-1 LNP 1
EV1
EXIT FILTER SQ-5525 LNP 1
TRX AUXILARY TRANSFORMER 230/24V AC 63VA BK7-230/24-63VA LNP 1

B B

QTY. : 01 No.
A A
3 08.07.19 FACTORY MODIFICATION ASBUILT AQUIL AJMAL PANEL REF/DRG. TITLE : THE ROYAL ATLANTIS RESORT AND RESIDENCES
PROJECT:
2 31-03-19 FOR MODIFICATION AJMAL AJMAL PACIFIC OCEAN ELECTRICAL HT1-G00-CP-AHU-02 PALM JUMEIRAH CRESCENT, DUBAI, U.A.E.
1 14-01-19 ASBUILT KANNAN AJMAL
SWITCHGEAR INDUSTRIES L.L.C. [ FED FROM : SMDB-H1-GR01-01 ] MEP M/s. SPECON L.L.C.
CONTRACTOR:
0 08-10-18 FIRST ISSUE AJMAL AJMAL
REV DATE NATURE OF REVISION DRAWN DESIGNED SHARJAH: TEL.06 - 5345334, FAX 06 - 5347212 DRG. No. POET - 017/18-5-12 REV. : 4 SHEET NO. : 07 / 07
Mechanical Schedule - AHU
Electrical Data From Mechanical Electrical Data as per SLD and Load Schedules

General Data Electrical Data as per Mechanical Equipment Selection IFC SHOP DRAWING CONTROL PANEL
Run Around Coil Circulation
SUPPLY FAN FOR AHU EXHAUST FAN FOR AHU
Pump

Electrical Electrical Breaker


Number Electrical Number Electrical Fed From Phases TCL (kW)
load for load for Pump TCL Size
FAHU EQUIP. ID of load per Starter of load per Starter Starter PHASE Reference
Supply Exhaust Motor(w) (KW)
motors motor motors motor
Section Section

AHU-CA-02 1 30 30 VFD 0 0 - 0 30 SMDB-H1-GR01-01 3 PHASE 30 63 HT1-G00-CP-AHU-02


THE ROYAL ATLANTIS RESORT AND RESIDENCES SUBMITTAL & REVIEW FORM

TRA/SBJ/DEC/51543
SSANGYONG-BESIX Joint Venture Date: 09-Jul-20
Submitted For * Code
SUBMISSION OF DOCUMENTS, DRAWINGS, SAMPLES, ETC. APPROVAL 1
YOUR INFORMATION 2

ACTION **
RE: THE ROYAL ATLANTIS RESORT & RESIDENCES-MAIN CONTRACT Contract No.:
APPROVED A
CN0063 APPROVED AS NOTED B
DEC Dynamic Engineering Consultants
REVISE & RESUBMIT C
WE ARE SENDING HEREWITH / UNDER SEPARATE COVER, THE DRAWINGS/ REJECTED D
DOCUMENTS / SAMPLES LISTED BELOW. (DELETE AS NECESSARY)
DRWS., SPEC. OR CODE
Item REV DESCRIPTION TYPE
Submittal Action
BOQ. REF.

1 TRA-SPE-TEC-EL-GEN-00200 04 M2M3:Technical Submittal for MDB-H-19 & Associated Panels Load Schedules TEC 1
B

SBJV INTERNAL QA/QC CHECK COORDINATION

MEP __________________________ ARCHITECTURE ________________________ FAÇADE ____________________

OTHERS ( __________, __________ ) __________________


STRUCTURAL - STEEL ____________________ STRUCTURAL - CONCRETE ______________________

TYPE

PQD : PRE-QUALIFICATION DOCUMENTS OCT: ORGANIZATION CHART DDG : DESIGN DRAWINGS


MAR : MATERIAL SUBMITTAL
SDG : SHOP DRAWINGS MST : METHOD STATEMENT GEN : GENERAL CAL : CALCULATION
Programme of Work Activity ID Ref: Planned Start: 09-Jul-20
Programme of Work Description:
Planned Finish: 16-Jul-20
Copies
Electronic Copy to:

Mr.Andrew Pugh - Sr.Project Manager,F +G VALERY PAQUIER, PROJECT DIRECTOR S.P. HAN , DEPUTY PROJECT DIRECTOR
Document Control,F +G For Contractor
CONSULTANT'S COMMENTS
FM
Refer to the comments in the attached load distribution schedule. 20.07.2020
Copies To:

Project Director:

For DEC Dynamic Engineering Consultants


EMPLOYER'S COMMENTS

Copies To:

For Employer
Corrections or comments made relative to submittals during this review do not relieve the contractor from compliance with the requirements of the drawings and specifications. This check is only for review of general conformance with the design concept of the project and general compliance with
the information given in the contract documents. The contractor is responsible for confirming and correlating all quantities and dimensions selecting fabrication processes and techniques of construction; coordinating his work with that of other trades, and performing his work in a safe and
satisfactory manner.

1.08 Technical Transmittal Form.xls


TRA-SBJ-QCD-QA-GEN-00013 Rev.02 Date: 28/03/19
Document type TRA-SPE-TEC-EL-GEN-00171-R02
TRA-SPE-TEC-EL-GEN-00200-R04

Technical Submittal for


MDB-R-1 & Associated Panels Load Schedules
MDB-H-19
Project : The Royal Atlantis Resort and Residences (TRA)
Client: ATLANTIS THE PALM LIMITED 2 (ATP2)
Consultant: DYNAMIC EINGINEERING CONSULTANTS (DEC)
Main Contractor : SsangYong - Besix Joint Venture (SBJV)
MEP subcontractor: SPECON LLC
DETAILS OF CONNECTED LOAD/MAXIMUM DEMAND
AREA: Palm Jumeirah Crescent, Dubai U.A.E.
PROJECT : THE ROYAL ATLANTIS RESORT AND RESIDENCES CLIENT : KERZNER INTERNATIONAL
PLOT: PJCRC 19-27C
SMDB REF: SMDB-H1-GR01-01
CONSULTANT: DEC/WSP LOCATION : ELEC. ROOM (G-0808)
SMDB CONNECTED TO: SMDB-H1-GR01
RATING - AMPS CABLE SIZE ECC LENGTH OF CONNECTED LOAD IN kW TOTAL MAX. PROBE TYPE & NO OF kWh METERS
CIRCUIT/ FAULT PVC/
SP/ ISO/ 2/4 x 1C 2/3/4C SIZE CABLE R-PHASE Y-PHASE B-PHASE CONNECTED DEMAND 1 PHASE LV/HV CT REMARKS
FEEDER/ DUTY XLPE/ 3 PHASE
DB NO.
TP ACB MCCB MCCB
kA SWA/LSF mm2 mm2 mm2 (Mtrs) kW kW kW LOAD(TCL) LOAD (MDL) (1)
(2)
(3)
N/A KW KW

INCOMER TP 200 XLPE/LSF/SWA/LSF/CU 4C 95 1C 50 15

OUT GOING:

AHU-CA-01 TP 40 35 XLPE/LSF/SWA/LSF/CU 4C 10 1C 10 34 5.00 5.00 5.00 15.00 15.00 ELCB provided in control panel

AHU-CA-02 TP 63 35 XLPE/LSF/SWA/LSF/CU 4C16 1C 16 25 10.00 10.00 10.00 30.00 30.00 ELCB provided in control panel

AHU-CA-03 TP 20 35 XLPE/LSF/SWA/LSF/CU 4C 6 1C 6 31 1.33 1.33 1.33 4.00 4.00 ELCB provided in control panel

AHU-CA-04 TP 40 35 XLPE/LSF/SWA/LSF/CU 4C 10 1C 10 26 6.33 6.33 6.33 19.00 19.00 ELCB provided in control panel

AHU-CA-05 TP 20 35 XLPE/LSF/SWA/LSF/CU 4C 6 1C 6 22 1.00 1.00 1.00 3.00 3.00 ELCB provided in control panel

MAU-CA-01 TP 40 35 XLPE/LSF/SWA/LSF/CU 4C 10 1C 10 30 3.67 3.67 3.67 11.00 11.00 ELCB provided in control panel

DB-H1-GR01-05 MOVE TO SMDB-H1-GR02

DWEF-CA-01 TP 20 35 XLPE/LSF/SWA/LSF/CU 4C 6 1C 6 36 0.37 0.37 0.37 1.10 1.10 ELCB provided in control panel

TOTAL CONNECTED LOAD PER PHASE 27.70 27.70 27.70 83.10 83.10

MAXIMUM DEMAND [3PH] @ D.F 1.00 = 83.10kW TOTAL CONNECTED LOAD [3 PH] 83.10 kW

TYPE OF METER [RATING OF INCOMER] : [1] Upto 60A [2] Upto125A [3] LV CT............./A / HV CT....../......A

[1 Phase] [3 Phase]

CONTRACTOR : SSANGYONG - BESIX JOINT VENTURE (SBJV) FM


MEP CONTRACTOR : SPECON L.L.C DEC DATE: 08-Jul-20

20.07.2020
TRA-SPE-TEC-EL-GEN-00200 Page 33 MDB-H-19