Professional Documents
Culture Documents
Ba2398614 04 en Trafoguard
Ba2398614 04 en Trafoguard
Ba2398614 04 en Trafoguard
TRAFOGUARD®
Operating Instructions
2398614/04 EN
© All rights reserved by Maschinenfabrik Reinhausen
Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited
unless expressly permitted.
Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents,
utility models or designs.
The product may have been altered since this document was published.
We reserve the right to change the technical data, design and scope of supply.
Generally the information provided and agreements made when processing the individual quotations and orders
are binding.
The original operating instructions were written in German.
Table of contents
Table of contents
1 Introduction ......................................................................................................................... 7
1.1 Manufacturer ....................................................................................................................................... 7
1.2 Subject to change without notice ......................................................................................................... 7
1.3 Completeness...................................................................................................................................... 7
1.4 Supporting documents......................................................................................................................... 7
1.5 Safekeeping......................................................................................................................................... 8
1.6 Notation conventions ........................................................................................................................... 8
1.6.1 Hazard communication system ............................................................................................................................. 8
1.6.2 Information system ................................................................................................................................................ 9
1.6.3 Instruction system ................................................................................................................................................. 9
1.6.4 Typographic conventions .................................................................................................................................... 10
2 Safety ................................................................................................................................. 11
2.1 General safety information ................................................................................................................ 11
2.2 Appropriate use ................................................................................................................................. 11
2.3 Inappropriate use............................................................................................................................... 11
2.4 Personnel qualification ...................................................................................................................... 12
2.5 Operator's duty of care ...................................................................................................................... 12
5 Mounting ............................................................................................................................ 37
5.1 Preparation ........................................................................................................................................ 37
5.2 Mounting device ................................................................................................................................ 37
5.3 Connecting device ............................................................................................................................. 38
5.3.1 Cable recommendation ....................................................................................................................................... 38
5.3.2 Information about laying fiber-optic cable............................................................................................................ 40
5.3.3 Electromagnetic compatibility .............................................................................................................................. 40
5.3.4 Connecting cables to the system periphery ........................................................................................................ 43
5.3.5 Wiring device ....................................................................................................................................................... 43
5.3.6 Checking functional reliability .............................................................................................................................. 44
7 Commissioning ................................................................................................................. 48
7.1 Check wiring of device....................................................................................................................... 48
7.2 Setting up TAPCON®-trol.................................................................................................................. 48
7.2.1 Starting TAPCON®-trol ....................................................................................................................................... 48
7.2.2 Establishing connection....................................................................................................................................... 50
7.2.3 Creating device ................................................................................................................................................... 51
7.3 Checking the device's basic settings ................................................................................................. 52
7.3.1 Setting the display contrast ................................................................................................................................. 52
7.3.2 Checking basic settings via TAPCON®-trol ........................................................................................................ 52
7.4 Checking parameters, limit values and event configuration .............................................................. 66
Glossary........................................................................................................................... 169
1 Introduction
This technical file contains detailed descriptions on the safe and proper in-
stallation, connection, commissioning and monitoring of the product.
It also includes safety instructions and general information about the prod-
uct.
This technical file is intended solely for specially trained and authorized per-
sonnel.
1.1 Manufacturer
The product is manufactured by:
Falkensteinstraße 8
93059 Regensburg, Germany
Tel.: (+49) 9 41/40 90-0
Fax: (+49) 9 41/40 90-7001
E-mail: sales@reinhausen.com
Further information on the product and copies of this technical file are avail-
able from this address if required.
The document number and version number of this technical file are shown in
the footer.
1.3 Completeness
This technical file is incomplete without the supporting documentation.
1.5 Safekeeping
This technical file and all supporting documents must be kept ready at hand
and accessible for future use at all times.
Important information.
Single-step instructions
Instructions which consist of only a single process step are structured as fol-
lows:
Aim of action
ü Requirements (optional).
► Step 1 of 1.
ð Result of step (optional).
ð Result of action (optional).
Multi-step instructions
Aim of action
ü Requirements (optional).
1. Step 1.
ð Result of step (optional).
2. Step 2.
ð Result of step (optional).
ð Result of action (optional).
2 Safety
3 Product description
This chapter contains an overview of the design and function of the product.
The monitoring system collects the captured measured values and transfers
them to your monitoring computer. This gives you an overview of the current
status of your transformer at all times and also allows you to follow changes
in measured values.
You can use the configuration software also supplied to flexibly adapt the
monitoring system to your requirements. The communication interfaces pro-
vided allow you to integrate the TRAFOGUARD® monitoring system in your
control system.
Remote mode (REMOTE) In remote mode, you can perform commands using an external control level.
In this case, manual operation of the , , and keys is disa-
bled.
3.6 Hardware
The individual assemblies are fitted in a standardized 19-inch plug-in hous-
ing. The front panels of the assemblies are secured to the plug-in housing at
the top and bottom. An IEC 60603-2 plug connector provides the electrical
connection.
The assemblies are connected to one another via a data bus and direct cur-
rent (DC) supply. This allows for an upgrade with additional plug-in modules
and extension cards at a later date.
Main screen
3.6.5 Assemblies
Depending on configuration, the device may have various assemblies which
perform the functions required. Depending on configuration, the device may
be equipped with the following assemblies:
Card Default/option Max. number
SU Standard 1
CPU Standard 1
IO Standard 1
MI Standard 1
SID Standard 1
UC Option 6
MI1 Option 1
MI3G Option 1
TEM Option 5
AD8 Option 5
AC Option 1
AN Option 1
MC1 Option 1
CIC Option 2
External Option 1
switch
Table 4: Assemblies
The functions of the assemblies are described in the following sections. You
can find more information about the assemblies in the Technical data sec-
tion.
The wide range power supply (SU card) supplies the device with power. De-
pending on configuration, the device is equipped with one of the following
variants:
▪ SUH-P: Rated input voltage 100...240 V AC or 88...353 V DC (input volt-
age range 88...264 V AC, 88...353 V DC)
▪ SUM-P: Input voltage 36...72 V DC
▪ SUL-P: Input voltage 18...36 V DC
To measure voltage and current, the device can be equipped with the as-
sembly MI or MI3-G:
▪ MI: 1-phase measurement of voltage and current
▪ MI3-G: 3-phase measurement of voltage and current
Only connect the MI card to one current transformer, otherwise the current
measurement will not work.
To record and output digital signals, the device may be equipped with the
following assemblies:
▪ IO card
▪ UC card
IO card
UC card
To record and output analog signals, the device may be equipped with the
following assemblies:
▪ AD card
▪ AD8 card
▪ AN card
AD card
The analog input card has 1 input or with an extension card 2 inputs that can
record the following analog signals:
▪ 0...±10 V
▪ 0...±10 mA
▪ 0...±20 mA
▪ Resistance measurement (50...2 000 Ω)
Only use the R8/R12 and R42/R46 rotary potentiometers to calibrate the re-
sistance measurement.
AD8 card
The analog input card has 8 inputs that can record the analog signals
(4...20mA).
AN card
The CPU card is the device's central computing unit. All internal device func-
tions and the application functions, such as processing measured values,
are controlled and monitored by the CPU card.
The CPU card contains a flash memory (optional measured value memory)
as a non-volatile data storage in which the operating data such as measured
values or events are stored. An EEPROM for storing parameters and a real-
time clock (RTC) for recording time are included on the CPU card.
CIC card
As an option, the device can be equipped with up to 2 CIC cards. The CIC
cards are used to communicate using a control system protocol or
TAPCON®-trol software (CIC2).
SID card
The SID interface card is used to connect the device to the control station
system (SCADA). The IEC 61850 protocol transfers the data using Ethernet.
MC1 card
The optional MC1 card is used to convert the SID card's RJ45 interface into
a F-ST type fiber-optic cable connection. In this case the wavelength of the
fiber-optic cable connection is 1310 nm.
You can use the external switch (Hirschmann RSP20 or RSP25) to integrate
the communication interfaces available in the device (e.g. control system
and visualization) into your communication network via a connection. Device
communication can also be set up redundantly. The following redundancy
protocols are supported:
RSP20 RSP25
RSTP (Rapid Spanning Tree Protocol) x x
MRP (Media Redundancy Protocol) x x
PRP (Parallel Redundancy Protocol) - x
Table 5: Redundancy protocols
You can only use the PRP protocol with interfaces 1 and 2 of the switch
[► 165].
Note the installation manual provided. When supplied, the switch is set to
the RSTP protocol. If you want to use a different redundancy protocol, note
the manufacturer's instructions. For information about configuring the switch,
please visit www.hirschmann.com.
TAPCON®-trol:
▪ Configuring basic device parameters and setting the "Voltage regula-
tion", "Tap changer monitoring" and "Cooling system control" function
packages
▪ Backing up device data
TRAFOSET™:
▪ Configuring "Basic monitoring", "Advanced monitoring", "DGA" and
"Free inputs/outputs" function packages
▪ Setting limit values
▪ Routing the inputs and outputs
TRAFOVISOR™:
▪ Graphically displaying operating status and measured values
▪ Displaying events
▪ Assessing and exporting measured values
TRAFOSET™ The program interface of the TRAFOSET™ configuration software is split in-
to 4 areas:
4.1 Packaging
Inlays inside the box stabilize the goods, preventing impermissible changes
of position, and protect them from vibration.
4.1.2 Markings
The packaging bears a signature with instructions for safe transport and cor-
rect storage. The following symbols apply to the shipment of non-hazardous
goods. Adherence to these symbols is mandatory.
If a crate tips over, falls from a certain height (e.g. when slings tear) or expe-
riences an unbroken fall, damage must be expected regardless of the
weight.
Every delivered shipment must be checked for the following by the recipient
before acceptance (acknowledgment of receipt):
▪ Completeness based on the delivery slip
▪ External damage of any type.
The checks must take place after unloading when the crate or transport con-
tainer can be accessed from all sides.
Visible damage If external transport damage is detected on receipt of the shipment, proceed
as follows:
▪ Immediately record the transport damage found in the shipping docu-
ments and have this countersigned by the carrier.
▪ In the event of severe damage, total loss or high damage costs, immedi-
ately notify the sales department at Maschinenfabrik Reinhausen and
the relevant insurance company.
▪ After identifying damage, do not modify the condition of the shipment
further and retain the packaging material until an inspection decision
has been made by the transport company or the insurance company.
▪ Record the details of the damage immediately onsite together with the
carrier involved. This is essential for any claim for damages!
▪ If possible, photograph damage to packaging and packaged goods. This
also applies to signs of corrosion on the packaged goods due to mois-
ture inside the packaging (rain, snow, condensation).
▪ Be absolutely sure to also check the sealed packaging.
Hidden damage When damages are not determined until unpacking after receipt of the ship-
ment (hidden damage), proceed as follows:
▪ Make the party responsible for the damage liable as soon as possible by
telephone and in writing, and prepare a damage report.
▪ Observe the time periods applicable to such actions in the respective
country. Inquire about these in good time.
With hidden damage, it is very hard to make the transportation company (or
other responsible party) liable. Any insurance claims for such damages can
only be successful if relevant provisions are expressly included in the insur-
ance terms and conditions.
5 Mounting
This chapter describes how to correctly mount and connect the device. Note
the connection diagrams provided.
5.1 Preparation
The following tools are needed for mounting:
▪ Screwdriver for the fixing bolts (M6)
▪ Small screwdriver for connecting the signal lines and supply lines
Depending on installation site and mounting variant, you may need addition-
al tools and corresponding attachment material (screws, nuts, washers)
which are not included in the scope of supply.
Below you will find a description of how to mount the device in a 19" frame.
For control panel installation or wall mounting, note the technical files sup-
plied.
Supply the voltage via separators and ensure that current paths can be
short circuited. Fit the separator, clearly labeled, near the device's power
supply so that it is freely accessible. This will allow the device to be re-
placed with ease in the event of a defect.
Excessive line capacitance can prevent the relay contacts from breaking the
contact current. In control circuits operated with alternating current, take into
account the effect of the line capacitance of long control lines on the func-
tion of the relay contacts.
1 Cable duct for lines causing 3 Cable duct for lines suscepti-
interference ble to interference
2 Line causing interference (e.g. 4 Line susceptible to interfer-
power line) ence (e.g. signal line)
▪ Short-circuit and ground reserve lines.
▪ The device must never be connected using multi-pin collective cables.
▪ Signal lines must be routed in a shielded cable.
▪ The individual conductors (outgoing conductors/return conductors) in
the cable core must be twisted in pairs.
▪ The shield must be fully (360º) connected to the device or a nearby
ground rail.
Using "pigtails" may limit the effectiveness of the shielding. Connect close-
fitting shield to cover all areas.
The device is fully mounted and can be configured. The actions required for
this are described in the following chapter.
Once you have inserted the installation CD in your PC's disk drive and
launched the setup.exe file, you can pick from 2 types of setup:
▪ Standard
▪ Custom installation
You can select the setup type which meets your requirements. Both are de-
scribed below.
3. Select the installation option desired in the selection list for the
relevant feature.
4. If you have to change the installation path, click on the Change button.
5. Click on the Continue > button.
ð The configuration software is installed with all the selected features.
7 Commissioning
The device is delivered preconfigured in accordance with the technical clari-
fication. For completed commissioning, you must check the following items:
▪ Wiring the device
▪ Basic settings for the device
▪ Parameters, limit values and event configuration
The actions required for this are described in the following section.
If you are connecting the device to a PC for the first time, you are then
prompted to create a new device in the TAPCON®-trol. Observe the corre-
sponding information [► 51].
If you are establishing the connection to a new device, the Basic details
dialog appears automatically. You can also access this dialog by going to
Device > New.
You can access the above settings via the function tree. The description that
follows states the corresponding path in the function tree for each parame-
ter, starting with the parameter set.
Example Path: [Parameter set] > Configuration > General > Language
You can use this parameter to set the display language for the device. The
following languages are available:
▪ German
▪ English
This parameter sets how the measured voltage is displayed and used. You
can select the following options:
▪ V: The secondary voltage of the system's voltage transformer is dis-
played in V and is the reference value for the control parameters.
▪ kV: The primary voltage of the system's voltage transformer is displayed
in kV and is the reference value for the control parameters.
Path: [Parameter set] > Configuration > General > Display kV/V
Also refer to
2 Transformer data [► 55]
You can use this parameter to activate or deactivate automatic display dim-
ming. You can select the following options:
▪ On: The display is automatically dimmed if no key is pressed for 15 mi-
nutes. The display returns to full brightness by pressing any key.
▪ Off: Automatic display dimming is deactivated.
Path: [Parameter set] > Configuration > General > Display dark
You can use this parameter to set the measured value interval. This interval
defines when measured values are stored in the Flash memory.
Path: [Parameter set] > Configuration > Memory > Measured value interval
To adjust the TRAFOGUARD® time to the local time, you can set the time
shift to GMT with this parameter.
Example:
Region Time shift to GMT
Mumbai, India +5:30 h
Peking, China +8:00 h
Rio de Janeiro, Brazil -4:00 h
Table 9: Time shift to GMT (Greenwich Mean Time)
Path: [Parameter set] > Configuration > Memory > Time shift in hours to
GMT
If you have established a connection to a device, you can change the date
and time on this device.
To set the time and date, proceed as follows with the aid of the menu bar:
The transformation ratios and measuring set-up for the voltage and current
transformers used can be set with the following parameters. The device
uses this information to calculate the corresponding measured values on the
primary side of the current transformer (and therefore the transformer) from
the recorded measured values. These are then displayed.
The measured values displayed for the device are influenced by the settings
for the above parameters. Note the table below.
Parameter set Measured value display
Primary Secon- Primary Trans- Voltage (main Current Current (info
voltage dary current former screen) (main screen) screen)
voltage connec-
tion
- Yes - - Secondary volt- - Secondary cur-
age [V] rent [% of con-
nection]
Yes Yes - - Primary voltage - Secondary cur-
[kV] rent [% of con-
nection]
Yes Yes Yes - Primary voltage Primary cur- Secondary cur-
[kV] rent [A] rent [% of con-
nection]
Yes Yes - Yes Primary voltage - Secondary cur-
[kV] rent [A]
Yes Yes Yes Yes Primary voltage Primary cur- Secondary cur-
[kV] rent [A] rent [A]
Table 10: Influence of transformer data on measured value display
This parameter can be used to set the primary transformer voltage in kV.
When you are setting the primary transformer voltage, the device shows the
primary voltage rather than the secondary voltage in the main screen and
you can also set the control parameters in kV.
Path: [Parameter set] > Configuration > Transformer data > Primary voltage
Path: [Parameter set] > Configuration > Transformer data > Secondary volt-
age
Path: [Parameter set] > Configuration > Transformer data > Primary trans-
former current
This parameter can be used to set the current transformer connection. This
setting is needed for the device to display the correct secondary current in
the info screen.
If you select the "Unknown" option, the percentage of current (with reference
to the current transformer connection used) is displayed in the info screen.
Path: [Parameter set] > Configuration > Transformer data > Current trans-
former connection
You can use this parameter to set the phase difference of the current trans-
former and voltage transformer. You can set the common transformer cir-
cuits as follows:
Setting Measurement meth- Phase difference
od
0 1PH 1 phase 0°
0 3PHN 3 phase 0°
0 3PH 3 phase 0°
90 3PH 3 phase 90°
30 3PH 3 phase 30°
-30 3PH 3 phase -30°
Table 11: Set values for transformer circuit
Note the following sample circuits to select the correct transformer circuit.
Circuit C:
Circuit D
Circuit E
Circuit F
Circuit G
Circuit H
The following parameters are available for configuring the serial interface
COM1:
▪ Device ID
▪ Baud rate
Device ID You can use the device ID parameter to assign a 4-digit ID to the device.
This ID is used to uniquely identify the device in the TAPCON®-trol software.
Path: [Parameter set] > Configuration > General > Device ID.
Baud rate You can use the baud rate parameter to set the COM1 interface's baud rate.
You can select the following options:
▪ 9.6 kilobaud
▪ 19.2 kilobaud
▪ 38.4 kilobaud
▪ 57.6 kilobaud
Path: [Parameter set] > Configuration > General > Baud rate.
The RJ45 Ethernet interface on the SID card is used to link with the
TRAFOVISOR™ visualization software and to link with the IEC 61850 con-
trol system (optional). Depending on device configuration, you have to set
the following parameters:
TRAFOVISOR™ IEC 61850
Network mask Yes Yes
Network address Yes Yes
Time server address - Yes
Gateway - Yes
IED name - Yes
Table 12: Ethernet interface parameters
Network mask You can use this parameter to set the network mask.
Path: [Parameter set] > Configuration > Communication SID > Network
mask.
Network address You can use this parameter to assign a network address to the device.
Path: [Parameter set] > Configuration > Communication SID > Network ad-
dress.
Time server address You can use this parameter to enter the IP address of the SNTP time server.
If you are using a time server, the device uses the time of the time server as
the system time.
Path: [Parameter set] > Configuration > Communication SID > Time server
address.
Gateway You can use this parameter to set the gateway's IP address.
Path: [Parameter set] > Configuration > Communication SID > Gateway.
IED name You can use this parameter to assign the device an IED name in order for it
to be identified in the IEC 61850 network.
The IED name must start with a letter and may contain no more than 11
characters.
Path: [Parameter set] > Configuration > Communication SID > IED name.
The interfaces of the CIC1 card are used to connect to the control system
via DNP3 (optional). Depending on device configuration, you have to set the
following parameters:
Communication port You can use this parameter to select the communication port used for the
CIC card. You can select the following options:
▪ RS232
▪ RS485
▪ Ethernet
▪ Optical fiber
You can only select one communication port. All remaining ports remain dis-
abled. It is not possible to use several communication ports at the same
time.
Path: [Parameter set] > Configuration > Communication CIC1 > Communica-
tion port.
Baud rate You can use this parameter to set the desired baud rate for the communica-
tion interface. You can select the following options:
▪ 9.6 kilobaud
▪ 19.2 kilobaud
▪ 38.4 kilobaud
▪ 57.6 kilobaud
The baud rate of 57.6 kilobaud is only active for communication interfaces
RS232, RS485 and optical fiber.
A baud rate of 57.6 kilobaud cannot be used for Ethernet.
Path: [Parameter set] > Configuration > Communication CIC1 > Baud rate.
Network address You can use this parameter to assign a network address (IPv4) to the de-
vice. If you want to connect the device by means of Ethernet, you need to
set a valid network address.
Path: [Parameter set] > Configuration > Communication CIC1 > Network ad-
dress.
TCP port You can use this parameter to assign a TCP port to the device. If you want
to connect the device by means of Ethernet, you need to set a valid TCP
port.
Path: [Parameter set] > Configuration > Communication CIC1 > TCP port.
Optical fiber transmission You can use this parameter to set the device's transmission behavior, when
behavior you connect the device via optical fiber (OF). This determines whether or not
the transmit LED lights up when the signal (logical 1) is active.
Setting Logical 1 Logical 0
ON Light on Light off
OFF Light off Light on
Table 13: Transmission behavior for various parameter settings
Path: [Parameter set] > Configuration > Communication CIC1 > Optical fiber
transmission behavior.
Local SCADA address You can use this parameter to assign a SCADA address to the device. You
have to define this parameter if the device is to communicate via the control
system protocol.
Path: [Parameter set] > Configuration > Communication CIC1 > Local SCA-
DA address.
SCADA master address You can use this parameter to set the SCADA address for the master sta-
tion. When the device is restarted, the device data is sent to this master sta-
tion without prompting.
Path: [Parameter set] > Configuration > Communication CIC1 > SCADA
master address.
Unsolicited messages When using the control system protocol DNP3, you can release the unsolicit-
ed data transmission through the device with this parameter. Data is trans-
ferred when a corresponding event occurs.
Path: [Parameter set] > Configuration > Communication CIC1 > Unsolicited
messages.
Repeat unsolicited This parameter is used to set the maximum number of attempts to transmit
messages unsolicited messages.
If the device receives no release for data transmission through the Master
(for example, in case of transmission errors), then the data transmission is
repeated in accordance with the set maximum number of send attempts.
Path: [Parameter set] > Configuration > Communication CIC1 > Repeat un-
solicited messages.
Application timeout You can use this parameter to define the permissible time which the device
confirmation response waits for the following feedback from the master device:
▪ Application confirmation response
▪ Confirmation of unsolicited message
Path: [Parameter set] > Configuration > Communication CIC1 > Application
timeout confirmation response.
Send delay time RS485 You can use this parameter to set a send delay for the interface, for exam-
ple, to compensate for the reaction time of an external RS485/RS232 trans-
former when changing between transmitting and receiving operation.
Path: [Parameter set] > Configuration > Communication CIC1 > Send delay
time RS485.
Network address You can use this parameter to assign a network address (IPv4) to the de-
vice. If you want to connect the device by means of Ethernet, you need to
set a valid network address.
Path: [Parameter set] > Configuration > Communication CIC2 > Network ad-
dress.
TCP port You can use this parameter to assign a TCP port to the device. If you want
to connect the device by means of Ethernet, you need to set a valid TCP
port.
Path: [Parameter set] > Configuration > Communication CIC2 > TCP port.
Note the description in the relevant sections for checking the parameters,
limit values and event configuration:
▪ Setting analog signals [► 78]
▪ Setting binary signals [► 79]
▪ Routing input signals [► 81]
▪ Managing events [► 82]
▪ Routing output signals and LEDs [► 85]
The signals described below are available to you and can be set using the
TRAFOSET™ configuration software:
Function Description Limit Signal type Signal source
values
Lower transform- Monitoring of lower oil tem- 4 Analog: 4… Temperature sensor
er oil temp. perature of the transformer 20 mA, PWM or
Pt100
Winding temp. Monitoring of winding tem- 4 Analog: 4… Temperature sensor
1…3 perature 1...3 20 mA, PWM or
Pt100
8.1.3 DGA
You can use the "DGA " function package to measure the gas and moisture
content of the oil. You can record up to 9 DGA signals with this function
package. The signals described below are available to you and can be set
using the TRAFOSET™ configuration software:
*) Applies likewise to all other gas types (CH4, C2H6, C2H4, C2H2, CO,
CO2, O2, N2)
You can select the following cards and the corresponding inputs:
▪ AD8 card: 8 analog inputs (4...20 mA)
▪ TEM card: 2 analog inputs (PT100) and 9 digital inputs (PWM)
▪ UC card: 10 binary inputs and 10 binary outputs
The monitoring system checks the calculated values with regard to the fol-
lowing limit values:
▪ Absolute value of the wear
▪ Difference in wear between main switching contact and transition con-
tact
▪ Difference in wear between two transition contacts
If these limit values are exceeded, the monitoring system triggers appropri-
ate events.
Function The monitoring system monitors the following temperatures to control the
cooling system:
▪ Topoil temperature: Oil temperature at top of transformer (measured
value)
▪ Hotspot temperature (winding temperature): Highest temperature on the
transformer winding (calculated value)
If the temperatures exceed the threshold values set, the respective cooling
stages are activated.
For the cooling system control to function correctly, you have to set the fol-
lowing parameters.
Alternating operation of The monitoring system allows equivalent cooling stages to be operated in
cooling stages turn. This spreads the load over several cooling stages and therefore ex-
tends the service life.
Automatic cooling stage You can use the "Automatic cooling stage activation" function to set the cool-
activation ing stages to be automatically activated after a certain time. They are then
activated regardless of the temperatures measured.
Load-dependent cooling You can use the "Load-dependent cooling stage activation" function to set
stage activation the cooling stages to be activated using the transformer's load current. They
are then activated regardless of the temperatures measured.
Signals and measured The signals described below are available to you in the cooling system con-
values trol function package and can be set using the TRAFOSET™ configuration
software:
Function Description Limit Signal type Signal source
val-
ues
Oil temperature, Monitoring of lower oil tem- 4 Analog: 4… Temperature sensor
top perature of the transformer 20 mA, PWM or
Pt100
Hotspot calculated Monitoring of winding tem- 4 Calculated value
perature 1...3
Inlet temperature Monitoring of cooler's inlet 4 Analog: 4… Temperature sensor
temperature 20 mA, PWM or
Pt100
Failsafe mode In the event of an error, TRAFOGUARD® activates all cooling stages to pre-
vent the transformer from overheating. Failsafe mode is activated if the fol-
lowing errors arise:
▪ Failure of a temperature sensor
▪ Parameter error
Test functions TRAFOGUARD™ has a test function you can use to activate individual cool-
ing stages. You can use a further test function to simulate various tempera-
ture values.
If the control deviation is greater than the specified bandwidth (B%), the volt-
age regulator emits a switching pulse after a defined delay time T1. The
switching pulse triggers an on-load tap-changer tap change which corrects
the transformer's output voltage.
The voltage regulator parameters can be optimally adjusted to the line volt-
age behavior to achieve a balanced control response with a small number of
tap-change operations.
NORMset NORMset mode enables you to quickly start up voltage regulation. You must
set the following parameters for this:
▪ Desired value 1
▪ Primary voltage
▪ Secondary voltage
Voltage regulation Full voltage regulation in which you can define all control parameters your-
self.
Limit values The device has a limit value monitoring function. If a limit value is exceeded,
automatic voltage regulation is blocked.
Line drop compensation If necessary, you can use the line drop compensation function to compen-
sate for the load-dependent voltage drop between the transformer and con-
sumer. The device supports the following methods for this:
▪ Line drop compensation
▪ Z compensation
You can use the TRAFOSET™ to set and monitor the following signals:
Function Description Limit Signal type Signal source
values
Motor current Motor current 4 Analog Motor-drive unit
0...5 A
Motor Current In- Motor Current Index in ac- 2 Calculated value
dex cordance with
IEEE PC57.143
Motor current Calculated average value 2 Calculated value
average for motor current during a
tap change
Table 18: Motor Current Index
8.2 Configuration
2. Tick the checkboxes for the signals desired in the Selection column or
remove the tick from those not wanted.
3. Select the desired signal type in the Signal type column.
The number of free inputs depends on the number of input signals selected.
If your selection means that there are inputs available on the cards required,
you can use these for any purpose.
You can assign a unique signal designation to each free input. You must al-
so define how the 4...20 mA signal is to be interpreted by the
TRAFOGUARD®. To do this you need to state the factor, unit and decimal
places.
Example: If you measure a voltage of between 5.0 and 30.0kV and want to
transfer this to the TRAFOGUARD® as a 4...20 mA signal, you need to se-
lect k (for kilo) in the factor column and V (for volt) in the unit column. You
need to select 1 in the decimal places column.
The set values impact on how the limit values are depicted in
TRAFOVISOR™ (Free I/Os menu).
2. Tick the checkboxes for the signals desired in the Selection column.
3. Enter the name of the signal in the Signal name column.
4. Select the desired parameters in the Factor, Unit and Decimal places
columns.
Defining limit values and Depending on the measured value, you can define up to 2 upper limit values
switch-off hysteresis and 2 lower limit values. You can then define what action the monitoring sys-
tem is to trigger when a limit value is exceeded.
You can also define a switch-off hysteresis. If the value falls below the limit
value again, including the switch-off hysteresis, the triggered action is deacti-
vated. The switch-off hysteresis prevents actions from being activated and
deactivated when the measured value fluctuates around the limit value.
The example below shows changes in the measured value and what actions
are triggered by the monitoring system when a limit value is exceeded.
2. Enter the desired limit values in the Upper limit 2, Upper limit 1, Lower
limit 1 and Lower limit 2 columns.
3. Enter the desired switch-off hysteresis in the Hysteresis column.
Setting 4...20 mA values If you are using a 4...20 mA type analog signal, you need to set the real
measured value to which 4 mA relates and the real measured value to which
20 mA relates.
The number of free inputs depends on the number of input signals selected.
If your selection means that there are inputs free on the cards required, you
can use these for any purpose.
2. Tick the checkboxes for the signals desired in the Selection column.
3. Enter the name of the signal in the Signal name column.
The TRAFOSET™ configuration software tells you when the current configu-
ration is contradictory. An appropriate icon is displayed in the signal name
column to indicate this:
(red): The configuration is not OK, one connection terminal has been as-
signed several times.
Managing events You can change any event text as you see fit. You can also activate or deac-
tivate any event and define the priority of events.
You can use the Reset highlighted line to default text button to restore the
factory settings.
Changing basic texts The basic texts comprise text and a variable. The following variables are
used:
Variable Definition
%s Signal name
%d Number of the cooling stage
Table 20: Variables available
Example: The basic text Measured value %s upper limit 2 exceeded be-
comes the event text Measured value ambient temperature upper limit 2 ex-
ceeded. The basic short text G>> %s becomes G>> ambient temperature.
If you change the basic text, this change only affects the default texts. Event
texts that have already been adapted are not changed.
2. Make the changes desired in the Text and Short text columns.
You can use the Reset highlighted line to default values button to restore
the factory settings.
Removing event To cancel the assignment of an event to an output or LED, proceed as fol-
lows:
► Select the event to be removed in the Event column.
ð Click on the Remove event button.
You can only assign entries from the data model to the data points with a
gray background. All other data points are permanently defined.
2. Select the desired entry from the data model in the Description column.
3. If necessary, click on the Export to XLS file button to export the data
point table.
The 0...10 V signal type is only available for the AN1-X1:05 and AN1-X1:07
outputs.
You can use these parameters to set the limit for a maintenance notification.
If this limit value is reached, the monitoring system triggers an event mes-
sage.
You can use these parameters to define 2 separate intervals after which the
monitoring system issues a message. You can define the following interval
types:
▪ Tap-change operation interval
▪ Time interval
This parameter sets the message limit for the number of operator tap-
change operations. If this limit value is achieved, the corresponding progress
bar flashes in the display.
This parameter defines a time interval. Together with the "operator date in-
terval" parameter, the time interval is used to calculate the status bar.
This parameter defines the final date for the operator interval. An event mes-
sage is triggered when the limit value is reached.
The date can be set from 01.01.2001 to 29.12.2099 and has the following
format:
DD:MM:YY
The limit for the operator time interval message is set using this parameter. If
this limit value is achieved, the corresponding progress bar flashes in the
display.
Also refer to
Determining contact wear The thickness of the wear to be entered is the sum of the wear of the mova-
ble and the fixed contact part.
Setting contact wear You have to enter the previously determined contact wear for each switching
and transition contact.
▪ Main switching contact A (SKA)
▪ Main switching contact B (SKB)
▪ Transition contact A (WKA or WK1A)
▪ Transition contact B (WKB or WK1B)
▪ Transition contact 2A (WK2A)*
▪ Transition contact 2B (WK2B)*
*) The transition contacts WK2A and WK2B are not available with every on-
load tap-changer. If these contacts are not available with your on-load tap-
changer, you have to set the value 0.000 mm.
The monitoring system ignores contact wear entries that deviate greatly
from the calculated value (zentry > 10 ∙ zcalculated) in order to avoid entry errors.
Nevertheless, if you would like to enter a value that deviates greatly, you
have to set the contact wear to 0.000 mm beforehand.
You can set the tap changer parameters using these parameters.
▪ Passes through neutral position
▪ On-load tap-changer serial number*
▪ Factor "s" of current splitting*
▪ On-load tap-changer type*
▪ Average step voltage*
▪ Parallel sectors*
▪ R1*
▪ R2*
*) These parameters are pre-set and can only be changed after consulting
with Maschinenfabrik Reinhausen.
You can use this parameter to set the number of passes through the neutral
position.
You can use this parameter to activate "Test operations" mode. When in
"Test operations" mode, contact wear and soot are not calculated during the
tap-changes then undertaken.
You can set the parameters listed below under the General cooling menu
item.
You can use this parameter to define the maximum difference in operating
hours for alternating cooling stages [► 71]. If this value is exceeded, the
monitoring system automatically switches to the cooling stage with the short-
er operating period.
Aging rate
You can use this parameter to set the current aging rate for your transform-
er.
Calculating aging
You can use this parameter to define the standard in line with which aging is
to be calculated. You can select between IEC 60076-7 and AN-
SI IEEE C57.91.
Hotspot factor
You can use this parameter to set the hotspot factor for calculating the hot-
spot temperature in accordance with IEC 60076-7 (transformer-specific).
This is factor H which has no dimensions.
Hotspot factor H = 1.1 can be set with sufficient accuracy for distribution
transformers with a short-circuit impedance ≤ 8 %. For mid-size and large
transformers, a hotspot factor of H = 1.3 may result in more accurate calcu-
lations.
You can use this parameter to set the cooling system's current runtime.
You can use this parameter to define which hotspot type activates the cool-
ing stage. You can select the following options:
▪ Forecast hotspot: The cooling stage is activated by the forecast hotspot
temperature before the real hotspot temperature is reached. This re-
duces aging.
▪ Real hotspot: The cooling stage is activated by the real hotspot (meas-
ured or calculated).
You can use this parameter to set how the real hotspot is recorded. You can
select the following options:
▪ Measured: The hotspot temperature is measured by up to 3 sensors. If
the hotspot is recorded by several sensors, the monitoring system uses
the maximum temperature.
▪ Calculated: The hotspot temperature is calculated using the transformer
load.
Aging calculation
You can use this parameter to activate or deactivate the aging calculation.
When you deactivate the aging calculation, the following events are no lon-
ger monitored or reported:
▪ Transformer aging rate measured value not available
▪ Transformer aging rate measured value limit exceeded
You can use this parameter to undertake an offset correction for the meas-
ured oil temperature. The value set here is added to the measured oil tem-
perature if the measured oil temperature is greater than 30 °C.
Also refer to
2 Cooling system control [► 71]
You use the following parameters in the Contact S1...S6 menu item to define
when the monitoring system is to activate or deactivate the individual cooling
stages. Both the oil temperature (topoil) and winding temperature (hotspot)
can be used as the threshold value.
Alternating
You can use this parameter to activate or deactivate alternating mode [► 71]
for a cooling stage.
Hysteresis
You can use this parameter to set the switch-off hysteresis. The switch-off
limit value is the threshold value less the switch-off hysteresis. If the value
falls below the limit value, the monitoring system deactivates the respective
cooling stage after an optional delay time.
Switching criterion
You can use this parameter to define the criterion for switching on and off.
The switching criterion regulates which threshold values are used to switch
the cooling stage on and off.
Setting Threshold value for Threshold value for
switching on switching off
Oil/Oil Oil temperature Oil temperature
Hotspot/Hotspot Winding temperature Winding temperature
Hotspot/Oil Winding temperature Oil temperature
Table 22: Setting options for switching criterion
Delay
You can use this parameter to define the switch-off delay. If the value falls
below the switch-off limit, the cooling stage is deactivated after the switch-off
delay.
Winding temperature
You can use this parameter to define the threshold value for the winding
temperature (hotspot). If the threshold value is exceeded, the monitoring
system activates the respective cooling stage.
Oil temperature
You can use this parameter to define the threshold value for oil temperature
(topoil). If the threshold value is exceeded, the monitoring system activates
the respective cooling stage.
Also refer to
2 Cooling system control [► 71]
You use the following parameters in the Cooling stage 0...6 menu item to set
the parameters for the individual cooling stages.
Gradient
You can use this parameter to set the temperature gradients of the average
winding temperature to the average oil temperature at rated current for cal-
culating hotspot temperature in accordance with IEC 60076-7. This is factor
gr.
Winding exponent
You can use this parameter to set the winding exponents for calculating the
hotspot temperature in accordance with IEC 60076-7. This is parameter y.
Time constant
You can use this parameter to set the time constants for calculating the hot-
spot temperature in accordance with IEC 60076-7. This is parameter τ.
Rated value
You can use this parameter to enter the rated value of the cooling stage.
This parameter is needed to calculate the hotspot temperature.
You can use this parameter to define the type of oil circulation.
The parameter must be configured separately for each cooling stage. The
following options are available:
Option Description
ON Oil Natural - natural oil convection
OF Oil Forced (radial pump) - forced oil convection
Option Description
OP Oil Forced (impeller pump) - forced oil convection
OD Oil Directed - forced flow which is directed at the winding.
Table 23: Possible selections for type of oil circulation
Cooling medium
The parameter must be configured separately for each cooling stage. The
following options are available:
Option Description
AN Air Natural - natural convection (air)
AF Air Forced - forced convection (fan)
WF Water Forced - forced convection (water)
Table 24: Possible selections for cooling medium
You can individually activate every cooling stage with this function. This
checks whether the cooling stages are functioning properly.
1. Press > Info > Measured values > until the display
appears.
ð Cooling stages test
Simulating temperatures
You can use this function to simulate various temperatures. This allows you
to check whether signals, messages and device contact are working correct-
ly.
1. Press > Info > Measured values > until the display
appears.
ð Temperature
3. Press and hold down ... to simulate the temperature. If desired, with
the key pressed, you can adjust the temperature with or .
You can use the "Automatic cooling stage activation" function to set the cool-
ing stages to be automatically activated after a certain time. They are then
activated regardless of the temperatures measured.
You can use this function to regularly activate rarely used cooling stages and
thereby avoid damage to the cooling stages from long down periods.
If you operate more than 1 cooling stage, the individual cooling stages are
activated one after another at intervals of 2 minutes to avoid peaks in volt-
age.
Switch-on delay
You can use this parameter to set the time after which the cooling stages are
to be automatically activated for the first time. The time starts as soon as you
activate the automatic cooling stage activation (Auto. cooling On/Off param-
eter)
You can use this parameter to set how long the cooling stages are to remain
activated. Once the cooling stages runtime has elapsed, the cooling stages
are deactivated again.
Interval time
You can use this parameter to set the time after which the cooling stages are
to be activated again.
You can use these parameters to activate or deactivate the automatic cool-
ing stage activation.
You can use the "Load-dependent cooling stage activation" function to acti-
vate the cooling stages using the load current measured. They are then acti-
vated regardless of the temperatures measured.
Path: [Parameter set] > Configuration > Load-dep. cooling st. active
Load-dep.CS activ.threshold
You can use this parameter to set the switch-on threshold for the load-de-
pendent cooling stage activation. If the set value is exceeded, all cooling
stages are activated.
You can use this parameter to set how long the cooling stages are to contin-
ue running once the value again falls below the switch-on threshold for the
load-dependent cooling stage activation.
8.2.14.1 NORMset
Normset activation
Primary voltage
With this parameter, you can set the voltage transformer's primary voltage.
Secondary voltage
With this parameter, you can set the voltage transformer's secondary volt-
age.
Desired value 1
With this parameter, you can set the desired value for automatic voltage reg-
ulation. You can enter the desired value in V or in kV. If you enter the de-
sired value in V, the value relates to the voltage transformer's secondary
voltage. If you set the desired value in kV, the value relates to the voltage
transformer's primary voltage.
Settings in kV are only possible if you have previously entered the parame-
ters for primary and secondary voltage.
This submenu contains all the parameters required for the control function.
▪ Desired value 1, 2 and 3
▪ Bandwidth
▪ Delay time T1
▪ Control response T1
▪ Delay time T2
Desired value 1, 2, 3
With these parameters, you can set the desired value for automatic voltage
regulation. You can enter the desired value in V or in kV. If you enter the de-
sired value in V, the value relates to the voltage transformer's secondary
voltage. If you set the desired value in kV, the value relates to the voltage
transformer's primary voltage.
Settings in kV are only possible if you have previously entered the parame-
ters for primary and secondary voltage.
You can specify 3 desired values. Desired value 1 is the default desired val-
ue. You can activate desired value 2 or 3 by creating a continuous signal at
the IO-X1:17 or IO-X1:16 binary inputs. If there is a signal at both inputs, de-
sired value 2 is active.
Bandwidth
You can use this parameter to set the maximum permissible deviation in
measured voltage Vactual. The deviation relates to the activated desired value.
Function behavior If the measured voltage Vactual is inside the set bandwidth , then no con-
trol commands are issued to the on-load tap-changer. Control commands
will also not be issued to the on-load tap-changer if the measured voltage re-
turns to the tolerance bandwidth within the set delay time T1 . How-
ever, if the measured voltage deviates from the set bandwidth for a long pe-
riod , a tap-change command occurs after the set delay time T1 . The
on-load tap-changer carries out a tap-change in a positive or negative direc-
tion to return to the tolerance bandwidth.
Determining bandwidth In order to set the correct value, the transformer's step voltage and nominal
voltage must be known.
You have to set the bandwidth in such a way that the output voltage of the
transformer (Vactual) returns to within the specified tolerance bandwidth after
the tap change. If too small a bandwidth is defined, the output voltage ex-
ceeds the bandwidth selected and the device must immediately issue a tap-
change command in the opposite direction. If a very large bandwidth is se-
lected, this results in a major control deviation.
The following transformer parameters are used for determining the recom-
mended bandwidth:
Nominal voltage Vnom = 11000 V
Step voltage in tap position 4 VStep4 = 11275 V
Step voltage in tap position 5 VStep5 = 11000 V
Delay time T1
Delay time T1 delays the issuing of a tap-change command for a defined pe-
riod. This function prevents unnecessary tap-change operations if the toler-
ance bandwidth is exited.
If the current measured voltage exits the bandwidth, delay time T1 starts.
This is shown in the display by the time bar filling and the remaining time be-
ing indicated. If the control deviation is still present after the delay time, a
tap-change command is issued.
If during the delay time the measured voltage returns to within the tolerance
bandwidth, the delay time still running is counted down in seconds starting
from the time already expired. The absolute time display disappears from the
display. The time bar is shown hatched and shrinks steadily. If the measured
voltage again exceeds the set bandwidth, then the time delay is restarted
from the remaining time.
Control response T1
Linear control response T1 With linear control response, the device responds with a constant delay time
regardless of the control deviation.
Integral control response With integral control response, the device responds with a variable delay
T1 time depending on the control deviation. The greater the control deviation
(ΔV) in relation to the set bandwidth (B), the shorter the delay time. The de-
lay time can therefore be reduced down to 1 second. This means that the
device responds faster to large voltage changes in the grid. Regulation accu-
racy improves as a result but the frequency of tap-changes increases too.
Delay time T2
With this parameter, you can set delay time T2. Delay time T2 is used to
compensate for large control deviations faster.
The delay time T2 only takes effect if more than one tap-change operation is
required for returning the voltage to within the set bandwidth. The first output
pulse occurs after the set delay time T1. After the set delay time T2 has
elapsed, additional pulses occur in order to correct the existing control devia-
tion.
The delay time T2 must be greater than the pulse duration and the maxi-
mum operating time of the motor-drive unit.
T2 activation
With this parameter, you can activate the delay time T2 function.
This sub-menu contains the parameters for monitoring the limit values.
Function monitoring
If the bandwidth is exceeded for more than 15 minutes, the device issues the
Function monitoring event message and the associated relay is activated.
You can use this parameter to activate or deactivate the function monitoring.
V< blocking
You can use this parameter to set how the device behaves if the voltage falls
below the undervoltage limit. You can select the following options:
Setting Function
On Automatic regulation is blocked.
Off Automatic regulation remains active.
Table 26: Behavior
V< Delay
You can use this parameter to set the delay time after which the Undervolt-
age relay is to activate. This can be used to prevent messages from being
issued when the value briefly falls below the limit value. The undervoltage
LED always lights up immediately regardless.
With this parameter, you can set whether the undervoltage message is to be
suppressed at a measured value of less than 30 V. This setting is used to
ensure that no event message appears when the transformer is switched off.
You can select the following options:
Setting Function
On The Undervoltage message is also displayed
when the measured value is less than 30 V.
Off The Undervoltage message is no longer dis-
played when the measured value is less than
30 V.
Table 27: Behavior
8.2.14.4 Compensation
You can use the "Compensation" function to compensate for the load-de-
pendent voltage drop between the transformer and consumer. The device
provides 2 methods of compensation for this purpose:
▪ R&X compensation (line drop compensation)
▪ Z compensation
You can use R&X compensation and Z compensation at the same time. If
you do not want to use one method, you have to set the associated parame-
ters to 0.
If you are using the IEC 61850 control system protocol, you can only acti-
vate one of the two compensation methods at any one time. A control sys-
tem command is available for this.
Also refer to
2 Setting transformer circuit [► 57]
R&X compensation (LDC) requires exact cable data. Line voltage drops can
be compensated very accurately using LDC.
To set R&X compensation correctly, you need to calculate the ohmic and in-
ductive voltage drop in V with reference to the secondary side of the voltage
transformer. You also need to correctly set the transformer circuit [► 57]
used.
You can calculate the ohmic and inductive voltage drop using the following
formulas. This voltage drop calculation relates to the relativized voltage on
the secondary side of the voltage transformer.
You can set the parameters for line drop compensation in the Compensation
sub-menu.
Ohmic voltage drop Ur You can use this parameter to set the ohmic voltage drop (ohmic resistance
load).
If you do not want to use line drop compensation, you have to set the value
0.0 V.
Inductive voltage drop Ux You can use this parameter to set the inductive voltage drop (inductive re-
sistance load). The compensation effect can be rotated by 180° in the dis-
play using a plus or minus sign.
If you do not want to use line drop compensation, you have to set the value
0.0 V.
Also refer to
2 Setting transformer circuit [► 57]
8.2.14.4.2 Z compensation
To keep the voltage constant for the consumer, you can use Z compensation
to activate a current-dependent increase in voltage. You can also define a
limit value to avoid excess voltage on the transformer.
The following sections describe how you can set the parameters you need
for Z compensation.
You can set the parameters for line drop compensation in the Compensation
sub-menu.
If you do not want to use Z compensation, you have to set the value 0.0 %.
Z compensation limit value You can use this parameter to define the maximum permissible voltage in-
crease to avoid excess voltage on the transformer.
If you do not want to use a limit value, you have to set the value 0.0 %.
8.2.14.5 General
You can use this parameter to set the duration of the switching pulse for the
motor-drive unit.
If you set the switching pulse time to 0 s, the motor-drive unit is activated
with a continuous signal. The signal then remains active for as long as the
or keys are pressed.
Switching pulse in normal If you set the switching pulse time to 1.5 seconds for example, after the set
mode delay time T1 or delay time T2 there will be a switching pulse of 1.5 sec-
onds .
If the motor-drive unit does not start with the factory setting (1.5 seconds),
you need to extend the raise switching pulse time / lower switching pulse
time.
Switching pulse for rapid If you set the raise switching pulse time or lower switching pulse time to
return control 1.5 seconds, for example , the next earliest switching pulse occurs in rapid
return control mode 1.5 seconds after the previous switching pulse
ended.
1 Start of first raise switching 3 Earliest time for the next raise
pulse/lower switching pulse switching pulse/lower switch-
ing pulse (for example
1.5 seconds)
2 Set switching pulse time (for
example 1.5 seconds)
Motor runtime
You can use this motor runtime parameter to set the motor runtime. The mo-
tor-drive unit's runtime can also be monitored by the device. This function is
used to identify motor-drive unit malfunctions during the tap-change opera-
tion and to trigger any actions needed.
Behavior The motor-drive unit issues the Motor-drive unit running signal during the
tap-change operation. This signal is present until the tap-change operation is
complete. The device compares the duration of this signal with the set motor
runtime. If the set motor runtime is exceeded, the device triggers the follow-
ing actions:
1. Motor runtime monitoring message is issued
2. Continuous signal via output relay Motor-drive unit runtime exceeded
(optional)
3. Pulse signal via Trigger motor protective switch output relay (optional)
Parameterizing control To use runtime monitoring, you need to correctly wire the corresponding
input control input and parameterize to Motor running. The motor runtime must al-
so be set.
In theParallel operation menu item, you can set the parameters needed for
parallel transformer operation. Parallel transformer operation is used to in-
crease the throughput capacity or short-circuit capacity in one place.
Conditions for parallel Compliance with the following general conditions is required for operating
operation transformers in parallel:
▪ Identical rated voltages
▪ Transformer power ratio (< 3 : 1)
▪ Maximum deviation of short-circuit voltages (UK) for transformers con-
nected in parallel < 10%
▪ Same number of switching groups
▪ The same current-transformer connection has to be used for all devices
running in parallel
Parallel operation method The device supports parallel operation following the methods described be-
low:
▪ Parallel operation following the "Circulating reactive current minimiza-
tion" principle
▪ Parallel operation following the "Tap synchronization" (master/follower)
principle
You must select the same parallel operation method (circulating reactive
current minimization or tap synchronization) for all voltage regulators oper-
ating in parallel. Otherwise you cannot operate the devices in parallel.
The following sections describe how you can set the parameters. Ensure
that you have set the following parameters when activating parallel opera-
tion:
▪ CAN bus address
You can use this parameter to assign a CAN bus address to the device. So
that all devices can communicate using the CAN bus, each device requires a
unique identifier. Addresses can be set from 1 to 16. If the value is set to 0,
then no communication takes place.
You can use this parameter to select a parallel operation method. Two differ-
ent methods can be assigned to the device.
▪ Circulating reactive current minimization
▪ Tap synchronization (master/follower)
You must select the same parallel operation method for all voltage regula-
tors operating in parallel.
The following sections describe how you can set the parameters for a paral-
lel operation method.
When using the circulating reactive current parallel operation method, you
have to set the parameters for the circulating reactive current sensitivity
and circulating reactive current blocking.
As soon as you change the circulating reactive current sensitivity value, the
value for the result changes in the help text in the display.
You can use this parameter to set the limit value for the maximum permissi-
ble circulating reactive current. If, during parallel operation, the circulating re-
active current exceeds the set limit value, then the following event is activat-
ed:
▪ Problem with parallel operation
All devices operating in parallel are blocked. Depending on the set delay
time for the parallel operation error message, the signaling relay Problem
with parallel operation is activated.
With the tap synchronization method, you need to designate one voltage
regulator as the master and all others as followers. The master handles volt-
age regulation and transmits its latest tap positions to all followers via the
CAN bus. The followers compare the tap position received with their own tap
position. If the set permissible tap difference between the tap position re-
ceived and their own position is exceeded, the followers switch to the tap po-
sition received from the master. This ensures that the transformers operating
in parallel are always in the same tap position.
For the tap synchronization method, you can select the following options:
Option Description
Master The voltage regulator is designated as the master.
Follower The voltage regulator is designated as the follower.
Sync.auto Automatic assignment of master or follower.
If no master is detected, the voltage regulator with the
lowest CAN bus address is automatically designated
as the master. All other voltage regulators are desig-
nated as followers.
Table 28: Tap synchronization method
You can use this parameter to correct the follower's switching direction, with-
out re-configuring the system. Since in parallel operation using the Tap syn-
chronization master/follower method the tap positions of the transformers
which are running in parallel are compared, it is absolutely essential that
these transformers have the same tap position designation and that the
"Raise" or "Lower" signals produce the same voltage change in all trans-
formers.
Swapped switching If you have wired the device such that a RAISE operation results in lower
direction voltage, you can use this parameter to swap the switching direction. If the
switching direction is swapped, the "Lower" relay is activated during a volt-
age RAISE operation. The wiring no longer has to be corrected. But be sure
that the wiring between the device and motor-drive unit is correct.
Parameters Definition
Standard A raise signal results in the follower switching
up one step to increase the voltage.
A lower signal results in the follower switching
down one step to decrease the voltage.
Swapped A raise signal results in the follower switching
down one step to increase the voltage.
A lower signal results in the follower switching
up one step to decrease the voltage.
Table 29: Device behavior
Ensure that you only set this parameter for the follower. The tapping direc-
tion can only be swapped for a follower.
You can use this parameter to set the delay time for a parallel operation er-
ror message so that brief fault messages are not received if the motor-drive
units involved in the parallel operation have different runtimes. Once the set
delay time has elapsed, the event is issued at the output relay. Automatic
regulation is blocked and the on-load tap-changers can only be adjusted in
manual mode.
To deactivate parallel operation, you have to set the option Off for the paral-
lel operation method parameter.
Defining password
Entering password
8.3 TAPCON®-trol
Further functions of the TAPCON®-trol software are described in the follow-
ing section.
You can use the Insert group function to create a new group in the visuali-
zation software.
The abbreviation appears in the function tree and status bar and is compul-
sory. The designation is only displayed in the status bar and is optional.
You can change the abbreviation and designation at any time (renaming
group).
You can use the Open group function to import the archived groups, includ-
ing the associated devices and device data.
Before you can import the archived data, you have to extract the zip file
(.zip).
If groups or devices with the same name or ID are imported, the visualiza-
tion software automatically adapts the name and ID.
You can change the designation and abbreviation of a group at any time. To
change the group's designation, proceed as follows:
1. Select the desired group in the function tree.
2. Go to Rename group in the context menu.
When you delete a group, all the devices and data belonging to this group
are also deleted. We would therefore recommend archiving the data before
deleting a group.
The visualization software allows you to archive both group data and device
data. You can import archived group data again later on. This function is
identical to the "Archiving device" function. You receive a compressed ZIP
file.
4. Select the Serial interface option and click on the Connect button.
ð The connection is established and the current device data downloaded.
If you are connecting the device to a PC for the first time, you are then
prompted to create a new device in the TAPCON®-trol. Observe the corre-
sponding information.
You can use the Create new device function to add a new device to the vis-
ualization software. The visualization software automatically calls up all the
device's parameters and configuration data.
You can shorten the download process by activating the quick parameter
download option in the communication settings.
After downloading, you have to enter the device's basic details. You can en-
ter the following data in the General settings tab:
▪ Device group: Assignment of device to group
▪ Device identcode (regulator ID): 4-digit code for identifying the device
▪ Device name: Designation of device
▪ You can enter a designation, location and comments about a parameter
set under Parameter set.
The data entered is shown in the status bar and display area.
These details only serve as guidelines. They do not affect the visualization
and device settings.
You can use the Open device function to import the archived devices, in-
cluding the device data. You can both import archived groups and devices
(.zip file) and add individual devices (.tap file).
When you import a .zip file, the Archive integration window appears.
If groups or devices with the same name or ID are imported, the visualiza-
tion software automatically adapts the name and ID.
When you import a .tap file, the Edit parameter set window appears. In this
window you can check the device data and information relating to the pa-
rameter set and adapt it if necessary.
When you delete a device, all the associated information about the device is
deleted. We would therefore recommend archiving the data before deleting
a device.
The visualization software allows you to archive device data. You can import
archived device data again later on. This function is identical to the archiving
group function. You receive a compressed ZIP file.
You can use the Download parameters function to download the device's
current parameters at any time.
You can use the visualization software to change the device's parameters.
When you have changed all the desired parameter values, you have to send
the configuration to the device. Proceed as described in the Uploading pa-
rameters [► 127] section.
When you have changed parameters, you can then transfer these changes
to the device. The Upload parameters function is provided for this purpose.
You can change the parameter set information, for example the designation,
at any time.
You can use the Cut parameter set function to cut any parameter set and
paste it somewhere else.
You can use the Copy parameter set function to copy any parameter set
and paste it somewhere else.
You can use the Paste parameter set function to paste previously copied or
cut parameter sets somewhere else.
When you delete a parameter set, all associated entries are deleted from
the computer's hard disk.
8.3.4 Modules
The following modules are available:
▪ Maintenance data
▪ Remote
8.3.4.1 Remote
In the Remote module, you can view the device's display and control the de-
vice remotely. The display is structured like the front of the device. There is a
progress bar under the display which shows the time remaining until the dis-
play next updates.
You can view the current maintenance data in the TAPCON®-trol software.
Current status
The Current status tab shows the individual maintenance work, progress as
a % and the forecast maintenance dates.
The Current wear values tab shows the individual contact wear and the cal-
culated maximum wear difference.
8.4 TRAFOSET™
8.5 TRAFOVISOR™
The TRAFOVISOR™ visualization software is used to graphically display the
measured values recorded by the TRAFOGUARD® monitoring system.
You can also change the IP address during operation. To do so, proceed as
follows:
1. Go to Settings > Communication > Communication setting.
ð The dialog box for inputting the IP address will appear.
2. Enter the IP address as described above and click on the OK button.
3. Restart the TRAFOVISOR™ visualization software to adopt the
changes.
1 Menu bar
2 Main menu
3 Sub-menu
4 Display area
▪ On-load tap-changer
▪ Inputs
▪ Outputs
You can view the current status of the transformer in the operating status
sub-menu. The following information is displayed:
▪ Current status
▪ Currently queued events
▪ Measured values (Favorites)
▪ Transformer description (optional)
▪ Illustration of the transformer (optional)
Current status
Current events
This overview shows the number of event messages currently active. If you
want to view the event messages in detail, please proceed as is described in
the Displaying events [► 145] section.
In addition to the operating overview, you can graphically display the record-
ed measured values and status values. Depending on how your Trafoguard
is configured, various sub-menus are available for selection:
▪ Transformer
▪ DGA
▪ Cooling system
▪ Voltage regulation
▪ On-load tap-changer
▪ Inputs
▪ Outputs
Digital signal
Cooling system
The display of the Number of starts and Number of hours values are up-
dated hourly.
No limit values are defined in TRAFOSET™ for some of the measured val-
ues. Therefore, it is possible to set scaling for these measured values.
► Enter the desired values in the Lower limit and Upper limit fields.
You can change the way the diagram is displayed to suit your requirements.
The following changes are possible:
▪ Zooming into, zooming out of and moving diagram
▪ Displaying and hiding peak values and average value
▪ Changing between current values and past values
▪ Selecting measured values shown
▪ Setting color and line thickness of diagram
You can use the following buttons to zoom into, zoom out of and move the
diagram:
▪ : Move diagram
▪ : Using this button, you can retrieve the device's past values (older
than 24 hours). You can then view the past values in the Diagrams and
Tables menus, respectively.
To set the color and line thickness of the diagram, proceed as follows:
► Click on the Line setting button.
ð The line settings window opens.
You can select the measured values shown in the following menu.
In order to display the past values, you need to retrieve them from the de-
vice. In this regard, note the "Retrieving the device's past values" descrip-
tion in the Diagram [► 141] section.
Past events are displayed only if you have downloaded them from the de-
vice. Note the following information in this regard.
You can use the buttons on the right-hand edge of the screen to display and
hide the events depending on their priority:
Display Hide
Red
Yellow
Green
You can download historic events from the device using the button.
2. Select the directory and then click on the OK button to export the event
list.
8.6.1 General
You can call up the following information in the General menu.
Communication card
1. Press > Info > Gen. information > until the desired
display appears.
ð CIC1 card SCADA information
LED-Test
You can check whether the LEDs are functioning properly. To do this, press
the relevant function key to illuminate an LED:
This function will only test the functional reliability of the respective LED.
The function of the device linked to the LED is not tested.
1. Press > Info > Gen. information > until the desired
display appears.
ð LED test
2. To carry out the function test, press any F key for the LED you want to
test.
Real-time clock
An operations counter is started when the device is first switched on. This
continues to run even if the device is switched off. Each of the operations
counter's times is overwritten with that of the PC to visualize the measured
values.
► Press > Info > Gen. information > until the desired
display appears.
ð RTC.
Resetting parameters
With this display you can reset your settings to the factory settings .
1. Press > Info > Gen. information > until the desired
display appears.
ð Parameters.
3. Press .
ð All parameters have been reset to the factory settings.
In this screen, you can display additional information on the individual data-
bases. The following information is displayed:
▪ Name of the database
▪ Date of the first data set
▪ Number of data sets
1. Press > Info > Gen. information > until the desired
display appears.
ð Measured value memory.
8.6.2 Events
The event overview can be used to display the number of current red, yellow
and green events. In addition, you can display additional information on the
individual events.
► Press > Info > Measured values > until the display
appears.
8.6.4 Status
The status of all cards is displayed in the Status menu. Note the connection
diagram supplied for the arrangement of the terminals.
IO card
The status of the IO card's inputs and outputs is shown in this display.
► Press > Info > Status > until the desired display ap-
pears.
ð IO card status / IO card relay.
UC card
The status of the UC card's inputs and outputs is shown in this display.
1. Press > Info > Status > until the desired display ap-
pears.
ð UC card status / UC card status relay.
TEM card
The measured temperatures of the TEM card are shown in this display.
► Press > Info > Status > until the desired display ap-
pears.
ð TEM card status.
The analog measured values of the AD8 card are shown in this display.
1. Press > Info > Status > until the desired display ap-
pears.
ð AD8 card status.
Status of MI card
The current and voltage values measured by the MI card are shown in this
display.
► Press > Info > Status > until the desired display ap-
pears.
ð MI card status.
Parallel operation
This display indicates the control number for parallel operation (= CAN bus
address) and the number of devices which are currently operating in parallel.
► Press > Info > Status > until the desired display ap-
pears.
ð Parallel operation.
1. Press > Info > Status > until the desired display ap-
pears.
ð DATA ON CAN BUS.
9 Fault elimination
This chapter describes how to eliminate simple operating faults.
10 Technical data
SUL-P SUM-P
Permissible voltage 18...36 V DC 36...72 V DC
range
Input current Max. 2.3 A Max. 1 A
Internal fuse 250 V; 3 A; 6.3 x 32 mm, "fast-acting" character-
istics
Table 36: Special model
Interfaces
Interface Pin Description
1 Voltage transformer
2 Voltage transformer
5 Shared return conductor
6 Current transformer with rated current
of 5 A
9 Current transformer with rated current
of 1 A
10 Current transformer with rated current
of 0.2 A
Table 39: MI card terminal X1
1 Ohmic load
AC-115 AC-230
Power consumption 0.16 A 0.08 A
Internal fuse 250 V; 3 A; 6.3 x 32 mm, "fast-acting" character-
istics
Table 43: Control voltage supply
*) Alternatively, you can fit the cable shield to the partition plate's cable clip.
SID
RJ45 Max. 100 m
Ethernet
100 MBit/s
Table 55: Technical data for SID card
MC1
Power supply 85...264 V AC; 110 V DC, 220 V DC
47...63 Hz
Power consumption approx. 6 W
Insulation 4.242 V DC
Temperature range Operation: 0...40 °C
Storage: -20...85 °C
Fiber-optic cable Connection type: F-ST
Fiber type: Multimode
Max. cable length: 2 km
Wave length: 1310 nm
Table 57: Technical data for MC1 card
For more information about the technical data, please consult the user guide
for the Ethernet switch.
10.13 Tests
Glossary
ANSI OLTC
American National Standards Institute Abbreviation for on-load tap-changer
DGA SKB
Abbreviation for "Dissolved Gas Analysis", analy- Abbreviation for main switching contact B
sis of the gases dissolved in the oil
WKA
DIN Abbreviation for transition contact A
Deutsches Institut für Normung (German Institute
for Standardization) WKB
Abbreviation for transition contact B
DSI
Abbreviation for diverter switch insert
EMC
Electromagnetic compatibility
EN
European standard
IEC
International Electrotechnical Commission
IEEE
Abbreviation for "Institute of Electrical and Elec-
tronics Engineers"
LDC
Line drop compensation
LED
LED (Light Emitting Diode)
NORMset
Operating mode for quickly starting voltage regu-
lation.
E
L
Electromagnetic compatibility 40
Ethernet switch 29 Language 53
Line drop compensation
Inductive voltage drop 109
Ohmic voltage drop 109
Load-dependent cooling stage ac-
tivation 101
Activation threshold 101
Overrun 101
M R V
Maintenance R&X compensation 108 V< also below 30 V 107
Confirm 91 Raise/Lower pulse duration 111 V< blocking 107
MC1 card 29 Rated value 97 V< delay 107
Measured value interval 54 Regulator ID 62 Voltage display kV/V 53
MI 22 Remote 130 Voltage regulation 73
MI3-G 22 Repeat unsolicited messages 65
Modules 130
Motor Current Index 74
W
Motor runtime 113
S Winding exponent 97
SCADA address Winding temperature 96
Device 64 Wiring 43
N Master 64
Network address 62, 64, 65 Secondary voltage 102
Network mask 62 Send delay time RS485 65
Z
NORMset 102 Short-circuit capacity 114 Z compensation 110
SID card 28 Activate 110
SNTP time server 63 Limit value 111
O SU card 21
Oil circulation 97 Switch 29
Oil temperature Switching criterion 96
Offset correction 95 Switching direction 116
Threshold value 96 Standard 117
Operating controls 16 Swapped 117
operating mode Switch-on delay 100
Local mode 15
Remote mode 15
Optical fiber transmission behavior T
64 T2 activation 106
Tap changer monitoring 70
TCP port 64, 66
P TEM card 26
Parallel operation 114 Temperature test 99
CAN bus 114 Test operations 93
Circulating reactive current Throughput capacity 114
115 Time 55
Parallel operation error mes- Time constant 97
sage 117 Time server address 63
Parallel operation method 115 Time shift 54
Switching direction 116 Transformer
Parameters Primary current 57
Reset 150 Transformer data 55
Passes through neutral position Current transformer connection
93 57
Password 118 Primary voltage 56
Phase difference 57 Secondary voltage 56
Primary voltage 102 Transformer circuit 57
U
UC card 23
Unsolicited messages 65
Luxembourg
Reinhausen Luxembourg S.A.
72, Rue de Prés
L-7333 Steinsel
Phone: +352 27 3347 1
Fax: +352 27 3347 99
E-Mail: sales@lu.reinhausen.com
2398614/04 EN ▪ 08/14 ▪