Professional Documents
Culture Documents
Notifier Manual N6000
Notifier Manual N6000
Notifier Manual N6000
N-6000
Manual
REV :A
DATE :2007-07-24
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Detectors that have ionizing-type sensing chambers
smoke detectors, heat detectors, manual pull stations, tend to detect fast-flaming fires better than smoldering
audible warning devices, and a fire alarm control with fires. Because fires develop in different ways and are
remote notification capability—can provide early warning of often unpredictable in their growth, neither type of
a developing fire. Such a system, however, does not assure detector is necessarily best and a given type of detector
protection against property damage or loss of life resulting may not provide adequate warning of a fire.
from a fire. Smoke detectors cannot be expected to provide adequate
While fire alarm systems are designed to provide early warning of fires caused by arson, children playing with
warning against fire, they do not guarantee warning or matches (especially in bedrooms), smoking in bed, and
protection against fire. A fire alarm system may not provide violent explosions (caused by escaping gas,
timely or adequate warning, or simply may not function, for improper storage of flammable materials, etc.).
a variety of reasons: Heat detectors do not sense particles of combustion
Smoke detectors may not sense fire where smoke cannot and alarm only when heat on their sensors increases at
reach the detectors such as in chimneys, in or a predetermined rate or reaches a predetermined level.
behind walls, on roofs, or on the other side of closed Rate-of-rise heat detectors may be subject to reduced
doors. Smoke detectors also may not sense a fire on sensitivity over time. For this reason, the rate-of-rise
another level or floor of a building. feature of each detector should be tested at least once
Particles of combustion or “smoke” from a developing per year by a qualified fire protection specialist. Heat
fire may not reach the sensing chambers of smoke detectors are designed to protect property, not life.
detectors because:
• Barriers such as closed or partially closed doors, Smoke detectors must be installed in
walls, or chimneys may inhibit particle or smoke flow. the same room as the control panel. If detectors are not so
• Smoke particles may become “cold,” stratify, and not located, a developing fire may damage the alarm system,
reach the ceiling or upper walls where detectors are crippling its ability to report a fire.
located. Audible warning devices such as bells may not alert
• Smoke particles may be blown away from detectors people if these devices are located on the other side of
by air outlets. closed or partly open doors or are located on another
• Smoke particles may be drawn into air returns before floor of a building.
reaching the detector. A fire alarm system will not operate without any electrical
• The amount of “smoke” present may be insufficient to power. If AC power fails, the system will operate from
alarm smoke detectors. standby batteries only for a specified time and only if the
Smoke detectors are designed to alarm at various levels of batteries have been properly maintained and replaced
smoke density. If such density levels are not created by a regularly.
developing fire at the location of detectors, the detectors Equipment used in the system may not be technically
will not go into alarm. compatible with the control. It is essential to use only
Smoke detectors, even when working properly, have equipment listed for service with your control panel.
sensing limitations. Detectors that have photoelectronic Telephone lines needed to transmit alarm signals from
sensing chambers tend to detect smoldering fires better a premise to a central monitoring station may be out of
than flaming fires, which have little visible smoke. service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission
systems are recommended.
Verify that wire sizes are adequate for all initiating and
Several different sources of power can be indicating device loops. Most devices cannot tolerate more
connected to the fire alarm control panel. Disconnect all than a 10% I.R. drop from the specified device voltage.
sources of power before servicing. Control unit and Like all solid state electronic devices, this system may
associated equipment may be damaged by removing operate erratically or can be damaged when subjected to
and/or inserting cards, modules, or interconnecting cables lightning-induced transients. Although no system is
while the unit is energized. Do not attempt to install, service, completely immune from lightning transients and
or operate this unit until this manual is read and interferences, proper grounding will reduce susceptibility.
understood. Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning strikes.
System Reaccepting Test after Software Consult with the Technical Services Department if any
Changes. To ensure proper system operation, this product problems are anticipated or encountered.
must be tested after any programming operation or change Disconnect AC power and batteries prior to removing
in site-specific software. or inserting circuit boards. Failure to do so can damage
All components, circuits, system operations, or software circuits.
functions known to be affected by a change must be 100% Remove all electronic assemblies prior to any drilling,
tested. In addition, to ensure that other operations are not filing, reaming, or punching of the enclosure. When
inadvertently affected, at least 10% of initiating devices that possible,
are not directly affected by the change, up to a maximum of make all cable entries from the sides or rear. Before making
50 devices, must also be tested and proper system modifications, verify that they will not interfere with battery,
operation verified. transformer, and printed circuit board location.
Table of Content
Section 1:About This Manual ................................................................................................................. 6
1.1Notes, Cautions & Warnings......................................................................................................... 6
1.2Font Definition .............................................................................................................................. 6
Section 2:System Overview.................................................................................................................... 7
2.1Introduction ................................................................................................................................... 7
2.2Characteristics of the Product........................................................................................................ 7
Section 3:System Configuration & Installation ...................................................................................... 9
3.1Features Main Performances ......................................................................................................... 9
3.2Electrical Specifications ................................................................................................................ 9
3.3System Configuration.................................................................................................................... 9
3.4System Block Diagram................................................................................................................ 10
3.5Installation & Connection ........................................................................................................... 11
3.5.1Enclosures............................................................................................................................ 11
3.5.2Connection Requirements.................................................................................................... 12
3.5.3Connection of Circuit Board Terminals............................................................................... 12
3.5.3.1CPU Diagram ............................................................................................................... 12
3.5.3.2Power Supply Connection ............................................................................................ 15
3.5.3.3NIC-EC......................................................................................................................... 17
3.5.3.4Loop Control Module Connection................................................................................ 19
3.5.3.5MCU-16B Annunciator Control Module Connection .................................................. 21
3.6Equipment Debugging ............................................................................................................ 23
3.6.1Connection Inspection..................................................................................................... 23
3.6.2Power-on Inspection........................................................................................................ 24
3.6.3External Connection ........................................................................................................ 24
3.6.4Important Points .............................................................................................................. 24
3.6.5Inspection Methods for Addressable Device Connections.............................................. 25
Section 4:Operation .............................................................................................................................. 26
4.1LED Indicators and Keys ............................................................................................................ 26
4.1.1Control Panel Display LED Indicators and Keys ................................................................ 26
4.1.2Annunciator Control Module LED Indicators and Keys ..................................................... 29
4.2Power-on ..................................................................................................................................... 30
4.3System Self-test........................................................................................................................... 30
4.4Event Display .............................................................................................................................. 32
4.4.1Trouble Screen..................................................................................................................... 32
4.4.2Fire Alarm Screen................................................................................................................ 33
4.4.3Supervisory Screen .............................................................................................................. 34
4.4.4Point Disabled Screen.......................................................................................................... 35
4.4.5CBE Screen.......................................................................................................................... 36
4.4.6Pre-alarm Screen.................................................................................................................. 36
4.4.7Horn / strobe Screen ............................................................................................................ 37
4.4.8Feedback Screen .................................................................................................................. 37
Section 5:Programming ........................................................................................................................ 38
5.1Menu ....................................................................................................................................... 38
5.2System Management............................................................................................................... 40
5.2.1System setting ................................................................................................................. 41
5.2.2Password modification .................................................................................................... 42
5.2.3Main Reset....................................................................................................................... 43
5.3Device Configuration.............................................................................................................. 44
5.3.1Loop card......................................................................................................................... 45
5.3.1.1Parameter setting .......................................................................................................... 45
5.3.1.2Auto Programming ....................................................................................................... 47
5.3.1.3Point Programming....................................................................................................... 49
5.3.2Annunciator Control Module .......................................................................................... 50
5.3.2.1Parameter setting .......................................................................................................... 51
5.3.2.2Point Programming....................................................................................................... 51
5.3.3Remote Display ............................................................................................................... 52
5.3.3.1Parameter setting .......................................................................................................... 53
5.3.3.2Label Download ........................................................................................................... 53
5.3.3.3Point Programming....................................................................................................... 54
5.3.4CBE Programming............................................................................................................... 54
5.3.4.1General Zone ................................................................................................................ 55
5.3.4.2Logic Zone ................................................................................................................... 55
5.3.5Device Control..................................................................................................................... 56
5.3.5.1Manual Output.............................................................................................................. 57
5.3.5.2Status Tracking............................................................................................................. 58
5.3.5.3Walk Test ..................................................................................................................... 58
5.3.5.4Loop Drill..................................................................................................................... 60
5.3.5.5Power Supply Management.......................................................................................... 60
5.3.6History Events .......................................................................................................................... 61
Section 6:Miscellaneous ....................................................................................................................... 62
6.1Safety Protection Device ............................................................................................................. 62
6.2Usage and Maintenance............................................................................................................... 62
6.3Common Troubles....................................................................................................................... 62
6.4Transportation & Storage ............................................................................................................ 63
6.5Out-of-box Audit......................................................................................................................... 63
Appendix A........................................................................................................................................... 64
Section 1:About This Manual
1.2Font Definition
Special font styles used in this manual are listed in Table 1-1, Specifications of
Manual Characters:
Font Meaning Example
Key on the control panel Press the key 【 Signals
【Bold】 Silenced】
2.1Introduction
The N-6000 is a new generation intelligent fire alarm control panel recently
released by Notifier. This panel satisfies all related requirements defined in
GB4717-2005.
This control panel combines both alarm and CBE control functions. The N-6000
can also be programmed off-line when using a PC with Notifier Verifire Tools
(NVT).
The N-6000 fire alarm control panel has many intelligent characteristics; these
include but are not limited to drift compensation, sensitivity adjustment and
self-optimizing alarm.
The N-6000 control panel with CBE (control by event) control can manage both
alarm paging and gas extinguishing systems. The N-6000 connected with a CRT
display terminal forms a comprehensive and reliable fire alarm control system,
perfect for medium to large-scale facilities.
3.2Electrical Specifications
y Voltage range
Input voltage: 220 VAC
Output voltage:
Two – 24 VDC non-resetable outputs
One – 24 VDC resetable output
Two – 5 VDC outputs
Several dry contacts - power supply trouble relay output
y Maximum output current: 14.6A
3.3System Configuration
y Intelligent control panel: N-6000
y Remote display: LCD-100B, LDM-64B
y Intelligent detectors:
Intelligent photoelectric smoke detector: ND-751P
Intelligent heat detector: ND-751T
Intelligent laser smoke detector: FSL-751
Intelligent smoke detector: FSB-200S
y Intelligent base:
B601
B501
y Intelligent modules:
Intelligent monitor module: MMX-7
Intelligent monitor/control module: CMX-7
Intelligent control module: CMX-7C
Monitor module for two-wire 24 VDC conventional detectors:
MMX-7P
Isolator: ISO-7
Intelligent manual call point: M500K
Intelligent manual call point: M700K
y Micro printer: uPRT-380S
y Chinese graphic and text management software: N-NCS, N-VFT
If there are many addressable units in the loop bus, user should install the
shortcut isolator in front of the loop bus. The addressable units are less than 25
units between adjacent two isolators.
3.5Installation & Connection
3.5.1Enclosures
Wall-mount designs use a standard NOTIFIER® C-type cabinet. This cabinet is
shown in Fig. 3-2 Cabinet Appearance:
All NOTIFIER cabinets are fabricated from 16-gauge steel. The cabinet assembly
consists of two basic parts: a backbox and a locking door. The backbox has been
engineered to provide ease-of-entry for the installer. Knockouts are positioned at
numerous points to aid the installer in bringing a conduit into the enclosure.
3.5.2Connection Requirements
y All incoming/outgoing external conduits should use the control panel cabinet’s
bottom knockout or opening for terminal connections.
y Loop transmission line adopts twisted shielded pair cable, the type and
specification are: RVSP-2×1.5mm2
y Loop resistance (refers to loop resistance between the machine and two leads of
the farthest addressing unit) should be less than 50 Ω.
y Power wiring should use two-color multiple plastic cable, red for male terminal,
black for female terminal. The type and specification are: RV-2×2.5mm2
3.5.3.1CPU Diagram
Control panel includes in a circuit board, it has CPU and extend device interface.
You can order the board supports for 8, 16, 30 loops. The connections terminals,
jumper and status lights are showed below:
Fig. 3-4 CPU Diagram
3.6Equipment Debugging
3.6.1Connection Inspection
y Visually inspect the control panel condition
y Visually inspect the external connection ports
y Open the control panel and visually inspect all connections. Confirm connections
are correct, that there are no loose connections, no short circuits, unplugged or
disconnected connectors as well as confirm the power supply does not have
any short circuit trouble.
y Visually inspect the jumpers in the circuit to confirm there are no duplicate
numbers.
3.6.2Power-on Inspection
After you have finished the visual inspection, power-on the battery power supply.
With the battery started a buzzer should be heard and the LCD should temporarily
function normally. Once the control panel enters normal operation status, a buzzer
and LED horn/strobe will indicate a troubled status because main power is not
connected. Power-down and disconnect the battery power supply then connect and
power on the main power supply. Once the control panel enters normal operation
status, a buzzer and LED horn/strobe will indicate a troubled status because the
battery power supply is not connected. At this time, connect the battery power
supply. Soon after the control panel will return to normal operating status.
During normal operation, if both the main and battery power supplies are
connected the power supply status lamp (on the main panel of the control panel)
will maintain normal illumination.
When the main power supply fails because of loss of power, poor power
connection, an over-voltage or under-voltage of 5V and 24V, or a short circuit with
rack earth and communication trouble with the mainframe, the power supply status
lamp (on main panel of the control panel) illumination will stop. Then both a
buzzer and LED horn/strobe will indicate a troubled status while additional
information will be shown on the control panel LCD.
3.6.3External Connection
Look for any short-circuits or disconnections to and from the control panel. Once
everything has been inspected, connect the control panel.
Batch installation -- connecting 10-20 detectors or modules on the loop per time --
is highly recommended. After installing the detectors or modules restart the control
panel to ensure the newly installed devices are recognized and installed correctly.
If the control panel gives a trouble signal recheck the circuit and addressable
devices are installed properly. Once the trouble signal has been solved, continue
batch installation and power testing. After all the devices have been installed, the
simulated trouble, fire alarm and CBE event functions maybe tested. Confirm that
the control panel alarms normally, properly links field equipment and accurately
prints corresponding alarm information. Continue testing and adjusting until panel
maintains normal operating status.
3.6.4Important Points
y Avoid touching the circuit board IC chip during installation
y Pay attention to polarity during connection and installation
y Before starting the system, check for short circuits, disconnection or reverse
polarity
y Connectors among leads shall be wielded and inter-line insulation shall be
guaranteed.
The annunciator control module has a total of 32 indicating lamps, 16 keys and 16
feedback signals.
• One composite button: Time function key has 3 functions
1、Press for about 1 second: LED lamp below the key will illuminate locking the
control key module
2、Press for more than 1 second: LED lamp on the right side of the key will
illuminate with manual/automatic allowed
3、Press for more than 4 seconds: horn/strobe self-test
• No. 1-16 Start Keys:
-Press a key and the corresponding feedback signal a (Lamp 1-16) flash, which
means corresponding key has been pressed.
-When a feedback indicating lamp (Lamp 1-16) flashes, it indicates that an
operational signal from CBE equipment has been received and the
corresponding CBE equipment will be started.
4.2Power-on
Connect 220V AC power, and then turn on the main power supply using the switch
inside the cabinet. Power-on Screen is shown in Fig. 4-4:
4.3System Self-test
After the N-6000 has been turned on, it will self-test both the hardware and
software of the system. During the self-test all LED indicating lamps on the left
side of the mainframe panel will flash. Once the self-test has finished a buzzer will
sound and LEDs will temporarily illuminate after which the panel will return to a
normal operation status. Additionally, the system will show the display screen
while the power supply indicating lamp continues to flash.
After a self-test, the system will show the following screen:
The normal system screen is divided into three bars; these include the event
statistics bar, the alarm screen bar and the status bar. The event statistics bar shows
fire alarms, trouble alarms, supervision, CBE and point disabled locations. The
status bar shows the node number, manual/automatic status, transmission
equipment status, main or reserved power supply status, the current date/delay
status of the latest logic zone as well as the current time.
①Manual/Automatic Status
——System in manual status
4.4Event Display
• Event Order:
First: Fire alarm, CBE, feedback
Second: Supervision
Third: Trouble
Fourth: Point Disabled - disabled
4.4.1Trouble Screen
When the control panel detects a failing power supply or other trouble, it will
execute a series of operations:
• A trouble relay will be activated and the control panel will alarm
• A system trouble indicating lamp on the control panel display will flash and the
LCD will show a trouble screen
• Detailed trouble type will show the exact geographic location and occurrence
time on the LCD
• A trouble event will be saved to the native Flash ROM and the printer will print a
record of the trouble event
Press the 【△】 key or the 【▽】 key on the main panel to review the previous or
next trouble event and press the【<】key or the【>】key to page up or down. Press
【ACK】 key on the main panel to acknowledge, and all trouble events will be
shown one by one. Once the alarm has silenced and all trouble events have been
acknowledged, the system trouble indicating lamp on the main panel will return to
its normal illumination.
The most common trouble events include but are not limited to: equipment off-line,
grounding the equipment’s positive terminal, grounding the equipment’s negative
terminal, the equipment’s positive terminal is disconnected, the equipment’s
negative terminal is disconnected, power supply shows low voltage, power supply
shows high voltage, unmatched load types, low threshold values, database errors.
4.4.3Supervisory Screen
When a point disabled location exists in a loop, each disabled point (detector,
module, and loop) will be shown one by one (see Fig. 4-10). The control panel will
execute a series of operations:
• A point disabled indicating lamp on the control panel will flash but the control
panel will not alarm
• A point disabled indicating lamp will be illuminated
• The point disabled information will be saved to the native Flash and the printer
will print the current point disabled information
Press the 【△】 key or the 【▽】 key on main panel of the control panel to review
the previous or next point disabled event and press the 【<】 key or the 【>】 key
to page up or down. Press 【OK】 key on main panel of the control panel to
acknowledge all Point disabled information has been shown. Once the alarm has
silenced and all point disabled events have been acknowledged, the point disabled
indicating lamp on the main panel will return to its normal illumination.
4.4.5CBE Screen
4.4.6Pre-alarm Screen
To enter the pre-alarm screen and also query the pre-alarm screen keep pressing the
【Fire alarm/Pre-alarm】composite key on the main panel. The pre-alarm screen is
shown below:
4.4.8Feedback Screen
To enter the supervision/feedback screen and also query the supervision/feedback
screen keep pressing the【Supervision/Feedback】composite key on the main panel.
The supervision/feedback screen is shown below:
5.1Menu
System Setting
Main Reset
Setting
Point Programming
Setting
DCU
Point Programming
Device Configuration
Setting
MCU
Point Programming
Menu Setting
Point Programming
General Zone
CBE Programming
Logic Zone
Manual Output
Status Track
Device Control
Status Track
Walk Test
Power Management
History Event
Once a user has entered the correct password, he/she will enter the main menu and
view the following screen. In the main menu screen, he/she can update or change
the system management, device configuration, CBE programming, device control
and history events.
5.2System Management
Under “System management” the operator has 3 options; (1) System setting, (2)
Modify Password, or (3) Main Reset. The system management screen is shown as
follows:
Fig. 5-4 System Management Screen
5.2.1System setting
Under “System Setting” the following screen will be shown:
Line 1: The node is the control panel’s address within the network while the label is
a description of the control panel
Line 2: If “ (YES)” is selected for the time server option, then this control panel is
the time master within the network and all other panels will synchronous
accordingly. Click the button “time & date” to set the time and date of the control
panel
Line 3: Language—determines the language of the control panel display. At
present two languages are currently available: Chinese and English
Line 4: Backlight—the duration of time the LED display remains lit. There are four
choices available: Normal Open, Normal Close, Off in 30 Seconds and No Display.
Line 5 to Line 7: Relays—there are 3 relays each with 7 operational modes:
① Disabled—the relay is disabled
② Fire alarm output—the relay will close upon fire alarm
③ Trouble output—the relay will close during trouble status
④ CBE—the relay will close during CBE
⑤ Supervision—the relay will close during supervision
⑥ CBE logic output—the relay will only be used in CBE output expression.
When the value of located expression is true, the relay will close and re-open in
the opposite condition
⑦ Reset output—the relay will close during normal operation or when the system
is being reset.
Line 8& Line 9: COM—2 serial ports each with 4 operational modes:
Degradation CBE: “ (YES)”/ “ (NO).” The default status “ (YES)” is
Normal Open. Degradation CBE only works when enabled
Fire Alarm Verification: “ (YES)”/ “ (NO).” The default status is “ (YES).”
This function has a time sensitive fire alarm, ensuring an alarmed status will be
accurate. This setting can greatly reduce false alarms and improve system
efficiency
Failover: “ (YES)”/ “ (NO).” The default status is “ (NO).” Failover is the
trouble display switch for the whole control panel. If “ (YES)” is chosen, all
trouble signals will be disabled without any display or alarm although a history
record is still maintained
Main Power Supply: “ (YES)”/ “ (NO).” The default status is “ (YES),”
which installs the main power supply for the control panel
Reserved Power Supply: “ (YES)”/ “ (NO).” The default status is “ (YES),”
which installs the reserved power supply for the control panel
Reset Verification: “ (YES)”/ “ (NO).” The default status is “ (NO).” If “
(YES)” is chosen, a password needs to be entered before resetting. If “ (NO)” is
chosen, a password does not need to be entered before resetting
5.2.2Password modification
Under “Password modification,” a user can modify his/her password according to
their system status (Admin, Engineer, or Guest). The password modification screen
is shown below:
Fig. 5-6 Password Modification Screen
The N-6000 has 3 different user levels, each level is password protected. The three
levels are (ordered from highest to lowest) Administrator, Engineer and User. Each
level has its own password. The Administrator user can modify any password in
the system (including the Administrator level). The User can only operate on the
4th setting, “Device Control” and the 5th setting, “History event.” The Engineer
can operate all five settings in the menu but will be interrupted (exit programming)
when an alarm event occurs. The Administrator can operate all five settings in the
menu and will not be interrupted during an alarm event.
Factory default passwords are as follows: 333333 for Administrator, 222222 for
Engineer and 111111 for User.
After the initial login the user will enter the password modification screen. He/she
can change the password by entering a new password in the “Enter new password”
dialogue box and then re-entering the new password in the “Confirm new
password” dialogue box. Once the system has confirmed the two passwords are the
same, the user should press 【OK】 to confirm the password change. After the user
has pressed 【OK】 the password will be successfully modified, to cancel the
previous operation press the 【Cancel】 button.
Note: If an incorrect password is entered, the system will show another dialogue
box requesting the correct password be entered.
5.2.3Main Reset
In the “System Setting” screen choose “Main Reset” to reset the system to all
default factory settings.
Fig. 5-7 Main Reset Screen
After the correct Administrator password has been entered, a dialogue box will
prompt to verify the “Main Reset” choice. Press “OK” to confirm the reset and
restore default factory settings. Press “Cancel” to cancel the operation and exit the
screen.
5.3Device Configuration
Choose the “Device Configuration” screen to adjust the settings of the loop cards,
multi-line control modules, annunciator control modules and repeaters. Screen
shown below:
Fig. 5-8 Device Configuration Screen
5.3.1Loop card
In the “Device Configuration” screen, choose the “LCM” option to enter the screen
shown below in Fig. 4-23:
5.3.1.1Parameter setting
In the “LCM” screen, to adjust the settings and program options, choose “Setting,”
“Auto Programming,” or “Point programming.” The screen is shown in Fig. 4-24:
Fig. 5-10 Parameter Setting Screen
5.3.1.2Auto Programming
Each loop has 3 status options: Installed, Uninstalled, and Disabled. During normal
installation, the programmer may enter the “Auto Programming” screen. When
he/she selects a loop number for automatic programming and then presses “OK,”
the system will verify each device on the selected loop.
Caution: When either a CMX-2 control module or a M500K call point are on
a loop using “Auto Programming” the control panel will misidentify the CMX-2 as
a CMX-7(C) and misidentify the M500K as an MMX-7. When this happens, the
user should enter 4.5.2.1.3 Point Programming screen (device configuration→
LCM→point programming) to modify the device identity by selecting the proper
equipment type.
Fig. 5-12 Automatic Programming
5.3.2.1Parameter setting
5.3.2.2Point Programming
Point Programming of MCU can access to set the relative module address of keys
and feedback led.
Fig. 5-17 Point Programming Screen
5.3.3Remote Display
In the “Remote Display” screen, a programmer can access the “Setting,”
“Download Label” and “Point Programming” option screens. One N-6000 fire
alarm control panel can have up to 64 remote displays.
5.3.3.2Label Download
5.3.3.3Point Programming
Line 1: Displays the remote display number, point number and installation status.
These include: Uninstalled, Normal, and Disabled.
Line 2: Displays the current remote display point description
Line 3: Point Mapping—Each remote display can have up to 64 points. Each point
must have a specific zone and loop address. After each point has been mapped,
during an event (fire alarm, trouble, etc) the mapped equipment’s location and
event will be shown on the relative remote display screen.
Press “Save” to save the current settings. If the user presses “Exit” without saving,
the following dialogue box will be prompted. At this time the user can also save the
current settings. The user can also exit the current screen to retain previous settings;
the current settings will not be saved.
5.3.4CBE Programming
In the “CBE Programming” screen programmers can access both the “General
Zone” and “Logic Zone” setting screens.
Fig. 5-22 CBE Programming Screen
5.3.4.1General Zone
Within the “General Zone” screen a user can select zones 0-499 to review the
relative logic equation of a particular zone. Use the VFT programming software to
modify the logic equations as necessary.
5.3.4.2Logic Zone
Within the “Logic Zone” screen a user can select zones 0-999 to review the relative
equation of a particular zone. Use the VFT programming software equation to
modify the logic equations as necessary.
Fig. 5-24 Logic Zone
5.3.5Device Control
In the “Device Control” screen a user can access the “Point Output,” “Status
Tracking,” “Walking Test,” “Loop Exercise” and “Power Supply Management”
setting screens.
Within the “Point Output” screen a user can set the loop number, address number,
type of equipment, label and the inspection lamp ON/OFF status. Press the 【△】
key or the 【▽】 key to review a points’ status.
Line 1: Displays the current loop number, address and status. These include:
Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
Line 7: Displays the selected output module status. If the user chooses “Start” and
then presses “OK”, the point in the current loop will be output by the module; if set
at “Close”, the point will not be output by the module.
5.3.5.2Status Tracking
Within the “Status Track” screen a user can set the loop number, address number,
address type as well as monitor the point.
Line 1: Displays the current loop number, loop address and its status. These include:
Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Display the current equipment type and model.
Line 7: Displays the current point status.
5.3.5.3Walk Test
N-6000 fire alarm control panel uses the MPS-350W power supply. Within the
“Power Management” screen the user can review the current status of each power
supply.
Line 1: Displays the currently connected power supply type. The MPS-350W is the
primary power supply for the N-6000.
Line 2: Displays the current status and voltage of the main power supply.
Line 3: Displays the current status and voltage of the reserved power supply.
Line 4: Press 【Discharge】 to discharge the power supply. Press 【Stop】 to stop
discharging. Press 【Exit】 to exit the power supply control screen.
5.3.6History Events
Within the “History Events” screen a user can access the systems history
records/events. This screen is seen below:
Line 1: Displays the type of history event. History event types include but are not
limited to: fire alarm, trouble, supervision, CBE and Isolation. When “All Events”
is selected, detailed information will be provided for each event. If “All Events” is
not selected the user must select a particular event to view the additional and
detailed information.
Line 2: Displays the total number of events that can be reviewed.
Line 3: Displays the status of the current event. The operator may obtain detailed
information about the current event including location, type, time of occurrence,
serial number, as well as additional information from the following text box.
Line 4: Press 【Exit】 to exit the history event screen.
Pressing the【NEXT】key or the【PREV】key on main panel of the control panel,
a user can review the detailed description of the next or previous history event.
N-6000 can record and display up to 8000 individual history events.
Section 6:Miscellaneous
6.3Common Troubles
The N-6000 has advanced features such as self-diagnosis and self-protection; however even
with the advanced technology an occasional trouble signal is unavoidable. Table 5-1 has
additional information regarding common troubles.
Trouble Cause analysis Solution
Re-connect the AC220V
Poor AC220V connection
Main power supply power supply
trouble Fuse blowing out due to external
Replace the fuse
short circuit or over-current
LCD display fails Failure to regulate the luminance Regulate the luminance
6.5Out-of-box Audit
When opening the control panel box for the first time the user should carry out an out-of-box
audit to ensure the control panel is complete, untouched and undamaged from transportation.
The control panel should include: a CPU, loop card, MCU, POM-8A, MPS-350W,
complement keys and connecting wires, etc.
Open the control panel door to ensure all internal connections are normal and that there are no
loose connections, short circuits and/or disconnected items. Check the power supply status to
ensure it is normal and does not have any short circuits, etc.
Appendix A
Alarm level cross-reference table for the ND682 photoelectric smoke detector:
Actual physical threshold range of
Alarm level setting alarm
(Unit: 0.1 OBS%/FT)
LEVEL 1 0 -2.5
LEVEL 2 2.5 – 5
LEVEL 3 5 - 7.5
LEVEL 4 7.5 – 10
LEVEL 5 10 -14
LEVEL 6 14 – 16
LEVEL 7 16 -18
LEVEL 8 18 – 20
LEVEL 9 over 20
LEVEL 10 Over 20
Table 1: Alarm level cross-reference table for the ND682
The following is the trouble level cross-reference table for drift compensation:
Physical value of drift compensation
Alarm level setting
(Unit: 0.01%/ft)
LEVEL 1(Warning) 30
LEVEL 2(Warning) 60
LEVEL 3(Trouble) 90
Table 4: Alarm level cross-reference table for FSL-751
Limited Warranty
NOTIFIER® warrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, under
normal use and service. Products are date stamped at time of manufacture.
The sole and exclusive obligation of NOTIFIER® is to repair or replace, at its
option, free of charge for parts and labor, any part which is defective in
materials or workmanship under normal use and service. For products not
under NOTIFIER® manufacturing datestamp control, the warranty is eighteen
(18) months from date of original purchase by NOTIFIER® 's distributor
unless the installation instructions or catalog sets forth a shorter period, in
which case the shorter period shall apply. This warranty is void if the product
is altered, repaired or serviced by anyone other than NOTIFIER® or its
authorized distributors or if there is a failure to maintain the products and
systems in which they operate in a proper and workable manner. In case of
defect, secure a Return Material Authorization form from our customer
service department. Return product, transportation prepaid, to NOTIFIER®, 12
Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by NOTIFIER® with respect to
its products. NOTIFIER® does not represent that its products will prevent any
loss by fire or otherwise, or that its products will in all cases provide the
protection for which they are installed or intended. Buyer acknowledges that
NOTIFIER® is not an insurer and assumes no risk for loss or damages or the
cost of any inconvenience,
transportation, damage, misuse, abuse, accident or similar incident.
This warranty replaces all previous warranties and is the only warranty made
by NOTIFIER®. No increase or alteration, written or verbal, of the obligation of
this warranty is authorized.