Notifier Manual N6000

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 68

Fire Alarm Control Panel

N-6000
Manual

REV :A

DATE :2007-07-24
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

An automatic fire alarm system—typically made up of Detectors that have ionizing-type sensing chambers
smoke detectors, heat detectors, manual pull stations, tend to detect fast-flaming fires better than smoldering
audible warning devices, and a fire alarm control with fires. Because fires develop in different ways and are
remote notification capability—can provide early warning of often unpredictable in their growth, neither type of
a developing fire. Such a system, however, does not assure detector is necessarily best and a given type of detector
protection against property damage or loss of life resulting may not provide adequate warning of a fire.
from a fire. Smoke detectors cannot be expected to provide adequate
While fire alarm systems are designed to provide early warning of fires caused by arson, children playing with
warning against fire, they do not guarantee warning or matches (especially in bedrooms), smoking in bed, and
protection against fire. A fire alarm system may not provide violent explosions (caused by escaping gas,
timely or adequate warning, or simply may not function, for improper storage of flammable materials, etc.).
a variety of reasons: Heat detectors do not sense particles of combustion
Smoke detectors may not sense fire where smoke cannot and alarm only when heat on their sensors increases at
reach the detectors such as in chimneys, in or a predetermined rate or reaches a predetermined level.
behind walls, on roofs, or on the other side of closed Rate-of-rise heat detectors may be subject to reduced
doors. Smoke detectors also may not sense a fire on sensitivity over time. For this reason, the rate-of-rise
another level or floor of a building. feature of each detector should be tested at least once
Particles of combustion or “smoke” from a developing per year by a qualified fire protection specialist. Heat
fire may not reach the sensing chambers of smoke detectors are designed to protect property, not life.
detectors because:
• Barriers such as closed or partially closed doors, Smoke detectors must be installed in

walls, or chimneys may inhibit particle or smoke flow. the same room as the control panel. If detectors are not so
• Smoke particles may become “cold,” stratify, and not located, a developing fire may damage the alarm system,
reach the ceiling or upper walls where detectors are crippling its ability to report a fire.
located. Audible warning devices such as bells may not alert
• Smoke particles may be blown away from detectors people if these devices are located on the other side of
by air outlets. closed or partly open doors or are located on another
• Smoke particles may be drawn into air returns before floor of a building.
reaching the detector. A fire alarm system will not operate without any electrical
• The amount of “smoke” present may be insufficient to power. If AC power fails, the system will operate from
alarm smoke detectors. standby batteries only for a specified time and only if the
Smoke detectors are designed to alarm at various levels of batteries have been properly maintained and replaced
smoke density. If such density levels are not created by a regularly.
developing fire at the location of detectors, the detectors Equipment used in the system may not be technically
will not go into alarm. compatible with the control. It is essential to use only
Smoke detectors, even when working properly, have equipment listed for service with your control panel.
sensing limitations. Detectors that have photoelectronic Telephone lines needed to transmit alarm signals from
sensing chambers tend to detect smoldering fires better a premise to a central monitoring station may be out of
than flaming fires, which have little visible smoke. service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission
systems are recommended.

The most common cause of fire alarm malfunction is


inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance. A
maintenance agreement should be arranged through the
local manufacturer's representative. Maintenance should
be scheduled or as required by National and/or local fire
codes and should be performed by authorized professional
fire alarm installers only. Adequate written records of all
inspections should be kept.
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:

Verify that wire sizes are adequate for all initiating and
Several different sources of power can be indicating device loops. Most devices cannot tolerate more
connected to the fire alarm control panel. Disconnect all than a 10% I.R. drop from the specified device voltage.
sources of power before servicing. Control unit and Like all solid state electronic devices, this system may
associated equipment may be damaged by removing operate erratically or can be damaged when subjected to
and/or inserting cards, modules, or interconnecting cables lightning-induced transients. Although no system is
while the unit is energized. Do not attempt to install, service, completely immune from lightning transients and
or operate this unit until this manual is read and interferences, proper grounding will reduce susceptibility.
understood. Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning strikes.
System Reaccepting Test after Software Consult with the Technical Services Department if any
Changes. To ensure proper system operation, this product problems are anticipated or encountered.
must be tested after any programming operation or change Disconnect AC power and batteries prior to removing
in site-specific software. or inserting circuit boards. Failure to do so can damage
All components, circuits, system operations, or software circuits.
functions known to be affected by a change must be 100% Remove all electronic assemblies prior to any drilling,
tested. In addition, to ensure that other operations are not filing, reaming, or punching of the enclosure. When
inadvertently affected, at least 10% of initiating devices that possible,
are not directly affected by the change, up to a maximum of make all cable entries from the sides or rear. Before making
50 devices, must also be tested and proper system modifications, verify that they will not interfere with battery,
operation verified. transformer, and printed circuit board location.
Table of Content
Section 1:About This Manual ................................................................................................................. 6
1.1Notes, Cautions & Warnings......................................................................................................... 6
1.2Font Definition .............................................................................................................................. 6
Section 2:System Overview.................................................................................................................... 7
2.1Introduction ................................................................................................................................... 7
2.2Characteristics of the Product........................................................................................................ 7
Section 3:System Configuration & Installation ...................................................................................... 9
3.1Features Main Performances ......................................................................................................... 9
3.2Electrical Specifications ................................................................................................................ 9
3.3System Configuration.................................................................................................................... 9
3.4System Block Diagram................................................................................................................ 10
3.5Installation & Connection ........................................................................................................... 11
3.5.1Enclosures............................................................................................................................ 11
3.5.2Connection Requirements.................................................................................................... 12
3.5.3Connection of Circuit Board Terminals............................................................................... 12
3.5.3.1CPU Diagram ............................................................................................................... 12
3.5.3.2Power Supply Connection ............................................................................................ 15
3.5.3.3NIC-EC......................................................................................................................... 17
3.5.3.4Loop Control Module Connection................................................................................ 19
3.5.3.5MCU-16B Annunciator Control Module Connection .................................................. 21
3.6Equipment Debugging ............................................................................................................ 23
3.6.1Connection Inspection..................................................................................................... 23
3.6.2Power-on Inspection........................................................................................................ 24
3.6.3External Connection ........................................................................................................ 24
3.6.4Important Points .............................................................................................................. 24
3.6.5Inspection Methods for Addressable Device Connections.............................................. 25
Section 4:Operation .............................................................................................................................. 26
4.1LED Indicators and Keys ............................................................................................................ 26
4.1.1Control Panel Display LED Indicators and Keys ................................................................ 26
4.1.2Annunciator Control Module LED Indicators and Keys ..................................................... 29
4.2Power-on ..................................................................................................................................... 30
4.3System Self-test........................................................................................................................... 30
4.4Event Display .............................................................................................................................. 32
4.4.1Trouble Screen..................................................................................................................... 32
4.4.2Fire Alarm Screen................................................................................................................ 33
4.4.3Supervisory Screen .............................................................................................................. 34
4.4.4Point Disabled Screen.......................................................................................................... 35
4.4.5CBE Screen.......................................................................................................................... 36
4.4.6Pre-alarm Screen.................................................................................................................. 36
4.4.7Horn / strobe Screen ............................................................................................................ 37
4.4.8Feedback Screen .................................................................................................................. 37
Section 5:Programming ........................................................................................................................ 38
5.1Menu ....................................................................................................................................... 38
5.2System Management............................................................................................................... 40
5.2.1System setting ................................................................................................................. 41
5.2.2Password modification .................................................................................................... 42
5.2.3Main Reset....................................................................................................................... 43
5.3Device Configuration.............................................................................................................. 44
5.3.1Loop card......................................................................................................................... 45
5.3.1.1Parameter setting .......................................................................................................... 45
5.3.1.2Auto Programming ....................................................................................................... 47
5.3.1.3Point Programming....................................................................................................... 49
5.3.2Annunciator Control Module .......................................................................................... 50
5.3.2.1Parameter setting .......................................................................................................... 51
5.3.2.2Point Programming....................................................................................................... 51
5.3.3Remote Display ............................................................................................................... 52
5.3.3.1Parameter setting .......................................................................................................... 53
5.3.3.2Label Download ........................................................................................................... 53
5.3.3.3Point Programming....................................................................................................... 54
5.3.4CBE Programming............................................................................................................... 54
5.3.4.1General Zone ................................................................................................................ 55
5.3.4.2Logic Zone ................................................................................................................... 55
5.3.5Device Control..................................................................................................................... 56
5.3.5.1Manual Output.............................................................................................................. 57
5.3.5.2Status Tracking............................................................................................................. 58
5.3.5.3Walk Test ..................................................................................................................... 58
5.3.5.4Loop Drill..................................................................................................................... 60
5.3.5.5Power Supply Management.......................................................................................... 60
5.3.6History Events .......................................................................................................................... 61
Section 6:Miscellaneous ....................................................................................................................... 62
6.1Safety Protection Device ............................................................................................................. 62
6.2Usage and Maintenance............................................................................................................... 62
6.3Common Troubles....................................................................................................................... 62
6.4Transportation & Storage ............................................................................................................ 63
6.5Out-of-box Audit......................................................................................................................... 63
Appendix A........................................................................................................................................... 64
Section 1:About This Manual

1.1Notes, Cautions & Warnings


The following graphics appear in this manual to indicate a note, a caution, or
warning:

Note: Information that highlights an important part of the preceding or


subsequent text or illustration.

Cautions: Information about procedures that could cause programming


errors, runtime errors, or equipment damage.

Warnings: Indicates information about procedures that could cause


irreversible damage to the control panel, irreversible loss of programming data or
personal injury.

1.2Font Definition
Special font styles used in this manual are listed in Table 1-1, Specifications of
Manual Characters:
Font Meaning Example
Key on the control panel Press the key 【 Signals
【Bold】 Silenced】

Script Name of document N-6000 User Manual

Table 1-1 Specifications of Manual Characters


Section 2:System Overview

2.1Introduction
The N-6000 is a new generation intelligent fire alarm control panel recently
released by Notifier. This panel satisfies all related requirements defined in
GB4717-2005.
This control panel combines both alarm and CBE control functions. The N-6000
can also be programmed off-line when using a PC with Notifier Verifire Tools
(NVT).
The N-6000 fire alarm control panel has many intelligent characteristics; these
include but are not limited to drift compensation, sensitivity adjustment and
self-optimizing alarm.
The N-6000 control panel with CBE (control by event) control can manage both
alarm paging and gas extinguishing systems. The N-6000 connected with a CRT
display terminal forms a comprehensive and reliable fire alarm control system,
perfect for medium to large-scale facilities.

2.2Characteristics of the Product


y Large LCD Display
This system uses a large 320x240 pixel LCD display. To ensure accurate and
timely detection the LCD displays a full Chinese interface (up to 320 Chinese
characters), equipment type, location, alarm level, loop number and address
number upon alarming.
y User Friendly Interface
The Menu contains all programming options. Software supports both English and
Chinese input, full suggest and user friendly dialogue prompts. A user can
conveniently toggle between the alarm information and CBE information screens.
y Convenient Programming Options
Multilevel pre-alarm and alarm sensitivity enable localizing detector sensitivity for
different applications. Have the function of trouble disenable also can choose to
disenable any addressing unit in loop bus. Auto programming allows the N-6000
to “learn” what devices are physically connected and automatically load them in
the program with default values for all parameters. The functions mentioned above
significantly ease system operation while reducing daily maintenance.
y Real-time Analogue Display Curve
Real-time threshold value variation monitoring is possible for both intelligent
analogue detectors and/or compound detectors.
y Powerful CBE Equations
y Accurate and Detailed Event Records
The system automatically and categorically stores and records the latest fire alarm,
trouble or system event. It can display and store up to 8000 historical events.
y Automatic Compensation Functions
Drift compensation allows the detector to retain its original ability to detect actual
smoke, and resist false alarms, even as dirt or dust accumulates. It reduces
maintenance requirements by allowing the system to automatically perform
periodic sensitivity measurements. Smoothing filters are also provided by software
to remove transient noise signals, usually caused by electrical interference.
y Printing Settings
The system can be networked and prompted to print the latest alarm event using a
Chinese printer.
y Equipped With 8 Bus Control Modules.
Built-in Degraded Mode option. In the event of a CPU failure, the system is
capable of general alarm if a fire condition is present.
y Off-line Programming and CRT display terminal
Connected with PC through the RS-232 interface, Screen of the control panel to
realize programming setting on circuit configuration, CBE control relation of the
control panel. Also can be connected with NCS through this Screen to carry out
centralized management.
Section 3:System Configuration &
Installation

3.1Features Main Performances


y Supports 1 to 30 Signaling Line Circuits (SLCs). Up to 199 detectors and 99
modules (N.O. manual stations, two-wire smoke, notification or relay) per
SLC
y Loop connection ports available, expandable up to 15 loop circuit cards
y Supports up to 64 remote LCD displays
y Supports up to 32 MCU control card
y Micro printer port
y N-CRT port provided - seamless connection to a third party system
y Fire alarm output and trouble output relays
y Real-time clock

3.2Electrical Specifications
y Voltage range
ƒ Input voltage: 220 VAC
ƒ Output voltage:
ƒ Two – 24 VDC non-resetable outputs
ƒ One – 24 VDC resetable output
ƒ Two – 5 VDC outputs
ƒ Several dry contacts - power supply trouble relay output
y Maximum output current: 14.6A

3.3System Configuration
y Intelligent control panel: N-6000
y Remote display: LCD-100B, LDM-64B
y Intelligent detectors:
ƒ Intelligent photoelectric smoke detector: ND-751P
ƒ Intelligent heat detector: ND-751T
ƒ Intelligent laser smoke detector: FSL-751
ƒ Intelligent smoke detector: FSB-200S
y Intelligent base:
ƒ B601
ƒ B501
y Intelligent modules:
ƒ Intelligent monitor module: MMX-7
ƒ Intelligent monitor/control module: CMX-7
ƒ Intelligent control module: CMX-7C
ƒ Monitor module for two-wire 24 VDC conventional detectors:
MMX-7P
ƒ Isolator: ISO-7
ƒ Intelligent manual call point: M500K
ƒ Intelligent manual call point: M700K
y Micro printer: uPRT-380S
y Chinese graphic and text management software: N-NCS, N-VFT

3.4System Block Diagram

Fig. 3-1 System Block Diagram

If there are many addressable units in the loop bus, user should install the
shortcut isolator in front of the loop bus. The addressable units are less than 25
units between adjacent two isolators.
3.5Installation & Connection

3.5.1Enclosures
Wall-mount designs use a standard NOTIFIER® C-type cabinet. This cabinet is
shown in Fig. 3-2 Cabinet Appearance:

Fig. 3-2 Cabinet Appearance

Detailed cabinet dimensions are shown in Fig. 3-3:

Fig. 3-3 C-type Cabinet Dimension Diagram

All NOTIFIER cabinets are fabricated from 16-gauge steel. The cabinet assembly
consists of two basic parts: a backbox and a locking door. The backbox has been
engineered to provide ease-of-entry for the installer. Knockouts are positioned at
numerous points to aid the installer in bringing a conduit into the enclosure.

3.5.2Connection Requirements
y All incoming/outgoing external conduits should use the control panel cabinet’s
bottom knockout or opening for terminal connections.
y Loop transmission line adopts twisted shielded pair cable, the type and
specification are: RVSP-2×1.5mm2
y Loop resistance (refers to loop resistance between the machine and two leads of
the farthest addressing unit) should be less than 50 Ω.
y Power wiring should use two-color multiple plastic cable, red for male terminal,
black for female terminal. The type and specification are: RV-2×2.5mm2

3.5.3Connection of Circuit Board


Terminals

3.5.3.1CPU Diagram
Control panel includes in a circuit board, it has CPU and extend device interface.
You can order the board supports for 8, 16, 30 loops. The connections terminals,
jumper and status lights are showed below:
Fig. 3-4 CPU Diagram

Connections terminal illuminate table:


Terminal Illumination
TB1 System Event Relay1,programmable;Default is fire alarm trigger
TB2 System Event Relay12,programmable;Default is trouble trigger
TB3 System Event Relay13,programmable;Default is reset trigger
TB4 24VDCPower
TB5 RS-232 Micro printer port
TB6 RS-232 NIC port
TB7 N-CRT Port(VFT、third party system)
TB8 RPT port
TB9 Loop communication port
TB10 Extended device port(MCU/POM-8C/MPS)
J10 Loudspeaker ,see J15
J13 Power, loop and extended device channel aggregate terminal
J15 Buzzer; user can select J10 or J15 to be system sound component
Table 3-1 CPU-6000 Board Terminal Illuminate
Jumper illuminate table:
Terminal Illumination
JP2 System Event Relay 1,output selection ,24Vor trunk node
JP3 System Event Relay 2,output selection ,24Vor trunk node
JP5 System Event Relay 3,output selection ,24Vor trunk node
JP9 ISP program write down jumper, user should cover jumper cap when
ISP upgrade program
JP18 Loop RS485 communication match terminal resistance selection
jumper
JP19 Loop RS485 communication match terminal capacitance selection
jumper
JP21 Extended device RS485 communication match terminal resistance
selection jumper
JP22 Extended device RS485 communication match terminal capacitance
selection jumper
JP23 RPT RS485 communication match terminal resistance selection
jumper
JP24 RPT RS485 communication match terminal capacitance selection
jumper
Table 3-2 CPU-6000 Board Jumper Illuminate
LED status illuminate table:
Terminal Illumination
LED1 System status normal;Green
LED2 System fire alarm and CBE event;Red
LED3 System trouble event;Yellow
LED4 System supervise event;Blue
LED5 Relay1;relay close is green
LED6 Relay2;relay close is green
LED7 Relay3;relay close is green
LED8 24VDC;Green
LED9 5VDC;Green
LED10 Micro printer channel signal send; signal on is green
LED11 N-CRT protocol channel signal send; signal on is green
LED12 Micro printer channel signal receive; signal on is green
LED13 N-CRT protocol channel signal receive; signal on is green
LED15 RPT channel signal receive; signal on is green
LED17 RPT channel signal send; signal on is green
LED18 Extended device channel signal receive; signal on is green
LED19 Loop channel signal receive; signal on is green
LED20 Extended device channel signal send; signal on is green
LED21 Loop channel signal send; signal on is green
Table 3-3 CPU-6000 Status Light Illumination

3.5.3.2Power Supply Connection


The N-6000 fire alarm control panel is powered by the MPS-350W power supply
module. This power module provides multi-path 24 VDC and 5 VDC outputs.
During a power loss the MPS-350W battery will automatically engage and provide
power. LED displays indicate the status of multiple functions, including: main
power trouble, reserve power trouble, grounding trouble, storage battery charging
trouble and power supply relay output trouble.
Refer to the MPS-350W user manual for additional information regarding function,
connection and/or application of the MPS-350W power supply.

Fig. 3-5 Power Supply Connection Diagram

Connections terminal illuminate table:


Terminal Illumination
TB1 Non-resetable 24VDC terminal
TB2 Non-resetable 24VDC terminal
TB3 Resetable 24VDC terminal
TB4 Non-resetable 24VDC terminal
TB5 Non-resetable 24VDC terminal
TB12 Trouble relay trunk node terminal
TB13 RS-485 serial communication port terminal
TB14 Extended system supervise signal terminal
Table 3-4 MPS-350 Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1 Program jumper, user can not change
JP2 RS-485 bus terminal match capacitance
JP3 RS-485bus terminal match resistance
JP4/ JP5 Earth trouble function enable, disable
Table 3-5 MPS-350 Jumper Illumination
LED status illuminate table:
LED Illumination
LED1 Non-resetable 24VDC fuse melt indication
LED2 Non-resetable 24VDC fuse melt indication
LED3 Resetable 24VDC fuse melt indication
LED13 Non-resetable 5VDC fuse melt indication
LED19 Non-resetable 5VDC fuse melt indication
LED23 Battery cut protect indication
LED24 Battery fuse melt indication
LED25 Power normal indication
LED26 Power trouble indication
LED27 Battery normal indication
LED28 Battery trouble indication
LED29 System running indication
LED30 Earth trouble indication
Table 3-6 MPS-350 Status Light Illumination
3.5.3.3NIC-EC
When N-6000 connect into N-NET fire alarm network, each control panel must
install a NIC-EC card. Connection terminal, jumper and indicative show as below:

Fig. 3-6 NIC-EC Connection Diagram

Connections terminal illuminate table:


Terminal Illumination
TB1 Network port A
TB2 24VDC power port
TB3 NIC-EC and CPU-6000 communication port(RS232)
TB5 Network port A
Table 3-7 NIC-EC Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP6 RS232 mode(leave factory set, not to change)
JP7 Open (leave factory set, not to change)
JP8 Open (leave factory set, not to change)
JP9 RS232 mode(leave factory set, not to change)
Table 3-8 NIC-EC Jumper Illumination
LED status illuminate table:
Blink when signal output
LED1 Green Port B signal output
otherwise off
Blink when signal input
LED2 Green Port B signal input
otherwise off
Status overturn after send or
Port B information
LED23 Green receive a frame information
status
correctly
LED on when send or receive a
LED24 Yellow Port B trouble frame information wrongly or
check out communication error
LED25 Red Port B circuit trouble LED on when any trouble occur
Blink when signal output
LED3 Green Port A signal output
otherwise off
Blink when signal input
LED4 Green Port A signal input
otherwise off
Status overturn after send or
Port A information
LED20 Green receive a frame information
status
correctly
LED on when send or receive a
LED21 Yellow Port A trouble frame information wrongly or
check out communication error
LED22 Red Port A circuit trouble LED on when any trouble occur
System running
LED5 Green Blink when running normally
indication
Control panel type LED on when connect to
LED6 Yellow
indication CPU-6000
Control panel type
LED7 Red LED on when connect to N-NCS
indication
+24V power status LED on when +24V power
LED8 Green
light supply normally
+5V power status LED on when +5V power supply
LED9 Green
light normally
TB3 port signal Blink when signal input
LED10 Green
input otherwise off
J9 signal input Blink when signal input
LED11 Green
indication otherwise off
TB3 port signal Blink when signal output
LED12 Green
output otherwise off
J9 signal output Blink when signal output
LED13 Green
indication otherwise off
LED14 Green Function reserve —
LED15 Green Function reserve —
LED16 Red Function reserve —
TB3 port Status overturn after send or
LED17 Green
information receive a frame information
correctly
LED on when receive
LED18 Yellow TB3 port trouble
information error
TB3 port circuit LED on when receive
LED19 Red
trouble information error
LED26 Blue Function reserve —
Table 3-9 NIC-EC Indicative Light Illumination
DIP switch network address setting table:
SW2 status Function
ON
1
OFF
ON
2 1~6bits switch
OFF
ON for 1,OFF for 0
ON
3 Composing a 6 bits binary number,
OFF
this number infer network card
ON address. Network card address
4 range is the number between 0~63.
OFF
Network card address must be same
ON
5 as the connect device’s address.
OFF
ON
6
OFF
ON Relay mode
7
OFF Bus mode
ON N-NCS
8
OFF CPU-6000
Table 3-10 NIC-EC Address Setting

3.5.3.4Loop Control Module Connection


N-6000 support 15 LCM-2 cards, and 30 loops. LCM-2 support style 4 or T-type
wiring. TB2 in LCM-2 board connect to CUP-6000 interface, the rest connect each
other. LCM-2 can connect with twisted shielded pair cable: signal connect to TB2,
power connect to TB3; also can connect each other through J2 and J4.
Fig. 3-7 Loop Control Module Connection Diagram

Connection terminal illuminate table:


Terminal Illumination
TB2 Connect to CPU-6000(RS485),also can connect to LCM card
TB3 24VDC power port
TB4 Loop 1 port(the loop number is SW1’s value)
TB5 Loop 2 port(the loop number is SW1’s value+1)
J2 Interlink port
J4 Interlink port
Table 3-11 LCM-2 Card Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1 Communication to CPU-6000 port terminal resistance (normal open)
JP2 Communication to CPU-6000 port terminal capacitance (normal
open)
JP4 Switch to RS232 mode(leave factory set, not to change)
JP5 Switch to RS232 mode(leave factory set, not to change)
Table 3-12 LCM-2 Card Jumper Illumination
LED Status Illuminate table:
Terminal Illumination
LED1 3.3V system power supply indication
LED2 24 V system power supply indication
LED3 5 V system power supply indication
LED4 CPU-6000 communication/LCM card local mode indecation
LED5 Loop 1 running indication
LED6 Loop 1 trouble indication
LED7 Loop 1 fire alarm indication
LED8 Loop 2 running indication
LED9 Loop 2 trouble indication
LED10 Loop 2 fire alarm indication
LED11 Communication to CPU-6000send indication
LED12 Communication to CPU-6000send indication
Table 3-13 LCM-2 Card Status Light Illumination
DIP Switch Loop Number Setting table:
SW1~8 1~8bits switch
ON for 1,OFF for 0
Composing a 8 bits binary number, infer LCM card
address. SW1 setting range is the odd number between
1~29
Table 3-14 LCM-2 Loop Number Setting

3.5.3.5MCU-16B Annunciator Control Module


Connection
N-6000 can connect MCU-16B. Support the manual control to output point of
control module, and use LED to show the status of controlled points.
MCU-16B includes 16 output indicative light, 16 feedback statuses light, 16 button
to manual control, a complex function button, a enable/disable button and a
manual/auto status light.
Each manual control module can be programmed to any control module. Each
feedback statuses light can be programmed to control an input device.
Enable/disable button use to enable or disable 16 manual control buttons.
MCU-16B connects to N-6000 by RS-485 port, this port can support 32
MCU-16B.
Fig. 3-8 Annunciator Control Module Connection Diagram

Connection terminal illuminate table:


Terminal Illumination
TB1 24VDC power port
TB2 Connect to CPU-6000(RS485)
J1 Interlink port
J3 Interlink port
Table 3-15 MCU-16B Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1 Open(leave factory set, not to change)
JP2 Communication to CPU-6000 port terminal resistance (normal
open)
JP3 Communication to CPU-6000 port terminal capacitance (normal
open)
JP4 Switch to RS232 mode(leave factory set, not to change)
JP5 Switch to RS232 mode(leave factory set, not to change)
JP6 Buzzer switch(default shortcut, enable)
Table 3-16 MCU-16B Jumper Illumination
LED Status Illuminate table:
Terminal Illumination
LED1 24 V system power supply indication
LED2 5 V system power supply indication
LED3 3.3 V system power supply indication
LED4 System running indication
LED39 Communication to CPU-6000send indication
LED40 Communication to CPU-6000send indication
Table 3-17 MCU-16B Status Light Illumination
DIP Switch Loop Number Setting table:
SW2 status function
ON
1
OFF
ON
2 1~8bits switch
OFF
ON for 1,OFF for 0
ON
3 Composing a 5 bits binary number, this
OFF number +1 infer MCU’s address.
ON MCU’s address range is the number
4 between 1~29
OFF
ON
5
OFF
ON
6 NONE
OFF
ON
7 NONE
OFF
8 ON NONE
Table 3-18 MCU-16B Network address setting

3.6Equipment Debugging

3.6.1Connection Inspection
y Visually inspect the control panel condition
y Visually inspect the external connection ports
y Open the control panel and visually inspect all connections. Confirm connections
are correct, that there are no loose connections, no short circuits, unplugged or
disconnected connectors as well as confirm the power supply does not have
any short circuit trouble.
y Visually inspect the jumpers in the circuit to confirm there are no duplicate
numbers.

3.6.2Power-on Inspection
After you have finished the visual inspection, power-on the battery power supply.
With the battery started a buzzer should be heard and the LCD should temporarily
function normally. Once the control panel enters normal operation status, a buzzer
and LED horn/strobe will indicate a troubled status because main power is not
connected. Power-down and disconnect the battery power supply then connect and
power on the main power supply. Once the control panel enters normal operation
status, a buzzer and LED horn/strobe will indicate a troubled status because the
battery power supply is not connected. At this time, connect the battery power
supply. Soon after the control panel will return to normal operating status.
During normal operation, if both the main and battery power supplies are
connected the power supply status lamp (on the main panel of the control panel)
will maintain normal illumination.
When the main power supply fails because of loss of power, poor power
connection, an over-voltage or under-voltage of 5V and 24V, or a short circuit with
rack earth and communication trouble with the mainframe, the power supply status
lamp (on main panel of the control panel) illumination will stop. Then both a
buzzer and LED horn/strobe will indicate a troubled status while additional
information will be shown on the control panel LCD.

3.6.3External Connection
Look for any short-circuits or disconnections to and from the control panel. Once
everything has been inspected, connect the control panel.
Batch installation -- connecting 10-20 detectors or modules on the loop per time --
is highly recommended. After installing the detectors or modules restart the control
panel to ensure the newly installed devices are recognized and installed correctly.
If the control panel gives a trouble signal recheck the circuit and addressable
devices are installed properly. Once the trouble signal has been solved, continue
batch installation and power testing. After all the devices have been installed, the
simulated trouble, fire alarm and CBE event functions maybe tested. Confirm that
the control panel alarms normally, properly links field equipment and accurately
prints corresponding alarm information. Continue testing and adjusting until panel
maintains normal operating status.

3.6.4Important Points
y Avoid touching the circuit board IC chip during installation
y Pay attention to polarity during connection and installation
y Before starting the system, check for short circuits, disconnection or reverse
polarity
y Connectors among leads shall be wielded and inter-line insulation shall be
guaranteed.

3.6.5Inspection Methods for Addressable Device


Connections
To test the function of the multi-meter, connect the loop in reverse polarity (the
positive pole connects with the loop negative and the negative pole connects with
the loop positive). The multi-meter should indicate a bias value for the diode.
Then connect the multi-meter normally (positive pole connects with the loop
positive and negative pole connects with the loop negative). The multi-meter
should indicate a low resistance value that increases with the charging of the loop
capacitor. If after proper polarity connection the multi-meter still indicates a bias
value for the diode, there is one or more addressable device(s) connected in reverse
polarity.
Section 4:Operation

4.1LED Indicators and Keys

4.1.1Control Panel Display LED


Indicators and Keys
The N-6000 is an intelligent addressable Fire Alarm Control Panel (FACP) with
advanced features ideal for a variety of applications. The CPU-6000 includes a
front display/keypad enabling localized control panel viewing and programming.
The display/keypad provides an easy-to-use keypad and large LCD (liquid crystal
display) that simplifies the programming process.
The display is 53 characters wide by 20 lines long and displays all programming
screens. These include the events, history, devices as well as other additional
information.
Fields may be entered or changed and commands may be issued using the display
keypad.

Fig. 4-1 Display/Keypad Diagram


• LED Lamp Status
LED Indicator Color Functions
Fire alarm Red Illuminates when at least one fire alarm event exists. It will
flash if any of these events are unacknowledged.
Pre-alarm Red Illuminates when at least one pre-alarm event exists. It will
flash if any of these events are unacknowledged.
Trouble Yellow Illuminates when at least one trouble event exists. It will flash
if any of these events are unacknowledged.
Power Green Indicates current status of the power supply. During normal
communication with the power supply, the lamp will flash.
Self-test Yellow Indicates the system is in self-test status. The LED will
remain lit during the self-test.
CBE Red I/O module is functioning properly or there is a feedback
signal.
Delay Red If the control panel has a delayed control output the LED will
remain illuminated throughout the delay period. It will turn
off upon termination of the delay period.
Signal Silenced Yellow Illuminates if NFS-3030 Notification Appliances have been
silenced. It flashes if some but not all of the N-6000 NACs
have been silenced.
Point Disabled Yellow Illuminates when at least one device has been disabled. It will
flash until all disabled points have been acknowledged.
Supervisory Red Illuminates when at least one supervisory event exists. It will
flash if any of these events are unacknowledged.
CPU Failure Yellow Illuminates if there is an abnormal hardware or software
condition. Contact technical support. The panel is out of
service when this LED is illuminated or flashing.
Table 4-1 LED Indicator Description
• Operation Keys:
ƒ 【A-a】: Caps lock key
ƒ 【Space】: During programming, change the status of the check box
to and change back to when finished
ƒ 【Backspace】 : Backspace key
ƒ 【Menu】 : Press to enter the menu
ƒ 【Help】 : Help key
ƒ 【PREV】 / 【NEXT】: Press to skip to the previous/next control screen
ƒ 【ESC】 : Escape key
ƒ 【Enter】: Key to acknowledge input
ƒ 【TAB】 : Switch key, same as the 【NEXT】 key
ƒ 【<】 / 【>】 : Previous page/next page
ƒ 【△】 / 【▽】 : Previous event/next event
• Fixed Function Keys:
ƒ 【Acknowledge】: Acknowledge event operation
ƒ 【Signals Silenced】:
1. Press for less than 1 second: carries out silencing operation on
peripheral equipment
2. Press for longer than 1 second: system exercise (please refer to
relevant topics under loop card setting)
ƒ 【Fire alarm/Pre-alarm】:
1. Press for less than 1 second: query fire alarm event
2. Press for longer than 1 second: query pre-alarm event
ƒ 【Trouble/ Horn / Strobe】: Carry out query operation during trouble
event
1. Press for less than 1 second: query trouble event
2. Press for longer than 1 second: query horn/strobe event
ƒ 【Supervision/Feedback】: Carry out query operation on supervision
event
1. Press for less than 1 second: query supervision event
2. Press for longer than 1 second: query feedback event
ƒ 【CBE/Delay】:
1. Press for less than 1 second: query CBE event information
2. Press for longer than 1 second: query the logic zone in delay status
with a logic value of TRUE
ƒ 【Manual/Automatic】: Control manual/automatic execution link
ƒ 【Lamp inspection/Self-test】: System lamp inspection/self-test
ƒ 【Reset】 : Reset system operation
4.1.2Annunciator Control Module LED
Indicators and Keys

Fig. 4-2 Bus Control Module Schematic Diagram

The annunciator control module has a total of 32 indicating lamps, 16 keys and 16
feedback signals.
• One composite button: Time function key has 3 functions
1、Press for about 1 second: LED lamp below the key will illuminate locking the
control key module
2、Press for more than 1 second: LED lamp on the right side of the key will
illuminate with manual/automatic allowed
3、Press for more than 4 seconds: horn/strobe self-test
• No. 1-16 Start Keys:
-Press a key and the corresponding feedback signal a (Lamp 1-16) flash, which
means corresponding key has been pressed.
-When a feedback indicating lamp (Lamp 1-16) flashes, it indicates that an
operational signal from CBE equipment has been received and the
corresponding CBE equipment will be started.

4.2Power-on
Connect 220V AC power, and then turn on the main power supply using the switch
inside the cabinet. Power-on Screen is shown in Fig. 4-4:

Fig.4-3 Power-on Screen

4.3System Self-test

Fig. 4-4 System Self-test Screen

After the N-6000 has been turned on, it will self-test both the hardware and
software of the system. During the self-test all LED indicating lamps on the left
side of the mainframe panel will flash. Once the self-test has finished a buzzer will
sound and LEDs will temporarily illuminate after which the panel will return to a
normal operation status. Additionally, the system will show the display screen
while the power supply indicating lamp continues to flash.
After a self-test, the system will show the following screen:

Fig. 4-5 Normal System Screen

The normal system screen is divided into three bars; these include the event
statistics bar, the alarm screen bar and the status bar. The event statistics bar shows
fire alarms, trouble alarms, supervision, CBE and point disabled locations. The
status bar shows the node number, manual/automatic status, transmission
equipment status, main or reserved power supply status, the current date/delay
status of the latest logic zone as well as the current time.
①Manual/Automatic Status
——System in manual status

——System in automatic status

②Transmission Equipment Status


——Both delivery and feedback
——Transmission equipment in delivery status
——Transmission equipment in feedback status
——Transmission equipment in normal status without delivery or feedback
——Transmission equipment in Point disabled status
——Transmission equipment in trouble status
③Operation Status of the Main or Reserved Power Supply
——Main power normal
——Low voltage in main power
——Trouble in main power
——Battery normal
——Low voltage in battery
——Battery disconnected
Current date/delay status of the latest logic zone, this item can show the current
date. When CBE appears, it will also show delay status information of the latest
logic zone. For example: , where “ZL0099” means logic zone
number 99 and “00001” means that CBE will output after a 1 second delay.

4.4Event Display
• Event Order:
First: Fire alarm, CBE, feedback
Second: Supervision
Third: Trouble
Fourth: Point Disabled - disabled

4.4.1Trouble Screen

Fig. 4-6 Trouble Screen

When the control panel detects a failing power supply or other trouble, it will
execute a series of operations:
• A trouble relay will be activated and the control panel will alarm
• A system trouble indicating lamp on the control panel display will flash and the
LCD will show a trouble screen
• Detailed trouble type will show the exact geographic location and occurrence
time on the LCD
• A trouble event will be saved to the native Flash ROM and the printer will print a
record of the trouble event
Press the 【△】 key or the 【▽】 key on the main panel to review the previous or
next trouble event and press the【<】key or the【>】key to page up or down. Press
【ACK】 key on the main panel to acknowledge, and all trouble events will be
shown one by one. Once the alarm has silenced and all trouble events have been
acknowledged, the system trouble indicating lamp on the main panel will return to
its normal illumination.
The most common trouble events include but are not limited to: equipment off-line,
grounding the equipment’s positive terminal, grounding the equipment’s negative
terminal, the equipment’s positive terminal is disconnected, the equipment’s
negative terminal is disconnected, power supply shows low voltage, power supply
shows high voltage, unmatched load types, low threshold values, database errors.

4.4.2Fire Alarm Screen

Fig. 4-7 Fire Alarm Screen

When a detector or monitoring module is activated (fire alarm detected), the


control panel will execute a series of operations:
• A system alarm relay will be activated and the control panel will alarm
• A fire alarm indicating lamp on control panel display will flash and the LCD will
show a fire alarm screen.
• Detailed fire alarm name will show the exact geographic location and occurrence
time on the LCD.
• Alarm information will be saved to the native Flash and the printer will print a
record of the alarm event.
Press the 【△】 key or the 【▽】 key on main panel to review the previous or next
fire alarm event and press the 【<】 key or the 【>】 key to page up or down. Press
the 【OK】 key on main panel to acknowledge, and all fire alarm events will be
shown one by one. Once the alarm has silenced and all fire alarm events have been
acknowledged, the system fire alarm indicating lamp on the main panel will return
to its normal illumination.

4.4.3Supervisory Screen

Fig. 4-8 Supervision Screen

The monitoring modules produce monitoring style codes. Once a monitoring


module has been activated, the control panel will execute a series of operations:
• A monitoring relay will be activated and the control panel will alarm
• A supervision indicating lamp on the control panel will flash and the display will
show the supervision screen
• Monitoring information will be saved to the native Flash and the printer will print
a record of the supervision event
Press the 【△】 key or the 【▽】 key on main panel review the previous or next
fire alarm event and press the 【<】 key or the 【>】 key to page up or down. Press
the【OK】key on main panel to acknowledge all supervision information has been
shown. Once the alarm has silenced and all the supervision events have been
acknowledged, the supervision indicating lamp on the main panel will return to its
normal illumination.
4.4.4Point Disabled Screen

Fig. 4-9 Point Disabled Screen

When a point disabled location exists in a loop, each disabled point (detector,
module, and loop) will be shown one by one (see Fig. 4-10). The control panel will
execute a series of operations:
• A point disabled indicating lamp on the control panel will flash but the control
panel will not alarm
• A point disabled indicating lamp will be illuminated
• The point disabled information will be saved to the native Flash and the printer
will print the current point disabled information
Press the 【△】 key or the 【▽】 key on main panel of the control panel to review
the previous or next point disabled event and press the 【<】 key or the 【>】 key
to page up or down. Press 【OK】 key on main panel of the control panel to
acknowledge all Point disabled information has been shown. Once the alarm has
silenced and all point disabled events have been acknowledged, the point disabled
indicating lamp on the main panel will return to its normal illumination.
4.4.5CBE Screen

Fig. 4-10 CBE Screen

4.4.6Pre-alarm Screen
To enter the pre-alarm screen and also query the pre-alarm screen keep pressing the
【Fire alarm/Pre-alarm】composite key on the main panel. The pre-alarm screen is
shown below:

Fig. 4-11 Pre-alarm Screen


4.4.7Horn / strobe Screen
To enter the horn/strobe screen and also query the horn/strobe screen keep pressing
the 【Trouble/Horn/Strobe】 composite key on the main panel. The horn/strobe
screen is shown below:

Fig. 4-12 Horn/Strobe Screen

4.4.8Feedback Screen
To enter the supervision/feedback screen and also query the supervision/feedback
screen keep pressing the【Supervision/Feedback】composite key on the main panel.
The supervision/feedback screen is shown below:

Fig. 4-13 Feedback Screen


Section 5:Programming

5.1Menu
System Setting

System Management Modify Password

Main Reset

Setting

LCM Auto Programming

Point Programming

Setting
DCU
Point Programming
Device Configuration

Setting
MCU
Point Programming

Menu Setting

Remote Display Download Labels

Point Programming

General Zone
CBE Programming
Logic Zone

Manual Output

Status Track
Device Control
Status Track

Walk Test

Power Management

History Event

Fig. 5-1 N-6000 Schematic Menu Diagram


When programming the control panel or reviewing history events, press the
【Menu】 key to view the following screen:

Fig. 5-2 User Login Screen

Once a user has entered the correct password, he/she will enter the main menu and
view the following screen. In the main menu screen, he/she can update or change
the system management, device configuration, CBE programming, device control
and history events.

Fig. 5-3 Main Menu Screen

5.2System Management
Under “System management” the operator has 3 options; (1) System setting, (2)
Modify Password, or (3) Main Reset. The system management screen is shown as
follows:
Fig. 5-4 System Management Screen

5.2.1System setting
Under “System Setting” the following screen will be shown:

Fig. 5-5 System Setting Screen

Line 1: The node is the control panel’s address within the network while the label is
a description of the control panel
Line 2: If “ (YES)” is selected for the time server option, then this control panel is
the time master within the network and all other panels will synchronous
accordingly. Click the button “time & date” to set the time and date of the control
panel
Line 3: Language—determines the language of the control panel display. At
present two languages are currently available: Chinese and English
Line 4: Backlight—the duration of time the LED display remains lit. There are four
choices available: Normal Open, Normal Close, Off in 30 Seconds and No Display.
Line 5 to Line 7: Relays—there are 3 relays each with 7 operational modes:
① Disabled—the relay is disabled
② Fire alarm output—the relay will close upon fire alarm
③ Trouble output—the relay will close during trouble status
④ CBE—the relay will close during CBE
⑤ Supervision—the relay will close during supervision
⑥ CBE logic output—the relay will only be used in CBE output expression.
When the value of located expression is true, the relay will close and re-open in
the opposite condition
⑦ Reset output—the relay will close during normal operation or when the system
is being reset.
Line 8& Line 9: COM—2 serial ports each with 4 operational modes:
Degradation CBE: “ (YES)”/ “ (NO).” The default status “ (YES)” is
Normal Open. Degradation CBE only works when enabled
Fire Alarm Verification: “ (YES)”/ “ (NO).” The default status is “ (YES).”
This function has a time sensitive fire alarm, ensuring an alarmed status will be
accurate. This setting can greatly reduce false alarms and improve system
efficiency
Failover: “ (YES)”/ “ (NO).” The default status is “ (NO).” Failover is the
trouble display switch for the whole control panel. If “ (YES)” is chosen, all
trouble signals will be disabled without any display or alarm although a history
record is still maintained
Main Power Supply: “ (YES)”/ “ (NO).” The default status is “ (YES),”
which installs the main power supply for the control panel
Reserved Power Supply: “ (YES)”/ “ (NO).” The default status is “ (YES),”
which installs the reserved power supply for the control panel
Reset Verification: “ (YES)”/ “ (NO).” The default status is “ (NO).” If “
(YES)” is chosen, a password needs to be entered before resetting. If “ (NO)” is
chosen, a password does not need to be entered before resetting

5.2.2Password modification
Under “Password modification,” a user can modify his/her password according to
their system status (Admin, Engineer, or Guest). The password modification screen
is shown below:
Fig. 5-6 Password Modification Screen

The N-6000 has 3 different user levels, each level is password protected. The three
levels are (ordered from highest to lowest) Administrator, Engineer and User. Each
level has its own password. The Administrator user can modify any password in
the system (including the Administrator level). The User can only operate on the
4th setting, “Device Control” and the 5th setting, “History event.” The Engineer
can operate all five settings in the menu but will be interrupted (exit programming)
when an alarm event occurs. The Administrator can operate all five settings in the
menu and will not be interrupted during an alarm event.
Factory default passwords are as follows: 333333 for Administrator, 222222 for
Engineer and 111111 for User.
After the initial login the user will enter the password modification screen. He/she
can change the password by entering a new password in the “Enter new password”
dialogue box and then re-entering the new password in the “Confirm new
password” dialogue box. Once the system has confirmed the two passwords are the
same, the user should press 【OK】 to confirm the password change. After the user
has pressed 【OK】 the password will be successfully modified, to cancel the
previous operation press the 【Cancel】 button.
Note: If an incorrect password is entered, the system will show another dialogue
box requesting the correct password be entered.

5.2.3Main Reset
In the “System Setting” screen choose “Main Reset” to reset the system to all
default factory settings.
Fig. 5-7 Main Reset Screen

After the correct Administrator password has been entered, a dialogue box will
prompt to verify the “Main Reset” choice. Press “OK” to confirm the reset and
restore default factory settings. Press “Cancel” to cancel the operation and exit the
screen.

5.3Device Configuration
Choose the “Device Configuration” screen to adjust the settings of the loop cards,
multi-line control modules, annunciator control modules and repeaters. Screen
shown below:
Fig. 5-8 Device Configuration Screen

5.3.1Loop card
In the “Device Configuration” screen, choose the “LCM” option to enter the screen
shown below in Fig. 4-23:

Fig. 5-9 Loop Card Screen

5.3.1.1Parameter setting
In the “LCM” screen, to adjust the settings and program options, choose “Setting,”
“Auto Programming,” or “Point programming.” The screen is shown in Fig. 4-24:
Fig. 5-10 Parameter Setting Screen

Line 1: LCM- Loop number.


Line 2: Name- Loop Description
Line 3: Installation status – these include: Uninstalled, Normal, and Disabled.
Line 4: Time Rapid Polling - the number of preferential in-process checks, the
default value is 0. This option controls both the point and card level settings. The
card level setting determines the preferential times while the point level setting
determines whether the point needs the preferential in-process check. The loop
card will carry out preferential in-process checks on the load points where
“Preferential in-process check” has been activated.
Line 5: Style 4 Wiring - “ (YES)”/ “ (NO).” The system default status is
“ (YES).” Using style 4 wiring the circuit status can be monitored through the
ring circuit line voltage. The system will detect differences between the positive
and negative circuits to monitor if a disconnection trouble within the loop occurs. If
the wiring connection does not use style 4 configuration, the mainframe will report
a disconnection trouble.
Line 6: Local Mode - “ (YES)”/ “ (NO).” If “ (YES)” is selected, the local
CBE setting will be effective within the loop.
Line 7: Silenceable - “ (YES)”/ “ (NO).” This option controls both the point and
card level settings. By programming definition the point level setting is the same as
the card level setting. When “ (YES)” is chosen and a horn/strobe alarm or alarm
bell activates, the user can press 【Signals Silenced】 on main panel of the control
panel to silence the alarmed equipment. If “ (NO)” is selected, the user cannot
silence the alarmed equipment using the 【Signals Silenced】 button.
Line 8: Address Conflict - “ (YES)”/ “ (NO).” If “ (YES)” is selected, during
inspection the system will search for device address duplications within a loop. If
duplication is found, the panel will show a prompt with further instructions. If
“ (NO)” is chosen, the detector will not report duplicate addresses.
Line 9: L+ Ground Fault Detect - “ (YES)”/ “ (NO).” When “ (YES)” is
selected and a positive end of the loop is grounded, the system will report positive
end grounding trouble. If “ (NO)” is chosen, the system will not report positive
end grounding trouble.
There are three function keys, “Sync,” “Save,” and “Quit” in the status bar. The
“Sync” button allows the operator to download parameter settings (both card level
and point level settings). The “Save” button saves the changes that have been
selected. The “Quit” button allows the user to quit without saving the changes.

5.3.1.2Auto Programming

Fig. 5-1 Automatic Login Screen

Each loop has 3 status options: Installed, Uninstalled, and Disabled. During normal
installation, the programmer may enter the “Auto Programming” screen. When
he/she selects a loop number for automatic programming and then presses “OK,”
the system will verify each device on the selected loop.

Caution: When either a CMX-2 control module or a M500K call point are on
a loop using “Auto Programming” the control panel will misidentify the CMX-2 as
a CMX-7(C) and misidentify the M500K as an MMX-7. When this happens, the
user should enter 4.5.2.1.3 Point Programming screen (device configuration→
LCM→point programming) to modify the device identity by selecting the proper
equipment type.
Fig. 5-12 Automatic Programming

Upon completion of auto-programming, the quantity, type, and status of each


device on the loop will be automatically shown. This is a convenient time for
system operators to inspect, check, and manage the connected field devices. Press
the【△】key or the【▽】key to review the address and type of each point installed
on the loop. The screen is shown in Fig. 5-13:

Fig. 5-13 Auto Programming


5.3.1.3Point Programming

Fig. 5-14 Point Programming Screen

To set all loop points, select the programming screen.


Line 1: Displays the loop number, device address, and installation status. These
include: Uninstalled, Normal, and Disabled.
Line 2 & Line 3: Displays the selected address point description and additional
details. Programmer can individualize entries.
Line 4: Displays the alarm type of the selected address point. These include: Fire
alarm, Supervision, Feedback or General Output.
Line 5 & Line 6: Displays the type and model of the connected equipment.
Line 7: Displays the LED mode of the selected equipment. These include:
NORMAL BLINK, NORMAL ON and Normal OFF.
Line 8: Displays the current loops correlation mode. These include: none, previous
point correlation, next point correlation, or both next and previous point
correlation.
Line 9 & Line 10: Displays the Fire alarm, Pre-alarm, and Trouble level settings.
Note: Different detector models will have different corresponding alarm thresholds
even when the control panel setting is the same. See Appendix A for details.
• Coincident Address Code: “ (YES)”/ “ (NO).” If “ (YES)” is selected,
during inspection the system will search for device address duplications within
a loop. If duplication is found, the panel will show a prompt with further
instructions. If “ (NO)” is chosen the system will not report duplicate
addresses.
• Walk Test: “ (YES)”/ “ (NO).” If “ (YES)” is selected, pressing the
【Self-test】 key on the mainframe will cause the system to inspect all
connected devices within the loop. During inspection all verification lamps will
be normally illuminated. If a verification lamp does not illuminate, that device
has failed inspection. If “ (NO)” is selected, the condition shall be opposite.
• Local Mode: “ (YES)”/ “ (NO).” The factory default setting is “ (NO).” This
option controls both the point and card level settings. By programming
definition the point level setting is the same as the card level setting. If the loop
card and mainframe have a communication failure all selected modules
(degradation mode) will automatically output a fire alarm signal.
• Silenceable: “ (YES)”/ “ (NO).” When “ (YES)” is chosen and a horn/strobe
alarm or alarm bell activates, the user can press 【Signals Silenced】 on main
panel of the control panel to silence the alarmed equipment. If “ (NO)” is
selected, the user cannot silence the alarmed equipment using the 【Signals
Silenced】 button.
• Switch Inhibited: “ (YES)”/ “ (NO).” When “ (YES)” is chosen manual
output point operation is inhibited.
• Resetable: “ (YES)”/ “ (NO).” When “ (YES)” is selected, the equipment
will automatically reset all output signals when the system is reset.
• Drift Compensation: “ (YES)”/ “ (NO).” When “ (YES)” is selected, the
system will restrain individual sensors from automatically performing drift
compensation.
• Rapid Polling: “ (YES)”/ “ (NO).” When “ (YES)” is selected, the system
will increase the frequency of in-process inspection on the loop thus increasing
the sensitivity of the equipment.
• Alarm Verification: “ (YES)”/ “ (NO).” When “ (YES)” is selected, there
will be an adjustable delay in the alarm period after a preliminary alarm has
registered, allowing time for the alarm to be verified before sending a general
alarm. Should an alarm condition still exist after verification, the panel will
then go into alarm. Verification time is adjustable (in second’s intervals) and
can be customized by using the edit feature on the right side of the alarm
verification label.

5.3.2Annunciator Control Module


In the “MCU” screen, a programmer can access the “Setting” and “Point
programming” options for an annunciator control module.
Fig. 5-15 Annunciator Control Module Screen

5.3.2.1Parameter setting

Fig. 5-16 Parameter setting Screen

Line 1: MCU—Select the MCU number.


Line 2: Description—Describe the selected MCU.
Line 3: Set the current MCU status. These include: Uninstalled, Normal and
Disabled.
Press “Save” to save the current settings. If the user presses “Exit” without saving,
the following dialogue box will be prompted. At this time the user can also save the
current settings. The user can also exit the current screen to retain previous settings;
the current settings will not be saved.

5.3.2.2Point Programming
Point Programming of MCU can access to set the relative module address of keys
and feedback led.
Fig. 5-17 Point Programming Screen

5.3.3Remote Display
In the “Remote Display” screen, a programmer can access the “Setting,”
“Download Label” and “Point Programming” option screens. One N-6000 fire
alarm control panel can have up to 64 remote displays.

Fig. 5-18 Remote Display Screen


5.3.3.1Parameter setting

Fig. 5-19 Parameter setting Screen

Line 1: Remote display—Displays the remote display number.


Line 2: Description—Describes the selected remote display.
Line 3: Set the current remote display status. These include: Normal, Disabled and
Uninstalled.
Press “Save” to save the current settings. If the user presses “Exit” without saving,
the following dialogue box will be prompted. At this time the user can also save the
current settings. The user can also exit the current screen to retain previous settings;
the current settings will not be saved.

5.3.3.2Label Download

Fig. 5-20 Download Label Screen

In the “Download Label” screen a programmer can view detailed information by


selecting the desired floor repeater number and pressing “OK.” At this time, the
system will download relative content for each point in the selected repeater floor
display. If past events have occurred in the selected equipment points, all
previously downloaded contents will also be shown on the remote display. This
allows field operators to update equipment settings for optimal device function.

5.3.3.3Point Programming

Fig. 5-21 Point Programming Screen

Line 1: Displays the remote display number, point number and installation status.
These include: Uninstalled, Normal, and Disabled.
Line 2: Displays the current remote display point description
Line 3: Point Mapping—Each remote display can have up to 64 points. Each point
must have a specific zone and loop address. After each point has been mapped,
during an event (fire alarm, trouble, etc) the mapped equipment’s location and
event will be shown on the relative remote display screen.
Press “Save” to save the current settings. If the user presses “Exit” without saving,
the following dialogue box will be prompted. At this time the user can also save the
current settings. The user can also exit the current screen to retain previous settings;
the current settings will not be saved.

5.3.4CBE Programming
In the “CBE Programming” screen programmers can access both the “General
Zone” and “Logic Zone” setting screens.
Fig. 5-22 CBE Programming Screen

5.3.4.1General Zone
Within the “General Zone” screen a user can select zones 0-499 to review the
relative logic equation of a particular zone. Use the VFT programming software to
modify the logic equations as necessary.

Fig. 5-23 General Zone

5.3.4.2Logic Zone
Within the “Logic Zone” screen a user can select zones 0-999 to review the relative
equation of a particular zone. Use the VFT programming software equation to
modify the logic equations as necessary.
Fig. 5-24 Logic Zone

5.3.5Device Control
In the “Device Control” screen a user can access the “Point Output,” “Status
Tracking,” “Walking Test,” “Loop Exercise” and “Power Supply Management”
setting screens.

Fig. 5-25 Device Control Screen


5.3.5.1Manual Output

Fig. 5-26 Manual Output Screen

Within the “Point Output” screen a user can set the loop number, address number,
type of equipment, label and the inspection lamp ON/OFF status. Press the 【△】
key or the 【▽】 key to review a points’ status.
Line 1: Displays the current loop number, address and status. These include:
Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
Line 7: Displays the selected output module status. If the user chooses “Start” and
then presses “OK”, the point in the current loop will be output by the module; if set
at “Close”, the point will not be output by the module.
5.3.5.2Status Tracking

Fig. 5-27 Status Tracking Screen

Within the “Status Track” screen a user can set the loop number, address number,
address type as well as monitor the point.
Line 1: Displays the current loop number, loop address and its status. These include:
Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Display the current equipment type and model.
Line 7: Displays the current point status.

5.3.5.3Walk Test

Fig. 5-28 Walk Test Screen


Within the “Walk Test” screen a user can set the loop number, address number,
address type as well as run a walking test on a particular loop.
Line 1: Displays the loop number, current address and installation status. These
include: Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
After adjusting the systems settings, pressing the【Lamp inspection/Self-test】key
on main panel will cause the control panel to run a self-test on the current loop.
During this test, both the self-test indicating lamp and the load verification lamp
will be normally illuminated. Press “Review the Result” to view every address in
the current walk test, the addresses will be displayed on the right hand side of the
walk test interface screen (Fig. 4-50).

Fig. 5-29 Walk Test Address Screen

Press “OK” to control current point set in the loop.


5.3.5.4Loop Drill

Fig. 5-30 Loop Drill Screen

5.3.5.5Power Supply Management

Fig. 5-31 Power Management Screen

N-6000 fire alarm control panel uses the MPS-350W power supply. Within the
“Power Management” screen the user can review the current status of each power
supply.
Line 1: Displays the currently connected power supply type. The MPS-350W is the
primary power supply for the N-6000.
Line 2: Displays the current status and voltage of the main power supply.
Line 3: Displays the current status and voltage of the reserved power supply.
Line 4: Press 【Discharge】 to discharge the power supply. Press 【Stop】 to stop
discharging. Press 【Exit】 to exit the power supply control screen.
5.3.6History Events
Within the “History Events” screen a user can access the systems history
records/events. This screen is seen below:

Fig. 5-32 History Event Screen

Line 1: Displays the type of history event. History event types include but are not
limited to: fire alarm, trouble, supervision, CBE and Isolation. When “All Events”
is selected, detailed information will be provided for each event. If “All Events” is
not selected the user must select a particular event to view the additional and
detailed information.
Line 2: Displays the total number of events that can be reviewed.
Line 3: Displays the status of the current event. The operator may obtain detailed
information about the current event including location, type, time of occurrence,
serial number, as well as additional information from the following text box.
Line 4: Press 【Exit】 to exit the history event screen.
Pressing the【NEXT】key or the【PREV】key on main panel of the control panel,
a user can review the detailed description of the next or previous history event.
N-6000 can record and display up to 8000 individual history events.
Section 6:Miscellaneous

6.1Safety Protection Device


The N-6000 has been designed with built-in safety devices to protect both the operator and
control panel in case of improper use and/or installation. These devices include an anti-misplug
terminal which can endure extremely high voltage and current ensuring the safety of both
operators as well as the control panel. Additionally the control panel has current limiting
protection for the power supply, protection circuits for communication devices, and special
grounding terminals provided within the cabinet.

6.2Usage and Maintenance


To ensure consistent and reliable operation the following items should be observed and
followed:
• The control panel must be installed and debugged by qualified technicians
• The operator on duty should be familiar with the current building structure as well as
understand all possible control panel events and operations
• An operator should monitor the control panel status to eliminate various trouble signals and
prevent alarm signals when possible
• If a power failure exceeds 8 hours, the reserve power supply should be disconnected to avoid
damage due to over-discharge
• If additional construction is performed in the protected building, shut down the control panel
to ensure fire detection capabilities are not compromised
• During any status other than operation (transportation, storage, etc), the reserve power supply
should be disconnected from the control panel

6.3Common Troubles
The N-6000 has advanced features such as self-diagnosis and self-protection; however even
with the advanced technology an occasional trouble signal is unavoidable. Table 5-1 has
additional information regarding common troubles.
Trouble Cause analysis Solution
Re-connect the AC220V
Poor AC220V connection
Main power supply power supply
trouble Fuse blowing out due to external
Replace the fuse
short circuit or over-current

Reserved power Poor plug connection Check connectors


supply trouble
Replace reserved power
Reserved power supply damaged
supply
Trouble Cause analysis Solution
Fuse blowing out due to external
Replace the fuse
short circuit or over-current

Poor connection between LCD and


Check connectors
display module card

LCD display fails Failure to regulate the luminance Regulate the luminance

Backlight socket connected Disconnect and plug the


improperly socket in again

Soft panel socket block connected Disconnect and plug the


Keypad fails
improperly socket in again

Loudspeaker socket connected Disconnect and plug the


No sound
improperly socket in again

Short circuit in loop bus Clear short circuit


Short circuit in loop Reverse connection of addressing Check connection of the
unit addressing unit

Clock chip M410T socket


Inaccurate clock Replace clock chip M410T
connected improperly or damaged
Table 5-1 Common Troubles
For additional trouble not found in Table 5-1 please contact the dealer or manufacturer directly.

6.4Transportation & Storage


After a post-factory inspection, the control panel can be stored. During storage the control
panel must be stored under normal atmospheric condition, ambient temperature and in a dry
room for a maximum of 6-months. During transportation the control panel must be kept
right-side up and protected from heavy overhead weight. The control panel can be transported
by train, truck, plane or ship.
Once the control panel has been opened, the user must use the control panel in accordance with
this manual. When used in conjunction with this manual all operation results will meet the
performance and functional requirements defined by this manual.

6.5Out-of-box Audit
When opening the control panel box for the first time the user should carry out an out-of-box
audit to ensure the control panel is complete, untouched and undamaged from transportation.
The control panel should include: a CPU, loop card, MCU, POM-8A, MPS-350W,
complement keys and connecting wires, etc.
Open the control panel door to ensure all internal connections are normal and that there are no
loose connections, short circuits and/or disconnected items. Check the power supply status to
ensure it is normal and does not have any short circuits, etc.
Appendix A
Alarm level cross-reference table for the ND682 photoelectric smoke detector:
Actual physical threshold range of
Alarm level setting alarm
(Unit: 0.1 OBS%/FT)
LEVEL 1 0 -2.5
LEVEL 2 2.5 – 5
LEVEL 3 5 - 7.5
LEVEL 4 7.5 – 10
LEVEL 5 10 -14
LEVEL 6 14 – 16
LEVEL 7 16 -18
LEVEL 8 18 – 20
LEVEL 9 over 20
LEVEL 10 Over 20
Table 1: Alarm level cross-reference table for the ND682

Alarm level cross-reference table for the ND685 heat detector:


Actual physical threshold range of
Alarm level setting alarm
(Unit ˚C)
LEVEL 1 30 – 34
LEVEL 2 34 – 37
LEVEL 3 37 – 40
LEVEL 4 40 – 45
LEVEL 5 45 – 50
LEVEL 6 50 – 55
LEVEL 7 55 – 60
LEVEL 8 60 – 65
LEVEL 9 Over 65
LEVEL 10 Over 65
Table 2: Alarm level cross-reference table for the ND685
Alarm level cross-reference table for the FSL-751 detector:
Alarm level setting Actual physical threshold range of
alarm
(Unit: 0.01%/ft)
LEVEL 1 0–2
LEVEL 2 2–3
LEVEL 3 3 – 10
LEVEL 4 10 – 50
LEVEL 5 50 – 100
LEVEL 6 100 – 150
LEVEL 7 150 – 200
Table 3: Alarm level cross-reference table for FSL-751

The following is the trouble level cross-reference table for drift compensation:
Physical value of drift compensation
Alarm level setting
(Unit: 0.01%/ft)
LEVEL 1(Warning) 30
LEVEL 2(Warning) 60
LEVEL 3(Trouble) 90
Table 4: Alarm level cross-reference table for FSL-751
Limited Warranty
NOTIFIER® warrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, under
normal use and service. Products are date stamped at time of manufacture.
The sole and exclusive obligation of NOTIFIER® is to repair or replace, at its
option, free of charge for parts and labor, any part which is defective in
materials or workmanship under normal use and service. For products not
under NOTIFIER® manufacturing datestamp control, the warranty is eighteen
(18) months from date of original purchase by NOTIFIER® 's distributor
unless the installation instructions or catalog sets forth a shorter period, in
which case the shorter period shall apply. This warranty is void if the product
is altered, repaired or serviced by anyone other than NOTIFIER® or its
authorized distributors or if there is a failure to maintain the products and
systems in which they operate in a proper and workable manner. In case of
defect, secure a Return Material Authorization form from our customer
service department. Return product, transportation prepaid, to NOTIFIER®, 12
Clintonville Road, Northford, Connecticut 06472-1653.

This writing constitutes the only warranty made by NOTIFIER® with respect to
its products. NOTIFIER® does not represent that its products will prevent any
loss by fire or otherwise, or that its products will in all cases provide the
protection for which they are installed or intended. Buyer acknowledges that
NOTIFIER® is not an insurer and assumes no risk for loss or damages or the
cost of any inconvenience,
transportation, damage, misuse, abuse, accident or similar incident.

NOTIFIER® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF


MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE
FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL NOTIFIER® BE
LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT,
INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR
INABILITY TO USE NOTIFIER® PRODUCTS. FURTHERMORE, NOTIFIER®
SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH
MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,
COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.

This warranty replaces all previous warranties and is the only warranty made
by NOTIFIER®. No increase or alteration, written or verbal, of the obligation of
this warranty is authorized.

"NOTIFIER®" is a registered trademark.

You might also like