PROJECT WATER SUPPLY PROJECTS PERTAINING TO SAMBALPUR & JHARSUGUDA BLOCK

SAMBALPUR DIST - ODISHA


SUBJECT DESIGN OF GIRDER FOR 1T HOIST

Design data
Load W = 1000 kg
Weight of hoist = 300 kg (approx.)
Total weight W' = 1300 kg
Impact factor considered = 1.06
After impact W1 = 1378 kg
Span (max.) L = 455 cm
Self weight (assuming ISMB 200) w = 0.242 kg/cm
Material of construction = I.S. 2062 Gr. E 250 - BR

1378 kg 0.242 kg/cm

A B

Span=455 cm

Ra=Rb = 744 kg
Bending moment = (W1xL)/4 + wL²/8
= (1378x455/4)+(0.242x455^2/8)
BM = 163010 kg-cm

Maximum Reacton from the 1T Crane Girder


(Considering Hoist at the Any End location)
Hoist Load Maximum 1378 kgs
Reaction Due to Self Weight 55.06 kgs
Total Maximum Reaction Due to Crane 1433.06 kgs
Consider 1500.00 kgs
Apply Load of 15kN @ Crane Location
PROJECT WATER SUPPLY PROJECTS PERTAINING TO SAMBALPUR & JHARSUGUDA BLOCK
SAMBALPUR DIST - ODISHA
SUBJECT DESIGN OF GIRDER FOR 1T HOIST
Section properties for ISMB 200
Section modulus Zxx = 212 cm³
Moment of Inertia Ixx = 2120 cm⁴
Youngs Modulus E = 2047000 kg/cm²
Web thickness t = 0.57 cm

Bending stress = 163010/212


= 769 kg/cm² < 1683 kg/cm²

Shear stress = 744/(20x0.57)


= 65 kg/cm² < 1148 kg/cm²

Deflection
Allowable deflection = L/500
= 455/500
= 0.91 cm
Actual deflection
Due to Load (without impact) = W'L³/(48EI)
= 1300x455^3/(48x2047000x2120)
= 0.59 cm

Due to Self weight = 5wL⁴/(384EI)


= 5x0.242x455⁴/(384x2047000x2120)
= 0.03 cm

Total deflection = 0.59+0.03


= 0.62 cm < 0.91 cm