Due to provision of FGD & SCR ,if the sizing of Station transformer changes , CT & VT
calculations for Station transformer metering & protections needs to be revised by
1 CT & VT calculations revised as per 110MVA station transformer rating.
BHEL accordingly. In this context SLD for Station transformer metering & protections
shall also be revised.
(Ref. 4.2.3 page 5/7)CT 2B, core 2….Through fault current on LV2 side of ST should
2 be taken as (100 * 1000)/ (1.732 * 11 * 0.21 * 0.9) instead of (100 * 1000)/ Incorporated in revised document.
(1.732 * 11.5 * 0.21 * 0.9)
(Ref. 4.2.4 page 6/7) CT 2A, core 2….Through fault current on LV2 side of ST should
3 be taken as (100 * 1000)/ (1.732 *11*0.21*0.9) instead of (100 *1000)/ (1.732 * Incorporated in revised document.
11.5 * 0.21* 0.9)
In view of above, please accord approval on "CT & VT calculations for station transformer metering & protection" and "SLD for station transformer metering
& protection"
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 1 of 7
1.0 LEGEND
CT : Current transformer
I : Relay rated current
Ie : Excitation current
If : CT secondary current corresponding to fault current
L : Length of cable between CT and relay
RL : One way lead resistance between CT and relay
RCT : Resistance of secondary winding of main CT
VK : Knee point voltage
4.1 CT RATIOS U
= 3068.13 A
= 3068.13 A
4.2.1 CT-4
CT ratio : 250/1 A
= 1534 A
If = 1534 x 1
250
= 6.136 A
VK ≥ 2 If (RCT + 2RL)
L = 150 M
RL (2.5 mm square) = 9.34 x 0.150
= 1.401 Ohm
Selected Vk ≥ 20Rct + 50 V
Ie ≤ 30 mA at VK/2
Accuracy class : PS
4.2.2 CT 3
CORE-1
CT ratio : 250/1 A
L = 150 M
RL (2.5 mm square) = 9.34 x 0.150
= 1.401 Ohm
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 4 of 7
Source of burden
U U Burden
U U
51NSTH 0.1 VA
Lead burden 2.802 VA
Selected burden : 10 VA
Accuracy class : 5P20
CORE-2
Purpose: Station Transformer HV Restricted Earth Fault Protection (64RST-HV)
CT ratio : 250/1 A
If = 1534 x 1
250
= 6.136 A
L = 150 M
RL (2.5 mm square cable) = (9.34 x 0.150)
1.401 Ohm
Selected Vk ≥ 20Rct + 50 V
Ie ≤ 30 mA at VK/2 B B
Accuracy class : PS
4.2.3 CT-2B
CORE-1
Purpose: Station Transformer LV2 Backup Earth Fault Protection (51NST-LV2)
CT ratio : 300/1 A
L = 150 M
RL (2.5 mm square)
B = 9.34 x 0.150
= 1.401 Ohm
Source of burden
U U burden
U U
51NSTL 0.1 VA
Lead burden 2.802 VA
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 5 of 7
Selected burden : 10 VA
Accuracy class : 5P20
CORE-2
Purpose: Station Transformer LV2 Restricted Earth Fault Protection (64RST-LV2)
CT ratio : 3500/1 A
110 x1000
Through fault current on LV2 side of ST =
3 x11x0.21 × 0.9
(Considering –10% tolerance of 21% for ZHV-LV2) = 30548.5 A
If = 30548.5 x 1
3500
= 8.73 A
VK ≥ 2 If (RCT + 2RL)
L = 150 M
RL (2.5 mm square) = 9.34 x 0.150
= 1.401 Ohm
Selected Vk ≥ 20Rct + 75 V
Ie ≤ 30 mA at VK/2
Accuracy class : PS
4.2.4 CT-2A
CORE-1
Purpose: Station Transformer LV1 Backup Earth Fault Protection (51NST-LV1)
CT ratio : 300/1 A
L = 150 M
RL (2.5 mm square)
B = 9.34 x 0.150
= 1.401 Ohm
Source of burden
U U burden
U U
51NSTL 0.1 VA
Lead burden 2.802 VA
Selected burden : 10 VA
Accuracy class : 5P20
CORE-2
Purpose: Station Transformer LV1 Restricted Earth Fault Protection (64RST-LV1)
CT ratio : 3500/1 A
110 x1000
Through fault current on LV1 side of ST =
3 x11x0.21 × 0.9
(Considering –10% tolerance of 21% for ZHV-LV1) = 30548.5 A
If = 30548.5 x 1
3500
= 8.73 A
VK ≥ 2 If (RCT + 2RL)
L = 150 M
RL (2.5 mm square) = 9.34 x 0.150
= 1.401 Ohm
Selected Vk ≥ 20Rct + 75 V
Ie ≤ 30 mA at VK/2
Accuracy class : PS
4.2.5 CT-1B
CORE-1
CT ratio : 3500/1 A
VK ≥ 40 I (RCT + 2RL)
I = 1A U
L = 80 M
RL (2.5 mm square cable) = (9.34 x 0.080)
0.7472 Ohm
VK ≥ 40 x 1 x (RCT + 2x 0.7472)
≥ 40(RCT + 1.4944) V
≥ 40RCT + 59.776 V
Accuracy class : PS
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 7 of 7
4.2.6 CT-1B
CORE-2
Purpose: Station Transformer LV2 Restricted Earth Fault Protection (64RST-LV2)
4.2.7 CT-1A
CORE-1
Purpose: Station Transformer Differential protection (87ST)
CT ratio : 3500/1 A
VK ≥ 40 I (RCT + 2RL)
I = 1A U
L = 80 M
RL (2.5 mm square cable) = (9.34 x 0.080)
0.7472 Ohm
VK ≥ 40 x 1 x (RCT + 2x 0.7472)
≥ 40(RCT +1.4944) V
≥ 40RCT + 59.776 V
Accuracy class : PS
CORE-2
Purpose: Station Transformer LV1 Restricted Earth Fault Protection (64RST-LV1)