REPLY TO COMMENTS ON DOCUMENT "CT & VT CALCULATIONS FOR STRP" (PE-DC-415-510-E043-R1)


S No MAHAGENCO COMMENTS dated 08.10.2018 BHEL REPLY dated 26.02.2019

Due to provision of FGD & SCR ,if the sizing of Station transformer changes , CT & VT
calculations for Station transformer metering & protections needs to be revised by
1 CT & VT calculations revised as per 110MVA station transformer rating.
BHEL accordingly. In this context SLD for Station transformer metering & protections
shall also be revised.

(Ref. 4.2.3 page 5/7)CT 2B, core 2….Through fault current on LV2 side of ST should
2 be taken as (100 * 1000)/ (1.732 * 11 * 0.21 * 0.9) instead of (100 * 1000)/ Incorporated in revised document.
(1.732 * 11.5 * 0.21 * 0.9)

(Ref. 4.2.4 page 6/7) CT 2A, core 2….Through fault current on LV2 side of ST should
3 be taken as (100 * 1000)/ (1.732 *11*0.21*0.9) instead of (100 *1000)/ (1.732 * Incorporated in revised document.
11.5 * 0.21* 0.9)

In view of above, please accord approval on "CT & VT calculations for station transformer metering & protection" and "SLD for station transformer metering
& protection"
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 1 of 7

1.0 LEGEND

CT : Current transformer
I : Relay rated current
Ie : Excitation current
If : CT secondary current corresponding to fault current
L : Length of cable between CT and relay
RL : One way lead resistance between CT and relay
RCT : Resistance of secondary winding of main CT
VK : Knee point voltage

2.0 REFERENCE DRAWINGS

Single Line Diagram of Station Transformer Protection - drawing no. PE-DG-415-510-E041.

Design calculations for Generator & MV systems, document no. PE-DC-415-565-E002.

3.0 MAIN EQUIPMENT DETAILS

3.1 STATION TRANSFORMER


Rating HV (MVA) 110
Rating LV1 (MVA) 55
Rating LV2 (MVA) 55
Voltage HV side (kV) 400
Voltage LV1 side (kV) 11.5
Voltage LV2 side (kV) 11.5
On load taps +10% to -10%
Tapping steps (%) 1.25
Impedance (Z)
ZHV-LV1 21% ± 10%
ZHV-LV2 21% ± 10%
ZLV1-LV2 38% (Approx.) ± 10%

3.2 Control Cable Details

Size (Sq mm)


U Material
U U
Resistance (Ω/km) at 70° C
U U

2.5 Copper 9.34

4.0 CURRENT TRANSFORMERS

4.1 CT RATIOS U

4.1.1 ST HV Side CT (CT-4)

ST HV side current (corresponding to 110 MVA) = 110 x 1000


√3 x 400x0.95
= 167.13 A
CT ratio for CT located on ST HV side = 250/1 A

4.1.2 ST HV Neutral CT (CT-3)


CORE-1: CT ratio (backup earth fault protection) = 250/1 A
CORE-2: CT ratio (restricted earth fault protection) = 250/1 A
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 2 of 7

4.1.3 ST LV2 (11kV) Neutral CT (CT-2B)

ST LV2 side current (corresponding to 55 MVA) = 55 x 1000____


√3 x 11.5 x 0.9

= 3068.13 A

CORE-2: CT ratio (restricted earth fault protection) = 3500/1 A


CORE-1: CT ratio (backup earth fault protection) = 300/1 A

4.1.4 ST LV1 (11kV) Neutral CT (CT-2A)

ST LV1 side current (corresponding to 55 MVA) = 55 x 1000____


√3 x 11.5 x 0.9

= 3068.13 A

CORE-2: CT ratio (restricted earth fault protection) = 3500/1 A


CORE-1: CT ratio (backup earth fault protection) = 300/1 A

4.1.5 ST LV2 (11kV) side CT (CT-1B)

CORE-1: CT ratio (differential protection) = 3500/1 A


CORE-2: CT ratio (restricted earth fault protection) = 3500/1 A

4.1.6 ST LV1 (11kV) side CT (CT-1A)

CORE-1: CT ratio (differential protection) = 3500/1 A


CORE-2: CT ratio (restricted earth fault protection) = 3500/1 A

4.2 CTs OTHER PARAMETERS

4.2.1 CT-4

Purpose: Station Transformer HV Restricted Earth Fault Protection (64RST-HV)

CT ratio : 250/1 A

Through fault current on HV side of ST = Through fault current


calculated from the equivalent impedance, Zeff
of Station Transformer

Impedance (Z) details of ST:


ZHV-LV1 21% ± 10%
ZHV-LV2 21% ± 10%
ZLV1-LV2 38% (Approx.) ± 10%

Equivalent Impedance of ST, Zeff = ZH + [ (ZL1* ZL2) / (ZL1+ ZL2)]

Equivalent Impedance of HV side, ZH = 0.5*[ ZHV-LV1 + ZHV-LV2 - ZLV1-LV2]


Equivalent Impedance of LV1 side,ZL1 = 0.5*[ ZHV-LV1 - ZHV-LV2 + ZLV1-LV2]
Equivalent Impedance of LV2 side, ZL2 = 0.5*[ -ZHV-LV1 + ZHV-LV2 + ZLV1-LV2]
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 3 of 7

Equivalent Impedance of HV side, ZH = 0.5*[ ZHV-LV1 + ZHV-LV2 - ZLV1-LV2]


= 0.5*[ 0.21*0.90 + 0.21 * 0.90 – 0.38*0.90]
=0.018

Equivalent Impedance of LV1 side,ZL1 = 0.5*[ ZHV-LV1 - ZHV-LV2 + ZLV1-LV2]


= 0.5*[0.21*0.90 - 0.21*0.90 + 0.38*0.90]
=0.171

Equivalent Impedance of LV2 side, ZL2 = 0.5*[ -ZHV-LV1 + ZHV-LV2 + ZLV1-LV2]


= 0.5*[- 0.21*0.90 + 0.21*0.90 + 0.38*0.90]
= 0.171

Equivalent Impedance of ST, Zeff = ZH + [ (ZL1* ZL2) / (ZL1+ ZL2)]


= 0.018 + [0.171 * 0.171] / [0.171 + 0.171]
=0.1035

Through fault current on HV side of ST = 110 x 1000


√3 x 400 x 0.1035

= 1534 A

If = 1534 x 1
250
= 6.136 A

VK ≥ 2 If (RCT + 2RL)

L = 150 M
RL (2.5 mm square) = 9.34 x 0.150
= 1.401 Ohm

VK ≥ 2 x 6.136 x (RCT + 2 x 1.401)


≥ 12.272 x (RCT + 2 x 1.401)
≥ 12.272 RCT + 34.38 V

Selected Vk ≥ 20Rct + 50 V
Ie ≤ 30 mA at VK/2
Accuracy class : PS

4.2.2 CT 3

CORE-1

Purpose: Station Transformer HV Backup Earth Fault Protection (51NST-HV)

CT ratio : 250/1 A

L = 150 M
RL (2.5 mm square) = 9.34 x 0.150
= 1.401 Ohm
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 4 of 7

Lead burden = 12 x 2 x 1.401


= 2.802 VA

Source of burden
U U Burden
U U

51NSTH 0.1 VA
Lead burden 2.802 VA

Total burden = 2.902 VA

Selected burden : 10 VA
Accuracy class : 5P20

CORE-2
Purpose: Station Transformer HV Restricted Earth Fault Protection (64RST-HV)

CT ratio : 250/1 A

Through fault current on HV side of ST = 1534 A

If = 1534 x 1
250
= 6.136 A

L = 150 M
RL (2.5 mm square cable) = (9.34 x 0.150)
1.401 Ohm

VK ≥ 2 x 6.136 x (RCT + 2 x 1.401)


≥ 12.272 x (RCT + 2 x 1.401)
≥ 12.272 RCT + 34.38 V

Selected Vk ≥ 20Rct + 50 V
Ie ≤ 30 mA at VK/2 B B

Accuracy class : PS

4.2.3 CT-2B

CORE-1
Purpose: Station Transformer LV2 Backup Earth Fault Protection (51NST-LV2)

CT ratio : 300/1 A

L = 150 M
RL (2.5 mm square)
B = 9.34 x 0.150
= 1.401 Ohm

Lead burden = 12 x 2 x 1.401


= 2.802 VA

Source of burden
U U burden
U U

51NSTL 0.1 VA
Lead burden 2.802 VA
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 5 of 7

Total burden = 2.902 VA

Selected burden : 10 VA
Accuracy class : 5P20

CORE-2
Purpose: Station Transformer LV2 Restricted Earth Fault Protection (64RST-LV2)

CT ratio : 3500/1 A

110 x1000
Through fault current on LV2 side of ST =
3 x11x0.21 × 0.9
(Considering –10% tolerance of 21% for ZHV-LV2) = 30548.5 A

If = 30548.5 x 1
3500
= 8.73 A

VK ≥ 2 If (RCT + 2RL)

L = 150 M
RL (2.5 mm square) = 9.34 x 0.150
= 1.401 Ohm

VK ≥ 2 x 8.73 x (RCT + 2 x 1.401)


≥ 17.46 x (RCT + 2 x 1.401)
≥ 17.46 RCT + 48.9 V

Selected Vk ≥ 20Rct + 75 V
Ie ≤ 30 mA at VK/2
Accuracy class : PS

4.2.4 CT-2A

CORE-1
Purpose: Station Transformer LV1 Backup Earth Fault Protection (51NST-LV1)

CT ratio : 300/1 A

L = 150 M
RL (2.5 mm square)
B = 9.34 x 0.150
= 1.401 Ohm

Lead burden = 12 x 2 x 1.401


= 2.802 VA

Source of burden
U U burden
U U

51NSTL 0.1 VA
Lead burden 2.802 VA

Total burden = 2.902 VA


DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 6 of 7

Selected burden : 10 VA
Accuracy class : 5P20

CORE-2
Purpose: Station Transformer LV1 Restricted Earth Fault Protection (64RST-LV1)

CT ratio : 3500/1 A

110 x1000
Through fault current on LV1 side of ST =
3 x11x0.21 × 0.9
(Considering –10% tolerance of 21% for ZHV-LV1) = 30548.5 A

If = 30548.5 x 1
3500
= 8.73 A

VK ≥ 2 If (RCT + 2RL)

L = 150 M
RL (2.5 mm square) = 9.34 x 0.150
= 1.401 Ohm

VK ≥ 2 x 8.73 x (RCT + 2 x 1.401)


≥ 17.46 x (RCT + 2 x 1.401)
≥ 17.46 RCT + 48.9 V

Selected Vk ≥ 20Rct + 75 V
Ie ≤ 30 mA at VK/2
Accuracy class : PS

4.2.5 CT-1B

CORE-1
CT ratio : 3500/1 A

Knee point voltage requirement for ST Differential protection (87ST)

VK ≥ 40 I (RCT + 2RL)

I = 1A U

L = 80 M
RL (2.5 mm square cable) = (9.34 x 0.080)
0.7472 Ohm

VK ≥ 40 x 1 x (RCT + 2x 0.7472)
≥ 40(RCT + 1.4944) V
≥ 40RCT + 59.776 V

Selected Vk ≥ 40Rct + 100 V


Ie ≤ 30 mA at VK/2 B B

Accuracy class : PS
DOCUMENT NO.
1 x 660MW Bhusawal Thermal Power Plant PE-DC-415-510-E043
REV NO: 02
CT & VT Calculations for Station Transformer DATE: 26.02.2019
Metering and Protection SHEET 7 of 7

4.2.6 CT-1B
CORE-2
Purpose: Station Transformer LV2 Restricted Earth Fault Protection (64RST-LV2)

CT DETAILS SAME AS CT-2B, CORE-2

4.2.7 CT-1A

CORE-1
Purpose: Station Transformer Differential protection (87ST)

CT ratio : 3500/1 A

Knee point voltage requirement for ST Differential protection (87ST)

VK ≥ 40 I (RCT + 2RL)

I = 1A U

L = 80 M
RL (2.5 mm square cable) = (9.34 x 0.080)
0.7472 Ohm

VK ≥ 40 x 1 x (RCT + 2x 0.7472)
≥ 40(RCT +1.4944) V
≥ 40RCT + 59.776 V

Selected Vk ≥ 40Rct + 100 V


Ie ≤ 30 mA at VK/2
B B

Accuracy class : PS

CORE-2
Purpose: Station Transformer LV1 Restricted Earth Fault Protection (64RST-LV1)

CT DETAILS SAME AS CT-2A, CORE-2