Professional Documents
Culture Documents
FF Troubleshooting Guide
FF Troubleshooting Guide
FF Troubleshooting Guide
Manual Type
FOUNDATION Fieldbus
6 Troubleshooting ..................................................................................... 12
Date of issue 25.08.2003
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 1
Troubleshooting Guide
Table of Contents
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
2 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
How to use this documentation
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 3
Troubleshooting Guide
FF segment Checklist
2 FF segment Checklist
! device supply voltage must be higher than 9 VDC with a maximum of 32 VDC
! device polarity must be correct
! two 100 Ω, 1 µF terminators must be connected at each end of the segment
! cable length plus spur length must not exceed the following values:
! The cable shield is to be hard grounded only at one point close to the DCS. In
addition, the cable shield can be capacitively grounded in multiple places to
improve EMC protection.
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
4 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
Introduction to the FF communication signal
The digital fieldbus signal is a current modulated ±10 mA signal on a 50 Ω test load -
this generates a 1.0 Vpp signal. A valid signal can range from 150 mVpp up to 1.0 Vpp
and noise must not exceed 75 mVpp (see figure 3.1).
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 5
Troubleshooting Guide
Introduction to the FF communication signal
The communication on a fieldbus segment follows a cyclic pattern. The figure below
shows the pattern that can be observed when an Emerson DeltaV DCS is used as
host along with three instruments.
Communication cycle
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
6 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
Introduction to the FF communication signal
The FOUNDATION Fieldbus signal is Manchester encoded and uses special charac-
ters for the preamble, start delimiter and end delimiter. The preamble is used to syn-
chronize the receiver with the sender - start and end delimiters frame the actual
message or data.
Preamble
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 7
Troubleshooting Guide
Shielding & Grounding
The FOUNDATION Fieldbus specification requires the shield of the transmission line
to be hard grounded at only one point.
2. Hard grounding on all field devices, capacitive grounding on the cabinet side.
3. Hard grounding on the cabinet side, capacitive grounding on all field devices.
Date of issue 25.08.2003
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
8 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
Shielding & Grounding
The best EMC protection is achieved by hard grounding both ends of the transmission
line and each field instrument. This requires a potential equalization line between the
marshalling cabinet and the field installation thus increasing installation costs.
North America:
Most installations in North America are done as shown in version 4 - leaving the shield
floating on the field device side. However, if communication problems due to noise are
encountered, the shield can be capacitively grounded in as many places as neces-
sary to improve the shield effectiveness (see version 3).
Europe:
In Europe version 2 or 3 are the common practice because they are considered a
good compromise between installation costs and EMC protection.
Date of issue 25.08.2003
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 9
Troubleshooting Guide
Measurements on a FF segment
5 Measurements on a FF segment
Figure 5.1: Using a single scope channel can induce additional noise onto the bus
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
10 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
Measurements on a FF segment
Figure 5.2: Using the oscilloscope in differential mode leads to more precise meas-
urement of the actual communication
Date of issue 25.08.2003
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 11
Troubleshooting Guide
Troubleshooting
6 Troubleshooting
The following suggestions should be considered once the checklist has been com-
pleted and still no stable communication has been established.
In order to guarantee all field devices function properly, at least 9 VDC must be sup-
plied to each of them. The voltage drop due to the cable and the current consumption
of all the field devices must be considered. In addition one or more short-circuits
should be added to the total current to guarantee operation during a fault condition. If
the segment extends over long distances, a power supply with 32 VDC can be used
to compensate for the voltage drop due to the cable. In addition, power repeaters can
extend the possible maximum cable length or better cable can be used to decrease
the signal attenuation.
The voltage at each device can be calculated with this formula (some supplies may
have Rin = 0 Ω):
x x
x
U x U out Rin ∑
= − ∗
n =1
I n
+ ∑
m =1
R m ∑In
∗
n=m
calculate the voltage drop using a current consumption equal to the holding current of
one channel of that short-circuit protective device. This will simulate a short-circuit
condition at the most onerous point in the network. It is also suggested to calculate
the network with one or two additional instruments to simulate future expansion.
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
12 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
Troubleshooting
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 13
Troubleshooting Guide
Troubleshooting
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
14 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
Troubleshooting
Figure 6.3: Supply Voltage glitches are passed into the FF segment by a non-regu-
lated FF supply
• bad shielding/grounding, make sure ground is only connected at one point.
• Noise from the DC power supply can be injected into the fieldbus. An indication of
a noisy power supply is a thick baseline. The noise amplitude can be determined
by measuring the baseline amplitude. Noise must not exceed 150 mV pk-pk.
• A regulated FF power supply can inject switching noise into the bus.
Date of issue 25.08.2003
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 15
Troubleshooting Guide
Troubleshooting
Figure 6.4: Regulated FF power supplies can cause high frequency switching noise
Date of issue 25.08.2003
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
16 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
Troubleshooting
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 17
Troubleshooting Guide
Troubleshooting
Figure 6.6: Bad signal form caused by improper termination (no terminator in the
segment)
• damaged components
• changes in component behavior.
Date of issue 25.08.2003
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
18 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Troubleshooting Guide
Troubleshooting
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com 19
Troubleshooting Guide
Troubleshooting
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
20 Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
With regard to the supply of products, the current issue of the following document is applicable:
The General Terms of Delivery for Products and Services of the Electrical Industry, as published by
the Central Association of the "Elektrotechnik und Elektroindustrie (ZVEI) e.V.v",
including the supplementary clause "Extended reservation of title".