The document provides specifications for the foundation plan of a structure. It lists requirements for dimensions, materials, design loads, reinforcement, and other construction details. Special notes specify that grade levels and soil conditions need confirmation on site before construction begins. Any discrepancies found between the plans and site conditions must be reported before proceeding.
Original Description:
Original Title
Sp Std _ Dg Set Foundation on Existing Rcc Slab Details_r0_gfc (100 Mm a... (1)
The document provides specifications for the foundation plan of a structure. It lists requirements for dimensions, materials, design loads, reinforcement, and other construction details. Special notes specify that grade levels and soil conditions need confirmation on site before construction begins. Any discrepancies found between the plans and site conditions must be reported before proceeding.
The document provides specifications for the foundation plan of a structure. It lists requirements for dimensions, materials, design loads, reinforcement, and other construction details. Special notes specify that grade levels and soil conditions need confirmation on site before construction begins. Any discrepancies found between the plans and site conditions must be reported before proceeding.
DIMENSION SHOULD BE FOLLOWED. * ALL DIMENSIONS ARE IN MM UNLESS AND OTHERWISE SPECIFIED * HEIGHT, LEVELS AND FOUNDING STRATA SHOULD BE CONFIRMED AT SITE BEFORE CONSTRUCTION * CHANGE IN FILLING HEIGHTS, LEVELS, STRATA ETC. TO BE CONVEYED TO DESIGN TEAM IMMEDIATELY * GRADE OF CONCRETE - M20 UNLESS & UNTIL NOTED PCC -M15 EQUIPMENT LINE * MIN. SBC OF SOIL 75KN/M2 CONSIDERED BREADTH (B)
* DESIGN LOAD CONSIDERED IS 2850KG MAX.
* GRADE OF STEEL - Fe-500 * CLEAR COVER - 50MM * ALL LAPS (LD) SHALL BE STAGGERED & NOT MORE THAN 50% BARS TO BE LAPPED AT ANY GIVEN SECTION. A A * GRADE OF REINF. M20 M25 M30 M35 M40 & ABOVE Fe415 55XD 47XD 44XD 39xD 35xD Fe500 (TMT) 66XD 56XD 53XD 46xD 42xD EXISTING RCC SLAB FOUNDATION PLAN SPECIAL NOTE:- *THE DIMENSIONS AND LOCATIONS OF DG SET TO BE CONFIRM AS PER GA & ARCHITECTURAL DRAWINGS *THE FOUNDATION SHOULD NOT BE REST ON BLACK COTTON SOIL *DG OF SIZE(2500MMX1150MM) TO BE D1
CHECK & CONFIRM BY SITE & ELECTRICAL TEAM .
*IF ANY DISCREPANCY FOUND PLEASE REVERT PRIOR TO THE CONSTRUCTION. LAYER -1 R0 ------ FOR CONSTRUCTION AP SB JG REV. DATE DRN CHCK APPR DESCRIPTION NO BY BY BY SECTION - AA RELIANCE RETAIL LTD TABLE: NOCIL COMPOUND GATE A, RCP TABLE: THANE BELAPUR ROAD, GHANSOLI, MAKE EQUIPMENT DIMENSION SIZE FOUNDATION SIZE REINFORCEMENT LAYER BELOW DG FOUNDATION NAVI MUMBAI 400 701. LENGTH BREADTH LENGTH (L) BREADTH(B) DEPTH (D1) DEPTH (D2) SR NO. DG SET MODEL TOP REINF. (A) BOTTOM REINF. (B) LAYER -1 LAYER -2 LAYER -3 PROJECT TITLE -------------- (KVA) (mm) (mm) (mm) (mm) (ABOVE FGL) (BELOW FGL) (BOTHWAY) (BOTHWAY) 1. ----- 2500 1150 3000 1650 100 0 --- --- EXISTING RCC SLAB NA NA SMART POINT CITY LOCATION SPECIAL NOTE : ---------- ---------- *SILENT TYPE DG SET OF COTTN GROVE IS CONSIDERED. UNIQUE ID : ------------- *DG SET TO BE CHECK AND CONFIRM BY ELECTRICAL & SITE TEAM *EQUIPMENT LOCATION TO BE CHECK AS PER EQUIPMENT GA. DRAWING TITLE: *BASE PLATE LOCATION TO BE CHECK AS PER EQUIPMENT GA. *DG SET DIMENSIONS TO BE CHECK AND CONFIRM AS PER GA. STD DG SET RCC FOUNDATION DETAILS *TRENCHES DIMENSION & LOCATION TO BE CONFIRM AS PER EQUIPMENT GA DRAWING DRAWN BY AP CHECK BY SB *LEVEL OF TOP OF FOUNDATION FROM FGL TO BE CHECK AND CONFIRM BY ELECTRICAL & SITE TEAM. *FOUNDATION SHOULD NOT BE LAIED ON MARSHY LAND AND BLACK COTTON SOIL. APPR BY JG SHEET 1 OF 1 *IF ANY DISCREPANCY FOUND IN DRAWING KINDLY CHECK / INFORM PRIOR TO THE CONSTRUCTION SCALE NTS *THE STRATA BENEATH THE FOUNDATION SHOULD BE WELL DATE R0 COMPACTED BY MANUAL/ MECHANICAL MEANS TO ACHIEVE 95% COMPACTION (PROCTOR DENSITY).