1 Z S E 2 75 0 -107 E N , R E V. 6
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole or in parts – is forbidden
without prior written consent of ABB.
—
Table of contents
Design 5
Shed form 5
Terminals 6
General specifications 6
Testing 7
Test tap 7
Test tap adapter 7
Electrical data 8
Conductor loading 9
Dimensions 10
Connection 11
Recommendations for positioning 12
Ordering particulars 13
TR ANSFORMER BUSHINGS T YPE GOH TECHNIC AL GUIDE 5
—
Design
The bushing is built up around a solid aluminium Both insulators are made in one piece of high
bolt which serves as a conductor for both the quality electrical porcelain. The mounting flange
current and for the heat losses. Cooling flanges is manufactured of corrosion-resistant aluminium
are milled directly in the conductor. alloy.
The upper insulator, lower insulator and mounting The mounting flange is protected by painting
flange are held between the end plates by spring with two-component primer and a grey-blue
pressures. Sealing is accomplished by oil- finishing coat of paint.
resistant rubber gaskets.
The bushings are delivered oil-filled and ready for
The radial seal at the bottom end consists of an use.
O-ring made in a special fluorocarbon rubber.
This material is very resistant to high- The bushing can be vertically or horizontally
temperature transformer oil, and has good mounted. If the bushing is horizontally mounted,
flexibility in the lower temperature range. special measures have to be taken to ensure
sufficient oil filling in the bushing and
The annular space between the condenser body communication with an expansion space. For
and the porcelain is filled with transformer oil. A further information, see the Installation and
gas-filled expansion space is left at the top. maintenance guide.
R8,5
8
R10
9 26
15° 20°
R8,5 70
R5.5
10
15°
20°
R5.5
— —
01 Transformer bushing type GOH. 02 Shed form.
6 TR ANSFORMER BUSHINGS T YPE GOH TECHNIC AL GUIDE
Terminals
Both air side and oil side contact surfaces are
plated with a tin/zinc alloy to prevent oxidizing.
The oil end is provided with threaded holes. The
threads are provided with self locking thread
inserts. The oil end has two contact surfaces
milled directly in the conductor. The air end is
equipped with four drilled flat terminals, welded
to the conductor.
—
03 Oil end..
General specifications
For conditions exceeding the standard specification, please consult the supplier.
Application: Transformers
Classification: Oil impregnated paper, capacitance graded, outdoor immersed bushing.
+40 °C to -40 °C, minimum value acc. to temperature class 2 of IEC 60137 (-50 °C according to
Ambient temperature: GOST 10693-81 item 2.26). +70 °C at bus duct according to IEC.
Altitude of site: < 1 000 m
Level of rain and humidity: 1-2 mm rain/min. horizontally and vertically as per IEC 60060-1.
Pollution level: According to specified creepage distance and IEC 60815.
Immersion medium: Transformer oil (see Conductor loading)
Oil level in transformer: Not lower than 25 mm from the bushing flange.
Max. pressure of medium: 100 kPa over pressure.
Mounting angle: Vertical or horizontal
Markings: Conforming to IEC/ IEEE
TR ANSFORMER BUSHINGS T YPE GOH TECHNIC AL GUIDE 7
—
Testing
Ø4
Measurements for detection of internal partial
discharge (PD measurements) are also made.
These measurements are carried out at the same
time as the power frequency withstand test. PD
measurements are made in steps up to the full
test voltage and down. It is always demonstrated
that the PD value is max. 5 pC at test voltage
equal to the rated system voltage.
—
05 Test tap adapter.
8 TR ANSFORMER BUSHINGS T YPE GOH TECHNIC AL GUIDE
—
Electrical data
Dynamic
Rating Routine test Short time current current Nominal
Nominal Phase- Dry Wet power capacitance
voltage, to-earth lightning frequency 1 min dry Reference 1th 1th 1 between conductor
U m, voltage, impulse, AC, 50 Hz, current 1s 2s Peak and test tap
Type GOH kV, RMS kV, RMS 1.2/50 kV kV, RMS kV, RMS 1)
, kA kA kA kA C1 ±10 % (pF)
170/10 36 21 170 75 80 10 100 2) 100 2) 250 2) 400
170/16 36 21 170 75 80 16 100 2)
100 2)
250 2) 570
170/25 36 21 170 75 80 25 100 2) 100 2) 250 2) 765
1) See Conductor loading
2) Highest value according to IEC 60137.
—
Conductor loading
Example: 25
I = 11 kA
t A2 = 30 °C
∆t = 55 K
GOH 170/16
t0 = t A2 + ∆t t1-tA1 K
20
t0 = 30 + 55 = 85 °C 80 40 0
t A1 = 45 °C
t1 = 105 °C
t1 - t0 = 105 - 85 = 20 K
Ex.
t1 - t A1 = 105 - 45 = 60 K 15
GOH 170/10
t1-tA1 K
The permissible current is obtained from the diagram.
80 40 0
For GOH 170/10 9.3 kA
For GOH 170/16 15.2 kA
10
For GOH 170/25 23.0 kA
GOH 170/16 will in this case be chosen.
0
5 10 15 20 25 30 35
t1 - t0 K
—
07 Current capacity.
10 TR ANSFORMER BUSHINGS T YPE GOH TECHNIC AL GUIDE
—
Dimensions
D=380
D=290
150 200 300
D=14 D=14
40 40 40 40 40 40 40 4040 40
22.5
40
155 40
D=385 D=520
505
265
M8 M8 D=560
M8 D=385
Test tap Test tap
Test tap
920 60
26
30
Max D=272 Max D=357 Max D=453
D=270 155 D=355 D=450
415
M12 M12
120 40 depth 30 depth 30
55
40 40 40 40 60 40
80 132 190
D=170 D=250 D=340
D=20 (12x)
D=20 (8x)
D=20 (8x)
25
25
25
Oil level
M12 plug M8 Oil level
plug M8
M12
M12 Oil level
220 300 400 plug M8
D=350 D=430 D=540
D=400 D=480 D=600
—
07 GOH dimensions.
The dimensions in axial direction are the same for standard GOH 170/10, 170/16 and 170/25.
—
Connection
—
Recommendations for positioning
The maximum stresses in the oil at the surface of 3) Area for uninsulated
earthed details
the conductor insulation must be limited to those
values normal for insulated conductors and
similar components in the same transformer. 3) 70
The adjacent recommendations are intended as Max D (See Fig. 06)
guide lines when complete calculations are not 45°
carried out.
Distance to
R flat surface
e.g. tank or
core clamp
—
08 Recommendations for positioning.
TR ANSFORMER BUSHINGS T YPE GOH TECHNIC AL GUIDE 13
—
Ordering particulars
Insulator colour
Designation Catalogue No. on air side
GOH 170/10 LF 126 007-A Brown
LF 126 007-B Light grey
GOH 170/16 LF 126 008-A Brown
LF 126 008-B Light grey
GOH 170/25 LF 126 009-A Brown
LF 126 009-B Light grey
—
Hitachi ABB Power Grids Sweden
Components
SE-771 80 Ludvika
Sweden
E-mail: sales@se.abb.com
www.hitachiabb-powergrids.com/offering/product-and-system/transformer