Professional Documents
Culture Documents
FIFI Pump Overhaul Instruction
FIFI Pump Overhaul Instruction
01
Sheet no: FFS-485
PUMP OVERHAULING
SFP 250X350 TRANSMISSION PUMP
This instruction is for overhauling of pump side of the SFP 250X350XP(C). For bronze version,
do also see separate instruction FFS-598.
10. Exchange wear rings. Ensure drain hole for large wear ring (item 5) is pointing downwards
(not relevant for bronze pump). Cool wear rings alternative heat the seating and knock in
with Loctite 641. The large wear ring to be installed with the 2x45° guide edge inwards
and to be secured with 6x set screws (item 5). Drill and tap M10 half/half in ring/housing.
11. Install the new Lip seal assembly and change of Sleeve
a. Replace Sleeve with o-ring. Ensure cleaned surfaces and assemble with Silicone
grease (typical Molycote 111).
b. Make sure the sealing lips are clean and filled with Silicone grease.
c. Make sure the O-ring outside Lip seal Housing is in place, clean and with Silicone
grease.
d. Make sure the Sleeve where the Lip seals are running on is on place and surface is
smooth, clean and without marks/scratches.
e. Place the Lip Seal Assemply carefully. Make sure the sealing surface is not
scratching in contact with sharp edges as key or keyway.
12. Install back the 2x M8 bolts in paragraph 7 above. Apply Loctite-243 on threads.
13. Make sure Impeller Key is in place.
14. Install back Fi-Fi Pump Impeller. Ensure it is all the way into position.
15. Place the Impeller Cap (item 10) in paragraph 5 above.
16. Fit the M10 Socket Screw for the impeller cap, apply Loctite-243 on threads, tightening
torque 50Nm.
Page 1 of 5
Written by: RS Rev.01
Sheet no: FFS-485
17. Place back the Fi-Fi pump Casing. Make sure the big O-ring (item 8) is clean, without
scratches and greased with Silicone grease ( typical Molycote 111)
18. Fit all 12x nuts with washers item 17.
19. Align the pump transmission. Final alignment check must be done after bolted to
foundation and Fi-Fi pump Suction/Discharge flanges are connected. Make sure no pipe
stress is transferred to the pump flanges. Check alignment is withing tolerance.
Page 2 of 5
Written by: RS Rev.01
Sheet no: FFS-485
Page 3 of 5
Written by: RS Rev.01
Sheet no: FFS-485
Page 4 of 5
Written by: RS Rev.01
Sheet no: FFS-485
Page 5 of 5