GM8806A-PL

USER
R’’ S M A N U A L

G M 8 8 0 6 A - P L 11 0 1 0 1
48010609 22101 0
©2011,Shenzhen General Measure Technology Co.,
Ltd reserve all copyright.
Without permission from Shenzhen General Measure
Technology Co., Ltd,Any corporations or person must not
copy, spread, record or translate into other language by any
forms.
Our company reserved the right to update user’s
manual without additional notice to make perfect for
customers. Thus please visit our website or contact with our
service person to get update information.
Website:http://www.szgmt.com

GB/T 7724
Approved standard:GB/T 7724——2008
Table
1 General Information............................................................1
1.1 Function.........................................................................1
1.2 Description.................................................................... 2
1.3 Rear illustration............................................................ 3
1.4 Specification..................................................................4
1.5 Dimension..................................................................... 5
2 Wiring................................................................................... 6
2.1 Installation..................................................................... 6
2.2 Power connection........................................................ 7
2.3 Load cell connection....................................................7
2.3.1 Six wires...............................................................7
2.3.2 Four wires............................................................ 8
2.4 I/O terminals..................................................................9
2.5 Analog output connection......................................... 10
2.6 Serial port connection................................................11
3 Calibration......................................................................... 12
3.1 Instruction....................................................................12
3.2 Flow chart....................................................................13
3.3 Millivolt display........................................................... 16
3.4 Calibration without weights.......................................17
3.5 Quick zero/gain calibration....................................... 19
3.6 Parameter table..........................................................19
3.7 Parameter record....................................................... 19
4 Parameter setting............................................................. 20
4.1 Defination.................................................................... 20
4.2 Operation parameter table....................................... 22
5 Recipe setting................................................................... 25
5.1 Recipe number........................................................... 25
5.2 Recipe configuration..................................................25
5.3 Recipe parameter table.............................................26
6 Operation........................................................................... 36
6.1 Operating status.........................................................36
6.2 Batching times setting............................................... 36
6.3 Sort batching in turn.................................................. 37
6.4 Check and clear accumulative total........................ 38
6.5 Manual discharging................................................... 39
6.6 Manual zeroing...........................................................39
6.7 Restore for broken power......................................... 39
6.8 Compensation............................................................ 39
6.9 Free fall compensation..............................................40
6.10 Discharging monitor................................................ 40
6.11 Batching monitor...................................................... 40
6.12 I/O testing..................................................................41
6.13 I/O defination............................................................ 42
6.14 Display testing..........................................................45
6.15 Reset......................................................................... 46
6.16 Backup...................................................................... 47
6.17 Restore backup........................................................47
6.18 Analog calibration & self-definition........................48
6.18 .1 Analog calibration.....................................48
6.18.1
6.18..2 Analog self-definition................................50
6.18
6.19 Password.................................................................. 51
6.20 Password setting..................................................... 51
6.2
6.211 Operation mode..................................................52
7 Automatical batching........................................................53
7.1 Sketch map.................................................................53
7.2 Description.................................................................. 53
8 Serial port communication...............................................55
8.1 RS protocol................................................................. 55
8.2 RE protocol................................................................. 78
8.3 MODBUS protocol..................................................... 80
9 Error and alarm message............................................. 105
GM8806A -PL Batching controller
GM8806A-PL

1 General information
GM8804A-PL batching controller is a kind of weighing
control instruments to control automatic batching machine at
high accuracy and powerful function, which widely used in
various batching systems for concrete, bitumen, fertilizer,
feeding stuff and so on.

1.1 Function
� Small volume, unique design, easy operation;
� Suit to all of load cells at bridge-type resistance strain
gauge;
� 14 I/O
I/O( 4 input / 10 output)
� RS232/RS485 to ensure stable communication;
� Fast, moderate and slow feeding with “Jog feeding” ;
� Multi digital filter;
� Automatical modify for free fall;
� High precision 16bit DA analog output;
� Automatical compensation
� Digital calibration with or without weights;
� Password for calibration, operation parameters etc.;
� Automatic zeroing when power up;
� Automatic zero tracking.
� Three operation modes(optional).

GM8806A-PL1100101
GM8806A-PL11 -1-
GM8806A -PL Batching controller
GM8806A-PL

1.2 Description

P 1-1
Keypad
:Display value when zeroing or exit present function.
:Parameters are optional.
:Set parameter mode.
:Enter parameters or calibration or confirmation.
Status indication:
:Light in batching.
/ :Both SP1 and SP2 light in fast feeding;SP1 SP1
SP2 light in slow feeding.
light in moderate feeding;SP2
:Light in discharging.
:Light for zero when weight is among 0±1/4d 1/4d.
:Light for stability when weight is in stable range.
Display:
Main display
display:6digits, display weight and parameters.
Sub-display
Sub-display:6digits, display G.W. and parameters.
Set point display
display:1 digit, display batching numbers.
-2- GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

1.3 Rear illustration

P 1-2
1 I/O input terminals
2 I/O output terminals
3 Load cell terminals
4 Serial port / analog terminals

5 Power connection

6 Fuse socket

GM8806A-PL1100101
GM8806A-PL11 -3-
GM8806A -PL Batching controller
GM8806A-PL

1.4 Specification
Common:
AC90V
Power supply:AC90V 260V 50Hz (or 60Hz) ± 2%
AC90V~260V
Inside
Filter:Inside
-10
Working temperature:-10 40
-10~40
40℃
90%R.H without dew
Max humidity:90%R.H
About 10W
Power consumption:A
105
Dimension:105
105××151
151××57mm
Analog:
DC5V 300mA (Max)
Load cell power:DC5V
10M
Input impedance:10M
10MΩΩ
0.02
Zero steady range:0.02 9mV
0.02~9mV
0.01uV/d
Input sensitivity:0.01uV/d
0.2
Gain input range:0.2 10mV
0.2~10mV
Sigma - Delta
Transfer mode:Sigma
120times
A/D conversion speed:120times
120times/sec
0.01%F.S
Non-linearity:0.01%F.S
10PPM/
Gain drift:10PPM/
10PPM/℃
1/30000
Display Precision:1/30000
Digital:
6digits red high-brightness LED
Weight display:6digits
Minus display:“-”
OFL
Overload display:“OFL
OFL”
5kinds (optional)
Decimal point:5kinds
-4- GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

1.5 Dimension

GM8806A-PL1100101
GM8806A-PL11 -5-
GM8806A -PL Batching controller
GM8806A-PL

2 Wiring
2.1 Installation

1. Cut hole as left size


in the suitable place of
control box.

2. Screw open in four


corners, then dismantle
mounting plates.

3. Install indicator in
the front of control box.

4. Insert mounting
plates on both sides
and then screw tightly.

P 2-1

-6- GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

2.2 Power connection


GM8806A-PL batching controller connects power as
follows:

P 2-2

1. AC power must connect with ground;


2. Please do not connect indicator’s earth line
with other huge electronic equipment directly.

2.3 Load cell connection


EX+
EX+: Excitation+ EX-
EX-: Excitation- SN+
SN+: Sense+ SN-
SN-: Sense- SIG+
SIG+: Signal+ SIG-
SIG-: Signal-

6 wires EX+ SN+ EX- SN- SIG+ SIG- Shield

4-wires EX+ EX- SIG+ SIG- Shield

1) 6 wires connection:

P 2-3
GM8806A-PL1100101
GM8806A-PL11 -7-
GM8806A -PL Batching controller
GM8806A-PL

2) 4 wires connection

P 2-4

1. As load cell output sensitive analog signal,


please use shield cable to separate with other
cables, especially AC power;
2. 4 wires connection is suitable for short distance
and stable temperature or low precision field,
otherwise use 6 wires connection.
3. For more load cells parallel connection, their
mV/V
sensitivity (mV/V
mV/V) should be same.

-8- GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

2.4 I/O terminals


GM8806A-CZ Weighing indicator transfer data by
optoelectronic isolation technology, thus need 24V DC
outside as power supply, which anode connect with indicator
24V +, and cathode with 24V- through the COM1 (DC+)
and the COM 2 (DC -) . The input signal is low level
effective, and the output is transistor open-collector output,
which driving current can reach 500mA .
I/O definition as follows:

P 2-5

Indicator input terminal connection:

P 2-6
Indicator output terminal connection:

GM8806A-PL1100101
GM8806A-PL11 -9-
GM8806A -PL Batching controller
GM8806A-PL

P 2-7
I/O tolerant definition as follows:
Output Input
Manual
OUT1 Mater ial no. 1 IN1
dischar ging
OUT2 Mater ial no. 2 IN2 Run
OUT3 Mater ial no. 3 IN3 Pause
OUT4 Mater ial no. 4 IN4 St op
OUT5 Fast feeding
OUT6 Moderat e feeding
OUT7 Slow feeding
OUT8 Discharging
OUT9 Over tolerance
OUT10 Run
2.5 Analog output connection
Analog output two kinds: voltage and electric current.
For voltage output, 0-5V/0-10V/-5-5V/-10-10V is optional
for voltage output;4-20mA/0-20mA/0-24mA is optional for
electric current output. Define terminals as follows:

- 10 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

P 2-8
Note : Analog output is optional function, please declare if
need when place orders.
2.6 Serial port connection
Serial port(RS485 or RS232) connection as follows:

P 2-9
RS232 connection:

P 2-10
RS485 connection:

GM8806A-PL1100101
GM8806A-PL11 - 11 -
GM8806A -PL Batching controller
GM8806A-PL

Controller 1 A A

Computer
B B
GND GND

.
.
. GND is ground of RS 4 8 5 , it can very
mu c h imp ro v e c o mmu n ic a tio n
A quality via connecting with GND by
Controller n

l o w -resistance wire when there is a lot


B of disturbance in working field .

GND
P 2-11

3 Calibration
3.1 Instruction
GM8806A-PL batching controller need calibrate at
beginning of operation or changing any parts on weighing
system or non-suitable application for user. The calibration
can define radix point, minimum scale division, maximum
scale capacity, zero and gain, etc.
User can press to enter next or press to
save setting to only change one parameter, and then
press to exit.

- 12 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

3.2 Flow chart


Press to display
CAL , and then press
to enter
password.

Input correct
password , when
CAL ON
display “CAL ON” one
second, then enter to
set radix point
automatically.

GM8806A-PL1100101
GM8806A-PL11 - 13 -
GM8806A -PL Batching controller
GM8806A-PL

1) Press set radix point


(0~0.0000 5 kinds optional) ,
press to save and enter
mini division.
2) If not change radix point,
press directly to enter
mini division.
1) Press to set mini
division(1~50 6kinds
optional),press to save
and enter max. capacity.
2) If not change mini division,
press directly to enter
max. capacity.

1) Input max. capacity(≤mini


division × 30000),press
to save and enter millivolt
display.
2) If not change, press
to enter millivolt display
directly.

1) Select suitable sensitivity


based on load cell,
press to save and enter
millivolt display. Otherwise to
press directly to enter
millivolt display.

- 14 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

1) When load cell output


millivolt value, press to
enter zero calibration directly.
2) The display value is similar
with millivolt from SIG+/SIG-
terminals. See Character 3.3
for details.
1) When scale platform is
stable, press to take
present weight as zero,and
enter gain calibration.
2 ) Press to reserve
original zero and enter gain
calibration.
1) Gain calibration as the
left chart.
▲When calibration with
weights, please record zero
millivolt, gain millivolt and
weight value in list. If no
weights, user will calibrate
according to these data.
2) Press to enter
password directly, no gain
calibration.
1) See Character 5.11 to set
password, then press to
exit calibration and return.
2) If not set password,
press directly to return.
GM8806A-PL1100101
GM8806A-PL11 - 15 -
GM8806A -PL Batching controller
GM8806A-PL

Normal working status.


3.3 Millivolt display
This function is mainly used to test weighing system,
four-corner position-error of force-transmitted equipment
and load cell’s linearity.
1. Test weighing system
(1) If the indicator display variational millivolt value
according to add weight, thus indicate load cells are
connected correctly and force-transmitted equipment is
operated normally.
(2) If the indicator display OFL (or –OFL), thus indicate
the weight is too heavy (or too light), then need unload (or
add) the weight. But if always display OFL (or –OFL) after
changing weight, maybe the following reason cause:
a. Please check force-transmitted equipment.
b. Please check the load cell’s connection.
c. Please check Load cells.
2. Test four-corner position-error of force-transmitted
equipment
Please load same weight on scale’s every corner and
record individual millivolt value. If the values are obviously
different, please adjust force-transmitted equipment.
3. Test load cell’s linearity

- 16 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Please load several same weight values within the


weighing capacity and record relevant millivolt value after
zeroing every time; if the discrepancy is bigger among
millivolt values, thus indicate that the load cell’s linearity is
not good, need change new load cell or adjust
force-transmitted equipment.

3.4 Calibration without weights


Calibration without weights is only for urgency. If
change new load cells or indicator, or adjust weighing
system, calibration without weights is not correct.

GM8806A-PL1100101
GM8806A-PL11 - 17 -
GM8806A -PL Batching controller
GM8806A-PL

- 18 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

3.5 Fast zero / gain calibration


In weighing status, press for long time, when
display password input, then input password correctly and
enter zero calibration. See Character 6.19 for details.
3.6 Calibration parameter table
Initial
Sign Parameter Type Division
value
Decimal 0,0.0,0.00,0.000,
Point 5 0
point 0.0000
1d= Mini division 6 1,2,5,10,20,50 1
Max
CP ≤mini division×30000 10000
capacity
System
St
millivolt
SE Sensitivity 2 2,3 2(mV/V)
E SCAL Zero
AddLd(d) Gain
Set
PASS 000000
password
3.7 Calibration parameter record
Parameter Valued Date Remark
Decimal point position
Mini division
Max capacity
Load cell sensitivity
Password setting
List(calibration with weights):
Zero Gain
Weights
Times millivolt millivolt Date Remark
(Kg
Kg
Kg)
(mV
mV
mV) (mV
mV
mV)
1
2
3
GM8806A-PL1100101
GM8806A-PL11 - 19 -
GM8806A -PL Batching controller
GM8806A-PL

4 Parameter setting

Note : Press to switch among


parameters ; press to enter next
menu ; press to return previous
menu.See Chapter 4.1 for details.

4.1 Defination
Press to select parameters, then press and
to set parameters, after that, press to save
setting.
1)Optional
Optional parameter setting
ON
Set“parameter 5 ”(ON
ON)for example:

- 20 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

1. Press , then sub-display


OFF
sparkle “OFF
OFF”.

2. Press , then sub-display


ON
show“ON
ON”.

3. Press to save setting. If not


need set other parameters,
press to return.
2)Numerical
Numerical parameter setting
Set “parameter 7”(as 35)for example:

1. Press 5”
, sub-display sparkle “5
in the left.

2. Press 3”,
till sub-display show “3
then press ,sparkle move to the
right one.

3. Press 5”,
till sub-display show“5
then press to save and finish.

GM8806A-PL1100101
GM8806A-PL11 - 21 -
GM8806A -PL Batching controller
GM8806A-PL

4.2 Operation parameter table


No. Para. Initial Description

1 01 99
01~99 01 Scale no.

1200~57
2 9600 Baud rate
600

Communication mode:
Read/Cont are optional in
Rs/Re
3 Rs item 3.1 for Rs/Re mode;
/Bus
Rtu/Asc is optional in item
3.1 for Bus mode.

Rs/Re mode:
Read/Co READ
READ:command;
3.1 Cont
nt
CONT
CONT:continue

Serial port data-sent speed


for CONT at Rs/Re mode:
3.1.1 0~5 1
1-5
1-5:means 10-50ms
10-50ms;
0:means one character time.

MODBUS communication
3.1 Rtu/Asc Rtu
mode: Rtu or Asc

MODBUS dual-byte register


storage turn for Rtu at
MODBUS
MODBUS:
Hi Lo
3.1.1 Hi Lo Hi Lo
Lo:High byte in the front,
Lo Hi
low byte at back;
Lo Hi
Hi:Low byte in the front,
high byte at back.

- 22 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Data format:
18N2 18N2
18N2: (R / C / B_r optional);
18E1 18E1
18E1: (R / C / B_r optional);
18O1
18O1:(R / C / B_r optional);
18O1
4 18N1 18E1
18N1
18N1: (R / C / B_r optional);
17N2
17E1 17N2
17N2: (RR / C optional);
17O1 17E1
17E1: (RR / C optional);
17O1:(R
17O1 R / C optional).

Automatic zeroing when


5 ON/OFF OFF
power on

Zero tacking range(00~99d


6 00 99
00~99 01 optional).
If setting 0, not zero tracking.

Zeroing range(01%~99% of
7 01 99
01~99 50
full capacity).

Stability criterion range(01~


8 01 99
01~99 01
99d optional).

Digital filter parameter


9 0~9 5
0:no filter;9:strongest filter

Stability filter: Second filter


10 0~9 0 based on first one:
0:no filter;9:strongest filter

Zeroing/tare-off operation
b_zero / before batching:
11 b_zero
b_tare b_tare
b_tare:tare off;
b_zero
b_zero:zeroing.

GM8806A-PL1100101
GM8806A-PL11 - 23 -
GM8806A -PL Batching controller
GM8806A-PL

Switch for Zeroing/tare-off


ON / operation before batching:
11.1 OFF
OFF ON
ON:operate;
OFF
OFF:shut.

Switch to count manual


ON / discharging into
12 OFF
OFF accumulative total:
ON
ON:yes;OFF OFF
OFF:not.

Material numbers. For


13 1~4 4 example, 1 means only to
batch one kind of material.

Save when power off:


ON / ON
ON:Restore after restart
14 OFF
OFF again when power off;
OFF
OFF:not restore.
Analog output:
4-20 / 4-20 4-20mA
4-20:4-20mA
0-20 / 0-20 0-20 mA
0-20:0-20
0-24 /
0-24 0-24 mA
0-24:0-24
15 0-5 / 4-20
0-10 / 0-5 :0-5V
0-5V
-5-5 / 0-10 0-10V
0-10:0-10V
-10-10 -5-5 :-5-5V
-5-5V
-10-10 :-10-10V
-10-10V
ON /
16 OFF Password switch
OFF
Password setting. See
16.1 ******
Character 6.20 for details.

- 24 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

5 Recipe setting

5.1 Recipe number


GM8806A-PL can store 40pcs recipes related number
01~40, which can be configured by user.
5.2 Recipe configuring
1) Optional recipe parameters
Alternate between recipe parameters F1~F12 by ,
enter by and return by .
GM8806A-PL1100101
GM8806A-PL11 - 25 -
GM8806A -PL Batching controller
GM8806A-PL

2) Configure recipe parameters


In recipe item, user can press to enter to check or
change.
5.3 Recipe parameter table

No. Par a. In i ti al Descri p ti o n

F1 U_LS et None None


Target value of material
1.A1 xxxxxx 000000
1.
no.1

Leading quantity of fast


feeding for material no.1;In
faxed value,if weight ≥
1.A2 xxxxxx 000000
target value - leading
quantity of fast feeding,then
fast feeding stop.

Leading quantity of
moderate feeding for
material no.1;In faxed
1.A3 xxxxxx 000000 value,if weight ≥ target
value - leading quantity of
fast feeding,then moderate
feeding stop.
Free fall value of material
no.1;In faxed value,if
1.A4 xxxxxx 000000 weight ≥ target value – free
fall value,then slow feeding
stop.
Target value of material
1.b1 xxxxxx 000000
2.
no.2
- 26 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Leading quantity of fast


feeding for material no.2;In
faxed value,if weight ≥
1.b2 xxxxxx 000000
target value - leading
quantity of fast feeding,then
fast feeding stop.
Leading quantity of
moderate feeding for
material no.2;In faxed
1.b3 xxxxxx 000000 value,if weight ≥ target
value - leading quantity of
fast feeding,then moderate
feeding stop.
Free fall value of material
no.2;In faxed value,if
1.b4 xxxxxx 000000 weight ≥ target value – free
fall value,then slow feeding
stop.

1.C1 xxxxxx 000000 Target value of material


3.
no.3
Leading quantity of fast
feeding for material no.3;In
faxed value,if weight ≥
1.C2 xxxxxx 000000
target value - leading
quantity of fast feeding,then
fast feeding stop.
Leading quantity of
moderate feeding for
material no.3;In faxed
1.C3 xxxxxx 000000 value,if weight ≥ target
value - leading quantity of
fast feeding,then moderate
feeding stop.
GM8806A-PL1100101
GM8806A-PL11 - 27 -
GM8806A -PL Batching controller
GM8806A-PL

Free fall value of material


no.3;In faxed value,if
1.C4 xxxxxx 000000 weight ≥ target value – free
fall value,then slow feeding
stop.

1.d1 xxxxxx 000000 Target value of material


4.
no.4
Leading quantity of fast
feeding for material no.4;In
faxed value,if weight ≥
1.d2 xxxxxx 000000
target value - leading
quantity of fast feeding,then
fast feeding stop.
Leading quantity of
moderate feeding for
material no.4;In faxed
1.d3 xxxxxx 000000 value,if weight ≥ target
value - leading quantity of
fast feeding,then moderate
feeding stop.
Free fall value of material
no.4;In faxed value,if
1.d4 xxxxxx 000000 weight ≥ target value – free
fall value,then slow feeding
stop.
Zero value;In faxed value,
if weight ≤ zero value,shut
1.e0 xxxxxx 000000
discharging output after
t7..
time t7

Time setting: press to


F2 Ti set None enter, or press into
F3..
item F3
- 28 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Feeding after time t1:


00.0 99. 9
00.0~99.
F2.1 00.5 Feeding after time t1 at the
seconds beginning of baching.

No contrast time t2 in fast


feeding: When fast
feeding within time t2, the
00.0 99. 9
00.0~99. batching controller don’t
F2.2 00.5
seconds contrast present weight with
the value (target value -
leading quantity of fast
feeding).

No contrast time t3 in
moderate feeding:
When moderate feeding
within time t3, the batching
00.0 99. 9
00.0~99.
F2.3 00.5 controller don’t contrast
seconds present weight with the
value (target value - leading
quantity of moderate
feeding).

No contrast time t4 in slow


feeding: When slow
feeding within time t4
t4, the
00.0 99. 9
00.0~99.
F2.4 00.5 bataching controller don’t
seconds contrast present weight with
the value (target value - free
fall value).

Over tolerance checking


00.0 99. 9
00.0~99. time t5
t5:: Check over
F2.5 00.5
seconds tolerance in stability after
time t5
t5.

GM8806A-PL1100101
GM8806A-PL11 - 29 -
GM8806A -PL Batching controller
GM8806A-PL

Fixed value time t6 after


00.0 99. 9
00.0~99.
F2.6 00.5 time t5 is over, then begin to
seconds discharge.

Shut off discharging after


00.0 99. 9
00.0~99.
F2.7 00.5 time t7 when weight is less
seconds than zero value.

Discharging monitor time t8 t8::


000 999
000~999 shut discharging if
F2.8 000
seconds discharging signal is still
effective after time t8
t8..

Batching monitor time t9


(Fast and slow feeding
000 999
000~999 effective time): alarm output
F2.9 000
seconds when system haven’t
finished batching within time
t9..
t9

Feeding mode:
ON
ON:Fast, moderate and
slow feeding individually.
Press to enter F3.1
F3.1;
F3 ON/ OF F OF F
press F4..
to enter F4
OFF
OFF:Fast, moderate and
slow feeding together.
Press or F4..
to F4

Pause time t10 between


fast feeding and moderate
00.0 99. 9
00.0~99.
F3.1 00.0 feeding: when fast feeding
seconds
finished, moderate feeding
t10..
start after time t10
- 30 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Pause time t1 1 between


t11
moderate feeding and slow
00.0 99. 9
00.0~99.
F3.2 00.0 feeding: when moderate
seconds
feeding finished, slow
feeding start after time t11.
t11

Over/under tolerance
alarm:
ON
ON:press to enter
F4 ON/ OF F OF F F4.1;press to enter F5
directly;
OFF: press or to
enter F5 directly.

Over tolerance percent:


When fixed value,if weight
F4.1 0.0 9. 9
0.0~9. 0. 5 ≥ target value + target value
× over tolerance percent,so
it is over tolerance.

Under tolerance percent:


When fixed value,if weight
F4.2 0.0 9. 9
0.0~9. 0. 5 ≤ target value - target value
x under tolerance percent,
so it is under tolerance.
Pause switch for
Over/under tolerance:
ON
ON:When over or under
tolerance, pause to wait for
4.3 ON/ OF F OF F
user. Batching controller
display present net weight,
so user can press or
input “clear alarm” effective

GM8806A-PL1100101
GM8806A-PL11 - 31 -
GM8806A -PL Batching controller
GM8806A-PL

signal, then go on;Also can


input “stop” effective signal
to return stop state.
OFF
OFF:When over or under
tolerance, batching
controller only output alarm
message, but not stop.
Over/under tolerance alarm
time t: When Over/under
00.0~99.9
F4.4 00.5 tolerance pause is off,
seconds
batching controller will
output alarm within time t.
Free fall compensation:
ON
ON:Press to enter
F5 ON/OFF OFF F5.1
F5.1;Press to enter F6
directly.
OFF
OFF:Press or to
enter F6 directly.

Free fall compensation


times: The indicator will
F5.1 00 99
00~99 01
make this average as
compensation value.

Free fall compensation


percent of target value: If
free fall value is more than
F5.2 00 99
00~99 02
the percent of target value,
the value will not be
accounted to average.
Free fall compensation
F5.3 1~3
3 2 range: 1 for 100%;2 for
50%;3 for 25%.
- 32 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Discharging-controlled
switch:
ON
ON:Press to enter
F6.1
F6.1;Press to enter F7
F6 ON/OFF OFF
directly.
OFF
OFF:Press or to
enter F7 directly,Initial as
OFF..
F6.1=F6.2= OFF
Discharging mode switch:
ON
ON:Discharge directly after
batching one kind of
F6.1 ON/OFF OFF
material.
OFF
OFF:Discharge when all of
material batching finished.
Discharging-permited
switch:
ON
ON:Discharge till received
F6.2 ON/OFF OFF
discharging signal.
OFF
OFF:Discharge directly
when finish batching.
Supplement switch:
ON
ON:Press to enter
F7 ON/OFF OFF F7.1
F7.1;Press to enter F8
directly.
OFF
OFF:Press or to
enter F8 directly.

GM8806A-PL1100101
GM8806A-PL11 - 33 -
GM8806A -PL Batching controller
GM8806A-PL

Jog-feeding supplement
times for under tolerance. If
F7.1 00 99
00~99 03
the weight is still under
tolerance, then stop directly.

00.0 99. 9
00.0~99. Jog-feeding supplement
F7.2 00.5
seconds effective time.

00.0 99. 9
00.0~99. Jog-feeding supplement
F7.3 00.5
seconds alternation time.

Jog-feeding output switch:


ON
ON:Press to enter
F8 ON/OFF OFF F8.1
F8.1;Press to enter F9
directly.
OFF
OFF:Press or to
enter F9 directly.

Jog-feeding output time:


00.0 99. 9
00.0~99.
F8.1 00.5 Slow feeding effective time
seconds
ta every time.

Jog-feedingoutput time:
00.0 99. 9
00.0~99.
F8.2 00.5 Slow feeding ineffective
seconds
time tb every time.

In stop status,sub-display:
dsp_re
dsp_re:Recipe no.;
dsp_DA
dsp_DA:Analog;
sdp_DA/
F9 dsp_re rdp_s1
rdp_s1:Accumulative total
sdp_re
for present material;
rdp_s3
rdp_s3:Total feedling
value.

- 34 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

In run status, sub-display:


rdp_fi
rdp_fi:Target value for
present material;
rdp_fi
rdp_s1
rdp_s1:Accumulative total
rdp_s1
F10 rdp_fi for present material;
rdp_s2
rdp_s3 rdp_s2
rdp_s2:Target value –
feeding value for present
material;
rdp_s3
rdp_s3:Total feeding value.

Batching compositor
switch:
ON
ON:Press to enter
F11 ON/OFF OFF F11.1
F11 .1;Press to enter
F1
F122 directly.
OFF
OFF:Press or to
F1 2
enter F12 directly.

XXXX sort in turn as 1、2 2、33、


4 from high to low in turn.
For example, if input 4231
4231,
F11.1 XXXX 1234
sort batching in turn from
4#
4#、2#2# 3#
2#、3#
3#、1#1#
1#,and XXXX
every digits are not same.

Password for recipe


F12 ON/OFF OFF
parameters.

Please refer Character 6.20


F12.1 ******
for details to set password.

GM8806A-PL1100101
GM8806A-PL11 - 35 -
GM8806A -PL Batching controller
GM8806A-PL

6 Operation
6.1 Operation status
1. When power on, buzzer hoot, main and sub-display
flash “8”,and instruction lights also sparkle.
2. After finished, main display
show “8806-P” , and sub-display
show “software no. ”.
3.(1)When operation parameter
no. 14=OFF or F14=ON power off in
stop status, batching controller show
present weight after display working mode and software no.
within 3 seconds.
(2)When operation parameter
14=ON and power off in running
no.14=ON
status, main display show gross weight, sub-display
show“Conti?” after display working mode and software no.
within 3 seconds. ID no. is material no. before power off,
such as right chart, material lno.3 is batching when power
off.

At this time, press to continue last batching


process;press to begin new batching process.
6.2 Batching times setting

0~9999.. When finished,


Batching times range is from 0~9999
ERROR5
batching controller display “ERROR5
ERROR5” alarm and pause.
When user press or input “clear alarm” effective signal,
batching controller return stop status.
- 36 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

3” as follows:
For example, set batching times “3

1. In stop status, press (4times


4times) till
main display show bAt.

2. Press to enter and sub-display


0000
show“0000
0000”and sparkle in hight digit.

3. Press to move sparkling digit to


the left, then press till sparkling digit
change to“3 3”.

4. Press to save and finish, then


press to return stop status.

1. If batching times are zero, then enter stop status


directly after discharging.
2. If batching several kinds of material individually,
only when total batching finished, batching controller
check if batching times are up.

6.3 Sort batching in turn


1) Operation parameter 13 to set material kinds and
recipe parameter F11 range.
For example, if operation parameter 13 set 3, which
means to batch 3kinds of material, then recipe parameter
F11 set the front 3digits, the fourth figit is 0. 。
2)Recipe parameter F11.1 to scort batching in turn(F11
is ON ERROR
ON). If setting value is illogicality, then outpt “ERROR
ERROR”
message.
GM8806A-PL1100101
GM8806A-PL11 - 37 -
GM8806A -PL Batching controller
GM8806A-PL

For example:operation parameter 13=3 and material


no. is 1、33、4,
4, so F11.1 “4310
4310
4310” to scort 4-3-1 in turn.
6.4 Check and clear accumulative total
1. In stop status, press (5times
5times) till
main display show total. Press to
enter material no. 1 accumulative total.
2. ID no.1 means accumulative total for
material no. 1. Accumulative total display
9digits at most, which main display show
3digits and sub-display show 6digits. For
example, main display show high 3digits
and the sub-display show low 6digits, the
accumulative total for material no. 1 is
123456789 as left chart.

3. Press to check accumulative total


of material no. 2-4.

4. When state show“tt”, it displays total


value of 4 kinds of materials.

5. When state shows“n n”, it display


accumulative total times, which can
display 6digits at most in main display.

1. When accumulative total disply, press for


sparkle value, then press to clear accumulative total
value, and return stop status.
2. Not clear accumulative total value when running.

- 38 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

6.5 Manual discharging


In stop status, input“manual discharging”signal,
batching controller output effective discharging signal; input
“manual discharging”signal again, then batching controller
output ineffective discharging signal.

In running status, after fixed value, when


received“discharging permit”effective signal, batching
controller output“discharging”effective signal to discharge.
6.6 Manual zeroing
When stop, press or input “zeroing” signal to clear
gross weight value.
Note: Operation must be in stable status or gross
weight is in the zeroing range. Otherwise the indicator will
display ERROR3 or ERROR2.
6.7 Save for broken power
When operation parameter 14 is ON, if power is broken,
batching controller can restore previous working status after
power restart again.
6.8 Compensation
When recipe parameter F4 is ON and present weight is
under tolerance, so batching controller begin compensation
if receipe parameter F7 is ON. After that, if present weight
ERROR9
still is under tolerance, then output “ERROR9
ERROR9” alarm
message within one second and return stop status.
GM8806A-PL1100101
GM8806A-PL11 - 39 -
GM8806A -PL Batching controller
GM8806A-PL

Batching controller begins compensation as following


mode:
(1)Present weight <target value – leading quantity of
fast feeding, restart fast, moderate and slow feeding again;
(2)Target value - leading quantity of fast feeding ≤
present weight≤ target value – leading quantity of moderate
feeding, restart moderate and slow feeding again;
(3)Target value – leading quantity of moderate
feeding ≤ present weight ≤ target value – leading quantity of
slow feeding, restart jog feeding.
6.9 Free fall compensation
When recipe parameter F5 is ON ON, batching controller
compensate free fall value automatically.

User need press long time to save the

compensation value in stop status.


6.10 Discharging monitor
After“discharging signal”is effective, then discharge within
discharging monitor time t8. After time t8 is over,
discharging signal is still effective, then
ERROR6
output“ERROR6
ERROR6”alarm message within one second and
0”, shut discharging monitor.
return stop status. If time t8 is“0
6.11 Batching monitor
In batching proceed, if the system hasn’t finish within
batching monitor time t9 ERROR7
t9, then output“ERROR7
ERROR7”alarm
message within one second and return stop status. If time t9
0”, shut batching monitor.
is“0
- 40 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

6.12 I/O testing


Press to switch among OUT1~OUT10 and
press to return. Please refer following flow chart:
Stop

Press tStio
8 times till main-display show“tStio
tStio”.

Sub-display indicate
F means IN1~IN4
Press , from left to right,
main-display when input
show“inPUt” effectively, F change
to O.
For example, F
change to O indicates
IN1 input effectively
Press to
and connect correctly.
enter I/O
input testing. OUTPUT means
testing. Main-display
show output number,
Press , sub-display show
main-display status.
oUtPUt
show“oUtPUt
oUtPUt”
Press ,sub-display
OFF change to ON
indicates OUT1 output
effectively and connect
correctly.
Press to Press to switch
enter I/O output numbers, such
output testing. as from OUT1 to
OUT2
OUT2.

GM8806A-PL1100101
GM8806A-PL11 - 41 -
GM8806A -PL Batching controller
GM8806A-PL

6.13 I/O definition


When stop, user can define I/O ports by and
to return.
The flow chart is to define OUT3 as O5
O5(SP5) for
example:
When stop, press 4times, main
iodEF
display show“iodEF
iodEF”.

Press to input correct calibration


password, the press to define. See
Character 6.19 for details.
Main display shows output and
sub-display show code, press till
main display show OUT3.

Press 05, then


till sub-display show05,
press to finish.

If not need define others, press to


return.
When slow feeding effect , OUT3
ouput effectively.
Output code table
table:
Ou tp u t
Co d e Defi n i ti on Descri pt i on
O0 None No def init ion
O1 Run Effective in unning status
O2 Stop Effective in stop status
- 42 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Begin fast feeding when weight


O3 Fast feeding <| target value – leading quantity
of fast feeding.

Begin moderate feeding when


Moderate
O4 weight <| target value – leading
feeding
quantity of moderate feeding.
Begin slow feeding when
O5 Slow feeding present weight <| target value –
free fall value.
O6 Ingredient no.1 Batching ingredient no.1
O7 Ingredient no.2 Batching ingredient no.2
O8 Ingredient no.3 Batching ingredient no.3
O9 Ingredient no.4 Batching ingredient no.4
Fixed value between slow
O10 Fixed value
feeding and discharging.

O11 Over / under Effective in over/under tolerance.


tolerance
O12 Discharging T4
T4..
Discharge material after timeT4
Effective when present net is
O13 Zero
less than near-zero value.
O14 Stability Effective when stability light on.
Effective when over/under
O15 Alarm tolerance, batching times
finished and so on.

O16 Finish batching Effective when finish batching


times times.
O17 Pause Effective in pause status.
GM8806A-PL1100101
GM8806A-PL11 - 43 -
GM8806A -PL Batching controller
GM8806A-PL

Input
Co d e Defi n i ti on Descri pt i on
Enter run status when impulse
I1 Start
input is effective.
Return to stop status when
I2 Stop
impulse input is effective.
Zeroing for gross weight when
I3 Zero
impulse input is effective.
Clear alarm when impulse input
I4 Clear alarm
is effective.
40.. If target value
Recipe no. 1 to 40
I5 Recipe no.
is 0, then go to next one.

Manual In stop status, manually


discharge from the hopper. Input
discharging /
I6 one time to discharge, again to
discharging
stop. In running status, permite
permission to discharge.

I7 Keypad lock Only can press effectively.


Enter pause status in running
I8 Pause
when impulse input is effective.
I9 Tare off Tare off and return net status.
Clear tare and return gross
I10 Clear tare
weight status.
Enter run / stop status when
I11 Run / Stop
level input is effective.

Note: Same input/output code can be defined as several


inputs/outputs, such as both IN1 and IN2 are defined as I3
I3.
- 44 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

6.14 Display testing


The following flow chart is to test lights on main-display
and sub-display, status and instruction:
Press 7 times in stop status
till main display show “tStdip”.

Press till all of main display,


sub-display and status lights are
bright.

Press till all of lights shine and


sparkle at 2seconds/time.

Press 2times to exit testing and


return.

GM8806A-PL1100101
GM8806A-PL11 - 45 -
GM8806A -PL Batching controller
GM8806A-PL

6.15 Reset
Reset present parameters to initial setting.
io
Reset “I/O definition (io
io)” for example:
1. In stop status, press till main
display show “init”.

2. Press to input correct calibration


password. See Character 6.19 for
details.

3. Press io
till sub-display show“io
(I/O definition”.
SETUP
Note: “SETUP
SETUP”to backup operation
CAL
parameters; “CAL
CAL”to backup calibration
rECiPE
parameters; “rECiPE
rECiPE”to backup recipe
parameters; “ALLALL
ALL”to reset all of
parameters.

4. Press , sub-display
YES?
show“YES?
YES?”.

5. Press , sub-display
SUCCES
show“SUCCES
SUCCES”to enter next
parameters. Press to return.

1. Suggestion: When reset, please backup first to be


used in the future.

- 46 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

6.16 Backup
User can make all of parameters backup.
ALL
Make“all of parameters (ALL
ALL)”backup for example:
1. When stop , press till main
display show bAC
bAC””.
“bAC And then
press input calibration password,
sub-display show “SET UP
UP””.

2. Press ALL
till sub-display show“ALL
(all of parameters)”
SETUP
Note: “SETUP
SETUP” operation parameters
CAL
backup; “CAL
CAL”calibration parameters
io
backup; “io
io”I/O definition backup.
rECiPE
“rECiPE
rECiPE”recipe parameters backup.

3. Press YES?
, sub-display show“YES?
YES?”,
then press to confirm and enter
next parameters. Otherwise
press to exit and return stop status.

6.17 Restore backup


User can restore all of parameters to backup status.
Operation to restore backup is similar with backup
rbAC
operation. When main display show “rbAC
rbAC”, press to
enter and restore. See Character 6.16 for details.

GM8806A-PL1100101
GM8806A-PL11 - 47 -
GM8806A -PL Batching controller
GM8806A-PL

6.18 Analog calibration & self-definition


1. In stop status, press till main
display show CALdA.

2.Press to input correct


calibration password, and then
press to enter analog self-
SET
definition (sub-display show“SET
SET”).

3.Press to set analog


self-definition parameters. Press
to switch analog calibration.

4.Press to set analog


calibration parameters.

6.18.1 Analog calibration


4mA
Calibrate at 4 values:4mA 12mA
4mA、12mA 20mA and maximum
12mA、20mA
current.
1) 4mA
4mA:Main display shows CAL DA, sub-display 10923 ,
ID indicates 1;
2) 12mA
12mA:Main display shows CAL DA, sub-display 32768,
ID indicates 2;
3) 20mA
20mA:Main display shows CAL DA, sub-display 54613,
ID indicates 3;
maximum current:Main display shows CAL DA, sub-display
24.000
24.000.
12mA output” and “Max. current”:
For example: calibrate “12mA

- 48 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

1. Press to calibrate 4mA.

2. Press 12mA,,
to calibrate 12mA
which ID indicate from 1 to 2;
Calibrate 20mA when ID indicate
3; If no ID indication, it calibrates
maximum current.

Note: Press long time in


calibration, sub-display value for all of
analog output restore to initial value.

Calibration method:
1. Please connect multi-meter with analog output terminals
correctly in calibration.
2.If the analog output value from multi-meter and terminals
are different, press , so sub-display sparkle, and then
press or to change DA digits and adjust analog
output value to be same as calibration value, after that,
press to finish.
3. If the analog output value from multi-meter and terminals
are same, press to next calibration item.
4.No need adjust DA digits to calibrate maximum analog,
only input analog value from multi-meter in the calibration.
6. Press to exit.
GM8806A-PL1100101
GM8806A-PL11 - 49 -
GM8806A -PL Batching controller
GM8806A-PL

6.18.2 Analog self-definition


1. Press to define voltage and
current parameters.

2. Press , sub-display sparkle, and


then press to switch and
press to save. After that,
press to define analog value.

3. Analog self-definition: minimum


analog value, zero analog value,
maximum capacity analog value and
maximum analog value.
Main display show SP1 SP2
SP1、SP2
SP2、 SP3
SP3、
SP4, which switch by .
Definition description:
1) minimum analog value is output analog value of minimum
analog. When the weight is less than zero,the linearity
between zero and maximum capacity is decreasing, then
stop to decrease at this value.
2) zero analog value is output analog value when the
indicator show zero. For example, SP0 define iout as 5.000,
so the analog value output 5.000mA when when the
indicator show zero.
3) maximum capacity analog value is output analog value
when the indicator show maximum capacity.
4) maximum analog value is output analog value when the
weight is overflow.
- 50 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

6.19 Password
All initial passwords are :000000
000000
000000。
Note:Calibration password is same password as reset,
backup, restore, I/O definition and analog calibration. When
calibration password changed, others also changed.
Password operation as follows
1. Press to enter password.
2. Press to input password.
Note: If input wrong,sub-display
Error
show“Error
Error”, then press again. If
input wrong for three times, main display
Error4
show“Error4
Error4”and self-lock, but user can
operate again when power on again.
3. Input correct password, then
press to set parameters.
6.20 Password setting
ON
User can set password in parameters when F6.1 is“ON
ON”.
Set operation parameters password for example:
1.When operation parameter 16 set
ON
ON,press ,main display show
16.
6.11,then press , main display
show PASS
PASS, enter password.
2. Press and in turn to input
password.
Note: User must input same new
passwordtwice to set password. If not
Error
same, main display show“Error
Error”one
second and return to PASS again.
3. Once input same new password
twice, press to save and return
16.1.
GM8806A-PL1100101
GM8806A-PL11 - 51 -
GM8806A -PL Batching controller
GM8806A-PL

6.21 Operation mode


GM8806A has three modes: weighing mode, bagging
mode and batching mode, which are optional for users.
Setting operation: When power on, press long
time in “8” sparkling till the indicator response two sonorants,
PASS
then the indicator show“PASS
PASS”without pressing . After
that, press 880606
to input password “880606
880606” on
sub-display.
SELECT
When password is correct, main display show “SELECT
SELECT”
and sub-display show GM8806-A ( Weighing mode )、
GM8806A-B
GM8806A-B(Bagging mode) or GM8806A-P
GM8806A-P(Batching
mode), which can be switched by pressing .
After selecting operation mode, press to confirm
and finish, then the indicator sparkle “8” to enter.

Note:After selecting operation mode, user need reset


the indicator to ensure parameters correct.

- 52 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

7 Automatical batching process


7.1 Sketch map

7.2 Description
1)When power on, indicator begin batching process.
(If setwrong parameters, indicator will show ERROR8).
Ingredient weight ≥ target value - leading quantity of fast
feeding, shut fast feeding.
GM8806A-PL1100101
GM8806A-PL11 - 53 -
GM8806A -PL Batching controller
GM8806A-PL

Ingredient weight ≥ target value - leading quantity of


moderate feeding, shut moderate feeding.
Ingredient weight ≥ target value - free fall value, shut
slow feeding.
2 ) t1: Begin batching process after time delay t1, but
zeroing first if need according to operation parameter 11.
t2 / t3 / t4: No contrast time t2 、 t3 、 t4 in fast feeding,
moderate feeding and slow feeding to avoid feeding-
crushed weight.
T5: Over tolerance checking time t5.
T6
T6: Fix value within time t6.
T7 : Shut off discharging after time t7 when weight is less
than near-zero value.
T8 :Discharging monitor time t8 to output alarm ERROR6 if
discharging signal is still effective after time t8.
T9: Batching monitor time t9 to output alarm ERROR7 if
batching process can’t finish after time t9.
3)In running status, stop and pause operation are available
to return stop status for effective input.
4 ) If recipe parameter F4=ON
F4=ON, the judge over / under
tolerance after every batching process finish. See
Character 5.3 for details.

- 54 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

8 Serial port communication


Note:Not permit to change parameters related with
serial port by serial ports.
GM8806A-PL has RS232/485 serial port to
communicate with host computer. See Character 2.6 for
details.
Communication protocols: RS RS/ RE MODBUS, which
RE/MODBUS,
4.
can be set in operation parameter item no.4.
8.1 RS protocol
Cont
Two modes:Continue(Cont Read
Cont)/Command(Read
Read)at
ASCII code.
1) Continue (Cont)
When operation parameter 3=RS 3.1=Cont, indicator
3=RS、3.1=Cont,
send weighing data to host computer without command.
Data Format:
Scale Ingredient StateState +/
STX R S G/N Value CRC CR LF
no. no. 1 2 -

Here:
STX —— 1bit,start character 02H
Scale no. —— 2bits,range at 01-99
01-99,For example: 01 is
30H 31H
R —— 1bit,52H
52H
53H
S —— 1bit,53H
Ingredient no. —— 2bits
2bits,range at 00~04
00~04(30H 30H~30H
34H).. 00 means stop status.
34H
State 1 —— 1bit
GM8806A-PL1100101
GM8806A-PL11 - 55 -
GM8806A -PL Batching controller
GM8806A-PL

Bit 0 1 2 3 4 5 6 7
Before Fast Moderate Slow
1 Run Pause 1
feeding feeding feeding feeding

Not Not before


0 Stop
pause feeding
State 2 —— 1bit
Bit 0 1 2 3 4 5 6 7
Finish one Finish
Fixed
1 ingredient Discharge batching Stable Overflow 1
value
feeding times
0 Unstable

G/N —— 1bit
Bit 0 1 2 3 4 5 6 7

1 Net 0 0 0 0 0 1

0 Gross

+/- —— 1bit1bit,sign:2BH(+) 、2DH(-)


Value —— 7bit7bit,including decimal point.
CRC —— 2bits
2bits,check sum,which add all of front digits and
transform decimal system, then take last two digits to
transform into ASCII.
CR —— 1bit 0DH
1bit,0DH
LF —— 1bit 0AH
1bit,0AH
The following data format for example:
02 30 31 52 53 30 31 79 50 41 2B 30 30 30 32 2E 30 30 30
36 0D 0A
Means indicator no. 1、fast feeding、stable、net、value +2.00
status.
- 56 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

2) Command mode (Read)


When operation parameters 3=RS 3.1=Read
3=RS、3.1=Read
3.1=Read,indicator
send present data to host computer only after received
command .
� Host computer read“present status”
Read command:
STX Scale no. R S CRC CR LF
Correct response:Same as Cont mode(RS communication)
Wrong response:
STX Scale no. R S N O CRC CR LF
02 30 31 52 53 36 34 0D 0A
For example:02
Correct response:
02 30 31 52 53 30 31 79 50 41 2B 30 30 30 32 2E 30 30 30
36 0D 0A
1、fast feeding、stable、net、value +2.00
Means indicator no.1 +2.00..
� Host computer read“present accumulative total”
Read command:
STX Scale no. R T CRC CR LF
Correct response:
Scale Total Accumulative
STX R T , CRC CR LF
no. times total
Scale Total Accumulative
STX 1 # , CRC CR LF
no. times 1
total for no.1
Scale Total Accumulative
STX 2 # , CRC CR LF
no. times total for no. 2
Scale Total Accumulative
STX 3 # , CRC CR LF
no. times total for no. 3
Scale Total Accumulative
STX 4 # , CRC CR LF
no. times total for no. 4
GM8806A-PL1100101
GM8806A-PL11 - 57 -
GM8806A -PL Batching controller
GM8806A-PL

Wrong response:
STX Scale no. R T N O CRC CR LF

Here:
T —— 1bit 54H
1bit,54H
Total times —— 4bits 0000~9999
4bits,0000~9999
,—— 1bit 2CH
1bit,2CH
Accumulative total —— 10bits
10bits,including decimal point
# —— 1bit 23H
1bit,23H
N —— 1bit 4EH
1bit,4EH
O —— 1bit 4FH
1bit,4FH
1 for example:
Read accumulative total command from no.1
02 30 31 52 54 36 35 0D 0A
Correct response:
02 30 31 52 54 30 30 31 30 2C 30 30 30 30 30 32 30 33 36
38 30 31 0D 0A
02 30 31 31 23 30 30 31 30 2C 30 30 30 30 30 30 37 34 34
38 32 33 0D 0A
02 30 31 32 23 30 30 31 30 2C 30 30 30 30 30 30 34 36 31
36 31 38 0D 0A
02 30 31 33 23 30 30 31 30 2C 30 30 30 30 30 30 35 34 34
34 31 39 0D 0A
02 30 31 34 23 30 30 31 30 2C 30 30 30 30 30 30 32 38 36
30 31 39 0D 0A
Means total times 10
10,accumulative total 20368 1、no.2
20368,no.1 no.2、
no.3 no.4 tatal value is:7448
no.3、no.4 7448 4616
7448,4616 5444 and 2860.
4616,5444
- 58 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

� Host computer read“recipes”


Read command:
Scale Ingredient Recipe
STX R R CRC CR LF
no. no. parameters

Correct response:
Scale Ingredient Recipe
STX R R DDDDDD CRC CR LF
no. no. parameters

Wrong response
STX Scale no. R R N O CRC CR LF

Here:
Ingredient no. —— 2bit , such as Ingredient no. 1 is 30H
31H
Recipe parameters —— 1bit
1bit,0 0:30H
30H target value,11:31H
31H
leading quantity of fast feeding,22:32H
32H
leading quantity of moderate feeding,3 3:
33H free fall value,, 4:34H near-zero value..
DDDDDD —— 6bits6bits,recipe parameter values

1 target value command::


Read Ingredient no.1
02 30 31 52 52 30 31 30 30 38 0D 0A
Correct response:
02 30 31 52 52 30 31 30 30 30 30 35 30 30 30 31 0D 0A
1 from
Means: The target value is 500 for Ingredient no.1
scale no. 1 .
� Host computer read“recipe parameters”
Read command:
STX Scale no. R F Parameters CRC CR LF

GM8806A-PL1100101
GM8806A-PL11 - 59 -
GM8806A -PL Batching controller
GM8806A-PL

Correct response:
STX Scale no. R F Parameters DDDDDD CRC CR LF

Wrong response:
STX Scale no. R F N O CRC CR LF
Here:
F —— 1bit 46H
1bit,46H
Parameters —— 3bits
3bits,such as feeding time delay F2.1 is
32H 31H 30H
DDDDDD —— 6bits
6bits,recipe parameter values
1 command:
Read parameter F2.1 from scale no.1
02 30 31 52 46 32 31 30 39 38 0D 0A
Correct response:
02 30 31 52 46 32 31 30 30 30 30 30 35 30 34 33 0D 0A
1 in scale no.1
Means parameter F2.1 of ingredient no.1 1 is 5.0
� Host computer read“Batching value”
Read command:
STX Scale no. R O ingredient no. 0 CRC CR LF
Correct response:
Scale Ingredient
STX R O 0 DDDDDD CRC CR LF
no. no.

Wrong response:
STX Scale no. R O N O CRC CR LF
Here:
4FH
O —— 1bit,4FH
2bits(1~4 optional),such as Ingredient
Ingredient no. —— 2bits

- 60 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

no 1(30H
30H 31H
31H)
0 —— 1bit 30
1bit,30
30H
DDDDDD —— 6bits
6bits,batching value

Read Ingredient no. 1 batching value command:


02 30 31 52 4F 30 31 30 30 35 0D 0A
Correct response:
02 30 31 52 4F 30 31 30 30 30 30 35 30 30 39 38 0D 0A
Means batching value of ingredient no. 1 in scale no. is 500.
� Host computer read“batching times”
Read command:
STX Scale no. R B CRC CR LF
Correct response:
STX Scale no. R B DDDDDD CRC CR LF
Wrong response:
STX Scale no. R B N O CRC CR LF

Here:
42H
B —— 1bit,42H
DDDDDD —— 6bits
6bits,batching times value

Read batching times value command:


02 30 31 52 42 34 37 0D 0A
Correct response:
02 30 31 52 42 30 30 30 31 30 30 33 36 0D 0A
Means batching times value in scale no. 1 is 100.
GM8806A-PL1100101
GM8806A-PL11 - 61 -
GM8806A -PL Batching controller
GM8806A-PL

� Host computer read“decimal point”


Read command:
STX Scale no. R P CRC CR LF
Correct response:
STX Scale no. R P DDDDDD CRC CR LF
Wrong response:
STX Scale no. R P N O CRC CR LF
Here:
P —— 1bit 50H
1bit,50H
DDDDDD —— 6bits
6bits,range at 0-4
0-4,which are decimal point
digits

Read decimal point for example:


02 30 31 52 50 36 31 0D 0A
Correct response:
02 30 31 52 50 30 30 30 30 30 31 35 30 0D 0A
Means the decimal point of scale no.1 is 1.
� Host computer read“Recipe no.”
Read command:
STX Scale no. R N CRC CR LF
Correct response:
STX Scale no. R N DDDDDD CRC CR LF

Wrong response:
STX Scale no. R N N O CRC CR LF

- 62 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Here:
N —— 1bit 4FH
1bit,4FH
DDDDDD —— 6bit
6bit,receipe no.

Read recipe no. for example:


02 30 31 52 4E 35 39 0D 0A
Correct response:
02 30 31 52 4E 30 30 30 30 30 31 34 38 0D 0A
1.
Means present recipe no. is 1 in scale no.1
� Host computer read“Restore for broken power”
Read command:
STX Scale no. R E CRC CR LF
Correct response:
STX Scale no. R E DDDDDD CRC CR LF
Wrong response:
STX Scale no. R E N O CRC CR LF

Here:
E —— 1bit 45H
1bit,45H
6bits,if it is conti status..
DDDDDD —— 6bits
For examples:
02 30 31 52 45 35 30 0D 0A
Correct response:
02 30 31 52 45 30 30 30 30 30 31 33 39 0D 0A
conti
Means scale no. 1 is in“conti
conti?”status.
GM8806A-PL1100101
GM8806A-PL11 - 63 -
GM8806A -PL Batching controller
GM8806A-PL

� Host computer read operation parameters


Read command:
Scale Operation
STX R U 0 CRC CR LF
no. parameter
Correct response:
Scale Operation
STX R U 0 DDDDDD CRC CR LF
no. parameter
Wrong response
STX Scale no. R U N O CRC CR LF
Here:
U —— 1bit 55H
1bit,55H
Operation parameter —— 3bit
3bit,such as:zeroing range 7
is 37H 30H 30H
Read operation parameter 7 command for example:
02 30 31 52 55 37 30 30 30 36 35 0D 0A
Correct response:
02 30 31 52 55 37 30 30 30 30 30 30 30 35 30 35 38 0D 0A
50..
Means scale no. 1 operation parameter is 50
� Host computer write“Recipe”
Write command:
Scale Ingredient Recipe
STX W R DDDDDD CRC CR LF
no. no. parameter

Correct response:
STX Scale no. W R O K CRC CR LF
Wrong response:
STX Scale no. W R N O CRC CR LF
- 64 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Here:
W —— 1bit 52H
1bit,52H
Ingredient no. —— 2bit
2bit, such as Ingredient no. 1 is 30H
31H
Recipe parameter —— 1bit 0:30H
1bit,0 30H target value 1:31H
value,1 31H
2:32H
leading quantity of fast feeding,2 32H
3:33H
leading quantity of moderate,3 33H free
fall value;; 4:34H
34H near-zero value.
DDDDDD —— 6bit,recipe parameter value
1500 for Ingredient no.1 in
For example:Write target value=1500
scale no.1
02 30 31 57 52 30 31 30 30 30 31 35 30 30 30 37 0D 0A
Correct response:
02 30 31 57 52 4F 4B 32 32 0D 0A
Means scale no. 1 has saved the weight value.
� Host computer set“Recipe parameter”
Write command:
Scale Set
STX W F DDDDDD CRC CR LF
no. parameter

Correct response:
STX Scale no. W F O K CRC CR LF
Wrong response:
STX Scale no. W F N O CRC CR LF
Here:
F —— 1bit 46H
1bit,46H
GM8806A-PL1100101
GM8806A-PL11 - 65 -
GM8806A -PL Batching controller
GM8806A-PL

Set parameter —— 3bit


3bit,such as feeding time delay F2.1 is
32H 31H 30H
DDDDDD —— 6bit
6bit,set parameter value
For example:write parameter F2.1 3 to scale no.1
F2.1=3
02 30 31 57 46 32 31 30 30 30 30 30 30 30 33 34 32 0D 0A
Correct response:
02 30 31 57 46 4F 4B 31 30 0D 0A
Means scale no. 1 has saved parameter F2.1 3.
F2.1=3
� Host computer write operation parameter
Write command:
Scale operation
STX W U 0 DDDDDD CRC CR LF
no. parameter

Correct response:
STX Scale no. W U O K CRC CR LF
Wrong response:
STX Scale no. W U N O CRC CR LF
Note:Not permit to write command on communication
parameters.
Here:
U —— 1bit 55H
1bit,55H
3bit,such as :zeroing range 7 is
Operation parameter —— 3bit
37H 30H 30H
0 —— 1bit 31H
1bit,31H
DDDDDD —— 6bit 6bit,operation parameter value
For example:Write 30 command on operation parameter 7
1:
in scale no.1:
- 66 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

02 30 31 57 55 37 30 30 30 30 30 30 30 33 30 36 31 0D 0A
Correct response:
02 30 31 57 55 4F 4B 32 35 0D 0A
Means scale no. 1 has saved operation parameter 7.
� Host computer write“Recipe no.”(only in stop status)
Write command:
STX Scale no. W N DD CRC CR LF
Correct response:
STX Scale no. W N O K CRC CR LF
Wrong response:
STX Scale no. W N N O CRC CR LF
Here:
DD —— 2bits
2bits,range at 01-40
01-40,which is recipe no.
01 on scale no. 1 command:
For example: Write recipe no. =01
02 30 31 57 4E 30 31 36 31 0D 0A
Correct response::
02 30 31 57 4E 4F 4B 31 38 0D 0A
Means scale no.1 has saved recipe no.
� Host computer write“Batching times”(only in stop
status)
Write command:
STX Scale no. W B DDDDDD CRC CR LF
Correct response:
STX Scale no. W B O K CRC CR LF

GM8806A-PL1100101
GM8806A-PL11 - 67 -
GM8806A -PL Batching controller
GM8806A-PL

Wrong response:
STX Scale no. W B N O CRC CR LF

Here:
B —— 1bit
1bit,42H
DDDDDD —— 6bits
6bits,range at 000000-009999
000000-009999,which is
batching times
1000 on scale no.1:
For example:Write batching times=1000
02 30 31 57 42 30 30 31 30 30 30 34 31 0D 0A
Correct response:
02 30 31 57 42 4F 4B 30 36 0D 0A
Means scale no. 1 has saved batching times.
� Host computer write“Restor for broken power”
Write command:
STX Scale no. W E D CRC CR LF
Correct response:
STX Scale no. W E O K CRC CR LF
Wrong response:
STX Scale no. W E N O CRC CR LF

Here:
E —— 1bit 45H
1bit,45H
1bit,range at 0 and 1,1
D —— 1bit 1 means to restore;; 0
means not to restore.
For example:Write restore 01 command on scale no.1:
02 30 31 57 45 31 30 34 0D 0A
- 68 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Correct response:
02 30 31 57 45 4F 4B 30 39 0D 0A
Means the command has been saved.
� Host computer calibrate“decimal point”
Write command:
Decimal
STX Scale no. C P CRC CR LF
point
Correct response:
STX Scale no. C P O K CRC CR LF
Wrong response:
STX Scale no. C P N O CRC CR LF

Here:
C —— 1bit 43H
1bit,43H
P —— 1bit 50H
1bit,50H
Decimal point —— 1bit
——1bit
1bit,range at 0~4
1:
For example:Calibrate decimal point 3 on scale no.1:
02 30 31 43 50 33 39 37 0D 0A
Correct response:
02 30 31 43 50 4F 4B 30 30 0D 0A
Means scale no.1 has saved decimal point value.
� Host computer“Add weights to calibrate zero”
Write command:
STX Scale no. C Z CRC CR LF
Correct response:
STX Scale no. C Z O K CRC CR LF
GM8806A-PL1100101
GM8806A-PL11 - 69 -
GM8806A -PL Batching controller
GM8806A-PL

Wrong response:
STX Scale no. C Z N O CRC CR LF

Here:
Z —— 1bit 5AH
1bit,5AH
For example:Add weights to calibrate zero on scale no.1
02 30 31 43 5A 35 36 0D 0A
Correct response:
02 30 31 43 5A 4F 4B 31 30 0D 0A
Means command has been performed.
� Host computer“calibrate zero without weights”
Write command:
STX Scale no. C Y DDDDDD CRC CR LF
Correct response:
STX Scale no. C Y O K CRC CR LF
Wrong response:
STX Scale no. C Y N O CRC CR LF
Here:
Y —— 1bit 59H
1bit,59H
DDDDDD —— 6bits
6bits,which is millivolt value related zero.

For example:Write zero command to indicator on scale no.1


02 30 31 43 59 30 30 31 35 30 30 34 39 0D 0A
Correct response:
02 30 31 43 59 4F 4B 30 39 0D 0A
Means scale no.1 has saved written data.
- 70 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

� Host computer calibrate“Minimum division and


maximum capacity”
Write command:
STX Scale no. C M DD DDDDDD CRC CR LF
Correct response:
STX Scale no. C M O K CRC CR LF
Wrong response:
STX Scale no. C M N O CRC CR LF

Here:
4DH
M —— 1bit,4DH
DD —— 2bits,individually 1、2
2、5
5、10
10 20
10、20 50
20、50
DDDDDD —— 6bits
6bits,maximum capacity value
For example:Write division and maximum capacity
command on scale no.1
02 30 31 43 4D 30 31 30 31 30 30 30 30 32 39 0D 0A
Correct response:
02 30 31 43 4D 4F 4B 39 37 0D 0A
Means scale no.1 has saved written value.
� Host computer“Add weights to calibrate gain”
Write command:
STX Scale no. C G DDDDDD CRC CR LF
Correct response:
STX Scale no. C G O K CRC CR LF
GM8806A-PL1100101
GM8806A-PL11 - 71 -
GM8806A -PL Batching controller
GM8806A-PL

Wrong response:
STX Scale no. C G N O CRC CR LF
Here:
G —— 1bit 47H
1bit,47H
DDDDDD —— 6bit
6bit,gain value
For example:Calibrate gain 10000 command on scale no. 1
02 30 31 43 47 30 31 30 30 30 30 32 36 0D 0A
Correct response:
02 30 31 43 47 4F 4B 39 31 0D 0A
Means scale no.1 has saved 10000.
� Host computer“calibrate gain without weights”
Write command:

STX Scale no. C L D1D1D1D1D1D1 D2D2D2D2D2D2 CRC CR LF

Correct response:
STX Scale no. C L O K CRC CR LF
Wrong response:
STX Scale no. C L N O CRC CR LF
Here:
L —— 1bit 4CH
1bit,4CH
D1D1D1D1D1D1 —— 6bits
6bits,gain millivolt value
D2D2D2D2D2D2 —— 6bits
6bits,gain weight value
For example:Calibrate gain without weights 4.110mV as
10000 on scale no. 1
02 30 31 43 4C 30 30 34 31 31 30 30 31 30 30 30 30 32 35
0D 0A
- 72 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Correct response:
02 30 31 43 4C 4F 4B 39 36 0D 0A
Means scale no. 1 has saved calibration value.
� Host computer“Discharging operation”
Write command:
STX Scale no. C D CRC CR LF
Correct response:
STX Scale no. C D O K CRC CR LF
Wrong response:
STX Scale no. C D N O CRC CR LF

Here:
D —— 1bit 44H
1bit,44H
For example:Send discharging operation on scale no. 1
02 30 31 43 44 33 34 0D 0A
Correct response:
02 30 31 43 44 4F 4B 38 38 0D 0A
Means the command has been performed.
� Host computer“Running operation”
Write command:
STX Scale no. C R CRC CR LF
Correct response:
STX Scale no. C R O K CRC CR LF
Wrong response:
STX Scale no. C R N O CRC CR LF
GM8806A-PL1100101
GM8806A-PL11 - 73 -
GM8806A -PL Batching controller
GM8806A-PL

Here
R —— 1bit 52H
1bit,52H
For example:Run scale no. 1
02 30 31 43 52 34 38 0D 0A
Correct response:
02 30 31 43 52 4F 4B 30 32 0D 0A
Means the command has been performed
� Host computer“Stop operation”
Write command:
STX Scale no. C J CRC CR LF
Correct response:
STX Scale no. C J O K CRC CR LF
Wrong response:
STX Scale no. C J N O CRC CR LF
Here:
J —— 1bit 4AH
1bit,4AH
For example:Stop scale no. 1
02 30 31 43 4A 34 30 0D 0A
Correct response:
02 30 31 43 4A 4F 4B 39 34 0D 0A
Means the command has been performed.
� Host computer“Pause operation”
Write command:
STX Scale no. C S CRC CR LF

- 74 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Correct response:
STX Scale no. C S O K CRC CR LF
Wrong response:
STX Scale no. C S N O CRC CR LF

Here:
S —— 1bit 53H
1bit,53H
For example:Pause scale no. 1
02 30 31 43 53 34 39 0D 0A
Correct response:
02 30 31 43 53 4F 4B 30 33 0D 0A
� Host computer“Tare-off operation”
Write command:
STX Scale no. C Q CRC CR LF
Correct response:
STX Scale no. C Q O K CRC CR LF
Wrong response:
STX Scale no. C Q N O CRC CR LF
Here:
Q —— 1bit 51H
1bit,51H
For example:Tare off on scale no. 1
02 30 31 43 51 34 37 0D 0A
Correct response:
02 30 31 43 51 4F 4B 30 32 0D 0A

GM8806A-PL1100101
GM8806A-PL11 - 75 -
GM8806A -PL Batching controller
GM8806A-PL

� Host computer“Clear tare operation”


Write command:
STX Scale no. C O CRC CR LF
Correct response:
STX Scale no. C O O K CRC CR LF
Wrong response:
STX Scale no. C O N O CRC CR LF

Here:
O —— 1bit 4FH
1bit,4FH
For example:Clear tare on scale no.1
02 30 31 43 4F 34 35 0D 0A
02 30 31 43 4F 4F 4B 39 39 0D 0A
Correct response:02
� Host computer“Clear alarm operation”
Write command:
STX Scale no. C B CRC CR LF
Correct response:
STX Scale no. C B O K CRC CR LF
Wrong response:
STX Scale no. C B N O CRC CR LF
Here:
B —— 1bit 42H
1bit,42H
For example:Clear alarm on scale no. 1
02 30 31 43 42 33 32 0D 0A
Correct response:0202 30 31 43 42 4F 4B 38 36 0D 0A
- 76 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

� Host computer“Zeroing operation”


Write command:
STX Scale no. C C CRC CR LF
Correct response:
STX Scale no. C C O K CRC CR LF
Wrong response:
STX Scale no. C C N O CRC CR LF

1
For example:Zeroing command on scale no.1
02 30 31 43 43 33 33 0D 0A
02 30 31 43 43 4F 4B 38 37 0D 0A
Correct response:02
� Host computer“Manual slow feeding operation”
Write command:
STX Scale no. C A CRC CR LF
Correct response:
STX Scale no. C A O K CRC CR LF
Wrong response:
STX Scale no. C A N O CRC CR LF
Here:
A —— 1bit 41H
1bit,41H
For example:Manual slow feeding command
02 30 31 43 41 33 31 0D 0A
02 30 31 43 41 4F 4B 38 35 0D 0A
Correct response:02
Note:The command is effective one time and ineffective
next time.
GM8806A-PL1100101
GM8806A-PL11 - 77 -
GM8806A -PL Batching controller
GM8806A-PL

8.2 RE protocol
Cont
Two modes:Continue (Cont Read
Cont)/ command (Read
Read).
Support all of data format in parameters F4.5; ASCII code.
Cont
1) Continue mode (Cont
Cont)
When operation parameters 3 for RE 3.1 for Cont
RE、3.1 Cont,
indicator send data to host computer without any command.
Data format as follows:
Status , GS , Sign Value Unit CR LF

Here:
OL
Status —— 2bits,OL ST
OL:( 4FH 4CH ) overflow;ST
ST:( 53H
54H )stable US
US:( 55H 53H )unstable
, —— 1bit,list separator 2CH
47H 53H
GS —— 2bits,47H
2BH
Sign —— 1bit,2BH 、2DH
2BH(+) 2DH
2DH(-)
Value
Value—— 7bits,including decimal point,if no, the highest
bit is 0
Kg 4BH 67H
Unit —— 2bits,Kg
0DH
CR —— 1bit,0DH
0AH
LF —— 1bit,0AH
For example:Indicator sends following data format:
53 54 2C 47 53 2C 2B 30 31 31 2E 31 32 30 4B 67 0D 0A
Means :stable、positive data、present weight value is 11.
120kg

- 78 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

2)Command mode (Read)


When operation parameters 3 for RERE、33.1 for Read
Read,
indicator send present data to host computer only after
received command .
Data format as follows:
R E A D CR LF

Here:
R —— 52H
E —— 45H
A —— 41H
D —— 44H
CR —— 0DH
LF —— 0AH
Response data format is same as data format in continue
mode.
For example
Command: 52 45 41 44 0D 0A
53 54 2C 47 53 2C 2B 30 31 31 2E 31 32 30 4B
Response:53
67 0D 0A
Means:stable、positive data、present weight value is 11.
120kg..
120kg

GM8806A-PL1100101
GM8806A-PL11 - 79 -
GM8806A -PL Batching controller
GM8806A-PL

8.3 MODBUS protocol


1) Communication mode
MODBUS communication by two mode:RTU RTU and AscAsc。
When parameter F4.4 is RTU
RTU,every 8-bit byte of the
message are divided into 2pcs of 4-bit hexadecimal
8- E-1
characters to transmit at binary code. Data format:8- E-1,
8- O-1 8- n-1
O-1,8- n-1,8- 8- n-2
n-2。
When parameter F4.4 is ASCII
ASCII,every 8-bit byte of the
message is transmitted as 2pcs ASCII characters at ASCII
code, which support all of data format in parameter F4.5.
2) MODBUS communication address
PLC Display
Description
address address

The following items are only-read register(code 0x03


0x03)
Bit Meaning
Ingredient 1 in fast
.0
feeding
Ingredient 1 in
.1
moderate feeding
Ingredient 1 in slow
.2
40001 0000 feeding
Preset state Ingredient 2 in fast
.3
1 feeding
Ingredient 2 in
.4
moderate feeding
Ingredient 2 in slow
.5
feeding
- 80 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Ingredient 3 in fast
.6
feeding
Ingredient 3 in
.7
moderate feeding
Ingredient 3 in slow
.8
feeding
Ingredient 4 in fast
.9
feeding
Ingredient 4 in
.10
moderate feeding
Ingredient 4 in slow
.11
feeding
Bit Meaning
.0 0:Stop 1:Run
0:Not pause
.1
1:Pause
0:Unstable
.2
1:Stable
0:None zero
.3
1:Zero
Preset state
40002 0001 0:Not overflow
2 .4
1:Overflow
0:Not minus
.5
1:Minus
.6 Before feeding
Single ingredient
.7
feeding finished
Check over/under
.8
tolerance.
GM8806A-PL1100101
GM8806A-PL11 - 81 -
GM8806A -PL Batching controller
GM8806A-PL

.9 Alarm
.10 Fix value output
.11 Discharging
.X Reserve
When weight overflow,
40003 0002
Present indicator display OFL
OFL,
weight return value
40004 0003
0xFFFFFFFF..
0xFFFFFFFF
40005 0004 Accumulate Only read,when write,
40006 0005 total times return error data address.
40007 0006 Accumulate Only read,when write,
40008 0007 total weight return error data address.
40009 0008 Ingredient 1
Only read,when write,
accumulated
40010 0009 weight return error data address.

40011 0010 Ingredient 2


Only read,when write,
accumulated
40012 0011 return error data address.
weight
40013 0012 Ingredient 3
Only read,when write,
accumulated
40014 0013 return error data address.
weight
40015 0014 Ingredient 4
Only read,when write,
accumulated
40016 0015 return error data address.
weight
40017 0016
40018 0017 Read zero from the
Reserve
40019 0018 address.
40020 0019
- 82 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

40021 0020 Ingredient 1 Only read,when write,


40022 0021 weight return error data address
40023 0022 Ingredient 2 Only read,when write,
40024 0023 weight return error data address
40025 0024 Ingredient 3 Only read,when write,
40026 0025 weight return error data address
40027 0026 Ingredient 4 Only read,when write,
40028 0027 weight return error data address
40029 0028
40030 0029 Read zero from the
Reserve
40031 0030 address.
40032 0031
0:Finish batching times;
1:Over zeroing range;
2:Unstable in zeroing;
Alarm
40033 0032 3,4:: Over/under
3,4
message
tolerance;
5:Target value is 0 when
start.
The following items are two bytes and available to read
and write(writing code 0x10
0x10,read code 0x03
0x03)
40034 0033 Ingredient 1
1.A1
40035 0034 target value
40036 0035 Ingredient 2 Note:Written
1.b1
40037 0036 target value value must less
than or same as
40038 0037 Ingredient 3 maximum
1.C1
40039 0038 target value capacity.
40040 0039 Ingredient 4
1.d1
40041 0040 target value
GM8806A-PL1100101
GM8806A-PL11 - 83 -
GM8806A -PL Batching controller
GM8806A-PL

40042 0041
40043 0042 Read zero from the
Reserve
40044 0043 address.
40045 0044

40046 0045 Ingredient 1


leading
1.A2
quantity of
40047 0046 fast feeding

40048 0047 Ingredient 2


leading
1.b2 Note : Written
quantity of
40049 0048 fast feeding value must less
than or same as
40050 0049 Ingredient 3 maximum
leading capacity.
1.C2
quantity of
40051 0050 fast feeding

40052 0051 Ingredient 4


leading
1.d2
quantity of
40053 0052 fast feeding
40054 0053
40055 0054 Read zero from the
Reserve
40056 0055 address.
40057 0056
Ingredient 1 Note : Written
40058 0057 leading value must less
quantity of 1.A3 than or same as
moderate maximum
40059 0058
feeding capacity.
- 84 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Ingredient 2
40060 0059 leading
quantity of 1.b3
40061 0060 moderate
feeding
Ingredient 3
40062 0061 leading
quantity of 1.C3
40063 0062 moderate
feeding
Ingredient 4
40064 0063 leading
quantity of 1.d3
40065 0064 moderate
feeding
40066 0065
40067 0066 Read zero from the
Reserve
40068 0067 address.
40069 0068
40070 0069 Ingredient 1
1.A4
40071 0070 free fall data
40072 0071 Ingredient 2 Note : Written
1.b4
40073 0072 free fall data value must less
than or same as
40074 0073 Ingredient 3 maximum
1.C4
40075 0074 free fall data capacity.
40076 0075 Ingredient 4
1.d4
40077 0076 free fall data
40078 0077
40079 0078 Read zero from the
Reserve
40080 0079 address.
40081 0080
GM8806A-PL1100101
GM8806A-PL11 - 85 -
GM8806A -PL Batching controller
GM8806A-PL

Note : Written
40082 0081
value must less
Near-zero
1.e0 than or same as
value
40083 0082 maximum
capacity.

40084 0083 Maximum capacity ≤


Maximum
minimum division × 30000
40085 0084 capacity
(Change only in stop).
Write 0001H to take
40086 0085 present weight as zero
Zero
when weight is stable;
calibration
Return present millivolt
with weights
40087 0086 atzero when read.
(Change only in stop).
Write present weight value
40088 0087 according to present
Gain
millivolt;
calibration
(Change only in stop).
with weights
40089 0088 Return present millvolt at
present weight when read.
Write millivolt value at
40090 0089 Zero
zero;
calibration
Return present millivolt
without
40091 0090 value at zero when read.
weights
(Change only in stop).
Gain Write gain millivolt value
40092 0091 calibration related gain weight,
without indicator save first;
weights Return millivolt value
(gain related present weight
40093 0092 millivolt when read.
value) (Change only in stop).
- 86 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Write weight value related


40094 0093 gain millivolt after writing
Gain
gain millivolt first, gain
calibration
calibration in this register
without
by both of weight and
weights(gain
millivolt;
40095 0094 weight value) Return 0000H when read.
(Change only in stop).

The following items are two bytes and are available to read
and write (write code 0x06
0x06,read code 0x03
0x03)
0000H
0000H:00bit
bit;
0001H
0001H:11bit
0002H
0002H:22bits
bits;
40096 0095 Decimal point
0003H
0003H:33bits
0004H
0004H:44bits
(Change only in stop).
0001H
0001H:11;0002H
0002H
0002H:2 2
Minimum 0005H
0005H:5 5;000AH
000AH
000AH:10 10
40097 0096
division 00014 20
00014:20 0032H
20;0032H
0032H:50 50
(Change only in stop).

0002H 2mV/V
0002H:2mV/V
40098 0097 Sensitivity 0003H 3mV/V
0003H:3mV/V
(Change only in stop).

Feeding time 0000H~03E7H


40099 0098 F2.1
delay t1 (00.0~99.9
00.0~99.9
00.0~99.9)

No contrast time
0000H~03E7H
40100 0099 t2 of fast F2.2
(00.0~99.9
00.0~99.9
00.0~99.9)
feeding

GM8806A-PL1100101
GM8806A-PL11 - 87 -
GM8806A -PL Batching controller
GM8806A-PL

No contrast time
0000H~03E7H
40101 0100 t3 of moderate F2.3
(00.0~99.9
00.0~99.9
00.0~99.9)
feeding
No contrast time
0000H~03E7H
40102 0101 t4 of slow F2.4
(00.0~99.9
00.0~99.9
00.0~99.9)
feeding
Check
0000H~03E7H
40103 0102 tolerance F2.5
(00.0~99.9
00.0~99.9
00.0~99.9)
time t5
Fixed value 0000H~03E7H
40104 0103 F2.6
time t6 (00.0~99.9
00.0~99.9
00.0~99.9)
Discharging 0000H~03E7H
40105 0104 F2.7
time delay t7 (00.0~99.9
00.0~99.9
00.0~99.9)
Discharging
0000H~03E7H
40106 0105 monitor time F2.8
(00.0~99.9
00.0~99.9
00.0~99.9)
t8
Feeding
0000H~03E7H
40107 0106 monitor time F2.9
(00.0~99.9
00.0~99.9
00.0~99.9)
t9
Pause time t10
between fast
0000H~03E7H
40108 0107 feeding F3.1
(00.0~99.9
00.0~99.9
00.0~99.9)
moderate
feeding
Pause time t11
between
0000H~03E7H
40109 0108 moderate F3.2
(00.0~99.9
00.0~99.9
00.0~99.9)
feeding and
slow feeding

- 88 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Over
0000H~0063H
40110 0109 tolerance F4.1
(0.0~9.9s)
percent
Under
0000H~0063H
40111 0110 tolerance F4.2
(0.0~9.9s)
percent
Over/under
0000H~03E7H
40112 0111 tolerance F4.4
(00.0~99.9
00.0~99.9
00.0~99.9)
alarm time
Free fall
0000H~0063H
40113 0112 compensation F5.1
(00~99)
times
Free fall
0000H~0063H
40114 0113 compensation F5.2
(00~99%)
range
Free fall 0 : 0% ; 1 :
40115 0114 compensation F5.3 100%;2:50%
100% 50%;
percent 3:25%
25%
Jog feeding 0000H~0063H
40116 0115 F7.1
times (00~99)
Jog feeding 0000H~03E7H
40117 0116 F7.2
effective time (00.0~99.9
00.0~99.9
00.0~99.9)
Jog feeding 0000H~03E7H
40118 0117 F7.3
ineffective time (00.0~99.9
00.0~99.9
00.0~99.9)
Jog feeding of
0000H~03E7H
40119 0118 slow feeding F8.1
(00.0~99.9
00.0~99.9
00.0~99.9)
effective time
Jog feeding of
0000H~03E7H
40120 0119 slow feeding F8.2
(00.0~99.9
00.0~99.9
00.0~99.9)
ineffective time

GM8806A-PL1100101
GM8806A-PL11 - 89 -
GM8806A -PL Batching controller
GM8806A-PL

0 : rdp_fi 1:
rdp_fi;1
Sub-display rdp_s1
rdp_s1;
40121 0120 F9
data when stop 2:rdp_s2
rdp_s2
rdp_s2;33:
rdp_s3
Sub-display Same as manual
40122 0121 F10
data when run setting
Ingredient
40123 0122 F11.1
compositor
40124 0123 Recipe no. 1~40
40125 0124
40126 0125
Read zero from the
40124 0126 Reserve
address.
40128 0127
40129 0128
Zero tracking 0000H~0063H
40130 0129 6
range (00~99)
0001H~0063H
40131 0130 Zeroing range 7
(01~99)
Stability 0001H~0063H
40132 0131 8
range (01~99)
0000H~0009H
40133 0132 AD filter 9
(0~9)
0000H~0009H
40134 0133 Stability filter 10
(0~9)
Ingredient
40135 0134 13 0001H~00004H
kinds
0000H~0007H
40136 0135 Analog mode 15
(0~7)
40137 0136
Read zero from the
40138 0137 Reserve
address.
40139 0138
- 90 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Batching
40140 0139 0000H~270FH
times
Write:Initialization
( Change only in stop)
8800 initialize all
parameters;8801 8801
initialize calibration;
8802 initialize operation
Back up / parameters;8803 8803
40141 0140 Restore initial initialize recipe
setting parameters;8804 8804
initialize IO definition.
Back up: (The highest bit
change to 6);
Restore: (The highest bit
change to 7).
Return 0 to read.
Write:Only in stop
status. Write 1 to start
I/O testing;Write 0 to
Start / Stop
40142 0141 exit.
I/O testing
Read:1 1 for I/O testing
status.00 for none I/O
testing status.
Write: not permit.
( Change only in stop)
Read: Input IN1 ~ IN6
40143 0142 Input testing
from low bit to high bit, 1
for effective input, 0 for
ineffective input.

GM8806A-PL1100101
GM8806A-PL11 - 91 -
GM8806A -PL Batching controller
GM8806A-PL

Write: Output from OUT1


~ OUT1
OUT10 0 from low bit to
high bit, 1 for effective
output, 0 for ineffective
40144 0143 Output testing
output. ( Change only in
stop)
Read: Return present
output status.
40145 0144 IN1
40146 0145 IN2
Write: write
40147 0146 IN3
value related
40148 0147 IN4 with I/O
40149 0148 OUT1 definition. For
example, if
40150 0149 OUT2 define IN2 as
40151 0150 OUT3 I3, user
I/O self-
definition should write 3
40152 0151 OUT4
in IN2
40153 0152 OUT5 register.
40154 0153 OUT6 ( Change only
in stop)
40155 0154 OUT7 Read: Return
40156 0155 OUT8 present I/O
self-definition.
40157 0156 OUT9
40158 0157 OUT10
40159 0158
Read zero from the
40160 0159 Reserve
address.
40161 0160

- 92 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Following items are bits and available to read and write in


loops (function code:0x01)
Restore for
00162 0161
broken power
Automatic
00163 0162 zeroing when
power on
Tare-off / FF00H = ON
Write:FF00H
00164 0163 zeroing 0000H = OFF
selection
0001H = ON
Read:0001H
Manual 0000H = OFF
00165 0164 discharging Note:
counted in total Tare-off / zeroing
Save when selection:
00166 0165
power off FF00H=b_tare
FF00H=b_tare;
Tare-off / 0000H=b_zero
00167 0166 Restore for broken
zeroing switch
power:
00168 0167 Feeding mode
FF00H=yes
Write:FF00H=yes
FF00H=yes;
Over/under 000H=no
00169 0168
tolerance alarm conti
Read:conti
conti?1 1 for
Over/under conti conti..
conti; 0 for not conti
00170 0169 tolerance
pause
Discharging
00171 0170
switch
Discharging
00172 0171
mode selection
Discharging -
00173 0172 permit
selection

GM8806A-PL1100101
GM8806A-PL11 - 93 -
GM8806A -PL Batching controller
GM8806A-PL

Compensation
00174 0173
switch
Jog feeding of
00175 0174 slow feeding
switch
Ingredient
00176 0175
compositor
Free fall
00177 0176
compensation
00178 0177
00179 0178
Read zero from the
00180 0179 Reserve
address.
00181 0180
00182 0181
Read:1 for effective,0
for ineffective;
00183 0182 Input state in1
Write:Not permit
(Change only in stop)
00184 0183 Input state in2 Write:Not permit
00185 0184 Input state in3 Write:Not permit
00186 0185 Input state in4 Write:Not permit
Read:From low to high
represent out1-out1 0,
out1-out10
Output state which 1 for effective,0
00187 0186
out1 for ineffective;
Write:Not permit
( Change only in stop)
Output state
00188 0187 Not permit to write
out2

- 94 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

Output state
00189 0188 Not permit to write
out3
Output state
00190 0189 Not permit to write
out4
Output state
00191 0190 Not permit to write
out5
Output state
00192 0191 Not permit to write
out6
Output state
00193 0192 Not permit to write
out7
Output state
00194 0193 Not permit to write
out8
Output state
00195 0194 Not permit to write
out9
Output state
00196 0195 Not permit to write
out10
Read zero from the
00197 0196 Reserve
address.
Read:Run = 1;Not run
00198 0197 Star t
=0
Read:Stop = 1;Not
00199 0198 Urgent stop
stop = 0
Read:Pause = 1;Not
00200 0199 Pause
pause = 0
Read:Zeroing = 1;
00201 0200 Zeroing
none zeroing = 0
Read:Clear = 1 ;Not
00202 0201 Clear alar m
clear = 0

GM8806A-PL1100101
GM8806A-PL11 - 95 -
GM8806A -PL Batching controller
GM8806A-PL

Clear
Read:Clear = 1;Not
00203 0202 accumulat ed
clear = 0
tot al
Read : always read
00204 0203 Select recipe
OFF( 0000H
OFF(0000H
0000H)
Manual Read:Effective
discharging/ discharging = 1;
00205 0204
dischar ging ineffective discharging
per mit =0
Lock keypad Read:keypad effective
00206 0205 (Change only =1
in stop) Keypad ineffective = 0
Tare- off Read : always read
00207 0206
input OFF(0000H)
Clear tar e Read : always read
00208 0207
input OFF(0000H)

3) Function code

Above Modbus communication protocols have five function

01 read coil、03
codes:01 03 read register、05
05 force single coil、

16
06 preset single register、16
16( 10 Hex
Hex) preset several

registers.
◆ 01 read coil
Inquiry:Regulate coil start and quantities.
Response:
a) Every coil state in response message is corresponding
1=ON
to every data in data area;1=ON 0=OFF
1=ON;0=OFF
0=OFF。The LSB in

- 96 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

first byte is start address in inquiry. Other coils are in


seriation from lowest to highest in the byte till full of 8pcs,
next byte same seriation.
b) If they are not 8 multiples, the last byte is full of zero
from the remain to the highest,which byte sections
indicate all of byte quantities.
For example:Inquiry weighing indicator 01 to read 40- 43
coil
A. RTU communication mode
mode:
Inquiry command:
Function Start Coil CRC
Address
code address quantity parity
1byte 1byte 2byte 2byte 2byte
Correct response:
Function Account CRC
Address Data area
code byte parity
1byte 1byte 1byte 1byte 2byte

01 01 00 28 00 04 BD C1
Inquiry command:01
01 01 01 02 D0 49
Correct response:01 49(Coil 43- 40 related
0- 0- 1- 0)
state:0-
B. ASCII communication mode
mode:
Inquiry command:
Function Start Coil LRC
Start Address Stop
code address quantities parity
1byte 2byte 2byte 4byte 4byte 2byte 2byte

GM8806A-PL1100101
GM8806A-PL11 - 97 -
GM8806A -PL Batching controller
GM8806A-PL

Correct response:
Function Account Data LRC
Start Address Stop
code byte area parity
1byte 2byte 2byte 2byte 2byte 2byte 2byte

Inquirycommand: 3A 30 31 30 31 30 30 32 38 30 30 30 34
44 32 0D 0A
3A 30 31 30 31 30 31 30 32 46 42 0D 0A
Correct response:3A
(Coil 0- 0- 1- 0)
Coil 43- 40 related status:0-
� 03 read register
Inquiry:Regulate to read register start address and register
quantities.
Response:Regulate read register byte quantities, every
register relate 2bytes respectively;Message also has data
from every read register.
For example:read register 0007 0008
0007、0008
0008。
A. RTU communication mode
mode:
Inquiry command:
Inquiry
Function Start CRC
Address register
code address parity
quantity
1byte 1byte 2byte 2byte 2byte

Correct response:
Function Account Register Register CRC
Address
code byte (0007) data (0008) data parity
1byte 1byte 1byte 2byte 2byte 2byte

- 98 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

01 03 00 07 00 02 75 CA
Inquiry command:01
01 03 04 00 00 00 05 3A 30
Correct response:01 30(Register
0007
0007、0008 0(Hex
0008 respective data:0 Hex 0000H)、5
0000H
Hex:0000H 5(Hex
Hex
Hex:
0005H
0005H)
B. ASCII communication mode
mode:
Inquiry command:
Inquiry
Function Start LRC
Start Address register Stop
code address parity
quantity
1byte 2byte 2byte 4byte 4byte 2byte 2byte

Correct response:
Register Register
Function Account LRC
Start Address (0007) (0008) Stop
code byte parity
data data
1byte 2byte 2byte 2byte 2byte 2byte 2byte 2byte

Inquirycommand: 3A 30 31 30 33 30 30 30 37 30 30 30 32
46 33 0D 0A
3A 30 31 30 33 30 34 30 30 30 30 30 30
Correct response:3A
30 35 46 33 0D 0A register 0007
0A(register 0008 respective data :
0007、0008
0(Hex
Hex 0000H
Hex:0000H
0000H)、5
5(Hex
Hex 0005H
Hex:0005H
0005H)
◆ 05 force single coil
Force:Regulate force coil address;and one normal item in
force data area,regulate requested coil ON/ OFF state:
FF00 for ON
ON,0000H for OFF
OFF,other data is ineffective to coil.

GM8806A-PL1100101
GM8806A-PL11 - 99 -
GM8806A -PL Batching controller
GM8806A-PL

Response:Return normal response for force coil.


For example:Force weighing indicator 01, 0056 coil is ON
A. RTU communication mode
mode:
Force command:
Function Coil CRC
Address Force data
code address parity
1byte 1byte 2byte 2byte 2byte
Correct response:
Function Coil CRC
Address Force data
code address parity
1byte 1byte 2byte 2byte 2byte
01 05 00 38 FF 00 0D F7
Force command:01
01 05 00 38 FF 00 0D F7
Correct response:01 F7((Coil 0056 is
ON
ON)
B. ASCII communication mode
mode:
Force command:
Function Coil Force LRC
Start Address Stop
code address data parity
1byte 2byte 2byte 4byte 4byte 2byte 2byte
Correct response:
Function Coil Force LRC
Start Address Stop
code address data parity
1byte 2byte 2byte 4byte 4byte 2byte 2byte
Force command:3A 3A 30 31 30 35 30 30 33 38 46 46 30 30
43 33 0D 0A
3A 30 31 30 35 30 30 33 38 46 46 30 30
Correct response:3A
43 33 0D 0A
0A(Coil0056 is ON
Coil0056 ON)
- 100 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

◆ 06 preset single register


Preset:Regulate to preset single register address and data.
Response:Return normal response after register is preset.
For example:Request 0009 register in weighing indicator 01
is preset 0005H
A. RTU communication mode:
Preset command:
Function Preset register Preset CRC
Address
code address data parity
1byte 1byte 2byte 2byte 2byte
Correct response:
Function Preset register Preset CRC
Address
code address data parity
1byte 1byte 2byte 2byte 2byte

01 06 00 09 00 05 99 CB
Preset command:01
01 06 00 09 00 05 99 CB
Correct response:01 register 0009
CB(register
data 5(Hex
data:5 Hex 0005H))
0005H
Hex:0005H
B. ASCII communication mode
mode:
Preset command:
Preset
Function Preset LRC
Start Address register Stop
code data parity
address
1byte 2byte 2byte 4byte 4byte 2byte 2byte

GM8806A-PL1100101
GM8806A-PL11 - 101 -
GM8806A -PL Batching controller
GM8806A-PL

Correct response:
Preset
Function Preset LRC
Start Address register Stop
code data parity
address
1byte 2byte 2byte 4byte 4byte 2byte 2byte
3A 30 31 30 36 30 30 30 39 30 30 30 35 45
Presetcommand:3A
42 0D 0A
3A 30 31 30 36 30 30 30 39 30 30 30 35
Correct response:3A
0A(register 0009 data: 5(Hex
45 42 0D 0A Hex 0005H))
0005H
Hex:0005H
◆16
16 10 hex
16(10 hex)) Preset several registers
Preset:Regulate to preset register start address and preset
value.
Response:Return address, function code, start address and
preset register quantity.
For example:Preset 2 registers in weighing indicator 01:
start register is 0030. Preset value is 0001H and 7318H
A. RTU communication mode
mode:
Preset command:
Function Start Register Account Preset CRC
Address
code address quantity byte data parity
1byte 1byte 2byte 2byte 1byte 4byte 2byte
Correct response:
Function Start Register CRC
Address
code address quantity parity
1byte 1byte 2byte 2byte 2byte
01 10 00 1E 00 02 04 00 01 73 18 07 D5
Preset command:01
- 102 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

01 10 00 1E 00 02 21 CE
Correct response:01
B. ASCII communication mode
mode:
Preset command:
Function Start Register Account Preset LRC
Start Address Stop
code address quantity byte data parity
1byte 2byte 2byte 4byte 4byte 2byte 8byte 2byte 2byte
Correct response:
Function Start Register LRC
Start Address Stop
code address quantity parity
1byte 2byte 2byte 4byte 4byte 2byte 2byte
Preset command:3A 3A 30 31 31 30 30 30 31 45 30 30 30 32
30 34 30 30 30 31 31 43 39 36 31 38 0D 0A
Correctresponse: 3A 30 31 31 30 30 30 31 45 30 30 30 32
43 46 0D 0A
4) MODBUS communication error message
When weighing indicator check other error message
except parity code( CRC or LRC)
LRC),indicator will send
message to host computer, the highest in function code is 1,
which means function code from weighing indicator to host
computer is added 128 based on function code from host
computer(For example: read register command 03H will be
changed to 83H
83H).
Error code:
02
02: error data address;Received data address is not
permitted by weighing indicator.
03
03: error data;Inquiry data is not permitted by weighing
indicator.
GM8806A-PL1100101
GM8806A-PL11 - 103 -
GM8806A -PL Batching controller
GM8806A-PL

0040
For example:Host computer read coil (0040
0040) by function
code 03.
Error message format:
1)RTU communication mode:
Address Function code Error code CRC parity

1byte 1byte 1byte 2byte


2)ASCII communication mode:
Function Error LRC
Start Address Stop
code code parity
1byte 2byte 2byte 2byte 2byte 2byte
1) RTU communication mode:
01 03 00 28 00 01 04 02
Inquiry command:01
01 83 02 C0 F1
Error response:01
2) ASCII communication mode
mode:
3A 30 31 30 33 30 30 32 38 30 30 30
Inquiry command:3A
31 44 33 0D 0A
3A 30 31 38 33 30 32 37 41 0D 0A
Error response:3A
From response message, the present error code is 02,
which means the present received data address is error, not
permit by weighing indicator.

- 104 - GM8806A-PL11
GM8806A-PL1100101
GM8806A -PL Batching controller
GM8806A-PL

9 Error and alarm message


ERROR :Input wrong value; please refer to related
parameter range to input again.
ERROR2
ERROR2:The present weight value is out of zeroing range.
ERROR3
ERROR3:Scale platform is not stable in zeroing.
ERROR4
ERROR4:Input wrong password more than 3 times.
ERROR5
ERROR5:Alarm for batching times
ERROR6
ERROR6:Alarm for discharging monitor
ERROR7
ERROR7:Alarm for batching monitor
ERROR8
ERROR8:Alarm for total target value is over maximum
capacity or target value is set as 0
ERROR9
ERROR9:Alarm for compensatory feeding
OVER :The load cell sign is too big in zero calibration.
UNDER :The load cell sign is too small in zero calibration.
OFL :Overflow