CLIENT: ISKAN

HVAC SYSTEM SET

LOCATION: KHARTOUM_SUDAN
PROJECT: THE GROCER PROJECT

Revision Schedule
Project No: Drawing Title: Project Title: MEP DESIGN : Revision Date Issued by Issued to Description Designed By: OSMAN MO.
C11 COVER SHEET_HVAC THE GROCER PROJECT 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

Sheet No: Drawn By: OSMAN MO.


SYSTEM Project Address:
M100_00 KHARTOUM_SUDAN Checked By: MO.BABIKER
Date: Scale:
2/11/2021 Approved By: MO.BABKIR REG. No. 6067
3:16:34 AM Client: ISKAN
All ideas, designs and plans represented by this drawing are the exclusive property of ISKAN ARCHITECTS, and shall not be reproduced in whole or in part without the express prior written permission of said designer, any unauthorized reuse of these plans other than for the project and location shown is prohibited.
All ideas, designs and plans represented by this drawing are the exclusive property of ISKAN ARCHITECTS, and shall not be reproduced in whole or in part without the express prior written permission of said designer, any unauthorized reuse of these plans other than for the project and location shown is prohibited.
REG. No. 6067
Approved By: MO.BABIKER
Checked By: MO.BABIKER
Designed By: OSMAN MO.

OSMAN MO.
Drawn By:
Description

DESIGN - INTENT - 00
Revision Schedule
Issued to

ISKAN
Issued by

MEP HOUSE
LIST OF DRAWING_ HVAC SYSTEM

11/02/2021
Date
Current Current Revision Issued Current Revision Issued Current Revision
Sheet Number Sheet Name Detail Sheet Drawn By Designed By Checked By Current Revision Date
Revision By To Description

Revision

1
M100_00 COVER SHEET_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_01 LIST OF DRAWING_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_02 GENERAL NOTES_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_03 INSTALLATION DETAILS_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

MEP DESIGN :
M100_04 INSTALLATION DETAILS_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_05 INSTALLATION DETAILS_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_06 BASEMENT FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_07 PART PLANE (01) BASEMENT FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_08 PART PLANE (02) BASEMENT FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_09 PART PLANE (03) BASEMENT FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

THE GROCER PROJECT


M100_10 GROUND FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

KHARTOUM_SUDAN
M100_11 PART PLANE (01) GROUND FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_12 PART PLANE (02) GROUND FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_13 PART PLANE (03) GROUND FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

ISKAN
M100_14 PART PLANE (04) GROUND FLOOR_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

Project Address:
M100_15 3D_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

Project Title:
M100_16 UTILITY AREA(01) 2D & 3DLANDSCAPE AREA_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

Client:
M100_17 UTILITY AREA(02) 2D & 3DLANDSCAPE AREA_HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_18 CALLOUT (01) 2D & 3D BASEMENT FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_19 CALLOUT (02) 2D & 3D BASEMENT FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_20 CALLOUT (03) 2D & 3D BASEMENT FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

DRAWING_HVAC
M100_21 CALLOUT (01) 2D & 3D GROUND FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_22 CALLOUT (02) 2D & 3D GROUND FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

SYSTEM
LIST OF
M100_23 CALLOUT (03) 2D & 3D GROUND FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

Drawing Title:
M100_24 CALLOUT (04) 2D & 3D GROUND FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

Scale:
M100_25 CALLOUT (05) 2D & 3D GROUND FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00
M100_26 CALLOUT (06) 2D & 3D GROUND FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

M100_01

3:16:35 AM
2/11/2021
M100_27 CALLOUT (07) 2D & 3D GROUND FLOOR _ HVAC SYSTEM HVAC SYSTEM OSMAN MO. OSMAN MO. MO.BABIKER 1 11/02/2021 MEP HOUSE ISKAN DESIGN - INTENT - 00

Project No:

Sheet No:
C11

Date:
All ideas, designs and plans represented by this drawing are the exclusive property of ISKAN ARCHITECTS, and shall not be reproduced in whole or in part without the express prior written permission of said designer, any unauthorized reuse of these plans other than for the project and location shown is prohibited.
NOTES

REG. No. 6067


1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CO-ORDINATION OF ALL SERVICES.

2. All DUCT, GRILLE AND PIPES SIZES ARE IN MM.

Checked By: MO.BABIKER

Approved By: MO.BABKER


Designed By: OSMAN MO.

OSMAN MO.
3. ALL WORKMANSHIP AND MATERIAL SHALL COMPLY TO THE RELEVANT B.S STANDARDS, ASHRAE, NFPA AND THE SPECIFICATION.

Drawn By:
4. ALL DUCT AND PIPE SUPPORTS TO BE DESIGNED TO WITHSTAND LATREAL MOVEMENTS AND LONGITUDINAL MOVEMENTS.

5. ALL EQUIPMENT, DUCT WORK, DAMPERS, SWITCHES, WIRES ETC. SHALL BE IDENTIFIED BY MARKERS/TAGS AS REQUIRED BY ENGINEER AND

Description
SPECIFICATION.

DESIGN - INTENT - 00
6. ALL THERMOSTAT IN PUBLIC AND COMMON AREA SHALL BE HOUSED IN LOCKABLE TRANSPARENT ENCLOSURE.

Revision Schedule
Issued to

ISKAN
7. ANY DISCREPANCY ARE TO BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND RESOLVED PRIOR TO FINALIZATION OF CONTRACT. ANY VARIATION DUE
TO NOT DOING SO WILL NOT BE ENTERTAINED.

Issued by

MEP HOUSE
8. WHERE MORE THAN ONE SERVICE (ELECTRICAL CABLES, DUCTS, PIPES) IS ROUTED THROUGH THE SAME AREA, THEY SHALL BE SUPPORTED BY

11/02/2021
Date
STRUCTURAL FRAME SUPPORT WITH SERVICES STACKED ONE ABOVE THE OTHER.

Revision

1
9. CONTRACTOR TO COORDINATE WITH STRUCTURAL DRAWINGS FOR OPENINGS AND PENETRATORS. SUBMIT BUILDING WORK SHOP DRAWING FOR
STRUCTURAL ENGINEER APPROVAL. ANY OPENING REQUIRED OTHER THAN THAT SHOWN

MEP DESIGN :
ON STRUCTURAL DRAWING SHALL BE APPROVED BY STRUCTURAL ENGINEER.

10. ALL ELECTRICAL LOADS SHOWN ON ELECTRICAL TENDER DRAWINGS/SPECIFICATION TO BE CHECKED AND CONFIRMED AND ADJUSTED AS DEEMED
NECESSARY.

THE GROCER PROJECT

KHARTOUM_SUDAN
11. SUITABLE APPROVED SLEEVES SHALL BE PROVIDED WHERE BOTH INSULATED AND NON INSULATED SERVICES PASS THROUGH WALLS AND FLOORS ETC.

12. PROVIDE STEEL PLATFORMS AND RAISED WALKWAYS TO CROSSOVER SERVICES ON ROOF/MECHANICAL FLOORS AND TO ACHIEVE ADEQUATE

ISKAN
Project Address:
MAINTENANCE ACCESS TO THE APPROVAL OF ENGINEER.

Project Title:

Client:
13. ALL EXPOSED ANGLE SUPPORTS FOR DUCTS/CHILLED WATER PIPES SHALL BE PAINTED AS SPECIFIED.

GENERAL NOTES_HVAC
14. HEATING, VENTILATION AND AIR CONDITIONING (HVAC) SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS MANUAL AND OTHER
APPROVED SUBMITTAL DATA

SYSTEM
15. VENTILATION AND AIR CONDITIONING DRAWINGS SHALL BE READ IN CONJUNCTION WITH GENERAL NOTES, SPECIFICATIONS, MISCELLANEOUS DETAILS,

Drawing Title:

1 : 500
ARCHITECTURAL, ELECTRICAL, MECHANICAL AND STRUCTURAL DRAWINGS.

Scale:
M100_02

3:16:35 AM
2/11/2021
Project No:

Sheet No:
C11

Date:
All ideas, designs and plans represented by this drawing are the exclusive property of ISKAN ARCHITECTS, and shall not be reproduced in whole or in part without the express prior written permission of said designer, any unauthorized reuse of these plans other than for the project and location shown is prohibited.
W

REG. No. 6067


MAX.SAG 1/2" PER FOOT OF
SUPPORT SPACING
25mm BAND
CLAMP 10mm
WITH WIRE IS SQUARE ROD
OPTINAL. VOLUME DAMPER WITH LOCKING
WxH
END BEARING TYPE IDICATOR QUADRANT AND
MAX.SAG 1/2" SADDLE TO CLEAR INSULATION
PER FOOT
300m OF SUPPORT CLINCH COLLAR
m M AXIM
UM SPACING BRANCH DUCT
*
FIG.A

Checked By: MO.BABIKER


Designed By: OSMAN MO.

OSMAN MO.
MAIN DUCT

Approved By: Approver


1/4W' , 100mm MINIMUM
45°

SUPPLY AIR FLOW


R = 1 1/2 W
W

Drawn By:
RETURN/EXHAUST AIR FLOW
MAX.SAG 1/2" 25mm MINIMUM WxH
PER FOOT
OF SUPPORT
SPACING
NOTES:
1.USE FOR SYMBOL 2.NOT TO BE USED AS
WHERE SUBSTITUTE FOR ELBOW
BRANCH DUCT AIR
QUANTITY IS

Description
LESS THAN 470 LPS.
FIG. B

DESIGN - INTENT - 00
01
FLEXIBLE DUCT SUPPORT DETAILS 02
RADIUS ELBOW 03
RECT.DUCT ANGULAR TAP WITH VOLUME DAMPER

Revision Schedule
Issued to
DUCT HANGER (TYP.) THREADED STUD
VOLUME DAMPER

ISKAN
SHEET METAL DUCT SEE PLANS
FOR CONTINUATION AND SIZES.
ACCOUSTICALLY LINED PLENUM ADAPTER
SPIN COLLAR
SUPPLY #24 GAUGE ALUMINUM SHEET METALCLADDING

Issued by
INSULATED
AIR

MEP HOUSE
REFRIGERANT PIPE FOR EXPOSED TO VIEW DUCT ONLY
DUCT
SUCTION & LIQUID

11/02/2021
Date
IT SQUARE EXTENSION DUCT COLLAR
UN
OIL
NC
FA DAMPER OPERATOR REMOVABLE INSULATION AS SPECIFIED

Revision

1
SPIN COLLAR DAMPER

OUTER CONE FLEXIBLE DUCT


WALL CHASING DUCT RING DUCT WORK

INNER INNER
CONS CONS
END TABS OR FLAPS FOR JOINTS FORMED BY STRIPPING FROM THE
FACTORY INSTALLED FLAME RESISTANT VAPOR BARRIER SEAL OVER LAPS WITH A QUICK TACKING ADHESIVE
CEILING QUICK TACKING
CONDENSING DRAIN SPONGE RUBBER GASKET ALL AROUND ADHESIVE TO BE

MEP DESIGN :
APPROX. OVERALL
FIELD INSTALLED COATED 100% OF ANGLE UNDERCUT WITH NEOPRENE GASKET
ALTERNATE LOCATION OF DUCT SURFACE AREA
SQUARE DIFFUSER WITH SQUARE NECK FIXED PATTERN #18 GAUGE TIE WIRE
WALL CHASING ALTERNATE LOCATION OF WITH SPACE AT
PLENUM BOX ADAPTER FOR FLEXIBLE CONNECTION 51 x 51 x 102AMM U.S.G #20
INSULATED 305mm OR APPROVED
GALVANIZED SHEET METAL CORNER BEADING
REFRIGERANT PIPE SUCTION EQUAL
NOTE:-
& LIQUID
DUCT INSDE THE MECHANICAL ROOM SHALL BE INSULATED WITH 25MM THICK
RIGID BOARD INSULATION AND WRAPPED WITH CANVAS AND PAINTED WITH POSTER PAINT.
(INSTEAD OF METAL CLADDING)

THE GROCER PROJECT


04
INSTALLATION OF SPLIT A/C UNIT 05
INSTALLATION OF SQUARE CEILING DIFFUSER Indoor Duct Insulation And Hanger
06
EVAPORATOR (INDOOR UNIT)

KHARTOUM_SUDAN

ISKAN
CONCRETE SLAB 9.3mm ∅ ALL THREADED
OIL RESISTANTBELTS

Project Address:
STRAP GALVANIZED STEEL RODS SUPPORT
ANCHOR (AS PER ROD SIZE TABLE-2) ADJUSTABLE SHEAVE DRIVE PULLEY
FROM BUILING STRUCTURE LENGTH ADJUSTABLE MOTOR MOUNT

Project Title:
OF RODS TO SUIT SPACE AVAILABLE SUPPORT RODS FROM MOTOR
WASHER BUILDINGS STRUCTURE STEEL SPRING AND RUBBER IN

Client:
NUT ALTERNATE MOTOR SHEAR TYPE VIBRATION ISOLATORS
DROP ROD - 2 Nos ALL THREADED STEEL SPRING AND RUBBER SUPPORT RODS FROM BUILDINGS STRUCTURE
FOR DUCTS UP TO 450mm. FOR DUCTS UP TO 910mm. (FOR SIZE SEE TABLE-2) LOCATION-FOR EXACT
IN SHEAR TYPE VIVRATION BELT GUARD
MAXIMUM DIMENSION. MAXIMUM DIMENSION. LOCATION SEE PROJECT
ISOLATION GREASE NIPPLES

DETAILS_HVAC SYSTEM
MOTOR DRAWINGS
BELT GUARD MOUNTING BRACKETS
DRIVE PIN THREADED STUD ADJUSTABLE MOTOR MOUNT
ADJUSTABLE SHEAVE TO POWER SOURCE SEE ALTERNATE MOTOR LOCATION-FOR EXACT
POWDER ACTUATED FASTENERS
DUCT INSULATION (AS PER DETAIL) DRIVE PULLEY PROJECT DWGS. LOCATION SEE PROJECT DRAWINGS
MOUNTING BRACKET
OIL RESISTANT BELTS
FLEXIBLE CONNECTION

INSTALLATION
HARDWOOD PAD 100x100x25 HIGH
DUCT
AIR FLOW AIR FLOW
FAN
MS ANGLE (FOR SIZE SEE TABLE-2) DUCT WORK END VIEW
STRAP ROD CONNECT DUCTWORK TO FAN
FOR DUCTS UP TO DUCTWORK

Drawing Title:
WITH 3.1mm THICK

1 : 500
450mm. FLEXIBLE CONNECTION
NEOPRENE GASKET
MAXIMUM

Scale:
DIMENSION. MOUNTING BRACKET BOLTS
25 25 DUCT SIZE 25 2 DUCTWORK
EXPANSION SHIELDS GREASE NIPPLES
5
CONCRETE ANCHORS EXPANSION NAIL FAN

M100_03

3:16:37 AM
2/11/2021
Project No:

Sheet No:
C11
UPPER ATTACHMENT FOR DUCT HANGERS HORIZONTAL DUCT SUPPORT RECTANGULAR DUCT

Date:
07 01 09
INLINE FAN DETAILS (SUPPLY/EXHAUST)
All ideas, designs and plans represented by this drawing are the exclusive property of ISKAN ARCHITECTS, and shall not be reproduced in whole or in part without the express prior written permission of said designer, any unauthorized reuse of these plans other than for the project and location shown is prohibited.
REG. No. 6067
NEOPRENE PADS 2 COATS OF VINYL BASED VAPOR BARRIER
4 OZ. CORA CLOTH BONDED ON THE INSULATION WITH 2 FOSTER 30-35 OR EQUIVALENT
LAYERS OF ATLAS FOSTER 30-36 OR EQUIVALENT
WALL CHASING

PITTSBURGH LOCK
LONGITUDINAL DRIVE SLIP
NEOPRENE PADS
SEAMS
W SUCTION PIPE

Checked By: MO.BABIKER


Designed By: OSMAN MO.

OSMAN MO.
BAR WHERE INDICATED IN
REFRIGERANT PIPE SUCTION & LIQUID TO FCU

Approved By: Approver


SCHEDULE

NEOPRENE PADS
H

Drawn By:
FINSHED GRADE LEVEL REFER TO CIVIL DWGS.

ANGLE IRON ADHESIVE FOSTER 85-20 OR EQUIVALENT


LIQUID PIPE

VIBRATION ISOLATOR
STANDING S1 STANDING S2

ANGLE IRON ADHESIVE FOSTER 85-20 OR EQUIVALENT

Description

DESIGN - INTENT - 00
DUCT JOINTS 11
INSTALLATION OF SPLIT A/C UNIT (CONDENSING UNIT) INSTALLATION OF REFRIGERANT EXPOSED PIPES
10 12

Revision Schedule
Issued to
STEEL HANGING WIRE (8G) (TYP.)
EXPANSION ANCHOR SOCKET (TYP.) EYE BOLT (TYP.)

ISKAN
FLEXIBLE DUCT FOR THERMAL INSULATION
SIZES SEE PLANS

DUCT PLENUM
WALL

Issued by
PLENUM INSIDE DIMENSIONAL

MEP HOUSE
UNDERSIDE
TABLE ( IN MM ) 25mm THK. LINING 25 MM BAND STEEL HANGING ROD
ALTERNATE INLET LOCATION OF SLAB
L/S/M X Y
OF FLEXIBLE DUCT CLAMP OR WIRE
28 250 250 TIMBER LINING 18mm THICK

11/02/2021
Date
46 250 250

62 250 250 DUCT


WALL

Revision
100
MM

SPECIAL SLOTTED LOCK

1
77 300 300 TO ALLOW ADJUSTMENT
OF COLLAR LENGTH ANGLE IRON SUPPORT DUCT
93 300 300
BAR GRILLE
108 300 300 WOOD PIECE TO REST
ON ANGLE IRON SUPPORT
123 300 300 INSULATED FLEXIBLE DUCT
(MAX. LENGTH 1000mm) DUCT INSULATION
139 300 300 X
MANUAL VOLUME CONTROL DAMPER
170 300 300
SEE NO OF SLOTS

MEP DESIGN :
INTERNALLY INSULATED
186 300 300 DIFFUSER ADAPTER
NOTE:-
UNLESS OTHERWISE SPECIFIED THE SIZE OF DIFFUSER
ADAPTER SHALL BE AS PER MANUFACTURER'S
NOTES:
RECOMMENDATIONS.
PLENUM LENGTH SHALL BE
25mm LONGER THAN THE
LINEAR SLOT DIFFUSER.

THE GROCER PROJECT


LINEAR SLOT DIFFUSER PLENUM DETAILS 15
LINEAR SUPPLY GRILLE DIFFUSER 14
INSTALLATION OF SPLIT A/C UNIT (CONDENSING UNIT)
13

KHARTOUM_SUDAN
LOW VELOCITY SUPPLY DUCT

CONTINUOUS PLENUM
GAGE 22

ISKAN
MANUAL VOLUME DAMPER WITH

Project Address:
LOCKING QUADRANT (WHERE FLEXIBLE DUCT
REQUIRED)

Project Title:
DUCT LINING RIGID FIBERGLASS 25 MM
BLOCK WALL

Client:
THICK 48 KG/M³ (AFICO QUITE LINER)
PIPE SLEEVE (SAME MATERIAL AS PIPE) FACING BLACK WOVEN-GLASS FIBER
FABRIC. FLEXIBLE DUCT
SEALANT

DETAILS_HVAC SYSTEM
W
PIPE NO.OF SLOTS MM

INSTALLATION
1 41 (1 5/8")
2 80 (3 1/8")

STAINLESS STEEL (OR GALVANIZED) NOTES:- 3 118 (4 5/8")

Drawing Title:
SPRING STEEL CINCH CLAMP (TYP.) 25 mm (TYP.) PIPE INSULATION (CHILLED WATER ONLY)

1 : 500
-DETAIL SHOWN FOR 4 SLOTS FOR NECK 4 155.5 (6 1/8")
WIDTH (W) SLOTS ARE SPECIFIED SEE TABLE

Scale:
INSULATED FLEXIBLE DUCT TO AIR SAFING INSULATION IN CASE OF FIRE RATED WALL ONLY -DIMENSIONS SHOWN ARE APPROXIMATE,
OUTLETS/INLETS CONTRACTOR TO VERIFY WITH
MANUFACTURER REQUIREMENTS.
-PLENUM BOX SHALL BE AS

M100_04

3:16:39 AM
MANUFACTURED BY ATAI OR APPROVED

2/11/2021
EQUAL.
INSULATED FLEXIBLE DUCT INSTALLATION DETAIL

Project No:

Sheet No:
C11
17 PIPE PENETRATION THROUGH BLOCK WALL
18
LINEAR SUPPLY GRILLE DIFFUSER

Date:
19
All ideas, designs and plans represented by this drawing are the exclusive property of ISKAN ARCHITECTS, and shall not be reproduced in whole or in part without the express prior written permission of said designer, any unauthorized reuse of these plans other than for the project and location shown is prohibited.
REG. No. 6067
THREADED STEEL HANGER RODS
&VIBRATION HANGERS; SUPPORT HEATING COIL
FROM BUILDING STRUCTURE -
TYP. COOLING COIL
PRE FILTER BAG FILTER MOTOR SUPPLY FAN

LIQUID LINE

SUCTION LINE
Condencate Drain

Checked By: MO.BABIKER


Designed By: OSMAN MO.

OSMAN MO.

Approved By: Approver


INLET AIR SUPPLY AIR
"CASSETTE" TYPE AIR CONDITIONING
ACU-1 UNIT c/wREMOVABLE FACE
P-TRAP ACU-3 GRILLE&FILTER.

Drawn By:
NOTES
1.) THIS DIAGRAM ID SCHEMATIC ONLY. EXACT ROUTING OF
PIPING AND MOUNTING OF UNITS TO BE DETERMINED ON- 150 mm THK. CONCRETE BED
15.5 mm THICK RUBBER PAD
SITE.
2.) REFRIGERANT TUBING & FITTINGS SHALL BE PROCESSED
TUBING SUITABLE FOR TIHS APPLICATION; EOXIDIZED,
INSULATED DEHYDRATED & SEALED, TYPE ACR w BRAZED
JOINTS. INSULATED SUCTION LINE 10mm thk ELASTOMER
PIPE INSULATION.

Description

DESIGN - INTENT - 00
Cassette Unit (Indoor Unit) 20 AIR HANDLING UNIT INSTALLATION DETAILS
16

Revision Schedule
Issued to

ISKAN
Issued by

MEP HOUSE
11/02/2021
Date
Revision

1
MEP DESIGN :
THE GROCER PROJECT

KHARTOUM_SUDAN

ISKAN
Project Address:
Project Title:

Client:
DETAILS_HVAC SYSTEM
INSTALLATION
Drawing Title:

1 : 500
Scale:
M100_05

3:16:40 AM
2/11/2021
Project No:

Sheet No:
C11

Date: