Professional Documents
Culture Documents
Building and Environment: 2 O.F. Yildiz, M. Yilmaz, A. Celik
Building and Environment: 2 O.F. Yildiz, M. Yilmaz, A. Celik
A R T I C L E I N F O A B S T R A C T
Keywords: Airport terminal buildings consume more energy than other buildings in an airport due to their functional and
Airport operational characteristics. Heating, ventilation and air conditioning (HVAC) systems have been major energy
Terminal building consumers with a significant contribution to the annual total energy consumption in terminal buildings partic
HVAC
ularly in harsh climates. Therefore, improvement of energy efficiency of the HVAC system is becoming an
Energy consumption
CO2 emission
increasingly important issue to reduce energy consumption and CO2 emissions of existing terminal buildings. The
aim of this study is to analyze and evaluate the effect of various energy conservation strategies on energy
consumption and CO2 emissions, including a number of modifications that can be applied to the HVAC system of
airport terminal buildings. Erzurum Airport terminal building, located in the coldest climate zone of Turkey, was
chosen as the airport terminal building. In order to achieve this goal, six strategies that can create energy savings
and cost savings and provide environmental benefits were analyzed and evaluated by building energy simulation.
The results indicated that energy consumption could be reduced from 6.3 GWh/year to 2.7 GWh/year and CO2
emissions from 1.9 million kg/year to 0.9 million kg/year by implementing feasible energy conservation stra
tegies. This means that, by implementing the proposed energy-saving projects, energy consumption and CO2
emissions can be reduced by 57.24% and 48.79%, respectively.
* Corresponding author.
E-mail addresses: farukmakina@hotmail.com (O.F. Yildiz), m.yilmaz@inonu.edu.tr (M. Yilmaz), acelik_25@hotmail.com (A. Celik).
https://doi.org/10.1016/j.buildenv.2021.108632
Received 15 July 2021; Received in revised form 23 November 2021; Accepted 24 November 2021
Available online 27 November 2021
0360-1323/© 2021 Elsevier Ltd. All rights reserved.
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
with other capital improvement projects [16]. Improvements in the ef commercial buildings. The approach was tested at the check-in hall of
ficiency of HVAC systems could be instrumental in maintaining existing the T-1 building of the Adelaide Airport in Australia. The results showed
power-plant generation capacity and avoiding further dependency on that the proposed HMPC scheme provides significant savings without
fossil fuels [17]. compromising thermal comfort. Malik [9] identified and assessed
The literature review shows that energy conservation of HVAC sys possible actions in key energy consuming equipment such as HVAC,
tems in terminal buildings has been the subject of many studies [7,10, lighting, and major electric motors to reduce energy use and improve
15,18,19]. The vast majority of these studies focused only on the control energy performance of three airport terminal buildings namely Raipur,
and operational strategies of the HVAC and lighting systems [7,15]. Aurangabad, and Udaipur in India. The results showed that the HVAC
However, there are few studies that comprehensively investigate mul system is one of the important energy consumers. Akyuz et al. [21]
tiple strategies which can be applied to HVAC system to reduce energy determined the energy performance indicators at airports using the
consumption and CO2 emissions of airport terminal buildings. Balaras method described in ISO 50001 energy management system (EnMS) and
et al. [18] evaluated different energy conservation strategies for 29 expressed mathematically the effects of these indicators on energy
Hellenic airports. In addition, the cost and simple payback period of the consumption. ISO 50001 EnMS is an international standard created by
strategies were estimated. Results showed that for the three airports, the International Organization for Standardization. This standard pro
potential energy savings range at 15–35%. Babu [8] recommended vides a systematic approach to improve the energy performance and
passive strategies like daylighting, natural ventilation, and passive reduce greenhouse gas emissions of an organization [22]. Through
downdraught evaporative cooling system to achieve energy efficiency in adopting ISO 50001 EnMS, guidelines are established for planning,
the HVAC and lighting system of the Ahmedabad International Airport implementing, monitoring and controlling the energy performance of an
terminal building in India. The study also identified various design re organization [23]. A study was performed under the ACRP project
sponses that have to be adopted by the building skin to achieve stepped 09-10, “Benchmarking and Profiling Airport Terminal Energy End Uses”,
temperature transitioning for identified zones in the terminal building. sponsored by the Transportation Research Board (TRB), Airport Coop
The stepped temperature transitioning is established as a result of erative Research Program (ACRP) [14]. A report entitled “Methodology
creating specific environments as the passenger traverses from landside to Develop the Airport Terminal Building Energy Use Intensity
to airside and vice versa with the help of the building envelope, which is (ATB-EUI) Benchmarking Tool” was published. An ATB was sub-divided
a result of the improved thermal design. It was found that energy savings into specific Zones: concession (food), concession (retail), office, tran
of up to 66% can be achieved in the terminal building by applying sient space, ticketing check-in, departures hold room, departure/border
passive design strategies and adopting an approach of mixed-modes in security, outbound/inbound baggage handling, arrivals/baggage claim,
buildings. The study also proved that in a building like an airport ter and service (mech/elec/server). Each of these Zones was assigned an
minal, the roof, which is one of the largest elements of the building, can Energy Use Intensity (EUI) based on the best available published EUIs
be put to effective use in ventilation, daylighting and temperature that are appropriate for that type of space. Five ATB Systems were
conditioning. Parker et al. [20] illustrated the role of simulation in identified and annual EU calculation per ATB system was performed: (i)
evaluating refurbishment options that reduce the carbon footprint of an people movers, escalators, elevators, (ii) baggage handling systems, (iii)
airport terminal building in the United Kingdom. Simulation results alternative systems (i.e., electric, heating/cooling), (iv) Airport Ground
showed that HVAC interventions resulted in a much greater reduction in Support Equipment (GSE), and (v) external/parking lighting. The utility
CO2 emissions. Mambo et al. [7] investigated the development of HVAC bills were used to calculate the (measured) Energy Use (EU) of an in
and lighting control strategies to provide sufficient comfort with opti dividual Airport Terminal Building (ATB). The utility bills usually con
mum energy use in the Manchester Airport terminal building. Perda sisted of electricity consumption (kWh) and gas consumption (MCF or
maian et al. [10] proposed and simulated three strategies to reduce the therms) data. The site visits resulted in collecting missing information
electricity consumption and CO2 emission of Terminal 3 Soekarno-Hatta for the EU/EUI (energy use intensity) benchmarking analysis. Thus, a
International Airport through an energy simulation software. The results methodology was developed to estimate the baseline of the total annual
showed that the strategies reduce electricity consumption and CO2 EU and EUI for the ATB building and an “Airport Terminal Building
emission. Akyuz et al. [12] investigated the application of thermal Energy Use Intensity (ATB-EUI) Benchmarking Tool” was created.
insulation on the walls and roof of the Hasan Polatkan Airport terminal Moreover, general recommendations were developed on how to achieve
building in Eskisehir, Turkey, from energy, environment and cost as greater energy efficiency, and better manage the energy consumption at
pects. They determined the optimum insulation thickness and assessed an airport terminal building.
its effects on environmental performance based on energy flows. Anal While these investigations are important, there is still a great need
ysis results showed that applying thermal insulation on the walls and for investigations that comprehensively explore the multiple strategies
roof of the terminal building reduces heat loss by 48% and 56%, that can be applied to the HVAC system to reduce the energy con
respectively. Huang et al. [15] presented a Hybrid Model Predictive sumption and the resultant CO2 emissions from the electricity and nat
Control (HMPC) scheme which can reduce HVAC energy consumption in ural gas use of airport terminal buildings. Therefore, the objective of this
2
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
study is to analyze and evaluate energy saving strategies that include fulfilled the required conditions within the scope of the ‘Green Airport
many different measures/applications that can be applied to the HVAC Project’ initiated by the General Directorate of Civil Aviation of Turkey.
system in order to reduce the energy consumption of the HVAC system of Erzurum Airport got this title by providing criteria in the TS EN ISO
airport terminal buildings. Erzurum Airport terminal building, located 14001 Environmental Management System Certification together with
in the coldest climate zone of Turkey, was chosen as the airport terminal the Greenhouse Gas Criteria Document and Green Airport Project Sec
building. Six strategies that can be applied practically were analyzed toral Criteria Document [25]. These criteria include: management of
and evaluated: (i) change the setpoint temperatures, (ii) night ventila waste water, management of environmental problems that may arise
tion, (iii) free cooling, (iv) adding heat exchangers, (v) retrofitting of the from de-ice/anti-icing activities, waste management, air pollution
air distribution system from CAV (constant air volume) to VAV (variable management (use of electric vehicles instead of fossil fueled vehicles in
air volume), and (vi) replacement of the existing circulating pumps. indoor environments, annual maintenance of combustion plants, etc.),
Potential energy saving rates and CO2 emission reductions were deter environmental noise management, management of rainwater, preven
mined for each strategy. Initial investment costs and payback periods tion of soil pollution (measures such as the use of water-oil separator, the
were calculated for each strategy. requirement that de-ice/anti-icing solvents be environmentally
friendly), and prevention of fuel leaks and intervention [2]. However,
2. Material and method there were no efficiency measures currently in place to reduce the en
ergy consumption, reduce energy costs and increase energy efficiency of
2.1. Erzurum Airport the HVAC system.
3
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
obtain the desired supply temperature. It can be designed with different constant air volume system is used in mixed air-handling units. The fan-
configurations depending on the mixture ratio. The domestic hot water coils are of two types, namely the floor standing type and the concealed
requirement of the terminal building is provided by a plate heat ceiling type. In addition to the terminal building, the VIP building is also
exchanger with 128 kW capacity which transfers heat from the hot water cooled by the chiller and 100% fresh air-handling unit. Terminal
in the boiler circuit flow to mains domestic water. In addition to the building cooling load is 1409 kW while the VIP building cooling load is
terminal building, other buildings at the airport are also heated by the 78 kW. Therefore, the share of the terminal building in the total cooling
central heating plant. load is approximately 95%.
The cooling of the terminal building is provided by air-cooled
chillers, mixed air-handling units and fan-coil units. A single-duct
4
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Table 1 Table 4
HVAC equipment in the terminal building. Existing condition of the building envelope.
No Equipment Capacity Number Roof Aluminum Granite Clad Windows
Panel Clad External Wall
1 Hot water boiler 1745 kW 3
External Wall
2 Air-cooled chiller 1087 kW 2
3 Unit heater 6 kW 9 Outermost Aluminum Aluminum Granite Clad: Tempered
4 Air handling unit (mixed air) Supply fan: 2500–12778 l/s 8 layer Sheet: 4 Clad: 20 Glass: 6
Exhaust fan: 1944–8333 l/s (mm) 2.5
Heating coil: 75–395 kW Layer 2 Rock Wall: Air Barrier Air Barrier Air:
Cooling coil: 52–233 kW (mm) 120 (Kraft Paper): (Kraft Paper): 14
5 Air handling unit (100% fresh air) Supply fan: 1528–2500 l/s 2 0.6 0.6
Exhaust fan: 1528–2500 l/s Layer 3 Polyethylene XPS: XPS: Laminated
Heating coil: 93–145 kW (mm) Moisture 100 100 Glass:
Cooling coil: 47–76 kW Barrier: 0.5 6
6 Exhaust air fan 167–2778 l/s, 150–340 Pa 15 Layer 4 Glass Wool: Polyethylene Polyethylene –
7 Fresh air fan 833–1389 l/s, 150 Pa 2 (mm) 30 Vapor Barrier: Vapor Barrier:
8 Fan-coil 1–7 kW, 0.07–0.33 l/s 126 0.5 0.5
Innermost Steel Sheet: Gypsum Wall Gypsum Wall –
layer 0.5 Board: Board:
(mm) 12.5 12.5
Table 2 Calculated U 0.22 0.313 0.312 1.761
The heating/cooling setpoint temperatures of the HVAC equipment used in the Value (W/
terminal building. m2K)
U Value 0.25 0.4 0.4 2.4
No Zone Name HVAC Heating setpoint Cooling setpoint specified
Equipment temperature temperature in TS 825
(oC) (oC) (W/m2K)
1 Offices Fan-coil, CAV, 22 23
Exhaust Air
Fan the values specified in the standard.
2 Check-In Hall CAV, Exhaust 22 23
Air Fan
3 Passenger and CAV, Exhaust 22 23 2.2. Method
baggage halls Air Fan
4 Incoming Unit Heater 15 – Terminal buildings are seen to have the largest share when consid
baggage and ering the total energy consumption at the airport in general terms. On
baggage
reception areas
the other hand, the system with the largest share of the energy consumed
5 Kitchen, CAV, Exhaust 22 23 in the terminal buildings has been found to be the HVAC system. Per
cafeteria and Air Fan, Fresh damaian et al. [10] determined that 86.59% of the total electricity
restaurant Air Fan consumption of the Terminal 3 Soekarno-Hatta International Airport
was consumed by the HVAC system, 9.33% by the lighting system,
2.41% by the electrical equipment, and 1.76% by the transportation
2.1.4. System pumps and fans
system. According to Alba [1], approximately 70% of the energy
In the terminal building, there are 16 pumps in various capacities
consumed in airport terminal buildings is used for heating, cooling and
used to circulate hot water, chilled water and domestic hot water
air conditioning purposes; this rate is higher in countries with cold cli
(Table 3). Eight of these pumps provide hot or chilled water to the air-
mates. In the study published by the U.S. National Academy of Sciences
handling units. Four pumps are used for the fan-coil systems. The
[14], a method, which are based on individual parameters of each sys
remaining four pumps provide the heated water to the heat exchanger
tem and its particular annual energy use estimation, for determining the
that produces domestic hot water. All of the circulation pumps are single
annual energy use per system of an airport terminal building was
speed or three speed.
developed. With the developed method, the total annual energy use of
escalator systems, people movers (moving walkways) systems, baggage
2.1.5. Building envelope
handling systems and elevators was calculated as 69,806 kBtu/yr, 115,
Table 4 shows the elements that make up the building envelope and
895 kBtu/yr, 22,288 kBtu/yr, 24,646 kBtu/yr, for a single unit,
their material thicknesses. The building envelope consists of an
respectively. In addition, the process of calculating and formulas of the
aluminum roof, aluminum panel clad external wall, granite clad external
total annual energy use of alternative systems, ground support equip
wall and tempered glass windows. According to the “TS 825 Thermal
ment and external lighting and parking lighting systems were illus
Insulation Requirements for Buildings” standard [29], Erzurum is
trated. The total energy consumption of the Erzurum Airport terminal
located in the fourth (coldest) degree day zone in Turkey. The overall
building is 6.301 GWh per year, with 69.99% of that is consumed by
heat transfer coefficients (U-Value) for Erzurum specified in this stan
heating system, 11.90% used by lighting system, 8.89% consumed by
dard and the overall heat transfer coefficients (U-Value) were calculated
pumps and fans, 4.29% used by domestic hot water, 2.54% consumed by
considering the thermal conductivity of the building elements given in
cooling system, 2.38% used by electricity equipment, and 0.02% used by
Table 4. As seen in the table, the calculated overall heat transfer co
exterior lighting [2]. These results reveal that approximately 81% of the
efficients (U-Value) of the building envelope are an improvement over
energy consumed in Erzurum airport terminal building is used for HVAC
purposes. All these results show that improvements to be made in HVAC
systems in airport terminal buildings will have significant energy saving
Table 3
potential.
System pumps in the terminal building.
In order to reduce the energy consumption and CO2 emissions of the
No Circulation Pumps Range of Max Flow Range of Head Max Number
terminal building, a number of modifications can be made in the HVAC
1 Heating system 3–14 l/s 4.5–7 m 6 system with an acceptable level of investment. Therefore, there is a need
2 Cooling system 14–32.5 l/s 8.5–10 m 6 to provide accurate and reliable energy simulation models to study
3 DHW system 0.5–2 l/s 4–4.5 m 4
feasibility of these modifications that could lead to energy savings [30].
5
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
6
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Table 7
Inputs for the HVAC modeling.
No Zone Name Outside Air Heating/Cooling Heating/Cooling System Heating/Cooling (days/ Air Temperature
(ac/h) Fuel Seasonal COP week) Distribution
Table 8
Inputs for the Lighting modeling.
No Zone Name Template Normalized Power Density (W/m2-100 lux) Luminaire Type Radiant Fraction Visible Fraction
determined. The savings were estimated by adding the gains from each
strategy that is feasible in terms of energy, cost and environmental to the Table 9
The proposed strategies and their characteristics.
next.
In addition, the costs and simple payback periods of the strategies No Strategy Characteristics References
were estimated in order to evaluate the economic benefit of the strate 1 Change of the setpoint The total energy consumption [19,
gies proposed in this study. When calculating the payback period, the temperatures could be reduced by decreasing/ 35–38]
natural gas tariff and electricity tariff were assumed to be 0.023 $/kWh increasing heating/cooling
setpoint temperatures of the
and 0.088 $/kWh, respectively. Electric demand costs and all taxes are zones to the temperature ranges
included in the electricity tariff. Simple payback period is calculated recommended by CIBSE.
using the following equation: 2 Night ventilation The total electrical energy [39–41]
consumption could be reduced by
Initial investment cost of modification [$] supplying the outdoor air, which
Payback Period = (2)
Annual energy cost saving [$/year] has a lower temperature than the
indoor temperature, to the indoor
during nighttime hours.
3. Energy conservation strategies for the HVAC system 3 Free cooling A considerable energy savings [42,43]
could be achieved by using a
A very large amount of the annual total energy consumed in Erzurum water-side economizer when the
outdoor air temperature is low
Airport terminal building is consumed by the HVAC system. Analysis of
enough.
the simulation results revealed that the HVAC system had significant 4 Adding heat exchanger The total energy consumption [44–46]
savings potential [2]. Therefore, it is very important to identify possible could be reduced by adding air-to-
strategies that can be implemented in the HVAC system in order to air heat exchangers into the
existing AHUs.
reduce the energy consumption and CO2 emissions of the terminal
5 Retrofitting of the air The total energy consumption [30,47]
building. In this study, six different energy saving strategies were pro distribution system from could be reduced by retrofitting
posed, including modifications to the HVAC system and changing the CAV to VAV the existing air distribution
setpoints of the HVAC system operating parameters, in order to reduce system from CAV to VAV.
energy consumption, reduce the energy costs of operating the HVAC 6 Replacement of the The total electrical energy [48,49]
existing circulation consumption could be reduced by
system and increase energy efficiency in the Erzurum Airport terminal
pumps replacing the existing single/
building. These strategies are: (i) change of the setpoint temperatures, three speed hot water and chilled
(ii) night ventilation, (iii) free cooling, (iv) adding a heat exchanger, (v) water circulation pumps with
retrofitting of the air distribution system from CAV to VAV, (vi) variable speed circulation pumps.
replacement of the existing circulation pumps with variable speed cir
culation pumps. Table 9 identifies the proposed strategies and their
CO2 emission of the building.
characteristics.
3.1.1. Heating setpoint temperature
3.1. Change of the setpoint temperature Heating setpoint temperature is one of the thermostat strategies used
in the HVAC systems and has a significant role in the space heating
This section aimed to identify the effect of changing the heating and energy demand of a building. A considerable energy savings can be
cooling setpoint temperatures, which is the one of the most significant achieved in a building that is in a cold climate region by decreasing the
thermostat strategies [35], on the total energy consumption and total heating setpoint temperature in the winter [35,37,38]. The Chartered
7
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
8
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Fig. 6. Schematic of air-cooled chiller with water-side economizer operating in hybrid mode [53].
9
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Fig. 8. Schematic of: a) the existing CAV system, b) the proposed VAV system.
consumption. building (the reference building) was the first step in the process of
determining the energy consumption pattern of an airport terminal
3.6. Replacement of existing circulating pumps building and suggesting practices/measures to reduce it. Therefore, the
Erzurum Airport terminal building was modeled and an energy simu
One of the most significant energy consumers in a terminal building lation was performed. The simulation results (energy and environ
are the chilled water and hot water circulating pumps, which are mental) were evaluated only at the building level. Fig. 9 shows the
commonly used in heating and cooling applications. As can be seen in monthly changes in total energy consumption of the terminal building.
Table 3, there are total 16 single/three speed hot water and chilled water The two main energy sources of the terminal building are natural gas
circulation pumps (4 of these pumps are single speed) in the terminal and electricity. The actual annual natural gas consumption of the ter
building with different capacities and pressure used in the heating and minal building was 4,677,042 kWh (16,837 GJ), electricity consumption
cooling systems. Unfortunately, the circulating pumps operate at is 1,614,464 kWh and annual total energy consumption is 6,291,506
maximum flow rate and pressure which can be significantly higher than kWh. The annual energy intensity of the terminal building was 485.83
required. This often results inefficient operation of the pumping systems. kWh/m2. The highest energy consumption was in January (908,526
However, variable speed circulation pumps adjust the motor speed ac kWh) due to the lower outdoor temperatures in January versus other
cording to the requested flow rate and pressure. This is important months while the lowest energy consumption was in July (249,568
because even small reductions in motor speed results large power re kWh). Although the electricity consumption of the terminal building
ductions. Thus, significant improvements in energy efficiency and cost increases in the summer months due to the need for cooling, the total
savings can be achieved [49]. energy consumption of the building decreases as there is no need for
In this study, various strategies were reviewed and analyzed in order heating during these months. Detailed information on the energy char
to achieve energy and cost savings and environmental gains in airport acteristics of Erzurum Airport terminal building can be found in Refs. [2,
terminal buildings. It has been determined that some of these strategies 57].
will reduce the heating and cooling load of the terminal building. Due to Fig. 10 shows a comparison of actual and simulated energy con
this reduction in heating and cooling loads, the hot water and chilled sumption of the Erzurum Airport terminal building. The annual actual
water circulation pumps used in the system should be resized according energy consumption in 2014 and 2015 was taken as basis for the actual
to their new load capacities. Therefore, the existing circulation pumps energy consumption of the Erzurum Airport terminal building. As seen
can be replaced with variable speed circulation pumps that are resized in the figure, the actual energy consumption of the terminal building is
according to the reduced heating and cooling loads. 7,015,081 kWh and the simulated energy consumption is 6,291,507
kWh. The difference between actual and simulated energy consumption
4. Results and discussion is 11% [2].
Fig. 11 illustrates the energy consumption pattern of the terminal
4.1. Results for the reference building building. In cold climate regions like Erzurum, space heating is a major
share of the annual total energy consumption. Space heating is followed
Performing an energy analysis on an existing airport terminal by lighting (including exterior lighting), pumps and fans, domestic hot
10
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Fig. 9. Monthly changes in total simulated energy consumption of the Erzurum Airport terminal building.
Fig. 10. Monthly changes in total actual and simulated energy consumption of the Erzurum Airport terminal building [2].
11
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Fig. 12. Daily simulated CO2 emission of the Erzurum Airport terminal building.
consumption and displaced CO2 emission was examined only at the criteria for specific areas in airport terminal building are presented in
whole building level. This allowed the strategies to be evaluated accu Table 10, and the comfort criteria for the general areas in the building
rately and reasonably using simulation. The proposed strategies were using CIBSE recommendations are shown in Table 11. Fig. 13 shows the
described and identified in Section 3. effect of reducing the heating setpoint temperatures to the temperatures
recommended by CIBSE on the monthly energy consumption and dis
4.2.1. Strategy 1: change of the setpoint temperature placed CO2 emissions of the terminal building. As seen in Fig. 13, the
The first simulated energy conservation strategy was decreasing/ simulated energy consumption decreased in all months when the heat
increasing indoor air setpoint temperatures. The recommended comfort ing setpoint temperatures are lowered to the temperatures
Fig. 13. The effect of reducing the heating setpoint temperatures on the monthly energy consumption and displaced CO2 emissions of the terminal building.
12
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
recommended by CIBSE. On the other hand, the displaced CO2 emissions 4.2.3. Strategy 3: free cooling
decreased in all months due to the decrease in energy consumption. Another strategy analyzed and evaluated the reduced energy con
Examination of the figure shows that although energy consumption in sumption of the terminal building from the use of a water-side econo
creases in September compared to August, displaced CO2 emissions mizer. Analysis of the simulation results reveals that there is no need for
decreased. This is due to the increase in the share of electricity con cooling in any part of the terminal building when the outside air tem
sumption in the total energy consumption and the fact that the estimated perature is lower than the return water temperature (11 ◦ C). However,
emission factor of electricity kg.CO2/kWh is larger than the natural gas the indoor air temperature of some areas may momentarily exceed the
emission factor. cooling setpoint temperature due to internal heat gains. This tempera
Table 12 provides a summary of the simulated effect of reducing the ture rise results in a barely noticeable increase (2.9 kW) in the energy
heating setpoint temperatures on energy consumption and energy costs. consumed for cooling. As a result, there has been no improvement in the
A significant reduction of the annual total energy consumption is ach energy efficiency of the HVAC system due to the use of this strategy.
ieved by reducing the heating setpoint temperatures. Natural gas and Therefore, it is not recommended to use free cooling to reduce the en
electricity consumption are reduced by approximately 20% and 2%, ergy consumption and displaced CO2 emissions of the terminal building.
respectively. The annual energy intensity decreased from 485.83 kWh/
m2 to 410.12 kWh/m2. The annual energy intensity reduction rate is 4.2.4. Strategy 4: adding heat exchanger
approximately 16%. Reducing the heating set point temperatures of the Fig. 15 shows the effect of adding a rotary heat exchanger to existing
spaces in the terminal building not only reduces the space heating en AHUs on the monthly energy consumption and displaced CO2 emissions
ergy consumption, but also the energy consumption of the system pumps of the terminal building. The use of rotary heat exchanger reduces en
and fans. ergy consumption in all months. The decrease in energy consumption is
Recommended comfort criteria for some specific areas in airport much higher in winter than in other months. For example, while the
terminal building are presented in Table 10, recommended comfort energy consumption is 802,520 kWh in January, with the use of the
criteria for general areas in a building by CIBSE in Table 11. Fig. 14 rotary heat exchanger, the energy consumption decreases by 49%–
shows the effect of changing the cooling setpoint temperatures to the 410,685 kWh. Due to the reduction in energy consumption, total dis
temperatures recommended by CIBSE on the monthly energy con placed CO2 emissions are also reduced.
sumption and displaced CO2 emissions of the terminal building. When The effect of adding rotary heat exchangers into the AHUs on energy
the cooling setpoint temperatures are changed to the temperatures consumption and energy cost of the terminal building is given in
recommended by CIBSE, the total energy consumption and the total Table 15. When the table is examined, it is seen that the annual total
displaced CO2 emissions of the terminal building do not change during energy consumption has decreased by approximately 48% although
the months when cooling system is not in operation (during the heating additional fan energy is required due to the increased pressure drop
season). Total energy consumption decreases during the cooling season across the rotary heat exchanger. This reduction leads to savings of
in which the cooling system is operated. For example, the decrease in $87,079 in annual energy cost. The fact that the addition of a rotary heat
total energy consumption in August is around 4%. Total displaced CO2 exchanger to existing AHUs provides such high energy savings is due to
emissions remain constant during the months when the cooling system is the fact that the large spaces in the terminal building are heated by
not operating. In the months when the cooling system is operating, the AHUs, and the energy demand for heating is very high since the airport
total displaced CO2 emissions are reduced due to the reduction in energy is located in the cold climate region.
consumption. In June, the building’s total displaced CO2 emission rea The initial investment cost of adding rotary heat exchangers to AHUs
ches its lowest value with 94,757 kg. is given in Table 16. Examination of Tables 15 and 16 shows that the
Table 13 presents the effect of increasing the cooling setpoint tem payback period for this modification is less than one year. Therefore, it
peratures on energy consumption and energy cost. When the cooling can be stated that it would be economically viable to add rotary heat
setpoint temperatures are increased the total energy consumption of the exchangers to AHUs.
terminal building reduce by almost 0.5%. There is generally a limited
need for cooling in Erzurum Airport terminal building since it is located 4.2.5. Strategy 5: retrofitting of the air distribution system from CAV to
in a cold climate region. Therefore, the cooling energy saving rate is very VAV
low. Warm climates benefit more from increased cooling setpoint tem The effect of retrofitting of the existing air distribution system from
peratures, while colder climates benefit more from decreased heating CAV to VAV on natural gas consumption, electricity consumption and
setpoint temperatures [36]. energy cost is summarized in Table 17. It is seen that this modification
has little effect on natural gas consumption and electricity consumption.
4.2.2. Strategy 2: night ventilation There is an annual decrease of 2.3% in natural gas consumption, and a
Table 14 shows a summary of the effect of night ventilation for the decrease of 0.7% in electricity consumption annually. The low effect of
office areas on energy consumption and energy cost of the terminal retrofitting the existing CAV system to a VAV system on energy con
building. The use of night ventilation for the office areas reduces the sumption indicates that a high supply air flow rate is generally needed in
cooling energy consumption of the terminal building. However, night the terminal building to keep the space temperature at a comfort level.
ventilation requires operating the supply and exhaust fans mounted in Retrofitting of the existing air distribution system from CAV to VAV
the AHUs of the offices. This leads to an increase in total electricity resulted saves $1561 in the annual energy cost of the building. The
consumption of the terminal building, since the base case simulation has initial investment cost of the retrofitting is shown in Table 18. The
the AHUs turned-off. Therefore, it was concluded that night ventilation payback period of this modification is approximately 12 years due to low
for the office areas is not economically viable. energy savings and high initial investment costs. Considering that the
lifetime of the existing CAV system is 20 years and the current system
Table 12
The effect of reducing the heating setpoint temperatures on energy consumption and energy cost.
Natural Gas Consumption (kWh) Electricity Consumption (kWh) Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)
13
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Fig. 14. The effect of increasing the cooling setpoint temperatures on the monthly energy consumption and displaced CO2 emissions of the terminal building.
Table 13
The effect of increasing the cooling setpoint temperatures on energy consumption and energy cost.
Natural Gas Consumption Electricity Consumption Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)
(kWh) (kWh)
Table 14
The effect of night ventilation for the office areas on energy consumption and energy cost of the terminal building.
Natural Gas Consumption (kWh) Electricity Consumption (kWh) Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)
has been used for about 16 years, this modification would not be feasible in September. As a result of the use of variable speed circulation pumps,
in terms of technical and economic considerations. the annual total displaced CO2 emissions are reduced by almost 3.6%.
The effect of replacement of single/three speed circulation pumps
4.2.6. Strategy 6: replacement of the existing circulation pumps with variable speed circulation pumps on energy consumption and en
Fig. 16 shows the effect of replacement of single/three speed circu ergy cost of the terminal building is given in Table 19. As can be seen
lation pumps with variable speed circulation pumps on the monthly from the table, replacement of the existing circulation pumps is reduced
energy consumption and displaced CO2 emissions of the terminal the annual total electricity consumption, whereas the annual total nat
building. The energy consumption and displaced CO2 emissions of the ural gas consumption remains unaffected. It has been determined that
terminal building reduce in all months. The energy consumption of the the use of variable speed circulation pumps will save $5031 per year.
terminal building reaches its lowest value of 119,246 kWh in June, The initial investment cost of using variable speed circulation pumps
whereas its displaced CO2 emission reaches its lowest value of 59,162 kg in the HVAC system has been calculated and given in Table 20.
14
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Fig. 15. The effect of adding the rotary heat exchangers into existing AHUs on the monthly energy consumption and displaced CO2 emissions of the termi
nal building.
Table 15
A summary of the effect of adding the rotary heat exchangers into the AHUs on energy consumption and energy cost.
Natural Gas Consumption (kWh) Electricity Consumption (kWh) Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)
Table 17
The effect of retrofitting of the existing CAV system to VAV system on energy consumption and energy cost.
Natural Gas Consumption (kWh) Electricity Consumption (kWh) Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)
15
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Fig. 16. The effect of replacing existing circulation pumps with variable speed circulation pumps on the monthly energy consumption and displaced CO2 emissions of
the terminal building.
Table 19
The effect of replacing existing circulation pumps with variable speed circulation pumps on energy consumption and energy cost.
Natural Gas Consumption (kWh) Electricity Consumption Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)
(kWh)
16
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
Table 21
The feasible ones among the suggested strategies.
Strategy Energy Consumed (kWh/ Energy Saving CO2 CO2 Reduction Initial Investment Cost Payback Period
year) (%) Emission (kg/ (%) ($) (years)
year)
To achieve this purpose, six strategies were analyzed and evaluated: (i) will require more natural gas use. Therefore, when examining
change of the setpoint temperatures, (ii) night ventilation, (iii) free these strategies, the total energy consumption of the terminal
cooling, (iv) adding heat exchanger, (v) retrofitting of the air distribu building must be carefully analyzed and evaluated.
tion system from CAV to VAV, (vi) replacement of the existing circula (8) Airports are suitable settlements for the installation of renewable
tion pumps with variable speed circulation pumps. The main energy systems as they have vast and free of shade areas. Through
conclusions are summarized as follows: further research, the renewable energy systems which have the
best benefit/cost ratio for the airport can be determined. Thus,
(1) An energy analysis of the airport terminal building has been made the net energy consumption of the terminal building can be
and it has been determined that the HVAC system is the largest reduced.
energy consumer compared to other systems in the terminal
building. The energy consumed by the HVAC system constitutes CRediT authorship contribution statement
approximately 81.6% of the total energy consumption of the
terminal building. HVAC system is followed by lighting O.F. Yildiz: Formal analysis, Data curation, Investigation, Method
(including exterior lighting), pumps and fans, domestic hot ology, Writing – original draft, Software. M. Yilmaz: Writing – review &
water, cooling, and room electricity, respectively. editing, Supervision, Conceptualization. A. Celik: Validation,
(2) Improving the energy efficiency of the HVAC system, which has a Visualization.
high energy consumption, is of great importance to reduce the
energy consumption and displaced CO2 emissions of the terminal
building. Declaration of competing interest
(3) Strategies that changed the setpoint temperatures, adding heat
exchanger and replacement of existing circulation pumps with The authors declare that they have no known competing financial
variable speed circulation pumps are found to be feasible in terms interests or personal relationships that could have appeared to influence
of energy, cost and environment. On the other hand, the strate the work reported in this paper.
gies of night ventilation, free cooling and retrofitting of the air
distribution system from CAV to VAV are found to be not References
economically viable.
(4) By implementing feasible strategies, considerable energy and [1] S. Alba, M. Manana, Energy research in airports: a review, Energies 9 (5) (2016)
349.
energy costs can be saved and displaced CO2 emissions reduced [2] O.F. Yildiz, M. Yilmaz, A. Celik, Energy analysis of cold climate region airports: a
for the electricity and natural gas that were saved. While the case study for airport terminal in Erzurum, Turkey, Int. J. Sustain. Aviat. 7 (1)
potential energy saving range of the strategies is between 0.44% (2021) 66–92.
[3] N. Sumathi, P.S. Ramnareddran, G.J.A. Revanth, G.V. Arasu, Sustainable methods
and 48.04%, the potential displaced CO2 emission reduction used to reduce the energy consumption by various facilities in airport terminals,
range of the strategies is between 0.79% and 40.08%. Int. J. Latest Technol. Eng. Manag. Appl. Sci. 6 (11) (2017) 41–44.
(5) Energy savings for the strategies of decreasing heating setpoint [4] G. Baxter, P. Srisaeng, G. Wild, Sustainable airport energy management: the case of
Kansai International Airport, Int. J. Traffic Transport. Eng. 8 (3) (2018).
temperature, increasing cooling setpoint temperature, adding [5] F. Greer, J. Rakas, A. Horvath, Airports and environmental sustainability: a
heat exchanger, and replacement of existing circulation pumps comprehensive review, Environ. Res. Lett. 15 (10) (2020) 103007.
with variable speed circulation pumps is 15.58%, 0.44%, [6] K.M. Reena, A.T. Mathew, L. Jacob, A flexible control strategy for energy and
comfort aware HVAC in large buildings, Build. Environ. 145 (2018) 330–342.
48.04%, and 2.08%, respectively. As can be seen, the positive
[7] D.A. Mambo, M. Efthekhari, T. Steffen, Occupancy-driven supervisory control
effect of adding rotary heat exchangers to AHUs is better than strategies to minimise energy consumption of airport terminal building, Sustain.
other strategies. Energy Build. (2013) 479–489.
(6) Displaced CO2 reduction for the strategies of decreasing heating [8] A.D. Babu, A low energy passenger terminal building for Ahmedabad Airport,
India: building envelope as an environment regulator, in: Proceedings of the 25th
setpoint temperature, increasing cooling setpoint temperature, Conference on Passive and Low Energy Architecture, Dublin, Ireland, 2008,
adding heat exchanger, and replacement of existing circulation pp. 22–24.
pumps with variable speed circulation pumps is 10.59%, 0.79%, [9] K. Malik, Assessment of energy consumption pattern and energy conservation
potential at Indian airports, J. Constr. Dev. Ctries. (JCDC) 22 (2017) 97–119.
40.08%, and 3.65%, respectively. [10] L.G. Perdamaian, R. Budiarto, M.K. Ridwan, Scenarios to reduce electricity
(7) Additional energy conservation strategies in the lighting system consumption and CO2 emission at terminal 3 Soekarno-Hatta international airport,
and the building envelope (such as improvement external wall Proc. Environ. Sci. 17 (2013) 576–585.
[11] B.L. Gowreesunker, S.A. Tassou, M. Kolokotroni, Coupled TRNSYS-CFD simulations
and roof thermal insulation, replacing the existing lighting fix evaluating the performance of PCM plate heat exchangers in an airport terminal
tures with LED, installation of lighting control system, exploit day building displacement conditioning system, Build. Environ. 65 (2013) 132–145.
lighting etc.) should be investigated in the future studies [12] M.K. Akyuz, O. Altuntas, M.Z. Sogut, Economic and environmental optimization of
an airport terminal building’s wall and roof insulation, Sustainability 9 (10) (2017)
considering their payback period. These strategies can reduce the 1849.
electricity consumption of the terminal building. However, the [13] C.R. Lau, J.T. Stromgren, D.J. Green, Airport Energy Efficiency and Cost Reduction.
electricity saved in the winter will lead to reduced heat gain that ACRP Synthesis Report 21, Transportation Research Board of the National
Academies, Washington, DC, 2010.
17
O.F. Yildiz et al. Building and Environment 208 (2022) 108632
[14] National Academies of Sciences, Engineering, and Medicine, Methodology to [37] A. Kotopouleas, M. Nikolopoulou, Thermal comfort conditions in airport terminals:
Develop the Airport Terminal Building Energy Use Intensity (ATB-EUI) indoor or transition spaces? Build. Environ. 99 (2016) 184–199.
Benchmarking Tool, The National Academies Press, Washington, DC, 2016, [38] H. Kim, T. Hong, Determining the optimal set-point temperature considering both
https://doi.org/10.17226/23495. labor productivity and energy saving in an office building, Appl. Energy 276
[15] H. Huang, L. Chen, E. Hu, A new model predictive control scheme for energy and (2020) 115429.
cost savings in commercial buildings: an airport terminal building case study, [39] B.R. Hughes, H.N. Chaudhry, S.A. Ghani, A review of sustainable cooling
Build. Environ. 89 (2015) 203–216. technologies in buildings, Renew. Sustain. Energy Rev. 15 (6) (2011) 3112–3120.
[16] W.D. Turner, M. Verdict, B. Yazdani, H. Huff, K. Clingenpeel, Model for improving [40] J. Le Dréau, P. Heiselberg, R.L. Jensen, Experimental investigation of convective
energy use in U.S. airport facilities, in: Research Results Digest, Energy Systems heat transfer during night cooling with different ventilation systems and surface
Laboratory, Texas A&M University, Texas, 2007. emissivities, Energy Build. 61 (2013) 308–317.
[17] M.M. Ardehali, T.F. Smith, Evaluation of variable volume and temperature HVAC [41] R. Guo, Y. Hu, M. Liu, P. Heiselberg, Influence of design parameters on the night
system for commercial and residential buildings, Energy Convers. Manag. 37 (9) ventilation performance in office buildings based on sensitivity analysis, Sustain.
(1996) 1469–1479. Cities Soc. 50 (2019) 101661.
[18] C.A. Balaras, E. Dascalaki, A. Gaglia, K. Droutsa, Energy conservation potential, [42] H. Bulut, M.A. Aktacir, Determination of free cooling potential: a case study for
HVAC installations and operational issues in Hellenic airports, Energy Build. 35 Istanbul, Turkey, Appl. Energy 88 (2011) 680–689.
(11) (2003) 1105–1120. [43] M. Deymi-Dashtebayaz, S.V. Namanlo, A. Arabkoohsar, Simultaneous use of air-
[19] A.S.H. Abdallah, A. Makram, M.A.A. Nayel, Energy audit and evaluation of indoor side and water-side economizers with the air source heat pump in a data center for
environment condition inside Assiut International Airport terminal building, cooling and heating production, Appl. Therm. Eng. 161 (2019) 114133.
Egypt, Ain Shams Eng. J. (2021). [44] M. Yari, R. Kalbasi, P. Talebizadehsardari, Energetic-exergetic analysis of an air
[20] J. Parker, P. Cropper, L. Shao, Using building simulation to evaluate low carbon handling unit to reduce energy consumption by a novel creative idea, Int. J.
refurbishment options for airport buildings, in: 12th Conference of International Numer. Methods Heat Fluid Flow 29 (10) (2019) 3959–3975.
Building Performance Simulation Association, 2011, pp. 14–16. [45] R. Kalbasi, A. Shahsavar, M. Afrand, Reducing AHU energy consumption by a new
[21] M.K. Akyuz, H. Kafali, O. Altuntas, An analysis on energy performance indicator layout of using heat recovery units, J. Therm. Anal. Calorim. 139 (4) (2020)
and GWP at Airports; a case study, Energy Sources, Part A Recovery, Util. Environ. 2811–2820.
Eff. 43 (19) (2021) 2402–2418. [46] A.S. Goldanlou, R. Kalbasi, M. Afrand, Energy usage reduction in an air handling
[22] Wikipedia, 2021. https://en.wikipedia.org/wiki/ISO_50001. unit by incorporating two heat recovery units, J. Build. Eng. 32 (2020) 101545.
[23] A. Fichera, R. Volpe, E. Cutore, Energy performance measurement, monitoring and [47] M.L. Maripuu, L. Jagemar, Energy Savings by Changing Constant Air Volume
control for buildings of public organizations: standardized practises compliant with Systems (Cav) to Variable Air Volume Systems (Vav) in Existing Office Buildings.
the ISO 50001 and ISO 50006, Dev. Built Environ. 4 (2020) 100024. Experience from A Plant Reconstruction Based on A New Supply Air Terminal
[24] Google Earth. https://earth.google.com/web, 2021. Device Concept, 2004.
[25] S.H.G.M. Sivil, Havacılık Genel Müdürlüğü, 2021. http://web.shgm.gov.tr/docume [48] S. Lingireddy, D.J. Wood, Improved operation of water distribution systems using
nts/sivilhavacilik/files/pdf/projeler/yhp.pdf. variable-speed pumps, J. Energy Eng. 124 (3) (1998) 90–103.
[26] S. Yilmaz, S. Toy, M.A. Irmak, H. Yilmaz, Determination of climatic differences in [49] R. Saidur, Energy consumption, energy savings, and emission analysis in Malaysian
three different land uses in the city of Erzurum, Turkey, Build. Environ. 42 (2007) office buildings, Energy Pol. 37 (10) (2009) 4104–4113.
1604–1612. [50] CIBSE, Guide A: Environmental Design, Chartered Institute of Building Services
[27] M.G.M. Meteoroloji, Genel Müdürlüğü, 2021. https://www.mgm.gov.tr/veridegerl Engineers, 2006.
endirme/il-ve-ilceler-statistik.aspx?m=ERZURUM. [51] T. Hong, H.-W. Lin, Occupant Behavior: Impact on Energy Use of Private Offices,
[28] K. Bakirci, O. Ozyurt, M. Yilmaz, S. Erdogan, Erzurum ili enerji çalışmaları için Berkeley National Laboratory and the Green Energy and Environment
iklim ve meteoroloji verileri, Tesisat Mühendisliği Dergisi 95 (2006) 19–26. Laboratories, Industrial Technology Research Institute, Taiway, ROC, 2013.
[29] TSI. Turkish Standards Institution, TS 825 Thermal Insulation Requirements for [52] M. Kolokotroni, A. Aronis, Cooling-energy reduction in air-conditioned offices by
Buildings, 2013. using night ventilation, Appl. Energy 63 (4) (1999) 241–253.
[30] I. Alanqar, M. Heidarinejad, J. Srebric, A sensitivity analysis of energy simulation [53] Daikin. https://www.mcsmms.com/wp-content/uploads/2019/11/Chillers-Free-
accuracy for a renovated healthcare building, Build. Eng. 120 (1) (2014), 736-736. Cooling-Brochure-ASP-31-521.pdf, 2019.
[31] DesignBuilder. https://designbuilder.co.uk/helpv4.5/, 2016. [54] C.A. Roulet, F.D. Heidtb, F. Foradinic, M.C. Pibiria, Real heat recovery with air
[32] EnergyPlus. https://energyplus.net/weather/, 2021. handling units, Energy Build. 33 (2001) 495–502.
[33] NOAA. National, Oceanic and Atmospheric Administration, 2021. https://www. [55] J. Wallin, J. Claesson, Improving heat recovery using retrofitted heat pump in air
ncei.noaa.gov/access/metadata. handling unit with energy wheel, Appl. Therm. Eng. 62 (2014) 823–829.
[34] C. Peng, Calculation of a building’s life cycle carbon emissions based on Ecotect [56] G.A. Johnson, Retrofit of a constant volume Air system for variable speed fan
and building information modeling, J. Clean. Prod. 112 (2016) 453–465. control, Build. Eng. 90 (2B) (1984) 201–211.
[35] J.W. Moon, S.H. Han, Thermostat strategies impact on energy consumption in [57] O.F. Yildiz, Erzurum Havalimanı Terminal Binasının Enerji Analizi Ve Net Sıfır
residential buildings, Energy Build. 43 (2–3) (2011) 338–346. Enerjili Bina Formuna Dönüştürülmesinin İncelenmesi. PhD Thesis, Ataturk
[36] T. Hoyt, E. Arens, H. Zhang, Extending air temperature setpoints: simulated energy University Institute of Science, Erzurum, 2017.
savings and design considerations for new and retrofit buildings, Build. Environ. 88 [58] G. Uzuner, Santrifüj Pompalarda Enerji Verimliliği Ve Önemi, WILO Pump Systems
(2015) 89–96. Inc, 2015. https://docplayer.biz.tr/8709235-Santrifuj-pompalarda-enerji-verimlili
gi-ve-onemi-gokhan-uzuner-wilo-pompa-sistemleri-a-s.html.
18