Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Building and Environment 208 (2022) 108632

Contents lists available at ScienceDirect

Building and Environment


journal homepage: www.elsevier.com/locate/buildenv

Reduction of energy consumption and CO2 emissions of HVAC system in


airport terminal buildings
O.F. Yildiz a, *, M. Yilmaz b, A. Celik c
a
Chairmanship of Investment Monitoring and Coordination, Sehitkamil, Gaziantep, Turkey
b
Department of Mechanical Engineering, Faculty of Engineering, Inonu University, Malatya, Turkey
c
8th Regional Directorate, General Directorate of State Hydraulic Works, Erzurum, Turkey

A R T I C L E I N F O A B S T R A C T

Keywords: Airport terminal buildings consume more energy than other buildings in an airport due to their functional and
Airport operational characteristics. Heating, ventilation and air conditioning (HVAC) systems have been major energy
Terminal building consumers with a significant contribution to the annual total energy consumption in terminal buildings partic­
HVAC
ularly in harsh climates. Therefore, improvement of energy efficiency of the HVAC system is becoming an
Energy consumption
CO2 emission
increasingly important issue to reduce energy consumption and CO2 emissions of existing terminal buildings. The
aim of this study is to analyze and evaluate the effect of various energy conservation strategies on energy
consumption and CO2 emissions, including a number of modifications that can be applied to the HVAC system of
airport terminal buildings. Erzurum Airport terminal building, located in the coldest climate zone of Turkey, was
chosen as the airport terminal building. In order to achieve this goal, six strategies that can create energy savings
and cost savings and provide environmental benefits were analyzed and evaluated by building energy simulation.
The results indicated that energy consumption could be reduced from 6.3 GWh/year to 2.7 GWh/year and CO2
emissions from 1.9 million kg/year to 0.9 million kg/year by implementing feasible energy conservation stra­
tegies. This means that, by implementing the proposed energy-saving projects, energy consumption and CO2
emissions can be reduced by 57.24% and 48.79%, respectively.

HVAC systems play a significant role in meeting the thermal comfort


requirements of the indoor environment [11] and they are responsible
1. Introduction
for a major share of the energy consumption in airport terminal build­
ings [3,12]. HVAC systems can consume greater than 40% of electrical
Airports are facilities that consume huge amounts of energy and
energy in airport terminal buildings. In addition, nearly all the natural
contribute significantly to greenhouse gas emissions in the atmosphere
gas used in terminal buildings is consumed by HVAC systems, with the
[1,2]. This energy is consumed in both the airside and the landside
exception of small systems such as domestic hot water and cooking [13].
operations of airports [3]. As energy consumers, in an airport airside,
The natural gas consumption for cooking depends on how many res­
there are infrastructures and facilities such as control towers, airfield
taurants are in terminal building [14]. However, HVAC systems in
lighting and radio navigation systems while on the landside there are
existing terminal buildings are not always operating in the most efficient
buildings such as airport terminal building, cargo terminal, adminis­
ways [15]. Therefore, improving the energy efficiency and reducing the
trative buildings, and parking garages [1,4,5].
energy consumption of the existing HVAC systems in terminal buildings
Airport terminal buildings are large buildings with multiple zones
has become an important task for airports.
and dynamic occupancy patterns [6]. They contain many spaces that are
Airports all around the world are increasingly adopting strategies,
different in functions and structure. The operations within these build­
which can be applied to HVAC systems for reducing energy consumption
ings are round-the-clock [7]. Therefore, a large part of the total energy
and improving energy efficiency. The high-energy consumption of
consumed in an airport is consumed by the airport terminal building [1,
HVAC systems indicates that there are many opportunities for signifi­
8,9]. In terminal buildings, energy is utilized in a variety of applications
cant energy efficiency savings through retrofit projects [13]. However,
including heating, ventilation and air conditioning (HVAC) system,
investments in energy improvements can be costly and often compete
lighting, room electricity and domestic hot water (DHW) [10].

* Corresponding author.
E-mail addresses: farukmakina@hotmail.com (O.F. Yildiz), m.yilmaz@inonu.edu.tr (M. Yilmaz), acelik_25@hotmail.com (A. Celik).

https://doi.org/10.1016/j.buildenv.2021.108632
Received 15 July 2021; Received in revised form 23 November 2021; Accepted 24 November 2021
Available online 27 November 2021
0360-1323/© 2021 Elsevier Ltd. All rights reserved.
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Nomenclature EUI Energy use intensity


EXV Expansion valve
Acronyms HMPC Hybrid model predictive control
AHU Air handling unit HVAC Heating, ventilating and air conditioning
CAV Constant air volume ILS Instrument landing system
CIBSE Chartered Institution of Building Services Engineers ISO International organization for standardization
CIP Commercially important passengers IWEC International weather for energy calculation
CO2 Carbon dioxide LED Light emitting diode
DHW Domestic hot water MV + LV Medium voltage + Low voltage
EF Emission factor VAV Variable air volume
EnMS Energy management system VIP Very important person
EU Energy use VSD Variable speed driver

with other capital improvement projects [16]. Improvements in the ef­ commercial buildings. The approach was tested at the check-in hall of
ficiency of HVAC systems could be instrumental in maintaining existing the T-1 building of the Adelaide Airport in Australia. The results showed
power-plant generation capacity and avoiding further dependency on that the proposed HMPC scheme provides significant savings without
fossil fuels [17]. compromising thermal comfort. Malik [9] identified and assessed
The literature review shows that energy conservation of HVAC sys­ possible actions in key energy consuming equipment such as HVAC,
tems in terminal buildings has been the subject of many studies [7,10, lighting, and major electric motors to reduce energy use and improve
15,18,19]. The vast majority of these studies focused only on the control energy performance of three airport terminal buildings namely Raipur,
and operational strategies of the HVAC and lighting systems [7,15]. Aurangabad, and Udaipur in India. The results showed that the HVAC
However, there are few studies that comprehensively investigate mul­ system is one of the important energy consumers. Akyuz et al. [21]
tiple strategies which can be applied to HVAC system to reduce energy determined the energy performance indicators at airports using the
consumption and CO2 emissions of airport terminal buildings. Balaras method described in ISO 50001 energy management system (EnMS) and
et al. [18] evaluated different energy conservation strategies for 29 expressed mathematically the effects of these indicators on energy
Hellenic airports. In addition, the cost and simple payback period of the consumption. ISO 50001 EnMS is an international standard created by
strategies were estimated. Results showed that for the three airports, the International Organization for Standardization. This standard pro­
potential energy savings range at 15–35%. Babu [8] recommended vides a systematic approach to improve the energy performance and
passive strategies like daylighting, natural ventilation, and passive reduce greenhouse gas emissions of an organization [22]. Through
downdraught evaporative cooling system to achieve energy efficiency in adopting ISO 50001 EnMS, guidelines are established for planning,
the HVAC and lighting system of the Ahmedabad International Airport implementing, monitoring and controlling the energy performance of an
terminal building in India. The study also identified various design re­ organization [23]. A study was performed under the ACRP project
sponses that have to be adopted by the building skin to achieve stepped 09-10, “Benchmarking and Profiling Airport Terminal Energy End Uses”,
temperature transitioning for identified zones in the terminal building. sponsored by the Transportation Research Board (TRB), Airport Coop­
The stepped temperature transitioning is established as a result of erative Research Program (ACRP) [14]. A report entitled “Methodology
creating specific environments as the passenger traverses from landside to Develop the Airport Terminal Building Energy Use Intensity
to airside and vice versa with the help of the building envelope, which is (ATB-EUI) Benchmarking Tool” was published. An ATB was sub-divided
a result of the improved thermal design. It was found that energy savings into specific Zones: concession (food), concession (retail), office, tran­
of up to 66% can be achieved in the terminal building by applying sient space, ticketing check-in, departures hold room, departure/border
passive design strategies and adopting an approach of mixed-modes in security, outbound/inbound baggage handling, arrivals/baggage claim,
buildings. The study also proved that in a building like an airport ter­ and service (mech/elec/server). Each of these Zones was assigned an
minal, the roof, which is one of the largest elements of the building, can Energy Use Intensity (EUI) based on the best available published EUIs
be put to effective use in ventilation, daylighting and temperature that are appropriate for that type of space. Five ATB Systems were
conditioning. Parker et al. [20] illustrated the role of simulation in identified and annual EU calculation per ATB system was performed: (i)
evaluating refurbishment options that reduce the carbon footprint of an people movers, escalators, elevators, (ii) baggage handling systems, (iii)
airport terminal building in the United Kingdom. Simulation results alternative systems (i.e., electric, heating/cooling), (iv) Airport Ground
showed that HVAC interventions resulted in a much greater reduction in Support Equipment (GSE), and (v) external/parking lighting. The utility
CO2 emissions. Mambo et al. [7] investigated the development of HVAC bills were used to calculate the (measured) Energy Use (EU) of an in­
and lighting control strategies to provide sufficient comfort with opti­ dividual Airport Terminal Building (ATB). The utility bills usually con­
mum energy use in the Manchester Airport terminal building. Perda­ sisted of electricity consumption (kWh) and gas consumption (MCF or
maian et al. [10] proposed and simulated three strategies to reduce the therms) data. The site visits resulted in collecting missing information
electricity consumption and CO2 emission of Terminal 3 Soekarno-Hatta for the EU/EUI (energy use intensity) benchmarking analysis. Thus, a
International Airport through an energy simulation software. The results methodology was developed to estimate the baseline of the total annual
showed that the strategies reduce electricity consumption and CO2 EU and EUI for the ATB building and an “Airport Terminal Building
emission. Akyuz et al. [12] investigated the application of thermal Energy Use Intensity (ATB-EUI) Benchmarking Tool” was created.
insulation on the walls and roof of the Hasan Polatkan Airport terminal Moreover, general recommendations were developed on how to achieve
building in Eskisehir, Turkey, from energy, environment and cost as­ greater energy efficiency, and better manage the energy consumption at
pects. They determined the optimum insulation thickness and assessed an airport terminal building.
its effects on environmental performance based on energy flows. Anal­ While these investigations are important, there is still a great need
ysis results showed that applying thermal insulation on the walls and for investigations that comprehensively explore the multiple strategies
roof of the terminal building reduces heat loss by 48% and 56%, that can be applied to the HVAC system to reduce the energy con­
respectively. Huang et al. [15] presented a Hybrid Model Predictive sumption and the resultant CO2 emissions from the electricity and nat­
Control (HMPC) scheme which can reduce HVAC energy consumption in ural gas use of airport terminal buildings. Therefore, the objective of this

2
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

study is to analyze and evaluate energy saving strategies that include fulfilled the required conditions within the scope of the ‘Green Airport
many different measures/applications that can be applied to the HVAC Project’ initiated by the General Directorate of Civil Aviation of Turkey.
system in order to reduce the energy consumption of the HVAC system of Erzurum Airport got this title by providing criteria in the TS EN ISO
airport terminal buildings. Erzurum Airport terminal building, located 14001 Environmental Management System Certification together with
in the coldest climate zone of Turkey, was chosen as the airport terminal the Greenhouse Gas Criteria Document and Green Airport Project Sec­
building. Six strategies that can be applied practically were analyzed toral Criteria Document [25]. These criteria include: management of
and evaluated: (i) change the setpoint temperatures, (ii) night ventila­ waste water, management of environmental problems that may arise
tion, (iii) free cooling, (iv) adding heat exchangers, (v) retrofitting of the from de-ice/anti-icing activities, waste management, air pollution
air distribution system from CAV (constant air volume) to VAV (variable management (use of electric vehicles instead of fossil fueled vehicles in
air volume), and (vi) replacement of the existing circulating pumps. indoor environments, annual maintenance of combustion plants, etc.),
Potential energy saving rates and CO2 emission reductions were deter­ environmental noise management, management of rainwater, preven­
mined for each strategy. Initial investment costs and payback periods tion of soil pollution (measures such as the use of water-oil separator, the
were calculated for each strategy. requirement that de-ice/anti-icing solvents be environmentally
friendly), and prevention of fuel leaks and intervention [2]. However,
2. Material and method there were no efficiency measures currently in place to reduce the en­
ergy consumption, reduce energy costs and increase energy efficiency of
2.1. Erzurum Airport the HVAC system.

2.1.1. General description 2.1.2. Climatic conditions


Erzurum Airport, which was located in the northeast of Erzurum city The city of Erzurum, with an altitude of 1850 m, is located in the
center was opened as a military airport in 1966. The airport was opened Eastern Anatolia Region of Turkey (39◦ 55′ N and 41◦ 16′ E). It is far
to international non-scheduled flights in 1993 and started to serve in the from the effect of the nearby ocean and therefore has an inland climate.
new terminal building in 2005. Its total installed area is 8.1 million m2. Meteorological observations have been carried out in the city since
It has 14 aircraft gates. There is an ILS that allows the aircraft to land 1929. The first established meteorological station was surrounded by the
more safely and a parking lot for 530 cars, which is open for 24 h. In urban area and a second station was established in the airport in 1988
addition to the terminal building, there are: garage, technical- [26]. The historical highest and lowest average temperatures for Erzu­
administrative block, VIP building, accident-fire building, central rum are 19.5 ◦ C and − 9.2 ◦ C (according to meteorological measure­
heating plant, customs building and police buildings at the Erzurum ments between 1929 and 2020) [27]. The precipitation in winter is
Airport. Fig. 1 shows the view of Erzurum Airport and Fig. 2 shows the mostly snow, the number of snow days is 50, and the average duration of
terminal building. The total floor area of the terminal building is 12.9 snow cover is 114 days. The rainiest season is spring and summer [28].
thousand m2. The airport serves as a domestic and international
terminal. 2.1.3. Definition of the HVAC system
Erzurum Airport terminal building consists of two floors, the ground Heating and cooling are performed by HVAC systems at the terminal
floor and the mezzanine floor. In the terminal building, there are apron building of Erzurum Airport. The cooling is performed in June, July and
office, check-in hall, domestic-international baggage reception area, August whereas the heating is performed in other months of the year.
domestic-international incoming baggage area, domestic-international The HVAC equipment in the terminal building is shown in Table 1.
arriving passenger, domestic-international departing passenger and Table 2 shows the heating/cooling setpoint temperatures of the HVAC
welcome halls, offices, CIP lounge, cafeteria, restaurant, staff kitchen, equipment in the terminal building. The heating of the terminal building
WC, etc. The plan view of the ground floor and plan view of the is provided by natural gas-fired central hot water boilers, mixed air-
mezzanine floor are shown in Fig. 3 and Fig. 4, respectively. handling units, fan-coil units and unit heaters. Mixed air-handling
Erzurum Airport received the title ‘Green Enterprise’ in 2015 as it units can mix the fresh air with the desired amount of exhaust air to

Fig. 1. The view of Erzurum Airport from Google Earth [24].

3
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Fig. 2. Erzurum Airport terminal building.

Fig. 3. Plan view of the ground floor.

Fig. 4. Plan view of the mezzanine floor.

obtain the desired supply temperature. It can be designed with different constant air volume system is used in mixed air-handling units. The fan-
configurations depending on the mixture ratio. The domestic hot water coils are of two types, namely the floor standing type and the concealed
requirement of the terminal building is provided by a plate heat ceiling type. In addition to the terminal building, the VIP building is also
exchanger with 128 kW capacity which transfers heat from the hot water cooled by the chiller and 100% fresh air-handling unit. Terminal
in the boiler circuit flow to mains domestic water. In addition to the building cooling load is 1409 kW while the VIP building cooling load is
terminal building, other buildings at the airport are also heated by the 78 kW. Therefore, the share of the terminal building in the total cooling
central heating plant. load is approximately 95%.
The cooling of the terminal building is provided by air-cooled
chillers, mixed air-handling units and fan-coil units. A single-duct

4
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Table 1 Table 4
HVAC equipment in the terminal building. Existing condition of the building envelope.
No Equipment Capacity Number Roof Aluminum Granite Clad Windows
Panel Clad External Wall
1 Hot water boiler 1745 kW 3
External Wall
2 Air-cooled chiller 1087 kW 2
3 Unit heater 6 kW 9 Outermost Aluminum Aluminum Granite Clad: Tempered
4 Air handling unit (mixed air) Supply fan: 2500–12778 l/s 8 layer Sheet: 4 Clad: 20 Glass: 6
Exhaust fan: 1944–8333 l/s (mm) 2.5
Heating coil: 75–395 kW Layer 2 Rock Wall: Air Barrier Air Barrier Air:
Cooling coil: 52–233 kW (mm) 120 (Kraft Paper): (Kraft Paper): 14
5 Air handling unit (100% fresh air) Supply fan: 1528–2500 l/s 2 0.6 0.6
Exhaust fan: 1528–2500 l/s Layer 3 Polyethylene XPS: XPS: Laminated
Heating coil: 93–145 kW (mm) Moisture 100 100 Glass:
Cooling coil: 47–76 kW Barrier: 0.5 6
6 Exhaust air fan 167–2778 l/s, 150–340 Pa 15 Layer 4 Glass Wool: Polyethylene Polyethylene –
7 Fresh air fan 833–1389 l/s, 150 Pa 2 (mm) 30 Vapor Barrier: Vapor Barrier:
8 Fan-coil 1–7 kW, 0.07–0.33 l/s 126 0.5 0.5
Innermost Steel Sheet: Gypsum Wall Gypsum Wall –
layer 0.5 Board: Board:
(mm) 12.5 12.5
Table 2 Calculated U 0.22 0.313 0.312 1.761
The heating/cooling setpoint temperatures of the HVAC equipment used in the Value (W/
terminal building. m2K)
U Value 0.25 0.4 0.4 2.4
No Zone Name HVAC Heating setpoint Cooling setpoint specified
Equipment temperature temperature in TS 825
(oC) (oC) (W/m2K)
1 Offices Fan-coil, CAV, 22 23
Exhaust Air
Fan the values specified in the standard.
2 Check-In Hall CAV, Exhaust 22 23
Air Fan
3 Passenger and CAV, Exhaust 22 23 2.2. Method
baggage halls Air Fan
4 Incoming Unit Heater 15 – Terminal buildings are seen to have the largest share when consid­
baggage and ering the total energy consumption at the airport in general terms. On
baggage
reception areas
the other hand, the system with the largest share of the energy consumed
5 Kitchen, CAV, Exhaust 22 23 in the terminal buildings has been found to be the HVAC system. Per­
cafeteria and Air Fan, Fresh damaian et al. [10] determined that 86.59% of the total electricity
restaurant Air Fan consumption of the Terminal 3 Soekarno-Hatta International Airport
was consumed by the HVAC system, 9.33% by the lighting system,
2.41% by the electrical equipment, and 1.76% by the transportation
2.1.4. System pumps and fans
system. According to Alba [1], approximately 70% of the energy
In the terminal building, there are 16 pumps in various capacities
consumed in airport terminal buildings is used for heating, cooling and
used to circulate hot water, chilled water and domestic hot water
air conditioning purposes; this rate is higher in countries with cold cli­
(Table 3). Eight of these pumps provide hot or chilled water to the air-
mates. In the study published by the U.S. National Academy of Sciences
handling units. Four pumps are used for the fan-coil systems. The
[14], a method, which are based on individual parameters of each sys­
remaining four pumps provide the heated water to the heat exchanger
tem and its particular annual energy use estimation, for determining the
that produces domestic hot water. All of the circulation pumps are single
annual energy use per system of an airport terminal building was
speed or three speed.
developed. With the developed method, the total annual energy use of
escalator systems, people movers (moving walkways) systems, baggage
2.1.5. Building envelope
handling systems and elevators was calculated as 69,806 kBtu/yr, 115,
Table 4 shows the elements that make up the building envelope and
895 kBtu/yr, 22,288 kBtu/yr, 24,646 kBtu/yr, for a single unit,
their material thicknesses. The building envelope consists of an
respectively. In addition, the process of calculating and formulas of the
aluminum roof, aluminum panel clad external wall, granite clad external
total annual energy use of alternative systems, ground support equip­
wall and tempered glass windows. According to the “TS 825 Thermal
ment and external lighting and parking lighting systems were illus­
Insulation Requirements for Buildings” standard [29], Erzurum is
trated. The total energy consumption of the Erzurum Airport terminal
located in the fourth (coldest) degree day zone in Turkey. The overall
building is 6.301 GWh per year, with 69.99% of that is consumed by
heat transfer coefficients (U-Value) for Erzurum specified in this stan­
heating system, 11.90% used by lighting system, 8.89% consumed by
dard and the overall heat transfer coefficients (U-Value) were calculated
pumps and fans, 4.29% used by domestic hot water, 2.54% consumed by
considering the thermal conductivity of the building elements given in
cooling system, 2.38% used by electricity equipment, and 0.02% used by
Table 4. As seen in the table, the calculated overall heat transfer co­
exterior lighting [2]. These results reveal that approximately 81% of the
efficients (U-Value) of the building envelope are an improvement over
energy consumed in Erzurum airport terminal building is used for HVAC
purposes. All these results show that improvements to be made in HVAC
systems in airport terminal buildings will have significant energy saving
Table 3
potential.
System pumps in the terminal building.
In order to reduce the energy consumption and CO2 emissions of the
No Circulation Pumps Range of Max Flow Range of Head Max Number
terminal building, a number of modifications can be made in the HVAC
1 Heating system 3–14 l/s 4.5–7 m 6 system with an acceptable level of investment. Therefore, there is a need
2 Cooling system 14–32.5 l/s 8.5–10 m 6 to provide accurate and reliable energy simulation models to study
3 DHW system 0.5–2 l/s 4–4.5 m 4
feasibility of these modifications that could lead to energy savings [30].

5
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Energy simulations, to be performed after modeling, are important to Table 6


determine and evaluate potential effectiveness of the proposed strate­ The activity (usage) of the zones.
gies on energy consumption, energy cost and the environment. No Zone Name Activity Density Metabolic DHW
As a first step, the existing terminal building was modeled using Template (people/ Activity Cons.
Software A (2016) [31]. Information on the architecture, construction, m2) Rate (l/
m2-day)
lighting, electricity and HVAC system required for the modeling of the
terminal building was obtained from the building energy manager at the 1 Offices Generic 0.05 Light office 0.16
airport. The existing terminal building will be referred to as the "refer­ Office Area work/
Standing/
ence building" in the following sections. Walking
The reference building was simulated by Software B (2016) [32] 2 Check-In Hall Generic 0.03 Standing/ 0.59
integrated within Software A (2016) [31] to understand the current Check-in Walking
energy consumption of the terminal building and make a preliminary Areas
3 Passenger and Circulation 0.05 Standing/ 0
assessment for the energy conservation potential. The simulation soft­
baggage halls area Walking
ware, used to perform simulations in this study, uses IWEC (Interna­ 4 Incoming Circulation 0.05 Standing/ 0
tional Weather for Energy Calculations) data files. The IWEC data files baggage and area Walking
are ’typical’ weather files suitable for use with building energy simu­ baggage
lation programs for 227 locations outside the USA and Canada. The files reception areas
5 Kitchen and Food 0.04 Light manual 0.43
are derived from up to 18 years (1982–1999 for most stations) of cafeteria Preparation work
DATSAV3 hourly weather data originally archived at the U. S. National Area
Climatic Data Center. The DATSAV3 Surface Database is composed of 6 Restaurant Eating/ 0.1 Eating/ 7.41
worldwide surface weather observations from about 10,000 stations Drinking Drinking
Area
(stations were active at the time of addition), collected and stored from
sources such as the Automated Weather Network and the Global Tele­
communications System [33]. IWEC data files are available at no cost for and 7). Information on passenger loads was obtained based on actual
three cities in Turkey (Istanbul, Ankara and Izmir). The IWEC data file flight schedules to accurately model the operating schedules of HVAC
for Erzurum was purchased as specified in Software B (2016) [32] systems, and it was seen that these operating schedules overlap with the
website. The total energy consumption (natural gas and electricity) and actual operating schedules. In other words, the timing model of the
CO2 emissions of the terminal building were obtained on an annual, zones for heating, cooling, natural ventilation and DHW operation is the
monthly, daily and hourly basis, by using Software B (2016) (see also same with the timing actual. The HVAC tab, that is a modeling header
Table 5 for CO2 emissions factor) [32]. While energy is transported and inside Software A, allows detailed modeling of the heating, cooling and
distributed from the generation site to the demand site, losses appear mechanical ventilation system based on the functions and type of the
due to both technical and non-technical factors. Therefore, when HVAC system. Selected HVAC data used in modeling the reference
calculating any energy efficiency savings, the electricity savings and the building are given in Table 7. The air change rates were: 1.0 (ACH) in the
natural gas savings were multiplied by 1.07 and by 1.02, respectively. check-in hall and passenger-baggage halls; whereas it is 2.3 in the
Thus, the energy consuming components analyzed and the energy kitchen and restaurant. Heating of the incoming baggage and baggage
saving potential of the building was determined. reception areas was provided by unit heaters. Therefore, the seasonal
CO2 emissions were calculated by multiplying fuel consumption by g COP of the heating system is lower than other zones (i.e., check-in hall,
CO2 per MJ emission factor for that fuel [31,34]: offices, restaurant). The number of heating/cooling days is 7 days/week
CO2 = Eelectricity [MJ] × EFelectricity [g / MJ] + Enatural gas [MJ] × EFnatural gas [g / MJ] in all zones except the offices.
Another important factor in the energy consumption of the airport
(1)
terminal buildings is lighting. The lighting analysis includes modeling of
CO2 emissions factors for electricity and natural gas by some coun­ the general lighting, task lighting, lighting controls, and exterior lighting
tries and regions are given in Table 5. The CO2 emission factor values of the zones. To accomplish this the lighting type, luminaire type,
given in Table 5 are from Software A (2016) [31]. mounting type, and power density were provided for the reference
The activity (usage) of the zones in the airport terminal buildings building and used as input to the lighting model. The lighting modeling
play an important role in energy consumption. The activity of the zones inputs of the terminal building are presented in Table 8. Fluorescent and
depends on parameters such as activity levels, occupancy, environ­ metal halide lighting luminaires are used in the building. These lumi­
mental conditions, domestic hot water consumption. Table 6 shows naires are recessed, suspended and surface mount types. The lighting
certain model data entered in the activity tab that defines the activity control, which is made according to the availability of natural daylight,
(usage) of zones. As can be seen from the table, the activity template of is not used in any zone. Lighting modeling is of great importance as the
passenger-baggage halls and baggage areas is defined as circulation heat emitted by lighting affect the internal heat gains calculated during
area. thermal simulations. In this study, no measures were suggested to
When modeling the building, the HVAC system sizing was obtained improve the lighting efficiency. The lighting data were used in modeling
from the actual equipment specification (see Table 1, Table 2, Tables 3 the reference building.
Six strategies including a number of modifications that can applied to
the HVAC system and change of HVAC system parameters (such as
Table 5 setpoint temperatures) were considered in order to reduce the energy
CO2 emission factors [31]. consumption and CO2 emissions of the terminal building. These strate­
Country/Region EF for Electricity (g/MJ) EF for Natural Gas (g/MJ) gies are: (i) change of the setpoint temperatures, (ii) night ventilation,
(iii) free cooling, (iv) adding heat exchanger, (v) retrofitting of the air
France 168.33 52.10
United Kingdom 144.17 60 distribution system from CAV to VAV, (vi) replacement of the existing
Canada 168.33 52.10 circulation pumps with variable speed circulation pumps. Potential en­
USA/Colorado 242.67 52.10 ergy saving rates and CO2 emission reduction rates were determined for
USA/Florida 175.64 52.10 each strategy. Initial investment costs, energy costs and payback periods
USA/New York 108.11 52.10
were calculated for each strategy. Thus, the gains of each strategy were
Turkey 168.33 52.10

6
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Table 7
Inputs for the HVAC modeling.
No Zone Name Outside Air Heating/Cooling Heating/Cooling System Heating/Cooling (days/ Air Temperature
(ac/h) Fuel Seasonal COP week) Distribution

1 Offices 2.2 Natural Gas/ 0.85/1.8 5/5 Mixed


Electricity
2 Check-In Hall 1 Natural Gas/ 0.85/1.19 7/7 Mixed
Electricity
3 Passenger and baggage halls 1 Natural Gas/ 0.85/1.19 7/7 Mixed
Electricity
4 Incoming baggage and baggage – Natural Gas/ 0.65/- 7/- Mixed
reception areas Electricity
5 Kitchen and cafeteria 2.3 Natural Gas/ 0.85/1.19 7/7 Mixed
Electricity
6 Restaurant 2.3 Natural Gas/ 0.85/1.19 7/7 Mixed
Electricity

Table 8
Inputs for the Lighting modeling.
No Zone Name Template Normalized Power Density (W/m2-100 lux) Luminaire Type Radiant Fraction Visible Fraction

1 Offices Fluorescent 1.66 Recessed 0.37 0.18


2 Check-In Hall Metal Halide 1.15 Suspended 0.42 0.18
3 Passenger and baggage halls Metal Halide 1.15 Suspended 0.42 0.18
4 Incoming baggage and baggage reception areas Fluorescent 1.66 Surface Mount 0.72 0.18
5 Kitchen and cafeteria Fluorescent 1.66 Recessed 0.37 0.18
6 Restaurant Metal Halide 1.15 Suspended 0.42 0.18

determined. The savings were estimated by adding the gains from each
strategy that is feasible in terms of energy, cost and environmental to the Table 9
The proposed strategies and their characteristics.
next.
In addition, the costs and simple payback periods of the strategies No Strategy Characteristics References
were estimated in order to evaluate the economic benefit of the strate­ 1 Change of the setpoint The total energy consumption [19,
gies proposed in this study. When calculating the payback period, the temperatures could be reduced by decreasing/ 35–38]
natural gas tariff and electricity tariff were assumed to be 0.023 $/kWh increasing heating/cooling
setpoint temperatures of the
and 0.088 $/kWh, respectively. Electric demand costs and all taxes are zones to the temperature ranges
included in the electricity tariff. Simple payback period is calculated recommended by CIBSE.
using the following equation: 2 Night ventilation The total electrical energy [39–41]
consumption could be reduced by
Initial investment cost of modification [$] supplying the outdoor air, which
Payback Period = (2)
Annual energy cost saving [$/year] has a lower temperature than the
indoor temperature, to the indoor
during nighttime hours.
3. Energy conservation strategies for the HVAC system 3 Free cooling A considerable energy savings [42,43]
could be achieved by using a
A very large amount of the annual total energy consumed in Erzurum water-side economizer when the
outdoor air temperature is low
Airport terminal building is consumed by the HVAC system. Analysis of
enough.
the simulation results revealed that the HVAC system had significant 4 Adding heat exchanger The total energy consumption [44–46]
savings potential [2]. Therefore, it is very important to identify possible could be reduced by adding air-to-
strategies that can be implemented in the HVAC system in order to air heat exchangers into the
existing AHUs.
reduce the energy consumption and CO2 emissions of the terminal
5 Retrofitting of the air The total energy consumption [30,47]
building. In this study, six different energy saving strategies were pro­ distribution system from could be reduced by retrofitting
posed, including modifications to the HVAC system and changing the CAV to VAV the existing air distribution
setpoints of the HVAC system operating parameters, in order to reduce system from CAV to VAV.
energy consumption, reduce the energy costs of operating the HVAC 6 Replacement of the The total electrical energy [48,49]
existing circulation consumption could be reduced by
system and increase energy efficiency in the Erzurum Airport terminal
pumps replacing the existing single/
building. These strategies are: (i) change of the setpoint temperatures, three speed hot water and chilled
(ii) night ventilation, (iii) free cooling, (iv) adding a heat exchanger, (v) water circulation pumps with
retrofitting of the air distribution system from CAV to VAV, (vi) variable speed circulation pumps.
replacement of the existing circulation pumps with variable speed cir­
culation pumps. Table 9 identifies the proposed strategies and their
CO2 emission of the building.
characteristics.
3.1.1. Heating setpoint temperature
3.1. Change of the setpoint temperature Heating setpoint temperature is one of the thermostat strategies used
in the HVAC systems and has a significant role in the space heating
This section aimed to identify the effect of changing the heating and energy demand of a building. A considerable energy savings can be
cooling setpoint temperatures, which is the one of the most significant achieved in a building that is in a cold climate region by decreasing the
thermostat strategies [35], on the total energy consumption and total heating setpoint temperature in the winter [35,37,38]. The Chartered

7
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Institution of Building Services Engineers (CIBSE) recommends comfort Table 11


criteria for specific areas in an airport terminal building and for general Recommended comfort criteria for general areas in a building [50].
building areas [50]. In this study, the operative temperatures recom­ Winter Summer Winter Summer Activity
mended by CIBSE were considered the optimum thermal comfort tem­ (met)
Operative Clothing (Clo)
perature condition. The current heating setpoint temperatures of the Temperature (oC)
zones in the terminal building are presented in Table 2. The operative
Office 21–23 22–24 0.85 0.7 1.2
temperatures for winter recommended by CIBSE are shown in Table 10 Small Shops 19–21 21–23 1.0 0.65 1.4
and Table 11. Comparison of Table 2 with Tables 10 and 11 reveals that Department
a warmer thermal environment than the recommended by CIBSE have Storesa
been preferred in the terminal building. The heating setpoint tempera­ Toilets 19–21 21–23 1.0 0.65 1.4
Kitchen 15–18 18–21 1.0 0.65 1.8
tures of the zones in the terminal building can be changed with the
(Commercial)
temperatures recommended by CIBSE. Restaurant 21–23 24–25 1.0 0.65 1.1
a
Based on comfort requirements of staff.
3.1.2. Cooling setpoint temperature
Each zone within Erzurum Airport terminal building has a separate
comfort need during heating and cooling seasons. In general, the cooling
system in the terminal building is operated during the cooling season
and the chillers consume electrical energy. The current cooling setpoint
temperatures of the cooled zones (passenger and baggage halls, offices,
etc.) are presented in Table 2 and cooling setpoint temperatures have
high impact on cooling energy consumption. The operative tempera­
tures recommended by CIBSE for summer are shown in Tables 10 and
11. From a comparison of Table 2 with Tables 10 and 11, it is seen that
the current cooling setpoint temperatures are lower than the operative
temperatures recommended by CIBSE for summer. Unfortunately, the
lower the cooling setpoint, the higher the cooling energy use [51].
Therefore, increasing the cooling setpoint temperatures can be consid­
ered as a different strategy to reduce the total energy consumption of the
terminal building.
Fig. 5. Daytime and nighttime operating modes of AHUs of the offices in cases
that use night ventilation in office areas.

3.2. Night ventilation


provides the areas with cool air throughout the night. Thus, the offices
Night ventilation is an active or passive cooling strategy [39] applied require less mechanical cooling during daylight hours and the cooling
for especially large volume buildings when located where nighttime energy consumption can be reduced. On the other hand, night ventila­
ambient temperature is suitable. Nighttime ventilation is a promising tion may lead to an increase in total electricity consumption of the
approach to reduce the energy needed for cooling buildings without terminal building because of the operation of the fans in the AHUs even
reducing thermal comfort [40]. The basic concept is to utilize the rela­ though it can reduce the cooling loads for the next day and save energy.
tively low-temperature, low-humidity ambient air during the nighttime Therefore, when night ventilation is used, the total energy consumption
by the natural or mechanical ventilation systems to cool down the in­ of the building must be carefully monitored and compared to baseline
door air as well as the building construction components to provide a conditions without nighttime ventilation [52].
heat sink for the following day [41]. All areas in the terminal building,
that are cooled, except the office areas, are used and cooled for 24 h. For 3.3. Free cooling
this reason, night ventilation can be activated only for the office areas
during the hours when the offices are closed. Fig. 5 shows daytime and Free cooling another opportunity for significant energy savings in
nighttime operating modes of the air-handling units for office zones in HVAC systems and is used when the outdoor air temperatures are low
case of using night ventilation in office areas. Night ventilation for the enough. There are two types of economizers, which provide free cooling
office areas was designed to start at 1:00 a.m., continue all night and for the air conditioning system. Those include: a water-side economizer
switched off at 8:00 a.m. for weekdays during the summer period of and an air-side economizer [42,43]. In this strategy, the use of the
June to August. During these hours, ambient air is supplied to the office water-side economizer, which is added in series to the condenser coil in
areas by mechanical ventilation. Night ventilation in the office areas the chiller, was proposed and analyzed to reduce cooling energy con­
sumption. The air-cooled chillers have been used to provide the cooling
Table 10 of the terminal building. The chilled water at 7 ◦ C that is produced by
Recommended comfort criteria for some specific areas in airport terminal the chillers is transmitted from the chillers to the AHUs through chilled
building [50]. water circulation pumps during the cooling season. Water-side econo­
Wintera Summera Activity (met) mizers operate in three different operating modes: i) hybrid mode, ii)
Operative Temperature (oC)
water-side economizer only mode, iii) mechanical cooling only mode. In
the hybrid mode, some of the cooling load is rejected whereas in a
Baggage Reclaim 12-19b 21-25b 1.8
water-side economizer only mode all the load is rejected by the
Check-In Areasc 18–20 21–23 1.4
Concourse (no seats) 19-24b 21-25b 1.8 water-side economizer. Fig. 6 shows the schematic of air-cooled chiller
Customs Area 18–20 21-23b 1.4 with a water-side economizer operating in the hybrid mode. When the
Departure Lounge 19–21 22–24 1.3 outside air temperature is lower than the return water temperature
a
Clothing insulation is 1.15 clo for winter conditions and is 0.65 clo for (11 ◦ C), the return chilled water (dark blue line) is directed to the
summer conditions. water-side economizer, since the economizer will be enabled, some of
b
Based on PMV of ±0.5. At other cases based PMV ±0.25. the load is rejected by the economizer coils and both mechanical and
c
Based on comfort requirements for check-in staff. free cooling are engaged. Thus, some of the required cooling is provided

8
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Fig. 6. Schematic of air-cooled chiller with water-side economizer operating in hybrid mode [53].

from water-side economizer. The compressor operates in partial load


(hybrid mode) or eliminates mechanical cooling (water-side economizer
only mode) thereby free cooling is provided.

3.4. Adding heat exchanger

Energy recovery is a suitable technique to reduce high-energy con­


sumption in a building [45]. To reduce heating or cooling energy de­
mand of a building an air-to-air heat exchanger is often implemented in
AHUs [54,55]. In this study the existing AHUs in the terminal building
were divided into two categories according to their operating modes.
Those are a 100% fresh air-handling unit and a mixed air-handling unit.
The 100% fresh air-handling units use 100% of outdoor air to meet the
minimum ventilation requirement whereas the mixed air-handling units
use 28% or 33% of return air as the supply air and 72% or 67% of
outdoor air to meet the minimum ventilation requirement [15]. In the
base case, eight of the ten AHUs in the terminal building have been
recovering waste heat of the exhaust air. This has been achieved by
using mixing air damper which mixes return air and outdoor air in Fig. 7. General layout of: a) existing the 100% fresh air-handling unit, b)
certain proportions in mixing box. In addition, an air-to-air rotary heat existing mixed air-handling unit, c) proposed 100% fresh air-handling unit with
exchanger, which are widely used in AHUs to reduce the hea­ rotary type heat exchanger, d) proposed the mixed air-handling unit with rotary
type heat exchanger.
ting/cooling load, can be added into the existing AHUs. The general
layout of the existing AHUs in the terminal building are shown in Fig. 7a
and Fig. 7b, and the general layout of the AHUs with heat exchanger VAV systems accurately measure and control the conditioned airflow
proposed and analyzed in this strategy are shown in Fig. 7c and d. depend on the heating load or cooling load whereas the CAV systems
An air-to-air rotary heat exchanger operates on the principle of supply a constant volume of conditioned air, even with small tempera­
recovering the waste heat of the exhaust air and improves the efficiency ture changes. Airport terminal buildings have different activity levels
of the AHU system. In such a system the exhaust air and the fresh air flow and variable occupancy rates. Therefore, the heating, cooling and
parallel to each other but in the opposite directions. In the heat ventilation requirements vary over the day depending on the actual
exchanger, the exhaust air cools the warm fresh air in the summer and flight schedules and passenger loads, which are nonlinear [18]. Hence,
warms the cold fresh air in the winter. Thus, fresh air is pre-cooled/pre- CAV systems lead to over ventilation and, as a result, more energy
heated. The rotary heat exchanger can be integrated upstream of the consumption during periods with low or no occupancy. As a result,
outside air mixing box. In this case, the outdoor air controller will retrofitting of the existing CAV system to VAV system can achieve
determine the modulation based on the conditions at the inlet node of improvement in energy efficiency [17,56]. The basic motivation of this
the outside air mixing box instead of outdoor air. It is also important that strategy, which is an important factor for reducing the energy con­
the controller account for the rotary heat wheel that may modify the sumption of the terminal building, is to retrofit the existing CAV system
condition of outdoor air before it reaches the mixer [31]. to become a VAV system. As seen in Fig. 8, this retrofitting includes
sizing and installing a new VAV terminal box, adding a variable speed
driver to both supply and return fans for variable airflow control and
3.5. Retrofitting of the existing CAV system to VAV system updating the control systems of the AHUs to utilize VAV control [30,47].
Thus, the conditioned airflow can be considerably reduced and signifi­
In general, the air-side equipment of the HVAC systems is divided cant savings can be achieved in heating, cooling, fans and pumps energy
into two categories, namely, a CAV system and a VAV system [17]. The

9
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Fig. 8. Schematic of: a) the existing CAV system, b) the proposed VAV system.

consumption. building (the reference building) was the first step in the process of
determining the energy consumption pattern of an airport terminal
3.6. Replacement of existing circulating pumps building and suggesting practices/measures to reduce it. Therefore, the
Erzurum Airport terminal building was modeled and an energy simu­
One of the most significant energy consumers in a terminal building lation was performed. The simulation results (energy and environ­
are the chilled water and hot water circulating pumps, which are mental) were evaluated only at the building level. Fig. 9 shows the
commonly used in heating and cooling applications. As can be seen in monthly changes in total energy consumption of the terminal building.
Table 3, there are total 16 single/three speed hot water and chilled water The two main energy sources of the terminal building are natural gas
circulation pumps (4 of these pumps are single speed) in the terminal and electricity. The actual annual natural gas consumption of the ter­
building with different capacities and pressure used in the heating and minal building was 4,677,042 kWh (16,837 GJ), electricity consumption
cooling systems. Unfortunately, the circulating pumps operate at is 1,614,464 kWh and annual total energy consumption is 6,291,506
maximum flow rate and pressure which can be significantly higher than kWh. The annual energy intensity of the terminal building was 485.83
required. This often results inefficient operation of the pumping systems. kWh/m2. The highest energy consumption was in January (908,526
However, variable speed circulation pumps adjust the motor speed ac­ kWh) due to the lower outdoor temperatures in January versus other
cording to the requested flow rate and pressure. This is important months while the lowest energy consumption was in July (249,568
because even small reductions in motor speed results large power re­ kWh). Although the electricity consumption of the terminal building
ductions. Thus, significant improvements in energy efficiency and cost increases in the summer months due to the need for cooling, the total
savings can be achieved [49]. energy consumption of the building decreases as there is no need for
In this study, various strategies were reviewed and analyzed in order heating during these months. Detailed information on the energy char­
to achieve energy and cost savings and environmental gains in airport acteristics of Erzurum Airport terminal building can be found in Refs. [2,
terminal buildings. It has been determined that some of these strategies 57].
will reduce the heating and cooling load of the terminal building. Due to Fig. 10 shows a comparison of actual and simulated energy con­
this reduction in heating and cooling loads, the hot water and chilled sumption of the Erzurum Airport terminal building. The annual actual
water circulation pumps used in the system should be resized according energy consumption in 2014 and 2015 was taken as basis for the actual
to their new load capacities. Therefore, the existing circulation pumps energy consumption of the Erzurum Airport terminal building. As seen
can be replaced with variable speed circulation pumps that are resized in the figure, the actual energy consumption of the terminal building is
according to the reduced heating and cooling loads. 7,015,081 kWh and the simulated energy consumption is 6,291,507
kWh. The difference between actual and simulated energy consumption
4. Results and discussion is 11% [2].
Fig. 11 illustrates the energy consumption pattern of the terminal
4.1. Results for the reference building building. In cold climate regions like Erzurum, space heating is a major
share of the annual total energy consumption. Space heating is followed
Performing an energy analysis on an existing airport terminal by lighting (including exterior lighting), pumps and fans, domestic hot

10
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Fig. 9. Monthly changes in total simulated energy consumption of the Erzurum Airport terminal building.

Fig. 10. Monthly changes in total actual and simulated energy consumption of the Erzurum Airport terminal building [2].

water, cooling, and room electricity, respectively. The total energy


consumption of the HVAC system is almost 5.13 GWh and its share in
total energy consumption of the building is about 81.6%.
Fig. 12 shows the daily CO2 emissions of the terminal building. CO2
emission increases in the winter days when the need for heating is higher
and decrease in the summer days. However, there is a slight increase in
July and August months (due to the increase in cooling requirement),
when the electricity consumption in total energy consumption increases.
The annual total CO2 emissions of the terminal building is 1,855,589 kg,
which are calculated using the conversion values from Table 5 [31].

4.2. Results for the strategies

This study focused on the analysis of strategies proposed for the


reduction of energy consumption and displaced CO2 emissions of HVAC
system energy use of the Erzurum Airport terminal building. Unfortu­
nately, the reduction in energy consumption of any single HVAC
component may lead to an increase or decrease of the energy con­
Fig. 11. Simulated consumption of the Erzurum Airport terminal building.
sumption of another HVAC component in the terminal building.
Therefore, in this study, the effect of each strategy on energy

11
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Fig. 12. Daily simulated CO2 emission of the Erzurum Airport terminal building.

consumption and displaced CO2 emission was examined only at the criteria for specific areas in airport terminal building are presented in
whole building level. This allowed the strategies to be evaluated accu­ Table 10, and the comfort criteria for the general areas in the building
rately and reasonably using simulation. The proposed strategies were using CIBSE recommendations are shown in Table 11. Fig. 13 shows the
described and identified in Section 3. effect of reducing the heating setpoint temperatures to the temperatures
recommended by CIBSE on the monthly energy consumption and dis­
4.2.1. Strategy 1: change of the setpoint temperature placed CO2 emissions of the terminal building. As seen in Fig. 13, the
The first simulated energy conservation strategy was decreasing/ simulated energy consumption decreased in all months when the heat­
increasing indoor air setpoint temperatures. The recommended comfort ing setpoint temperatures are lowered to the temperatures

Fig. 13. The effect of reducing the heating setpoint temperatures on the monthly energy consumption and displaced CO2 emissions of the terminal building.

12
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

recommended by CIBSE. On the other hand, the displaced CO2 emissions 4.2.3. Strategy 3: free cooling
decreased in all months due to the decrease in energy consumption. Another strategy analyzed and evaluated the reduced energy con­
Examination of the figure shows that although energy consumption in­ sumption of the terminal building from the use of a water-side econo­
creases in September compared to August, displaced CO2 emissions mizer. Analysis of the simulation results reveals that there is no need for
decreased. This is due to the increase in the share of electricity con­ cooling in any part of the terminal building when the outside air tem­
sumption in the total energy consumption and the fact that the estimated perature is lower than the return water temperature (11 ◦ C). However,
emission factor of electricity kg.CO2/kWh is larger than the natural gas the indoor air temperature of some areas may momentarily exceed the
emission factor. cooling setpoint temperature due to internal heat gains. This tempera­
Table 12 provides a summary of the simulated effect of reducing the ture rise results in a barely noticeable increase (2.9 kW) in the energy
heating setpoint temperatures on energy consumption and energy costs. consumed for cooling. As a result, there has been no improvement in the
A significant reduction of the annual total energy consumption is ach­ energy efficiency of the HVAC system due to the use of this strategy.
ieved by reducing the heating setpoint temperatures. Natural gas and Therefore, it is not recommended to use free cooling to reduce the en­
electricity consumption are reduced by approximately 20% and 2%, ergy consumption and displaced CO2 emissions of the terminal building.
respectively. The annual energy intensity decreased from 485.83 kWh/
m2 to 410.12 kWh/m2. The annual energy intensity reduction rate is 4.2.4. Strategy 4: adding heat exchanger
approximately 16%. Reducing the heating set point temperatures of the Fig. 15 shows the effect of adding a rotary heat exchanger to existing
spaces in the terminal building not only reduces the space heating en­ AHUs on the monthly energy consumption and displaced CO2 emissions
ergy consumption, but also the energy consumption of the system pumps of the terminal building. The use of rotary heat exchanger reduces en­
and fans. ergy consumption in all months. The decrease in energy consumption is
Recommended comfort criteria for some specific areas in airport much higher in winter than in other months. For example, while the
terminal building are presented in Table 10, recommended comfort energy consumption is 802,520 kWh in January, with the use of the
criteria for general areas in a building by CIBSE in Table 11. Fig. 14 rotary heat exchanger, the energy consumption decreases by 49%–
shows the effect of changing the cooling setpoint temperatures to the 410,685 kWh. Due to the reduction in energy consumption, total dis­
temperatures recommended by CIBSE on the monthly energy con­ placed CO2 emissions are also reduced.
sumption and displaced CO2 emissions of the terminal building. When The effect of adding rotary heat exchangers into the AHUs on energy
the cooling setpoint temperatures are changed to the temperatures consumption and energy cost of the terminal building is given in
recommended by CIBSE, the total energy consumption and the total Table 15. When the table is examined, it is seen that the annual total
displaced CO2 emissions of the terminal building do not change during energy consumption has decreased by approximately 48% although
the months when cooling system is not in operation (during the heating additional fan energy is required due to the increased pressure drop
season). Total energy consumption decreases during the cooling season across the rotary heat exchanger. This reduction leads to savings of
in which the cooling system is operated. For example, the decrease in $87,079 in annual energy cost. The fact that the addition of a rotary heat
total energy consumption in August is around 4%. Total displaced CO2 exchanger to existing AHUs provides such high energy savings is due to
emissions remain constant during the months when the cooling system is the fact that the large spaces in the terminal building are heated by
not operating. In the months when the cooling system is operating, the AHUs, and the energy demand for heating is very high since the airport
total displaced CO2 emissions are reduced due to the reduction in energy is located in the cold climate region.
consumption. In June, the building’s total displaced CO2 emission rea­ The initial investment cost of adding rotary heat exchangers to AHUs
ches its lowest value with 94,757 kg. is given in Table 16. Examination of Tables 15 and 16 shows that the
Table 13 presents the effect of increasing the cooling setpoint tem­ payback period for this modification is less than one year. Therefore, it
peratures on energy consumption and energy cost. When the cooling can be stated that it would be economically viable to add rotary heat
setpoint temperatures are increased the total energy consumption of the exchangers to AHUs.
terminal building reduce by almost 0.5%. There is generally a limited
need for cooling in Erzurum Airport terminal building since it is located 4.2.5. Strategy 5: retrofitting of the air distribution system from CAV to
in a cold climate region. Therefore, the cooling energy saving rate is very VAV
low. Warm climates benefit more from increased cooling setpoint tem­ The effect of retrofitting of the existing air distribution system from
peratures, while colder climates benefit more from decreased heating CAV to VAV on natural gas consumption, electricity consumption and
setpoint temperatures [36]. energy cost is summarized in Table 17. It is seen that this modification
has little effect on natural gas consumption and electricity consumption.
4.2.2. Strategy 2: night ventilation There is an annual decrease of 2.3% in natural gas consumption, and a
Table 14 shows a summary of the effect of night ventilation for the decrease of 0.7% in electricity consumption annually. The low effect of
office areas on energy consumption and energy cost of the terminal retrofitting the existing CAV system to a VAV system on energy con­
building. The use of night ventilation for the office areas reduces the sumption indicates that a high supply air flow rate is generally needed in
cooling energy consumption of the terminal building. However, night the terminal building to keep the space temperature at a comfort level.
ventilation requires operating the supply and exhaust fans mounted in Retrofitting of the existing air distribution system from CAV to VAV
the AHUs of the offices. This leads to an increase in total electricity resulted saves $1561 in the annual energy cost of the building. The
consumption of the terminal building, since the base case simulation has initial investment cost of the retrofitting is shown in Table 18. The
the AHUs turned-off. Therefore, it was concluded that night ventilation payback period of this modification is approximately 12 years due to low
for the office areas is not economically viable. energy savings and high initial investment costs. Considering that the
lifetime of the existing CAV system is 20 years and the current system

Table 12
The effect of reducing the heating setpoint temperatures on energy consumption and energy cost.
Natural Gas Consumption (kWh) Electricity Consumption (kWh) Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)

Reference Building 4,677,042 1,614,464 107,572 142,073 249,645


CIBSE Criteria (for Winter) 3,726,932 1,584,140 85,719 139,404 225,123
Energy Savings* and Cost Savings 969,112 32,447 21,853 2669 24,522

13
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Fig. 14. The effect of increasing the cooling setpoint temperatures on the monthly energy consumption and displaced CO2 emissions of the terminal building.

Table 13
The effect of increasing the cooling setpoint temperatures on energy consumption and energy cost.
Natural Gas Consumption Electricity Consumption Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)
(kWh) (kWh)

CIBSE Criteria (for Winter) 3,726,932 1,584,140 85,719 139,404 225,123


CIBSE Criteria (for Winter and 3,723,871 1,563,535 85,649 137,591 223,240
Summer)
Energy Savings* and Cost Savings 3122 22,047 70 1813 1883

Table 14
The effect of night ventilation for the office areas on energy consumption and energy cost of the terminal building.
Natural Gas Consumption (kWh) Electricity Consumption (kWh) Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)

No Night Ventilation 3,723,871 1,563,535 85,649 137,591 223,240


Night Ventilation 3,723,871 1,569,722 85,649 138,135 223,784
Energy Savings* and Cost Savings – − 6620 – − 544 − 544

has been used for about 16 years, this modification would not be feasible in September. As a result of the use of variable speed circulation pumps,
in terms of technical and economic considerations. the annual total displaced CO2 emissions are reduced by almost 3.6%.
The effect of replacement of single/three speed circulation pumps
4.2.6. Strategy 6: replacement of the existing circulation pumps with variable speed circulation pumps on energy consumption and en­
Fig. 16 shows the effect of replacement of single/three speed circu­ ergy cost of the terminal building is given in Table 19. As can be seen
lation pumps with variable speed circulation pumps on the monthly from the table, replacement of the existing circulation pumps is reduced
energy consumption and displaced CO2 emissions of the terminal the annual total electricity consumption, whereas the annual total nat­
building. The energy consumption and displaced CO2 emissions of the ural gas consumption remains unaffected. It has been determined that
terminal building reduce in all months. The energy consumption of the the use of variable speed circulation pumps will save $5031 per year.
terminal building reaches its lowest value of 119,246 kWh in June, The initial investment cost of using variable speed circulation pumps
whereas its displaced CO2 emission reaches its lowest value of 59,162 kg in the HVAC system has been calculated and given in Table 20.

14
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Fig. 15. The effect of adding the rotary heat exchangers into existing AHUs on the monthly energy consumption and displaced CO2 emissions of the termi­
nal building.

Table 15
A summary of the effect of adding the rotary heat exchangers into the AHUs on energy consumption and energy cost.
Natural Gas Consumption (kWh) Electricity Consumption (kWh) Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)

AHU Without Heat Exchanger 3,723,871 1,563,535 85,649 137,591 223,240


AHU With Heat Exchanger 1,624,569 1,122,682 37,365 98,796 136,161
Energy Savings* and Cost Savings 2,141,288 471,713 48,284 38,795 87,079

Considering the operating cost in Table 19 and the initial investment


Table 16
cost in Table 20, the payback period for using variable speed circulation
The initial investment cost of adding of rotary heat exchangers into the AHUs.
pumps in the HVAC system is found to be about 4.4 years. This short
Unit Price ($) Number Cost ($) payback period indicates that this modification is cost-effective and a
Rotary Heat Exchanger 1389-2083 l/s 2573 1 2573 good investment. These findings are consistent with the literature.
Rotary Heat Exchanger 2084-2778 l/s 3309 2 6618
Rotary Heat Exchanger 4167-5555 l/s 5479 3 16437
Rotary Heat Exchanger 5556-8333 l/s 6806 2 13612 Table 18
Rotary Heat Exchanger 11111-13889 l/s 11894 2 23788 The initial investment cost of retrofitting of the CAV system to VAV system.
TOTAL 63028
Unit Price ($) Numbers Cost ($)

VAV Terminal Box 325 10 3250


Variable Speed Driver 775 20 15500
TOTAL 18750

Table 17
The effect of retrofitting of the existing CAV system to VAV system on energy consumption and energy cost.
Natural Gas Consumption (kWh) Electricity Consumption (kWh) Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)

CAV 1,624,569 1,122,682 37,365 98,796 136,161


VAV 1,587,290 1,114,678 36,508 98,092 134,600
Energy Savings* and Cost Savings 38,025 8564 857 704 1561

15
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Fig. 16. The effect of replacing existing circulation pumps with variable speed circulation pumps on the monthly energy consumption and displaced CO2 emissions of
the terminal building.

Table 19
The effect of replacing existing circulation pumps with variable speed circulation pumps on energy consumption and energy cost.
Natural Gas Consumption (kWh) Electricity Consumption Natural Gas Cost ($) Electricity Cost ($) Total Energy Cost ($)
(kWh)

Single/Three Speed Circulation 1,624,569 1,122,682 37,365 98,796 136,161


Pumps
Variable Speed Circulation Pumps 1,624,569 1,065,516 37,365 93,765 131,130
Energy Savings* and Cost Savings – 61,168 – 5031 5031

4.3. Comparative evaluation of strategies


Table 20
The initial investment cost of replacing existing circulation pumps with variable
Table 21 shows the feasibility of the suggested strategies collectively.
speed circulation pumps.
Decreasing the setpoint temperatures could save 15.58% in annual en­
Sizes (Max Flow, Head Max) Unit Price ($) Number Cost ($) ergy consumption and could reduce annual displaced CO2 emissions by
1 l/s, 4.5 m 1183 2 2366 10.59%. By using all four strategies shown in the table, 57.24% savings
2 l/s, 4.5 m 1183 2 2366 are achieved in annual energy consumption and annual displaced CO2
0.5 l/s, 4 m 1183 2 2366
emissions are reduced by 48.79%.
5 l/s, 7 m 1400 2 2800
5.5 l/s, 8.5 m 1400 2 2800 The findings obtained in this study reveal that HVAC systems have a
11 l/s, 10 m 1693 4 6772 very important share in the energy consumption and displaced CO2
5.5 l/s, 7 m 1400 2 2800 emissions of airport terminal buildings, and that energy consumption
Total 16 22270 and displaced CO2 emissions can be significantly reduced by realizing
the proposed strategies in HVAC systems.
Uzuner [58] reported that the 18 circulation pumps at Atatürk Airport
were replaced with variable speed circulation pumps with an investment 5. Conclusions
of $19,410 and the payback period was 1.07 years by providing $18,173
electricity savings (37%) per year. This study presents the different energy conservation strategies that
can be applied to the HVAC system to reduce the energy consumption
and displaced CO2 emissions of the Erzurum Airport terminal building.

16
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

Table 21
The feasible ones among the suggested strategies.
Strategy Energy Consumed (kWh/ Energy Saving CO2 CO2 Reduction Initial Investment Cost Payback Period
year) (%) Emission (kg/ (%) ($) (years)
year)

Reference building 6,291,506 – 1,855,589 – – –


Decreasing heating setpoint 5,311,072 15.58% 1,659,012 10.59% – –
temperature
Increasing cooling setpoint 5,287,406 0.44% 1,645,951 0.79% – –
temperature
Adding heat exchanger 2,747,251 48.04% 986,261 40.08% 63,028 0.7
Replacement of the existing 2,690,085 2.08% 950,284 3.65% 22,270 4.4
circulation pumps

To achieve this purpose, six strategies were analyzed and evaluated: (i) will require more natural gas use. Therefore, when examining
change of the setpoint temperatures, (ii) night ventilation, (iii) free these strategies, the total energy consumption of the terminal
cooling, (iv) adding heat exchanger, (v) retrofitting of the air distribu­ building must be carefully analyzed and evaluated.
tion system from CAV to VAV, (vi) replacement of the existing circula­ (8) Airports are suitable settlements for the installation of renewable
tion pumps with variable speed circulation pumps. The main energy systems as they have vast and free of shade areas. Through
conclusions are summarized as follows: further research, the renewable energy systems which have the
best benefit/cost ratio for the airport can be determined. Thus,
(1) An energy analysis of the airport terminal building has been made the net energy consumption of the terminal building can be
and it has been determined that the HVAC system is the largest reduced.
energy consumer compared to other systems in the terminal
building. The energy consumed by the HVAC system constitutes CRediT authorship contribution statement
approximately 81.6% of the total energy consumption of the
terminal building. HVAC system is followed by lighting O.F. Yildiz: Formal analysis, Data curation, Investigation, Method­
(including exterior lighting), pumps and fans, domestic hot ology, Writing – original draft, Software. M. Yilmaz: Writing – review &
water, cooling, and room electricity, respectively. editing, Supervision, Conceptualization. A. Celik: Validation,
(2) Improving the energy efficiency of the HVAC system, which has a Visualization.
high energy consumption, is of great importance to reduce the
energy consumption and displaced CO2 emissions of the terminal
building. Declaration of competing interest
(3) Strategies that changed the setpoint temperatures, adding heat
exchanger and replacement of existing circulation pumps with The authors declare that they have no known competing financial
variable speed circulation pumps are found to be feasible in terms interests or personal relationships that could have appeared to influence
of energy, cost and environment. On the other hand, the strate­ the work reported in this paper.
gies of night ventilation, free cooling and retrofitting of the air
distribution system from CAV to VAV are found to be not References
economically viable.
(4) By implementing feasible strategies, considerable energy and [1] S. Alba, M. Manana, Energy research in airports: a review, Energies 9 (5) (2016)
349.
energy costs can be saved and displaced CO2 emissions reduced [2] O.F. Yildiz, M. Yilmaz, A. Celik, Energy analysis of cold climate region airports: a
for the electricity and natural gas that were saved. While the case study for airport terminal in Erzurum, Turkey, Int. J. Sustain. Aviat. 7 (1)
potential energy saving range of the strategies is between 0.44% (2021) 66–92.
[3] N. Sumathi, P.S. Ramnareddran, G.J.A. Revanth, G.V. Arasu, Sustainable methods
and 48.04%, the potential displaced CO2 emission reduction used to reduce the energy consumption by various facilities in airport terminals,
range of the strategies is between 0.79% and 40.08%. Int. J. Latest Technol. Eng. Manag. Appl. Sci. 6 (11) (2017) 41–44.
(5) Energy savings for the strategies of decreasing heating setpoint [4] G. Baxter, P. Srisaeng, G. Wild, Sustainable airport energy management: the case of
Kansai International Airport, Int. J. Traffic Transport. Eng. 8 (3) (2018).
temperature, increasing cooling setpoint temperature, adding [5] F. Greer, J. Rakas, A. Horvath, Airports and environmental sustainability: a
heat exchanger, and replacement of existing circulation pumps comprehensive review, Environ. Res. Lett. 15 (10) (2020) 103007.
with variable speed circulation pumps is 15.58%, 0.44%, [6] K.M. Reena, A.T. Mathew, L. Jacob, A flexible control strategy for energy and
comfort aware HVAC in large buildings, Build. Environ. 145 (2018) 330–342.
48.04%, and 2.08%, respectively. As can be seen, the positive
[7] D.A. Mambo, M. Efthekhari, T. Steffen, Occupancy-driven supervisory control
effect of adding rotary heat exchangers to AHUs is better than strategies to minimise energy consumption of airport terminal building, Sustain.
other strategies. Energy Build. (2013) 479–489.
(6) Displaced CO2 reduction for the strategies of decreasing heating [8] A.D. Babu, A low energy passenger terminal building for Ahmedabad Airport,
India: building envelope as an environment regulator, in: Proceedings of the 25th
setpoint temperature, increasing cooling setpoint temperature, Conference on Passive and Low Energy Architecture, Dublin, Ireland, 2008,
adding heat exchanger, and replacement of existing circulation pp. 22–24.
pumps with variable speed circulation pumps is 10.59%, 0.79%, [9] K. Malik, Assessment of energy consumption pattern and energy conservation
potential at Indian airports, J. Constr. Dev. Ctries. (JCDC) 22 (2017) 97–119.
40.08%, and 3.65%, respectively. [10] L.G. Perdamaian, R. Budiarto, M.K. Ridwan, Scenarios to reduce electricity
(7) Additional energy conservation strategies in the lighting system consumption and CO2 emission at terminal 3 Soekarno-Hatta international airport,
and the building envelope (such as improvement external wall Proc. Environ. Sci. 17 (2013) 576–585.
[11] B.L. Gowreesunker, S.A. Tassou, M. Kolokotroni, Coupled TRNSYS-CFD simulations
and roof thermal insulation, replacing the existing lighting fix­ evaluating the performance of PCM plate heat exchangers in an airport terminal
tures with LED, installation of lighting control system, exploit day building displacement conditioning system, Build. Environ. 65 (2013) 132–145.
lighting etc.) should be investigated in the future studies [12] M.K. Akyuz, O. Altuntas, M.Z. Sogut, Economic and environmental optimization of
an airport terminal building’s wall and roof insulation, Sustainability 9 (10) (2017)
considering their payback period. These strategies can reduce the 1849.
electricity consumption of the terminal building. However, the [13] C.R. Lau, J.T. Stromgren, D.J. Green, Airport Energy Efficiency and Cost Reduction.
electricity saved in the winter will lead to reduced heat gain that ACRP Synthesis Report 21, Transportation Research Board of the National
Academies, Washington, DC, 2010.

17
O.F. Yildiz et al. Building and Environment 208 (2022) 108632

[14] National Academies of Sciences, Engineering, and Medicine, Methodology to [37] A. Kotopouleas, M. Nikolopoulou, Thermal comfort conditions in airport terminals:
Develop the Airport Terminal Building Energy Use Intensity (ATB-EUI) indoor or transition spaces? Build. Environ. 99 (2016) 184–199.
Benchmarking Tool, The National Academies Press, Washington, DC, 2016, [38] H. Kim, T. Hong, Determining the optimal set-point temperature considering both
https://doi.org/10.17226/23495. labor productivity and energy saving in an office building, Appl. Energy 276
[15] H. Huang, L. Chen, E. Hu, A new model predictive control scheme for energy and (2020) 115429.
cost savings in commercial buildings: an airport terminal building case study, [39] B.R. Hughes, H.N. Chaudhry, S.A. Ghani, A review of sustainable cooling
Build. Environ. 89 (2015) 203–216. technologies in buildings, Renew. Sustain. Energy Rev. 15 (6) (2011) 3112–3120.
[16] W.D. Turner, M. Verdict, B. Yazdani, H. Huff, K. Clingenpeel, Model for improving [40] J. Le Dréau, P. Heiselberg, R.L. Jensen, Experimental investigation of convective
energy use in U.S. airport facilities, in: Research Results Digest, Energy Systems heat transfer during night cooling with different ventilation systems and surface
Laboratory, Texas A&M University, Texas, 2007. emissivities, Energy Build. 61 (2013) 308–317.
[17] M.M. Ardehali, T.F. Smith, Evaluation of variable volume and temperature HVAC [41] R. Guo, Y. Hu, M. Liu, P. Heiselberg, Influence of design parameters on the night
system for commercial and residential buildings, Energy Convers. Manag. 37 (9) ventilation performance in office buildings based on sensitivity analysis, Sustain.
(1996) 1469–1479. Cities Soc. 50 (2019) 101661.
[18] C.A. Balaras, E. Dascalaki, A. Gaglia, K. Droutsa, Energy conservation potential, [42] H. Bulut, M.A. Aktacir, Determination of free cooling potential: a case study for
HVAC installations and operational issues in Hellenic airports, Energy Build. 35 Istanbul, Turkey, Appl. Energy 88 (2011) 680–689.
(11) (2003) 1105–1120. [43] M. Deymi-Dashtebayaz, S.V. Namanlo, A. Arabkoohsar, Simultaneous use of air-
[19] A.S.H. Abdallah, A. Makram, M.A.A. Nayel, Energy audit and evaluation of indoor side and water-side economizers with the air source heat pump in a data center for
environment condition inside Assiut International Airport terminal building, cooling and heating production, Appl. Therm. Eng. 161 (2019) 114133.
Egypt, Ain Shams Eng. J. (2021). [44] M. Yari, R. Kalbasi, P. Talebizadehsardari, Energetic-exergetic analysis of an air
[20] J. Parker, P. Cropper, L. Shao, Using building simulation to evaluate low carbon handling unit to reduce energy consumption by a novel creative idea, Int. J.
refurbishment options for airport buildings, in: 12th Conference of International Numer. Methods Heat Fluid Flow 29 (10) (2019) 3959–3975.
Building Performance Simulation Association, 2011, pp. 14–16. [45] R. Kalbasi, A. Shahsavar, M. Afrand, Reducing AHU energy consumption by a new
[21] M.K. Akyuz, H. Kafali, O. Altuntas, An analysis on energy performance indicator layout of using heat recovery units, J. Therm. Anal. Calorim. 139 (4) (2020)
and GWP at Airports; a case study, Energy Sources, Part A Recovery, Util. Environ. 2811–2820.
Eff. 43 (19) (2021) 2402–2418. [46] A.S. Goldanlou, R. Kalbasi, M. Afrand, Energy usage reduction in an air handling
[22] Wikipedia, 2021. https://en.wikipedia.org/wiki/ISO_50001. unit by incorporating two heat recovery units, J. Build. Eng. 32 (2020) 101545.
[23] A. Fichera, R. Volpe, E. Cutore, Energy performance measurement, monitoring and [47] M.L. Maripuu, L. Jagemar, Energy Savings by Changing Constant Air Volume
control for buildings of public organizations: standardized practises compliant with Systems (Cav) to Variable Air Volume Systems (Vav) in Existing Office Buildings.
the ISO 50001 and ISO 50006, Dev. Built Environ. 4 (2020) 100024. Experience from A Plant Reconstruction Based on A New Supply Air Terminal
[24] Google Earth. https://earth.google.com/web, 2021. Device Concept, 2004.
[25] S.H.G.M. Sivil, Havacılık Genel Müdürlüğü, 2021. http://web.shgm.gov.tr/docume [48] S. Lingireddy, D.J. Wood, Improved operation of water distribution systems using
nts/sivilhavacilik/files/pdf/projeler/yhp.pdf. variable-speed pumps, J. Energy Eng. 124 (3) (1998) 90–103.
[26] S. Yilmaz, S. Toy, M.A. Irmak, H. Yilmaz, Determination of climatic differences in [49] R. Saidur, Energy consumption, energy savings, and emission analysis in Malaysian
three different land uses in the city of Erzurum, Turkey, Build. Environ. 42 (2007) office buildings, Energy Pol. 37 (10) (2009) 4104–4113.
1604–1612. [50] CIBSE, Guide A: Environmental Design, Chartered Institute of Building Services
[27] M.G.M. Meteoroloji, Genel Müdürlüğü, 2021. https://www.mgm.gov.tr/veridegerl Engineers, 2006.
endirme/il-ve-ilceler-statistik.aspx?m=ERZURUM. [51] T. Hong, H.-W. Lin, Occupant Behavior: Impact on Energy Use of Private Offices,
[28] K. Bakirci, O. Ozyurt, M. Yilmaz, S. Erdogan, Erzurum ili enerji çalışmaları için Berkeley National Laboratory and the Green Energy and Environment
iklim ve meteoroloji verileri, Tesisat Mühendisliği Dergisi 95 (2006) 19–26. Laboratories, Industrial Technology Research Institute, Taiway, ROC, 2013.
[29] TSI. Turkish Standards Institution, TS 825 Thermal Insulation Requirements for [52] M. Kolokotroni, A. Aronis, Cooling-energy reduction in air-conditioned offices by
Buildings, 2013. using night ventilation, Appl. Energy 63 (4) (1999) 241–253.
[30] I. Alanqar, M. Heidarinejad, J. Srebric, A sensitivity analysis of energy simulation [53] Daikin. https://www.mcsmms.com/wp-content/uploads/2019/11/Chillers-Free-
accuracy for a renovated healthcare building, Build. Eng. 120 (1) (2014), 736-736. Cooling-Brochure-ASP-31-521.pdf, 2019.
[31] DesignBuilder. https://designbuilder.co.uk/helpv4.5/, 2016. [54] C.A. Roulet, F.D. Heidtb, F. Foradinic, M.C. Pibiria, Real heat recovery with air
[32] EnergyPlus. https://energyplus.net/weather/, 2021. handling units, Energy Build. 33 (2001) 495–502.
[33] NOAA. National, Oceanic and Atmospheric Administration, 2021. https://www. [55] J. Wallin, J. Claesson, Improving heat recovery using retrofitted heat pump in air
ncei.noaa.gov/access/metadata. handling unit with energy wheel, Appl. Therm. Eng. 62 (2014) 823–829.
[34] C. Peng, Calculation of a building’s life cycle carbon emissions based on Ecotect [56] G.A. Johnson, Retrofit of a constant volume Air system for variable speed fan
and building information modeling, J. Clean. Prod. 112 (2016) 453–465. control, Build. Eng. 90 (2B) (1984) 201–211.
[35] J.W. Moon, S.H. Han, Thermostat strategies impact on energy consumption in [57] O.F. Yildiz, Erzurum Havalimanı Terminal Binasının Enerji Analizi Ve Net Sıfır
residential buildings, Energy Build. 43 (2–3) (2011) 338–346. Enerjili Bina Formuna Dönüştürülmesinin İncelenmesi. PhD Thesis, Ataturk
[36] T. Hoyt, E. Arens, H. Zhang, Extending air temperature setpoints: simulated energy University Institute of Science, Erzurum, 2017.
savings and design considerations for new and retrofit buildings, Build. Environ. 88 [58] G. Uzuner, Santrifüj Pompalarda Enerji Verimliliği Ve Önemi, WILO Pump Systems
(2015) 89–96. Inc, 2015. https://docplayer.biz.tr/8709235-Santrifuj-pompalarda-enerji-verimlili
gi-ve-onemi-gokhan-uzuner-wilo-pompa-sistemleri-a-s.html.

18

You might also like